CLIENT : DESIGN BY :
JOB NO. : DATE: REVIEW BY :
Metal Z-Purlins Design Based on AISI S100/SI-10
4 : 12 ( q =18.43
0
ROOF SLOPE )
MAXIMUM PURLIN SPAN L= 25 ft, (7.62 m)
YIELD STRESS (33 or 55) Fy = 55 ksi, (379 MPa)
SLOPED DEAD LOAD DL = 8 psf, (0.383 kPa)
PROJECTED ROOF LIVE LOAD LR = 20 psf, (0.958 kPa)
NET UPWARD WIND PRESSURE WIND = 25 psf, (1.197 kPa)
Cw = 30
4
Ie = 18.8 in Mn = 194 in-kips
q
Se = 3.53 in3 Vn = 9.25 lbs
B = 2.25 in d = 0.96 in
R = 0.1875 in Sx = 3.79 in3
d
w0.9DL+WIND = [(0.9 DL Cosq - WIND) S + Wt Cosq ] = -31.9487 lb/ft, uplift inward to roof
Mmid = w0.9DL+WIND L2 / 8 = -29.952 in-kips, conservative value at middle of span
Msupport = - w0.9DL+WIND L2 / 12 = 19.968 in-kips, conservative value at supports
V0.9DL+WIND = 2w0.9DL+WIND L / 3 = -0.5325 kips, conservative value at supports
C b r oA
Fe ey t 6.9 ksi < 2.78 Fy = 152.9 ksi
Sf
< 0.56 Fy = 30.8 ksi
(cont'd)
Where Cb = 1.0 xo = 0 in
ro = (rx2 + ry2 + xo2)0.5 = 3.893 in
2E
Sf = 3.79 in3, ( Sx ) ey 3.773 ksi
K yL y / r y
E= 29500 ksi (AISI pg xiv)
2
G= 11300 ksi (AISI pg xvi)
Ky = 1.0
1 2E C w
Kt = 1.0 t GJ 6.496 ksi
Ar o2 K t Lt 2
Ly = 300 in
Lt = 300 in
ì F y , for F e³2.78 F e
ï
ï10 10 F y
F c í F y1- , for 2.78> F e³ 0.56 F e = 6.9 ksi
ï 9 36 F e
ï
î F e , for F e £0.56F e
CHECK CAPACITY COMBINED BENDING & SHEAR AT ANY SAME SECTION (AISI C3.3.1)
2 2
WbM W vV
= 0.7956 < 1.0 [Satisfactory]
Mn Vn
W M W V
b = 0.78 > 0.5 v = 0.16 < 0.7
Mn Vn
W M WvV
0.6 b = 0.6278 < 1.3 [Satisfactory]
Mn Vn