SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1

DATE: 3/8/2018D:\CALCULOS HIDRAULICOS\2018\03. ALMACEN MILI\ALMACEN K11.2.SDF


JOB TITLE: Almacen rociadores k11.2
WATER SUPPLY DATA

SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D


NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)

17 (N/A) 0.0 (N/A) 0.0 499.0 66.1

AGGREGATE FLOW ANALYSIS:

TOTAL FLOW AT SOURCE 499.0 GPM


TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 499.0 GPM

NODE ANALYSIS DATA


NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)

1 23.0 - - - - 46.0 - - -
2 23.0 K=11.20 34.2 65.5
3 23.0 K=11.20 31.2 62.6
4 23.0 K=11.20 30.1 61.5
5 23.0 - - - - 30.1 - - -
6 23.0 - - - - 46.2 - - -
7 23.0 K=11.20 31.4 62.7
8 23.0 K=11.20 30.1 61.5
9 23.0 K=11.20 30.0 61.3
10 23.0 - - - - 30.1 - - -
11 23.0 - - - - 46.9 - - -
12 23.0 K=11.20 31.1 62.5
13 23.0 K=11.20 30.1 61.5
14 23.0 - - - - 30.1 - - -
15 23.0 - - - - 54.1 - - -
16 23.0 - - - - 61.5 - - -
17 23.0 SOURCE 66.1 499.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 3/8/2018D:\CALCULOS HIDRAULICOS\2018\03. ALMACEN MILI\ALMACEN K11.2.SDF
JOB TITLE: Almacen rociadores k11.2
PIPE DATA

PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.


END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)

Pipe: 1 -208.0 2.067 PL 32.53 PF 11.8


2 23.0 11.2 34.2 65.5 19.9 120 FTG ---- PE 0.0
1 23.0 0.0 46.0 0.0 0.364 TL 32.53 PV

Pipe: 2 -142.6 2.067 PL 16.41 PF 3.0


3 23.0 11.2 31.2 62.6 13.6 120 FTG ---- PE 0.0
2 23.0 11.2 34.2 65.5 0.181 TL 16.41 PV

Pipe: 3 -80.0 2.067 PL 17.00 PF 1.1


4 23.0 11.2 30.1 61.5 7.6 120 FTG ---- PE 0.0
3 23.0 11.2 31.2 62.6 0.062 TL 17.00 PV

Pipe: 4 -18.5 2.067 PL 8.14 PF 0.0


5 23.0 0.0 30.1 0.0 1.8 120 FTG ---- PE 0.0
4 23.0 11.2 30.1 61.5 0.004 TL 8.14 PV

Pipe: 5 208.0 4.026 PL 16.08 PF 0.2


6 23.0 0.0 46.2 0.0 5.2 120 FTG ---- PE 0.0
1 23.0 0.0 46.0 0.0 0.014 TL 16.08 PV

Pipe: 6 -151.1 2.067 PL 73.79 PF 14.9


7 23.0 11.2 31.4 62.7 14.4 120 FTG ---- PE 0.0
6 23.0 0.0 46.2 0.0 0.202 TL 73.79 PV

Pipe: 7 -88.4 2.067 PL 16.41 PF 1.2


8 23.0 11.2 30.1 61.5 8.5 120 FTG ---- PE 0.0
7 23.0 11.2 31.4 62.7 0.075 TL 16.41 PV

Pipe: 8 -26.9 2.067 PL 17.00 PF 0.1


9 23.0 11.2 30.0 61.3 2.6 120 FTG ---- PE 0.0
8 23.0 11.2 30.1 61.5 0.008 TL 17.00 PV

Pipe: 9 34.4 2.067 PL 8.14 PF 0.1


10 23.0 0.0 30.1 0.0 3.3 120 FTG ---- PE 0.0
9 23.0 11.2 30.0 61.3 0.013 TL 8.14 PV

Pipe: 10 18.5 4.026 PL 16.08 PF 0.0


5 23.0 0.0 30.1 0.0 0.5 120 FTG ---- PE 0.0
10 23.0 0.0 30.1 0.0 0.000 TL 16.08 PV

Pipe: 11 359.1 4.026 PL 16.89 PF 0.7


11 23.0 0.0 46.9 0.0 9.1 120 FTG ---- PE 0.0
6 23.0 0.0 46.2 0.0 0.039 TL 16.89 PV

Pipe: 12 -139.9 2.067 PL 90.20 PF 15.8


12 23.0 11.2 31.1 62.5 13.4 120 FTG ---- PE 0.0
11 23.0 0.0 46.9 0.0 0.175 TL 90.20 PV

Pipe: 13 -77.4 2.067 PL 17.07 PF 1.0


13 23.0 11.2 30.1 61.5 7.4 120 FTG ---- PE 0.0
12 23.0 11.2 31.1 62.5 0.059 TL 17.07 PV

Pipe: 14 -15.9 2.067 PL 8.14 PF 0.0


14 23.0 0.0 30.1 0.0 1.5 120 FTG ---- PE 0.0
13 23.0 11.2 30.1 61.5 0.003 TL 8.14 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 3/8/2018D:\CALCULOS HIDRAULICOS\2018\03. ALMACEN MILI\ALMACEN K11.2.SDF
JOB TITLE: Almacen rociadores k11.2
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)

Pipe: 15 -15.9 4.026 PL 16.89 PF 0.0


10 23.0 0.0 30.1 0.0 0.4 120 FTG ---- PE 0.0
14 23.0 0.0 30.1 0.0 0.000 TL 16.89 PV

Pipe: 16 -499.1 4.026 PL 100.37 PF 7.2


11 23.0 0.0 46.9 0.0 12.6 120 FTG ---- PE 0.0
15 23.0 0.0 54.1 0.0 0.072 TL 100.37 PV

Pipe: 17 499.1 4.026 PL 53.47 PF 7.4


16 23.0 0.0 61.5 0.0 12.6 120 FTG 5E PE 0.0
15 23.0 0.0 54.1 0.0 0.072 TL 103.47 PV

Pipe: 18 499.0 4.026 PL 22.96 PF 4.6


17 23.0 SRCE 66.1 (N/A) 12.6 120 FTG ETB PE 0.0
16 23.0 0.0 61.5 0.0 0.072 TL 64.96 PV

NOTES:

(1) Calculations were performed by the HASS 7.4 computer program


under license no. 2703113217 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084

(2) The system has been calculated to provide an average


imbalance at each node of 0.006 gpm and a maximum
imbalance at any node of 0.094 gpm.

(3) Total pressure at each node is used in balancing the system.


Maximum water velocity is 19.9 ft/sec at pipe 1.

(4) PIPE FITTINGS TABLE

Pipe Table Name: STANDARD.PIP

PAGE: A MATERIAL: S40 HWC: 120


Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
2.067 5.00 10.00 3.00 11.00 6.00 1.00 10.00 10.00 10.00
4.026 10.00 20.00 6.00 22.00 12.00 2.00 20.00 20.00 20.00
JOB TITLE: Almacen rociadores k11.2
DATE: 3/8/2018D:\CALCULOS HIDRAULICOS\2018\03. ALMACEN MILI\ALMACEN K11.2.SDF
WATER SUPPLY ANALYSIS
Fixed Source Pressure: 0.00 psi
80.0
LEGEND

70.0 Available pressure


1
2 0.00 psi @ 499.0 gpm
2 Required pressure
G

SPRINKLER SYSTEM HYDRAULIC ANALYSIS


66.13 psi @ 499.0 gpm
A 60.0
U
G
E
50.0
P
R
E
S 40.0
S
U
R
E 30.0

(
p
s 20.0
i
)
10.0

0.0 1

Page 4
-14.7
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 3/8/2018D:\CALCULOS HIDRAULICOS\2018\03. ALMACEN MILI\ALMACEN K11.2.SDF
JOB TITLE: Almacen rociadores k11.2
WATER SUPPLY CURVE

72+
|
|
|
66+ X
|
|
|
60+
|
|
|
54+
|
|
|
P 48+
R |
E |
S |
S 42+
U |
R |
E |
36+
( |
P |
S |
I 30+
) |
|
|
24+
|
|
|
18+
|
|
|==============================
12+ LEGEND "
| "
| X = Required Water Supply "
| 66.13 psi @ 499.0 gpm "
6+ "
| "
| "
| "
0*\\\\\\\\\\\\\\\\\+\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)

Vous aimerez peut-être aussi