Vous êtes sur la page 1sur 2

File: AtWater Paramount.

src

BS EN 62305-2:2006 Risk Management Calculations

Case details

Case name: LRT3 GS05 - BSS2 (TNB Switching Room)


Case title: TOKAI for Dynasynergy - BSS2 (TNB Switching Room)
Created: 02 February 2018
Modified: 05 February 2018
Case notes: TOKAI Engineering Risk Finding:

Consider typical school building at Shah Alam, Selangor. The structure is


situated in developing city with same height neighbouring residential
structures. It is fed by an underground power line and data line, both of
unknown length. The estimated dimensions of the area are:

L = 28 m
W = 26 m
H = 16 m

Lightning Density, Selangor : 200


Number Of Thurderstrom Days Per Year (2006-2010) = 20.0Ng

Primary risk totals

R1_T 3.5792E-05 Risk of loss of human life in the structure


The tolerable risk is exceeded, therfore protection measures must be
instigated
R2_T 0.E00 Risk of loss of service to the public in the structure
This risk has not been determined

R3_T 0.E00 Risk of loss of cultural heritage in the structure


This risk has not been determined

R4_T 0.E00 Risk of loss of economic value in the structure


This risk has not been determined

Protection system design parameters

LPS None

ISPD 0.00kA Maximum peak current of equipotential bonding SPD's for each of 'n'
lines defined (based upon simple current division concept)
NOTE: The worst case surge that could be expected on a two-wire telephone or data
line is
2.5kA (10/350 µs) per line (Category D test to BS EN 61643-21) to earth or 5 kA
(10/350 µs) per pair.

Environment

Ng 20.00 Lightning flash density (Flashes/km²/year)

Cd 0.25 Location factor

Ce 1.00 Environmental factor


Rho 200.00 Wm Soil resistivity (Ohm metres)

StrikeRisk Version 5.0 Run identification 20/6/2018 6:11:06PM Page 1 of 2


File: AtWater Paramount.src

Structures

Primary structure
Structure Primary Structure - Rectangular with a flat roof
ID:
Lb 28.00 m Length of primary structure
Wb 26.00 m Width of primary structure
Hb 16.00 m Height of primary structure

Secondary structures

Lines
Line 1 Power Line
Line 2 ELV/Data/Telco

Zones
Zone 1 LPZ 0a/1

StrikeRisk Version 5.0 Run identification 20/6/2018 6:11:07PM Page 2 of 2