CPU 319F-3 PN/DP

Function
 Password protection;
a password concept protects the user program from unauthorized access.
 Diagnostics buffer;
the last 100 error and interrupt events are stored in a buffer for diagnostic purposes.
 Maintenance-free data back-up;
all data (up to 700 KB) are automatically backed up by the CPU if the voltage is interrupted and are available
unchanged after the voltage has been reconnected.

Parameterizable properties
The S7 configuration as well as the properties and response of the CPUs can be parameterized using STEP 7:
 MPI multipoint interface;
determining station addresses
 Start-up/cyclic response;
determining maximum cycle time and loading
 Isochronous interrupts;
setting of DP master system, partial process image number and delay time
 Clock bit memory;
setting of addresses
 Retentivity;
setting of retentive areas
 Clock interrupts;
setting of start date, start time and periodicity
 Watchdog interrupts;
setting of periodicity Mar 2008
Page 1682 Siemens ITS
 Watchdog interrupts;
setting of periodicity
 System diagnostics;
determining handling and scope of the diagnostic alarms
 Clock;
setting the type of synchronization in the AS or on the MPI
 Protection level;
specifying the access rights to program and data
 Operation;
selection of either test operation or process operation
 Communication;
reserving the connection resources
 PROFIBUS DP master/slave interfaces;
user-oriented address assignment for distributed I/O
 PROFINET interface;
parameterization of time synchronization with NTP procedure

Information and display functions

 Status and error indications;


LEDs indicate hardware, programming, time, I/O and bus errors and operating statuses such as RUN, STOP
and starting.
 Test functions;
the PG is used to indicate signal status during program execution, to modify process variables
independently of the user program and to output the contents of stack memories.
Page 1683 Mar 2008 Siemens ITS
 Information functions;
the PG can be used to obtain information about the memory capacity and operating mode of the CPU, the
current loading of the work and load memory, current cycle times and diagnostics buffer content in plain text.

Integrated communication functions


 PG/OP communication
 Global data communication
 S7 basic communication
 S7 communication
 S5-compatible communication
 Routing
 PROFIBUS DP master/slave
 Open communication over TCP/IP, UDP and ISO-on-TCP (RFC1006)
 PROFINET IO controller
 PROFINET CBA
 System functions; the CPU offers a number of comprehensive system functions for diagnosis, parameterization,
synchronization, interrupts, time measurement, etc.
Further details can be found in the manual.

Communication

The safety related and standard communication between the central controller and the distributed stations takes
place over PROFIBUS DP and/or PROFINET. The specially developed PROFIsafe profile supports the transfer of
user data for the safety functions within the standard data message frame. Additional hardware components, e.g.
special safety buses are not required. The necessary software is either integrated in the hardware components as an
Page 1684
expansion Mar 2008
of the operating system or loaded into the CPU later as a certified software block. Siemens ITS
Mode of operation

The safety functions of the F-CPU are included in the F program of the CPU and in the fail-safe signal modules.
The signal modules monitor the output and input signals by means of discrepancy analysis and the injection of
test signals. CPU checks the proper operation of the controller by means of periodic self-tests, command tests
and logic-based and time-based program execution checks. Furthermore, the I/O is checked using requests for
signs of life.
If an error is diagnosed in the system, the system will be placed in a safe state.
An F runtime license is not required to operate the CPU 319F-3 PN/DP.

Programming

The CPU 319F-3 PN/DP is programmed in the same manner as the other SIMATIC S7 systems. The user
program for non-fail-safe plant sections is created using familiar programming tools, e.g. STEP 7.
SIMATIC S7 Distributed Safety option package
The STEP 7 option package "SIMATIC S7 Distributed Safety" is required for programming the safety-related
program components. The package contains all the functions and blocks required to create an F program.
The F program with the safety functions is connected in F FBD or F LAD or using special functions from the F
library. Use of F FBD or F LAD simplifies configuration and programming of the plant and also acceptance
testing thanks to the non-plant-specific uniform presentation form. The programmer can concentrate on
configuration of the safety-related application without the need to use additional tools.

Technical specifications
Page 1685 Mar 2008 Siemens ITS
6ES7 318-3FL00-0AB0
Product version
Hardware product version 03
Firmware version V2.8
General information
associated programming package STEP 7 V5.4 + SP5 or higher or STEP 7
V5.4 + SP4 or higher with HSP 186, S7
Distributed Safety V5.4 SP4 or higher
Supply voltage
24 V DC Yes
Input current
Current consumption (rated value) 1 050 mA
Current consumption (in no-load operation), 400 mA
typ.
Inrush current, typ. 4A
I²t 1.2 A²·s
Power losses
Power loss, typ. 14 W
Memory
Work memory
•integrated 1 400 Kibyte
•expandable No
•Size of retentive memory for retentive data 700 kbyte
blocks
Page 1686 Mar 2008 Siemens ITS
Load memory
•pluggable (MMC) Yes
•pluggable (MMC), max. 8 Mbyte
•Data management on MMC (after last 10 a
programming), min.
Backup
•present Yes; Guaranteed by MMC (maintenance-
free)
•without battery Yes; Program and data
CPU-blocks
Number of blocks (total) 4 096; (DBs, FCs, FBs); the maximum
number of loadable blocks can be reduced
by the MMC used.
DB
•Number, max. 4 096; Number range: 1 to 16000
•Size, max. 64 Kibyte
FB
•Number, max. 4 096; Number range: 0 to 7999
•Size, max. 64 Kibyte
FC
•Number, max. 4 096; Number range: 0 to 7999
•Size, max. 64 Kibyte
OB
•Size, max.
Page 1687 64 Kibyte
Mar 2008 Siemens ITS
Nesting depth
•per priority class 16
•additional within an error OB 4
CPU processing times
for bit operations, min. 0.01 µs
for word operations, min. 0.02 µs
for fixed point arithmetic, min. 0.02 µs
for floating point arithmetic, min. 0.04 µs
Counters, timers and their retentivity
S7 counter
•Number 2 048
•Retentivity
Yes
• adjustable
0
• lower limit
2 047
• upper limit
Z 0 to Z 7
• preset
•Counting range
Yes
• adjustable
Page 1688
0
Mar 2008 Siemens ITS
• lower limit
999
• upper limit
IEC counter
•present Yes
•Type SFB
•Number Unlimited (limited only by RAM capacity)
S7 times
•Number 2 048
•Retentivity
Yes
• adjustable
0
• lower limit
2 047
• upper limit
No retentivity
• preset
•Time range
10 ms
• lower limit
9 990 s
• upper limit
IECPage
timer
1689 Mar 2008 Siemens ITS
•present Yes
•Type SFB
•Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All, max. 700 KB
Flag
•Number, max. 8 192 byte
•Retentivity available Yes; MB 0 to MB 8191
•Retentivity preset MB 0 to MB 15
•Number of clock memories 8; 1 memory byte
Data blocks
•Retentivity adjustable Yes; via non-retain property on DB
•Retentivity preset Yes
Local data
•per priority class, max. 32 768 byte; Max. 2048 bytes per block
Address area
I/O address area
•Inputs 8 192 byte
•Outputs 8 192 byte
•of which, distributed
8 192 byte
• Inputs
8 192 byte
• Outputs
Page 1690 Mar 2008 Siemens ITS
Process image
•Inputs, adjustable 8 192 byte
•Outputs, adjustable 8 192 byte
•Inputs, default 1 024 byte
•Outputs, default 1 024 byte
Subprocess images
•Number of subprocess images, max. 1
Digital channels
•Inputs 65 536
•Outputs 65 536
•Inputs, of which central 1 024
•Outputs, of which central 1 024
Analog channels
•Inputs 4 096
•Outputs 4 096
•Inputs, of which central 256
•Outputs, of which central 256
Hardware configuration
Racks, max. 4
Modules per rack, max. 8
Number of DP masters
•integrated 2
•via CP 4
Number of operable FMs and CPs
Page 1691 Mar 2008 Siemens ITS
(recommended)
•FM 8
•CP, point-to-point 8
•CP, LAN 10
Time of day
Clock
•Hardware clock (real-time clock) Yes
•battery-backed and synchronizable Yes
•Deviation per day, max. 10 s
•Backup time 6 wk; At 40 °C ambient temperature
•Behavior of the clock following expiry of Clock continues to run with the time at
backup period which the power failure occurred
Operating hours counter
•Number 4
•Number/Number range 0 to 3
•Range of values 0 to 2^31 hours (when using SFC 101)
•Granularity 1 hour
•retentive Yes; Must be restarted at each restart
Clock synchronization
•supported Yes
•to MPI, master Yes
•to MPI, slave Yes
•to DP, master Yes; With DP slave only slave clock
•to Page
DP, 1692
slave Yes
Mar 2008 Siemens ITS
•in AS, master Yes
•in AS, slave Yes
•on Ethernet via NTP Yes; as client
1st interface
Type of interface Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), 150 mA
max.
Functionality
•MPI Yes
•DP master Yes
•DP slave Yes
•Point-to-point connection No
MPI
•Number of connections 32
•Services
Yes
• PG/OP communication
Yes
• Routing
Yes
• Global data communication
Page 1693 Yes
Mar 2008 Siemens ITS
• S7 basic communication
Yes
• S7 communication
No; but via CP and loadable FB
• S7 communication, as client
Yes
• S7 communication, as server
•Transmission rate, max. 12 Mbit/s
DP master
•Services
Yes
• PG/OP communication
No
• Global data communication
Yes; I blocks only
• S7 basic communication
Yes
• S7 communication
No
• S7 communication, as client
Yes
• S7 communication, as server
Yes
• Equidistance
Page 1694 mode support Mar 2008 Siemens ITS
No
• Isochronous mode
Yes
• SYNC/FREEZE
Yes
• Activation/deactivation of DP slaves
8
• Number of DP slaves that can be
simultaneously activated/deactivated,
max.
Yes; As subscriber
• Direct data exchange (slave-to-slave
communication)
Yes
• DPV1
•Transmission rate, max. 12 Mbit/s
•Number of DP slaves, max. 124
•Address area
8 Kibyte
• Inputs, max.
8 Kibyte
• Outputs, max.
•User data per DP slave
Page 1695 244
Mar 2008 byte Siemens ITS
• Inputs, max.
244 byte
• Outputs, max.
DP slave
•Services
Yes
• PG/OP communication
No
• Global data communication
No
• S7 basic communication
Yes
• S7 communication
No
• S7 communication, as client
Yes; Connection configured on one side
• S7 communication, as server only
Yes
• Direct data exchange (slave-to-slave
communication)
No
• DPV1
•Transmission rate, max. 12 Mbit/s
•Automatic baud rate search
Page 1696 Yes; only with passive interface
Mar 2008 Siemens ITS
•Transfer memory
244 byte
• Inputs
244 byte
• Outputs
•Address area, max. 32
•User data per address area, max. 32 byte
2nd interface
Type of interface Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), 200 mA
max.
Functionality
•MPI No
•DP master Yes
•DP slave Yes
•PROFINET IO Controller No
•PROFINET IO Device No
•PROFINET CBA No
•Local Operating Network No
DP master
•Services
Page 1697 Yes
Mar 2008 Siemens ITS
• PG/OP communication
No
• Global data communication
Yes; I blocks only
• S7 basic communication
Yes
• S7 communication
No
• S7 communication, as client
Yes; Connection
• S7 communication, as server
Yes
• Equidistance mode support
Yes; OB 61
• Isochronous mode
Yes
• SYNC/FREEZE
Yes
• Activation/deactivation of DP slaves
8
• Number of DP slaves that can be
simultaneously activated/deactivated,
max.
Page 1698 Yes;
Mar 2008 As subscriber Siemens ITS
• Direct data exchange (slave-to-slave
communication)
Yes
• DPV1
•Transmission rate, max. 12 Mbit/s
•Number of DP slaves, max. 124
•Address area
8 Kibyte
• Inputs, max.
8 Kibyte
• Outputs, max.
•User data per DP slave
244 byte
• Inputs, max.
244 byte
• Outputs, max.
DP slave
•Services
Yes
• PG/OP communication
No
• Global data communication
No
• S7
Page basic
1699 communication Mar 2008 Siemens ITS
Yes
• S7 communication
No
• S7 communication, as client
Yes; Connection configured on one side
• S7 communication, as server only
Yes
• Direct data exchange (slave-to-slave
communication)
No
• DPV1
•GSD file The latest GSD file is available at:
http://www.siemens.de/profibus-gsd
•Transmission rate, max. 12 Mbit/s
•Automatic baud rate search Yes; only with passive interface
•Transfer memory
244 byte
• Inputs
244 byte
• Outputs
•Address area, max. 32
•User data per address area, max. 32 byte
3rd interface
TypePage
of 1700
interface PROFINET
Mar 2008 Siemens ITS
Physics Ethernet RJ45
Isolated Yes
Integrated switch No
Number of ports 1
Automatic detection of transmission speed Yes; 10/100 Mbit/s
Autonegotiation Yes
Autocrossing Yes
Functionality
•MPI No
•DP master No
•DP slave No
•PROFINET IO Controller Yes
•PROFINET IO Device No
•PROFINET CBA Yes
•Local Operating Network No
PROFINET IO Controller
•Services
Yes
• PG/OP communication
Yes; with loadable FBs, max. configurable
• S7 communication connections: 16, max. number of instances:
32
No
• Isochronous
Page 1701 mode Mar 2008 Siemens ITS
Yes; Via TCP/IP, ISO on TCP, and UDP
• Open IE communication
•Transmission rate, max. 100 Mbit/s
•Number of connectable IO devices, max. 256
•Max. number of connectable IO devices 256
for RT
256
• of which in line, max.
•Number of IO devices with IRT and the 256
option "high flexibility"
61
• of which in line, max.
•Prioritized startup supported Yes
32
• Number of IO Devices, max.
•Activation/deactivation of IO Devices Yes
8
• Number of IO Devices that can be
simultaneously activated/deactivated,
max.
•IO Devices changing during operation Yes
(partner ports), supported
8
• Max.
Page 1702 number of IO devices per Mar tool2008 Siemens ITS
•Device replacement without swap medium Yes
•Send cycles 250 µs, 500µs, 1 ms
•Updating time 250 µs - 128 ms (with send cycle of 250
µs); 500 µs - 256 ms (with send cycle of
500 µs); 1 ms - 512 ms (with send cycle
1 ms); minimum value of the send cycle is
also dependent on the set communication
share for PROFINET IO, on the number of
I/O devices, and on the volume of
configured user data.
•Address area
8 Kibyte
• Inputs, max.
8 Kibyte
• Outputs, max.
•User data per address area, max.
254 byte
• User data consistency, max.
Open IE communication
•Open IE communication, supported Yes
•Number of connections, max. 32
•Local port numbers used at the system end0, 20, 21, 23, 25, 80, 102, 135, 161, 8080,
34962, 34963, 34964, 65532, 65533, 65534,
Page 1703 65535
Mar 2008 Siemens ITS
Communication functions
PG/OP communication Yes
Data record routing Yes
Global data communication
•supported Yes
•Number of GD loops, max. 8
•Number of GD packets, max. 8
•Number of GD packets, transmitter, max. 8
•Number of GD packets, receiver, max. 8
•Size of GD packets, max. 22 byte
•Size of GD packet (of which consistent), 22 byte
max.
S7 basic communication
•supported Yes
•User data per job, max. 76 byte
•User data per job (of which consistent), 76 byte; 76 bytes (with X_SEND or
max. X_RCV); 64 bytes (with X_PUT or
X_GET as server)
S7 communication
•supported Yes
•as server Yes
•as client Yes; via integrated PROFINET interface and
loadable FB or via CP and loadable FB
•User data
Page per job, max.
1704 See online help of STEP 7 (shared
Mar 2008 Siemens) ITS
parameters of the SFBs/FBs and of the
SFCs/FCs of S7 Communication)
S5-compatible communication
•supported Yes; via CP and loadable FC
Open IE communication
•TCP/IP Yes; via integrated PROFINET interface and
loadable FBs
32
• Number of connections, max.
1 460 byte
• Data length for connection type
01H, max.
8 192 byte
• Data length for connection type
11H, max.
•ISO-on-TCP (RFC1006) Yes; via integrated PROFINET interface and
loadable FBs
32
• Number of connections, max.
8 192 byte
• Data length, max.
•UDP Yes; via integrated PROFINET interface and
loadable FBs
Page 1705 32
Mar 2008 Siemens ITS
• Number of connections, max.
1 472 byte
• Data length, max.
Web server
•supported Yes; only read function
•Number of HTTP clients 5
PROFINET CBA (at set setpoint
communication load)
•Setpoint for the CPU communication load 20 %
•Number of remote interconnection partners 32
•Number of functions, master/slave 50
•Total of all Master/Slave connections 3 000
•Data length of all incoming connections 24 000 byte
master/slave, max.
•Data length of all outgoing connections 24 000 byte
master/slave, max.
•Number of device-internal and PROFIBUS 1 000
interconnections
•Data length of device-internal und 8 000 byte
PROFIBUS interconnections, max.
•Data length per connection, max. 1 400 byte
•Remote interconnections with acyclic
transmission
Page 1706 200 ms
Mar 2008 Siemens ITS
• Sampling frequency: Sampling time,
min.
100
• Number of incoming
interconnections
100
• Number of outgoing interconnections
3 200 byte
• Data length of all incoming
interconnections, max.
3 200 byte
• Data length of all outgoing
interconnections, max.
1 400 byte
• Data length per connection, max.
•Remote interconnections with cyclic
transmission
1 ms
• Transmission frequency:
Transmission interval, min.
300
• Number of incoming
interconnections
Page 1707 300
Mar 2008 Siemens ITS
• Number of outgoing interconnections
4 800 byte
• Data length of all incoming
interconnections, max.
4 800 byte
• Data length of all outgoing
interconnections, max.
250 byte
• Data length per connection, max.
•HMI variables via PROFINET (acyclic)
3; 2x PN OPC/1x iMap
• Number of stations that can log on
for HMI variables (PN OPC/iMap)
500 ms
• HMI variable updating
600
• Number of HMI variables
9 600 byte
• Data length of all HMI variables,
max.
•PROFIBUS proxy functionality
Yes
• supported
Page 1708 32
Mar 2008 Siemens ITS
• Number of linked PROFIBUS
devices
240 byte; Slave-dependent
• Data length per connection, max.
Number of connections
•Max. total number of instances 32
•usable for routing X1 as MPI: max. 10; X1 as DP master:
max. 24; X1 as DP slave (active): max.
14; X2 as DP master: max. 24; X2 as DP
slave (active): max. 14; X3 as PROFINET:
48 max.
S7 message functions
Number of login stations for message 32; Depending on the configured
functions, max. connections for PG/OP and S7 basic
communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Test commissioning functions
Status/control
•Status/control variable Yes
•Variables Inputs, outputs, memory bits, DB, times,
counters
•Number of variables, max.
Page 1709 30
Mar 2008 Siemens ITS
•of which status variables, max. 30
•of which control variables, max. 14
Forcing
•Forcing Yes
•Force, variables Inputs, outputs
•Number of variables, max. 10
Status block Yes; Up to 2 simultaneously
Single step Yes
Number of breakpoints 4
Diagnostic buffer
•present Yes
•Number of entries, max. 500
No
• adjustable
100
• Of which powerfail-proof
•Number of entries readable in RUN, max.
Yes; From 10 to 499
• adjustable
10
• preset
Isochronous mode
Isochronous mode Yes; Via 2nd DP interface
Ambient conditions
Page 1710 Mar 2008 Siemens ITS
Operating temperature
•Min. 0 °C
•max. 60 °C
Configuration
programming
•Programming language
Yes
• LAD
Yes
• FBD
Yes
• STL
Yes
• SCL
Yes
• CFC
Yes
• GRAPH
Yes
• HiGraph®
•Command set see instruction list
•Nesting levels 8
Know-how protection
protection
Page 1711 Mar 2008 Siemens ITS
protection
Dimensions
Width 120 mm
Height 125 mm
Depth 130 mm
Weight
Weight, approx. 1 250 g

6ES7 318-3FL01-0AB0
Product version
Hardware product version 01
Firmware version V3.2
General information
associated programming package STEP 7 V 5.5 or higher, Distributed Safety
V 5.4 SP4
Supply voltage
24 V DC Yes
Input current
Current consumption (rated value) 1 250 mA
Current consumption (in no-load operation), 500 mA
typ.
Inrush current, typ. 4A
I²t 1.2 A²·s
PowerPagelosses
1712 Mar 2008 Siemens ITS
Power loss, typ. 14 W
Memory
Work memory
•integrated 2 560 Kibyte
•expandable No
•Size of retentive memory for retentive data 700 Kibyte
blocks
Load memory
•pluggable (MMC) Yes
•pluggable (MMC), max. 8 Mbyte
•Data management on MMC (after last 10 a
programming), min.
Backup
•present Yes
•without battery Yes
CPU-blocks
Number of blocks (total) 4 096; (DBs, FCs, FBs); the maximum
number of loadable blocks can be reduced
by the MMC used.
DB
•Number, max. 4 096; Number range: 1 to 16000
•Size, max. 64 Kibyte
FB
•Number, max.
Page 1713 4 096; Number range: 0 to 7999
Mar 2008 Siemens ITS
•Size, max. 64 Kibyte
FC
•Number, max. 4 096; Number range: 0 to 7999
•Size, max. 64 Kibyte
OB
•Size, max. 64 Kibyte
Nesting depth
•per priority class 16
•additional within an error OB 4
CPU processing times
for bit operations, min. 0.004 µs
for word operations, min. 0.01 µs
for fixed point arithmetic, min. 0.01 µs
for floating point arithmetic, min. 0.04 µs
Counters, timers and their retentivity
S7 counter
•Number 2 048
•Retentivity
Yes
• adjustable
0
• lower limit
2 047
• upper limit Mar 2008
Page 1714 Siemens ITS
Z 0 to Z 7
• preset
•Counting range
Yes
• adjustable
0
• lower limit
999
• upper limit
IEC counter
•present Yes
•Type SFB
•Number Unlimited (limited only by RAM capacity)
S7 times
•Number 2 048
•Retentivity
Yes
• adjustable
0
• lower limit
2 047
• upper limit
No retentivity
• preset
Page 1715 Mar 2008 Siemens ITS
•Time range
10 ms
• lower limit
9 990 s
• upper limit
IEC timer
•present Yes
•Type SFB
•Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All, max. 700 KB
Flag
•Number, max. 8 192 byte
•Retentivity available Yes; MB 0 to MB 8191
•Retentivity preset MB 0 to MB 15
•Number of clock memories 8; 1 memory byte
Data blocks
•Retentivity adjustable Yes; via non-retain property on DB
•Retentivity preset Yes
Local data
•per priority class, max. 32 768 byte; Max. 2048 bytes per block
Address area
I/O address area
•Inputs
Page 1716 8 192
Mar 2008 byte Siemens ITS
•Outputs 8 192 byte
•of which, distributed
8 192 byte
• Inputs
8 192 byte
• Outputs
Process image
•Inputs, adjustable 8 192 byte
•Outputs, adjustable 8 192 byte
•Inputs, default 1 024 byte
•Outputs, default 1 024 byte
Subprocess images
•Number of subprocess images, max. 1; With PROFINET IO, the length of the
user data is limited to 1600 bytes
Digital channels
•Inputs 65 536
•Outputs 65 536
•Inputs, of which central 1 024
•Outputs, of which central 1 024
Analog channels
•Inputs 4 096
•Outputs 4 096
•Inputs, of which central 256
•Outputs, of which central
Page 1717 256
Mar 2008 Siemens ITS
Hardware configuration
Racks, max. 4
Modules per rack, max. 8
Number of DP masters
•integrated 2
•via CP 4
Number of operable FMs and CPs
(recommended)
•FM 8
•CP, point-to-point 8
•CP, LAN 10
Time of day
Clock
•Hardware clock (real-time clock) Yes
•battery-backed and synchronizable Yes
•Deviation per day, max. 10 s; Typ.: 2 s
•Backup time 6 wk; At 40 °C ambient temperature
•Behavior of the clock following POWER- Clock continues running after POWER OFF
ON
•Behavior of the clock following expiry of Clock continues to run with the time at
backup period which the power failure occurred
Operating hours counter
•Number 4
•Number/Number
Page 1718 range 0 to 3
Mar 2008 Siemens ITS
•Range of values 0 to 2^31 hours (when using SFC 101)
•Granularity 1 hour
•retentive Yes; Must be restarted at each restart
Clock synchronization
•supported Yes
•to MPI, master Yes
•to MPI, slave Yes
•to DP, master Yes; With DP slave only slave clock
•to DP, slave Yes
•in AS, master Yes
•in AS, slave Yes
•on Ethernet via NTP Yes; as client
1st interface
Type of interface Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V 150 mA
DC), max.
Functionality
•MPI Yes
•DP master Yes
•DP slave Yes
•Point-to-point connection No
MPIPage 1719 Mar 2008 Siemens ITS
•Services
Yes
• PG/OP communication
Yes
• Routing
Yes
• Global data communication
Yes
• S7 basic communication
Yes
• S7 communication
No; but via CP and loadable FB
• S7 communication, as client
Yes
• S7 communication, as server
•Transmission rate, max. 12 Mbit/s
DP master
•Services
Yes
• PG/OP communication
No
• Global data communication
Yes; I blocks only
• S7
Page basic
1720 communication Mar 2008 Siemens ITS
Yes
• S7 communication
No
• S7 communication, as client
Yes
• S7 communication, as server
Yes
• Equidistance mode support
No
• Isochronous mode
Yes
• SYNC/FREEZE
Yes
• Activation/deactivation of DP slaves
8
• Number of DP slaves that can be
simultaneously activated/deactivated,
max.
Yes; As subscriber
• Direct data exchange (slave-to-slave
communication)
Yes
• DPV1
•Transmission
Page 1721 rate, max. 12 Mbit/s
Mar 2008 Siemens ITS
•Number of DP slaves, max. 124
•Address area
8 Kibyte
• Inputs, max.
8 Kibyte
• Outputs, max.
•User data per DP slave
244 byte
• Inputs, max.
244 byte
• Outputs, max.
DP slave
•Services
Yes
• PG/OP communication
No
• Global data communication
No
• S7 basic communication
Yes
• S7 communication
No
• S7 communication, as client
Page 1722 Yes;
Mar 2008 Connection configured onSiemens
one side
ITS
• S7 communication, as server only
Yes
• Direct data exchange (slave-to-slave
communication)
No
• DPV1
•Transmission rate, max. 12 Mbit/s
•Automatic baud rate search Yes; only with passive interface
•Transfer memory
244 byte
• Inputs
244 byte
• Outputs
•Address area, max. 32
•User data per address area, max. 32 byte
2nd interface
Type of interface Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V 200 mA
DC), max.
Functionality
•MPI No
•DPPage
master
1723 Yes
Mar 2008 Siemens ITS
•DP slave Yes
•PROFINET IO Controller No
•PROFINET IO Device No
•PROFINET CBA No
DP master
•Services
Yes
• PG/OP communication
No
• Global data communication
Yes; I blocks only
• S7 basic communication
Yes
• S7 communication
No
• S7 communication, as client
Yes; Connection configured on one side
• S7 communication, as server only
Yes
• Equidistance mode support
Yes; OB 61 - isochronous mode is possible
• Isochronous mode either on DP or PROFINET IO (not
simultaneously)
Page 1724 Yes
Mar 2008 Siemens ITS
• SYNC/FREEZE
Yes
• Activation/deactivation of DP slaves
8
• Number of DP slaves that can be
simultaneously activated/deactivated,
max.
Yes; As subscriber
• Direct data exchange (slave-to-slave
communication)
Yes
• DPV1
•Transmission rate, max. 12 Mbit/s
•Number of DP slaves, max. 124
•Address area
8 Kibyte
• Inputs, max.
8 Kibyte
• Outputs, max.
•User data per DP slave
244 byte
• Inputs, max.
244 byte
• Outputs,
Page 1725 max. Mar 2008 Siemens ITS
DP slave
•Services
Yes
• PG/OP communication
No
• Global data communication
No
• S7 basic communication
Yes
• S7 communication
No
• S7 communication, as client
Yes; Connection configured on one side
• S7 communication, as server only
Yes
• Direct data exchange (slave-to-slave
communication)
No
• DPV1
•GSD file The latest GSD file is available at:
http://www.siemens.de/profibus-gsd
•Transmission rate, max. 12 Mbit/s
•Automatic baud rate search Yes; only with passive interface
•Transfer memory
Page 1726 Mar 2008 Siemens ITS
244 byte
• Inputs
244 byte
• Outputs
•Address area, max. 32
•User data per address area, max. 32 byte
3rd interface
Type of interface PROFINET
Physics Ethernet RJ45
Isolated Yes
Integrated switch Yes
Number of ports 2
Automatic detection of transmission speed Yes; 10/100 Mbit/s
Autonegotiation Yes
Autocrossing Yes
Media redundancy
•supported Yes
•Switchover time on line break, typically 200 ms; PROFINET MRP
•Number of stations in the ring, max. 50
Change of IP address at runtime, supported Yes
Functionality
•MPI No
•DP master No
•DPPage
slave
1727 No
Mar 2008 Siemens ITS
•PROFINET IO Controller Yes; Also simultaneously with I-Device
functionality
•PROFINET IO Device Yes; Also simultaneously with IO Controller
functionality
•PROFINET CBA Yes
PROFINET IO Controller
•Services
Yes
• PG/OP communication
Yes; with loadable FBs, max. configurable
• S7 communication connections: 16, max. number of instances:
32
Yes; OB 61 - isochronous mode is possible
• Isochronous mode either on DP or PROFINET IO (not
simultaneously)
Yes; Via TCP/IP, ISO on TCP, and UDP
• Open IE communication
•Transmission rate, max. 100 Mbit/s
•Number of connectable IO devices, max. 256
•Max. number of connectable IO devices 256
for RT
256
• of which in line, max.
•Number of IO devices with IRT and theMar 2008
Page 1728 256 Siemens ITS
option "high flexibility"
61
• of which in line, max.
•Number of IO Devices with IRT and the 64
option "high performance", max.
64
• of which in line, max.
•Shared device, supported Yes
•Prioritized startup supported Yes
32
• Number of IO Devices, max.
•Activation/deactivation of IO Devices Yes
8
• Number of IO Devices that can be
simultaneously activated/deactivated,
max.
•IO Devices changing during operation Yes
(partner ports), supported
8
• Max. number of IO devices per tool
•Device replacement without swap medium Yes
•Send cycles 250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in
the case of IRT with "high flexibility"
Page 1729
option)
Mar 2008 Siemens ITS
•Updating time 250 µs to 512 ms (depending on the
operating mode, see Manual "S7-300 CPU
31xC and CPU 31x, Technical Data" for
more details)
•Address area
8 Kibyte
• Inputs, max.
8 Kibyte
• Outputs, max.
•User data per address area, max.
1 024 byte
• User data consistency, max.
PROFINET IO Device
•Services
Yes
• PG/OP communication
Yes
• Routing
Yes; with loadable FBs, max. configurable
• S7 communication connections: 16, max. number of instances:
32
No
• Isochronous mode
Page 1730 Yes;
Mar 2008 Via TCP/IP, ISO on TCP,Siemens
and UDP
ITS
• Open IE communication
Yes
• IRT, supported
Yes; With SFB 73 / 74 prepared for
• PROFIenergy, supported loadable PROFIenergy standard FB for I-
Device
Yes
• Shared device, supported
2
• Number of IO controllers with
shared device, max.
•Transfer memory
1 440 byte; Per IO Controller with shared
• Inputs, max. device
1 440 byte; Per IO Controller with shared
• Outputs, max. device
•Submodules
64
• Number, max.
1 024 byte
• User data per submodule, max.
Open IE communication
•Open IE communication, supported Yes
•Number of connections, max.
Page 1731 32
Mar 2008 Siemens ITS
•Local port numbers used at the system end0, 20, 21, 23, 25, 80, 102, 135, 161, 8080,
34962, 34963, 34964, 65532, 65533, 65534,
65535
•Keep-alive function, supported Yes
Communication functions
PG/OP communication Yes
Data record routing Yes
Global data communication
•supported Yes
•Number of GD loops, max. 8
•Number of GD packets, max. 8
•Number of GD packets, transmitter, max. 8
•Number of GD packets, receiver, max. 8
•Size of GD packets, max. 22 byte
•Size of GD packet (of which consistent), 22 byte
max.
S7 basic communication
•supported Yes
•User data per job, max. 76 byte
•User data per job (of which consistent), 76 byte; 76 bytes (with X_SEND or
max. X_RCV); 64 bytes (with X_PUT or
X_GET as server)
S7 communication
•supported
Page 1732 Yes
Mar 2008 Siemens ITS
•as server Yes
•as client Yes; via integrated PROFINET interface and
loadable FB or via CP and loadable FB
•User data per job, max. See online help of STEP 7 (shared
parameters of the SFBs/FBs and of the
SFCs/FCs of S7 Communication)
S5-compatible communication
•supported Yes; via CP and loadable FC
Open IE communication
•TCP/IP Yes; via integrated PROFINET interface and
loadable FBs
32
• Number of connections, max.
1 460 byte
• Data length for connection type
01H, max.
32 768 byte
• Data length for connection type
11H, max.
•ISO-on-TCP (RFC1006) Yes; via integrated PROFINET interface and
loadable FBs
32
• Number of connections, max.
Page 1733 32 768
Mar 2008 byte Siemens ITS
• Data length, max.
•UDP Yes; via integrated PROFINET interface and
loadable FBs
32
• Number of connections, max.
1 472 byte
• Data length, max.
Web server
•supported Yes
•Number of HTTP clients 5
•User-defined websites Yes
PROFINET CBA (at set setpoint
communication load)
•Setpoint for the CPU communication load 20 %
•Number of remote interconnection partners 32
•Number of functions, master/slave 50
•Total of all Master/Slave connections 3 000
•Data length of all incoming connections 24 000 byte
master/slave, max.
•Data length of all outgoing connections 24 000 byte
master/slave, max.
•Number of device-internal and PROFIBUS 1 000
interconnections
•Data length
Page 1734 of device-internal und 8 000 byte
Mar 2008 Siemens ITS
PROFIBUS interconnections, max.
•Data length per connection, max. 1 400 byte
•Remote interconnections with acyclic
transmission
200 ms
• Sampling frequency: Sampling time,
min.
100
• Number of incoming
interconnections
100
• Number of outgoing interconnections
3 200 byte
• Data length of all incoming
interconnections, max.
3 200 byte
• Data length of all outgoing
interconnections, max.
1 400 byte
• Data length per connection, max.
•Remote interconnections with cyclic
transmission
1 ms
• Transmission
Page 1735 frequency: Mar 2008 Siemens ITS
Transmission interval, min.
300
• Number of incoming
interconnections
300
• Number of outgoing interconnections
4 800 byte
• Data length of all incoming
interconnections, max.
4 800 byte
• Data length of all outgoing
interconnections, max.
450 byte
• Data length per connection, max.
•HMI variables via PROFINET (acyclic)
3; 2x PN OPC/1x iMap
• Number of stations that can log on
for HMI variables (PN OPC/iMap)
500 ms
• HMI variable updating
600
• Number of HMI variables
9 600 byte
• Data
Page 1736 length of all HMI variables,Mar 2008 Siemens ITS
max.
•PROFIBUS proxy functionality
Yes
• supported
32
• Number of linked PROFIBUS
devices
240 byte; Slave-dependent
• Data length per connection, max.
Number of connections
•Max. total number of instances 32
•usable for routing X1 as MPI: max. 10; X1 as DP master:
max. 24; X1 as DP slave (active): max.
14; X2 as DP master: max. 24; X2 as DP
slave (active): max. 14; X3 as PROFINET:
48 max.
S7 message functions
Number of login stations for message 32; Depending on the configured
functions, max. connections for PG/OP and S7 basic
communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Test commissioning functions
Status/control
Page 1737 Mar 2008 Siemens ITS
•Status/control variable Yes
•Variables Inputs, outputs, memory bits, DB, times,
counters
•Number of variables, max. 30
•of which status variables, max. 30
•of which control variables, max. 14
Forcing
•Forcing Yes
•Force, variables Inputs, outputs
•Number of variables, max. 10
Status block Yes; Up to 2 simultaneously
Single step Yes
Number of breakpoints 4
Diagnostic buffer
•present Yes
•Number of entries, max. 500
No
• adjustable
100
• Of which powerfail-proof
•Number of entries readable in RUN, max. 499
Yes; From 10 to 499
• adjustable
Page 1738 10
Mar 2008 Siemens ITS
• preset
Isochronous mode
Isochronous mode Yes; Via 2nd PROFIBUS DP or
PROFINET interface
Ambient conditions
Operating temperature
•Min. 0 °C
•max. 60 °C
Configuration
programming
•Programming language
Yes
• LAD
Yes
• FBD
Yes
• STL
Yes
• SCL
Yes
• CFC
Yes
• GRAPH
Page 1739 Yes
Mar 2008 Siemens ITS
• HiGraph®
•Command set see instruction list
•Nesting levels 8
Know-how protection
•User program protection/password Yes
protection
•Block encryption Yes; With S7 block Privacy
Dimensions
Width 120 mm
Height 125 mm
Depth 130 mm
Weight
Weight, approx. 1 250 g