Metal Z-Purlins Design Based on AISI S100/SI-10

INPUT DATA & DESIGN SUMMARY

SECTION & SPACING 10ZS2.25x85 @ 24 in, o.c., (610 mm, o.c.)

4 : 12 ( q =18.43
0
ROOF SLOPE )
MAXIMUM PURLIN SPAN L= 25 ft, (7.62 m)
YIELD STRESS (33 or 55) Fy = 55 ksi, (379 MPa)
SLOPED DEAD LOAD DL = 8 psf, (0.383 kPa)
PROJECTED ROOF LIVE LOAD LR = 20 psf, (0.958 kPa)
NET UPWARD WIND PRESSURE WIND = 25 psf, (1.197 kPa)

LATERAL SUPPORTED BY DIAPHRAGM? 1 top flange


(0=No, 1=top flange, 2=bottom flange)
DEFLECTION LIMITATION FOR LIVE LOAD ? 1 L /240
(0=No., 1= L /240, 2= L /360, 3= L /180, 4= L /120)
THE DESIGN IS ADEQUATE.
ANALYSIS
SECTION PROPERTIES OF EACH Z PURLIN (AISI Manual, 2002, Table I-4 & Table II-4)
t = 0.085 in ry = 1.08 in
D = 10 in Wt = 4.6278 lb/ft
A = 1.36 in2 rx = 3.74 in
J = 0.00326 in4 in6


Cw = 30
4
Ie = 18.8 in Mn = 194 in-kips

q
Se = 3.53 in3 Vn = 9.25 lbs
B = 2.25 in d = 0.96 in
R = 0.1875 in Sx = 3.79 in3
d

CHECK MAX WEB DEPTH-TO-THICKNESS RATIO (AISI B1.2)


D/t= 117.65 < 200 [Satisfactory]

DETERMINE ASD LEVEL LOADS


wDL+LR = [(DL Cosq + LR Cos2q ) S + Wt Cosq ] = 55.569 lb/ft, down inward to roof
Mmid = wDL+LR L2 / 8 = 52.096 in-kips, conservative value at middle of span
Msupport = - wDL+LR L2 / 12 = -34.731 in-kips, conservative value at supports
VDL+LR = 2 wDL+LR L / 3 = 0.9262 kips, conservative value at supports

w0.9DL+WIND = [(0.9 DL Cosq - WIND) S + Wt Cosq ] = -31.9487 lb/ft, uplift inward to roof
Mmid = w0.9DL+WIND L2 / 8 = -29.952 in-kips, conservative value at middle of span
Msupport = - w0.9DL+WIND L2 / 12 = 19.968 in-kips, conservative value at supports
V0.9DL+WIND = 2w0.9DL+WIND L / 3 = -0.5325 kips, conservative value at supports

CHECK FLEXURAL CAPACITY (AISI C3.1)


Mn/Wb = 116.17 in-kips > M [Satisfactory]
Where M = Max( Mmid, Msupport) = 52.10 in-kips
Wb = 1.67

CHECK SHEAR CAPACITY (AISI C3.2)


Vn/WV = 5.78 lbs > V [Satisfactory]
Where V = Max( VDL+LR, V0.9DL+WIND) = 0.9262 lbs
Wv = 1.60

CHECK LATERAL-TORSIONAL BUCKLING (AISI C3.1.2)


CASE 1: BOTH TOP & BOTTOM FLANGES UNSUPPORTED <== Does not apply.

C b r oA
Fe   ey t  6.9 ksi < 2.78 Fy = 152.9 ksi
Sf
< 0.56 Fy = 30.8 ksi
(cont'd)
Where Cb = 1.0 xo = 0 in
ro = (rx2 + ry2 + xo2)0.5 = 3.893 in
 2E
Sf = 3.79 in3, ( Sx )  ey   3.773 ksi
K yL y / r y
E= 29500 ksi (AISI pg xiv)
2
G= 11300 ksi (AISI pg xvi)
Ky = 1.0  
1   2E C w 
Kt = 1.0 t  GJ   6.496 ksi
Ar o2   K t Lt 2 
Ly = 300 in 
Lt = 300 in

ì F y , for F e³2.78 F e
ï
ï10  10 F y 
F c  í F y1-  , for 2.78> F e³ 0.56 F e = 6.9 ksi
ï 9  36 F e 
ï
î F e , for F e £0.56F e

Mn/Wb = 15.70 in-kips < M [Satisfactory]


Where Sc = 3.79 in3
Wb = 1.67
Mn = ScFc = 26.21 in-kips
M= 52.10 in-kips

CASE 2: TOP OR BOTTOM FLANGE SUPPORTED ONLY


Mn/Wb = 66.85 in-kips > M [Satisfactory]
Where Se = 3.53 in3
Wb = 1.67
R= 0.575 (AISI Table D6.1.1-1)
Mn = RSeFy = 111.64 in-kips
M= 34.73 in-kips

CHECK CAPACITY COMBINED BENDING & SHEAR AT ANY SAME SECTION (AISI C3.3.1)
2 2
 WbM   W vV 
    = 0.7956 < 1.0 [Satisfactory]
 Mn   Vn 

Where M= 52.10 in-kips


V= 0.93 lbs
Vn/Wv = 5.78125 lbs
Mn = MIN( Bending , Buckling) = 111.64 in-kips

W M  W V 
 b  = 0.78 > 0.5  v  = 0.16 < 0.7
 Mn   Vn 
W M   WvV 
0.6 b    = 0.6278 < 1.3 [Satisfactory]
 Mn   Vn 

CHECK LIVE LOAD DEFLECTION


5 w LR  L 4
 LR   0.57 in < L /240 = 1.25 in [Satisfactory]
384 EI e
Where wLR = LR Cos2q S = 36 lb/ft, down inward to roof