Product 30HK,HL,HW

Reciprocating Liquid Chillers


Data 50/60 Hz
Nominal Capacities:
30HW 15 to 40 Tons (53 to 141 kW)
30HK 40 to 60 Tons (141 to 210 kW)
30HL 50 and 60 Tons (176 and 210 kW)

Economical, Easy-to-Install Packaged


Chillers Designed to Save Energy
• microprocessor control
• application versatility
• long range cost savings
• quiet, reliable operation

Features/Benefits
Installation ease
Units are designed to reduce installa-
tion time and costs. They arrive at the
jobsite able to fit easily through a
30HWC,S 30-in. (762 mm) (30HW units) or a
36-in. (914 mm) (30HK,HL units) wide
opening due to their compact design.
The 30HWB,HWC,HWS, and HK
units come complete with cooler, con-
denser(s), compressor(s), controls, re-
frigerant charge, and oil charge, and
need only the addition of a condenser
water supply, electrical power, and
chilled fluid distribution system.
The 30HWA and HL units are de-
signed for use with a remote condens-
er, and have a refrigerant holding
charge. They may be connected to
either air-cooled, evaporative condens-
er(s) or even water-cooled condenser(s)
sized to meet specific job re-
quirements.
30HWA,B
All internal piping and wiring is com-
plete, and since all essential controls
and protective devices are installed at
the factory, installation is completed in
minimal time. Units are UL (Underwrit-
ers’ Laboratories, U.S.A.) and UL,
Canada listed and conform to ASME
(American Society of Mechanical
Engineers) standards, simplifying the
final inspection process.

30HK,HL

Copyright 1999 Carrier Corporation Form 30H-7PD


ComfortLink™ control realize even greater overall system to match changing cooling load
Your link to a world of simple and easy energy savings in the chilled water requirements.
to use air-cooled chillers that offer out- pumping system of up to 85%, and not Compressors are mounted on
standing performance and value. The just at the chiller. Leaving temperature heavy-duty spring vibration isolators to
30HK,HL,HW liquid chillers employ set point can be set to within 0.1 F. minimize vibration transmission to the
more than the latest advanced micro- Energy management made building. Quiet operation is further as-
processor controls, they utilize an ex- easy sured by a hot gas muffler that damp-
pandable platform that grows as your ens hot gas pulsations and provides
needs change. From stand-alone oper- While 30HK,HL,HW chillers have smooth, trouble-free, quiet perfor-
ation to remotely monitored and oper- many standard features such as net- mance. To reduce sound even more,
ated multi-chiller plants, ComfortLink work communications capability and acoustic sound enclosures are available
controls can keep you plugged in. temperature reset based on return fluid as accessories.
temperature, they can also expand as
ComfortLink controls are fully com- needs change. Supply temperature re- Operating efficiency
municating, and are cable ready for set based on outside air or space tem-
connection to a Carrier Comfort Net- At full load, 30H chillers provide EERs
perature is as easy as adding a ther- (Energy Efficiency Ratios) up to 14.7.
work (CCN). Occupancy scheduling, mistor. The Energy Management op-
temperature and pressure read-outs, Multiple compressors on a refriger-
tion can allow you to take advantage of ant circuit (30HK,HL) enhance part-
and the ComfortLink scrolling mar- changing utility rate structures with
quee clear language display features load efficiency. Each circuit uses 100%
easy to use load shedding, demand lim- of the heat exchanger surface at all
are available, linking you to a world of iting and temperature reset capabili-
carefree comfort. times, optimizing performance at all
ties. Reset triggered via 4 to 20 mA loading conditions, especially part
Superior temperature control signal makes integrating from an exist- load. Since the chiller normally works
equals potential for greater ing building management system at part load for 97% of its operating
productivity simple. time, a substantial reduction in operat-
Operating reliability ing cost can be realized.
Whether in the classroom, on the pro-
duction floor, or in the office, Suction cutoff unloading — Un-
Carrier’s proven, serviceable, semi-
ComfortLink controls can help you to hermetic compressor(s) are standard loading eliminates unnecessary com-
adapt to changing weather and busi- pression of refrigerant gases during un-
on all units. In addition, standard solid- loaded operation. This substantially re-
ness conditions. Accurate temperature state electrical controls are fully tested
control provided by the Carrier and offer the utmost in reliability. duces part-load power consumption,
ComfortLink system helps to maintain resulting in an EER increase of as
higher levels of indoor air quality, ther- Standard dual refrigeration circuits much as 39.5% (at 33% load).
on 30HK,HL units save the day when
mal comfort, and space productivity. units are undergoing service and regu- Ease of service reduces cost
While many chillers use only leaving lar maintenance. Units can continue to When the 30H is in need of inspection
fluid temperature control, the operate at part load, avoiding a pro- and service, saving time is of the es-
30HK,HL,HW chillers utilize leaving longed shutdown of the entire system. sence. The reciprocating, semi-her-
fluids temperature control with a metic compressors and controls (solid-
standard entering fluid temperature Units have the capability to start and
pull down with up to 95 F (35 C) state electronic on all units) are familiar
compensation. This Carrier exclusive entering-fluid temperature due to the to technicians, so problems can be re-
provides smart control and intelligent solved quickly. The 30HWB,HWC,
machine capacity staging. Unlike many integral MOP (maximum operating
pressure) feature of the expansion HWS, and HK fluid-cooled units have
chillers, Carrier model 30HK,HL,HW valve. Multiple-step capacity control condensers that are cleanable to allow
chillers do not require constant fluid periodic maintenance, which helps to
flow. The ability to operate with vari- allows compressor(s) to load or unload
prolong the life of the system.
able flow also allows building owners to

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 ASME
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7 U STAMP
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 9 (60 Hz Only)
Base Unit Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-15
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-19
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21-40
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41-43
Control Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44-46
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47,48 UNDERWRITERS’
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49-51 LABORATORIES
(60 Hz Only)

2
Features/Benefits (cont)

30HWA,B COMPACT SIZE 30HK,HL WITH DUAL REFRIGERANT


CIRCUITS

06E SEMI-HERMETIC COMPRESSOR

°F
AT U R E 4 4 .1
MODE

T E M P E R Run Status
Service Test

L U ID
Temperature

L E AV IN G F
Pressures
Setpoints
Alarm Status
Inputs
Outputs
Configuration ESCAPE ENTER
Time Clock
Operating Modes
Alarms

AVAILABLE SCROLLING MARQUEE CLEAR LANGUAGE DISPLAY


(Standard on 60 Hz unit)

3
→ Model number nomenclature, 30HW units
30HW A 040 – C – 6 – 1 KA

30HW – Indoor Liquid Chiller Factory-Installed Options


KA – Standard,
No Options
NOTE: For Brine, Sound
Cooler Condenser Enclosure, Mobility Package
A – Brazed-Plate None (HWA/B only),
B – Brazed-Plate Brazed Plate Non-Fused Disconnect,
C – Brazed-Plate Shell-and-Tube with Part-Wind Start,
Copper Tubes (mechanically cleanable) Hot Gas Bypass,
S – Brazed-Plate Shell-and-Tube with Cupro-Nickel and other options,
Tubes and Tube Sheets and Zinc contact your Carrier
Anodes (mechanically cleanable) Representative.

Unit Size Packaging


018 1 – Domestic
025 3 – Export
028
035
040
V-Ph-Hz
1 – 575-3-60
2 – 380-3-60
Controls 5 – 208/230-3-60
C – ComfortLink™ Microprocessor Control with Quickset Single Dial Set Point* 6 – 460-3-60
D – ComfortLink Microprocessor Control with Scrolling Marquee Display† 9 – 380/415-3-50
E – 'D' with Energy Management Module

*Standard on 50 Hz unit.
†Standard on 60 Hz unit; factory-installed option on 50 Hz unit.


Model number nomenclature, 30HK,HL units
30HK – 060 – C – 6 0 1 --
30HK Packaging
Fluid-Cooled 1 – Domestic
Reciprocating 3 – Export
Liquid Chiller
Design Improvement
30HL 0 – Original
Condendserless 1-9 – Modification
Reciprocataing
Liquid Chiller
Volts-Phase-Hz
1 – 575-3-60
Refrigerant 5 – 208/230-3-60
- – R-22 6 – 460-3-60
8 – 230-3-50
9 – 380/415-3-50

Unit Size Controls


040* C – ComfortLink Microprocessor Control with Quickset Single Dial Set Point†
050 D – ComfortLink Microprocessor Control with Scrolling Marquee Display**
060 E – 'D' with Energy Management Module

*30HK only.
†Standard on 50 Hz unit.
**Standard on 60 Hz unit; factory-installed option on 50 Hz unit.

R
Rated in accordance with
ARI Standard 550/590-98.

(60 Hz Only)

4 403
Physical data — 30HWB,HWC,HWS,HK
fluid-cooled units
ENGLISH
UNIT 30 HW-018* HW-025* HW-028* HW-035* HW-040* HK040 HK050 HK060
OPERATING WT (Approximate) — lb
HWB 795 950 1065 1085 1310 — — —
HWC,S 1231 1359 1484 1508 1702 — — —
2830/ 2865/ 2980/
HK — — — — —
2875† 2980† 3020†
REFRIGERANT — lb R-22
HWB 12.5 15.0 17.5 18.5 30.0 — — —
HWC,S 35.0 37.0 42.0 42.0 47.0 — — —
HK — — — — — 70.0 80.0 90.0
COMPRESSOR — — — — — — — —
06E6175,
Model No. 06DG537 06E2150** 06E7265 06E7175** 06E7299 06E2150 06E6175
06E2150
Nominal Hp 15 20 25 30 35 20 (ea) 20,30 30 (ea)
Quantity 1 1 1 1 1 2 1 (ea) 2
Cylinders Per Compressor 6 4 6 6 6 4 (ea) 6,4 6 (ea)
Capacity Control — Standard
No. of Steps 3 2 3 3 3 4 4 4
Minimum Step Capacity (%) 33 50 33 33 33 25 20†† 33
Capacity Control — With Hot Gas Bypass
No. of Steps 4 3 4 4 4 5 5 5
Minimum Step Capacity (%) 10 10 10 10 10 10 10 10
COOLER
Fluid Side — psig 300 300 300 300 300 150 150 150
Refrigerant Side — psig 430 430 430 430 430 235 235 235
Net Fluid Volume — Gal. (includes nozzles) 1.4 1.6 2.1 2.1 3.3 13.1 15.2 15.2
Fluid Connections — in. Grooved End
Inlet 11/2 11/2 11/2 1
1 /2 21/2 3 3 3
Outlet 11/2 11/2 11/2 11/2 21/2 3 3 3
CONDENSER
30HWB (Water Cooled)
Water Side — psig 300 300 300 300 300 — — —
Refrigerant Side — psig 430 430 430 430 430 — — —
Net Water Volume — Gal. (includes nozzles) 0.9 1.2 1.6 1.8 3.3 — — —
Water Connections — in. Grooved End
Inlet 11/2 11/2 11/2 1
1 /2 21/2 — — —
Outlet 11/2 11/2 11/2 11/2 21/2 — — —
30HWC (Water Cooled)
Water Side — psig 300 300 300 300 300 — — —
Refrigerant Side — psig 365 365 365 365 365 — — —
Net Water Volume — Gal. 2.6 2.6 4.0 4.0 7.3 — — —
Water Connections — in. Weld
Inlet 11/2 11/2 11/2 11/2 21/2 — — —
Outlet 11/2 11/2 11/2 11/2 21/2 — — —
30HWS (Water Cooled)
Water Side — psig 300 300 300 300 300 — — —
Refrigerant Side — psig 365 365 365 365 365 — — —
Net Water Volume — Gal. 2.6 2.6 4.0 4.0 7.3 — — —
Water Connections — in. Weld
Inlet 21/2 21/2 21/2 21/2 21/2 — — —
Outlet 21/2 21/2 21/2 21/2 21/2 — — —
30HK (Water Cooled)
Water Side — psig — — — — — 250 250 250
Refrigerant Side — psig — — — — — 385 385 385
Net Water Volume — Gal. (includes nozzles) — — — — — 4.4,4.4 4.4,5.2 5.2,5.2
Water Connections — in. Weld
Inlet — — — — — 21/2 21/2 21/2
Outlet — — — — — 21/2 21/2 21/2
LEGEND NOTES:
ODS — Outside Diameter, Sweat 1. Operating weight includes refrigerant operating charge and weight of fluid in
the heat exchangers.
*Unless otherwise noted, data is for 30HWB, HWC, and HWS units. 2. 30HWB,C,S, and 30HK units are shipped with full operating charge.
†60 Hz/50 Hz units.
**For size 025 50 Hz units, compressor number is 06E2250, for size 035 50 Hz
units compressor number is 06E7275.
††With transfer switch set to compressor no. 2 position; 40% with transfer switch
set to compressor no. 1 position.

5
Physical data — 30HWB,HWC,HWS,HK
fluid-cooled units (cont)
SI
UNIT 30 HW-018* HW-025* HW-028* HW-035* HW-040* HK040 HK050 HK060
OPERATING WT (Approximate) — kg
HWB 361 431 483 492 594 — — —
HWC,S 554 611 668 679 766 — — —
1284/ 1300/ 1352/
HK — — — — —
1305† 1352† 1370†
REFRIGERANT — kg R-22
HWB 5.7 6.8 7.9 8.4 13.6 — — —
HWC,S 15.9 16.8 19.1 19.1 21.3 — — —
HK — — — — — 31.2 36.3 40.8
COMPRESSOR
06DG537 06E2150** 06E7265 06E7175** 06E7299 06E2150 06E6175, 06E6175
Model No. 06E2150
Nominal kW 11.1 14.9 18.7 22.4 26.1 14.9 (ea) 14.9,22.4 22.4 (ea)
Quantity 1 1 1 1 1 2 1 (ea) 2
Cylinders Per Compressor 6 4 6 6 6 4 (ea) 6,4 6 (ea)
Capacity Control — Standard
No. of Steps 3 2 3 3 3 4 4 4
Minimum Step Capacity (%) 33 50 33 33 33 25 20†† 33
Capacity Control — With Hot Gas Bypass
No. of Steps 4 3 4 4 4 5 5 5
Minimum Step Capacity (%) 10 10 10 10 10 10 10 10
COOLER
Fluid Side — kPa 2069 2069 2069 2069 2069 1034 1034 1034
Refrigerant Side — kPa 2965 2965 2965 2965 2965 1620 1620 1620
Net Fluid Volume — L (includes nozzles) 5.3 6.1 8.0 8.0 12.5 49.9 57.5 57.5
Fluid Connections — in. Grooved End
Inlet 11/2 11/2 11/2 1
1 /2 21/2 3 3 3
Outlet 11/2 11/2 11/2 11/2 21/2 3 3 3
CONDENSER
30HWB (Water Cooled)
Water Side — kPa 2069 2069 2069 2069 2069 — — —
Refrigerant Side — kPa 2965 2965 2965 2965 2965 — — —
Net Water Volume — L (includes nozzles) 3.4 4.5 6.1 6.8 12.5 — — —
Water Connections — in. Grooved End
Inlet 11/2 11/2 11/2 1
1 /2 21/2 — — —
Outlet 11/2 11/2 11/2 11/2 21/2 — — —
30HWC (Water Cooled)
Water Side — kPa 2069 2069 2069 2069 2069 — — —
Refrigerant Side — kPa 2517 2517 2517 2517 2517 — — —
Net Water Volume — L 9.8 9.8 15.4 15.4 27.6 — — —
Water Connections — in. Weld
Inlet 11/2 11/2 11/2 11/2 21/2 — — —
Outlet 11/2 11/2 11/2 11/2 21/2 — — —
30HWS (Water Cooled)
Water Side — kPa 2069 2069 2069 2069 2069 — — —
Refrigerant Side — kPa 2517 2517 2517 2517 2517 — — —
Net Water Volume — L 9.8 9.8 15.4 15.4 27.6 — — —
Water Connections — in. Weld
Inlet 21/2 21/2 21/2 21/2 21/2 — — —
Outlet 21/2 21/2 21/2 21/2 21/2 — — —
30HK (Water Cooled)
Water Side — kPa — — — — — 1724 1724 1724
Refrigerant Side — kPa — — — — — 2655 2655 2655
Net Water Volume — L (includes nozzles) — — — — — 17,17 17,20 20,20
Water Connections — in. Weld
Inlet — — — — — 21/2 21/2 21/2
Outlet — — — — — 21/2 21/2 21/2
LEGEND NOTES:
ODS — Outside Diameter, Sweat 1. Operating weight includes refrigerant operating charge and weight of fluid in
the heat exchangers.
*Unless otherwise noted, data is for 30HWB, HWC, and HWS units. 2. 30HWB,C,S, and 30HK units are shipped with full operating charge.
†60 Hz/50 Hz units.
**For size 025 50 Hz units, compressor number is 06E2250, for size 035 50 Hz
units compressor number is 06E7275.
††With transfer switch set to compressor no. 2 position; 40% with transfer switch
set to compressor no. 1 position.

6
Physical data — 30HWA,HL
condenserless units
ENGLISH
UNIT 30 HWA018 HWA025 HWA028 HWA035 HWA040 HL050 HL060
2070/ 2130/
OPERATING WT (Approximate) — lb 740 880 960 975 1080
2130† 2190†
REFRIGERANT* — lb R-22
1.6 2.0 2.4 2.4 3.0 10.5 10.6
COMPRESSOR
06DG537 06E2250 06E7265 06E7275 06E7299 06E6275,
Model No. 06E6275
06E2250
Nominal Hp 15 20 25 30 35 30,20 30 (ea)
Quantity 1 1 1 1 1 1 (ea) 2
Cylinders Per Compressor 6 4 6 6 6 6,4 6
Capacity Control — Standard
No. of Steps 3 2 3 3 3 4 4
Minimum Step Capacity (%) 33 50 33 33 33 20** 33
Capacity Control — With Hot Gas Bypass
No. of Steps 4 3 4 4 4 5 5
Minimum Step Capacity (%) 10 10 10 10 10 10 10
COOLER
Fluid Side — psig 300 300 300 300 300 150 150
Refrigerant Side — psig 430 430 430 430 430 235 235
Net Fluid Volume — Gal. (includes nozzles) 1.4 1.6 2.1 2.1 3.3 13.1 15.2
Fluid Connections — in. Grooved End
Inlet 11 / 2 11/2 11 / 2 11/2 21/2 3 3
Outlet 11 / 2 11/2 11 / 2 11/2 21/2 3 3
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS 7/ 7/ 8 7/8 7/8 7/ 8 2...7/8 2...7/8
8
Discharge Line ODS 11 / 8 11/8 13 / 8 13/8 15/8 2...13/8 2...13/8
LEGEND NOTE: Operating weight includes refrigerant operating charge and
ODS — Outside Diameter, Sweat weight of fluid in the heat exchangers.
*30HWA and HL units (condenserless) are shipped with a refrigerant
holding charge. Approximate cooler operating charge is shown.
†60 Hz/50 Hz units.
**With transfer switch set to compressor no. 2 position; 40% with trans-
fer switch set to compressor no. 1 position.
SI
UNIT 30 HWA018 HWA025 HWA028 HWA035 HWA040 HL050 HL060
940/ 967/
OPERATING WT (Approximate) — kg 336 399 435 442 490 967† 994†
REFRIGERANT* — kg R-22
0.7 0.9 1.1 1.1 1.4 4.8 4.8
COMPRESSOR
06DG537 06E2250 06E7265 06E7275 06E7299 06E6275, 06E6175
Model No.
06E2250
Nominal kW 11.2 14.9 18.7 22.4 26.1 22.4,14.9 22.4 (ea)
Quantity 1 1 1 1 1 1 (ea) 2
Cylinders Per Compressor 6 4 6 6 6 6,4 6
Capacity Control — Standard
No. of Steps 3 2 3 3 3 4 4
Minimum Step Capacity (%) 33 50 33 33 33 20** 33
Capacity Control — With Hot Gas Bypass
No. of Steps 4 3 4 4 4 5 5
Minimum Step Capacity (%) 10 10 10 10 10 10 10
COOLER
Fluid Side — kPa 2069 2069 2069 2069 2069 1034 1034
Refrigerant Side — kPa 2965 2965 2965 2965 2965 1620 1620
Net Fluid Volume — L (includes nozzles) 5.3 6.1 8.0 8.0 12.5 49.9 57.5
Fluid Connections — in. Grooved End
Inlet 11 / 2 11/2 11/2 11 / 2 21 / 2 3 3
Outlet 11 / 2 11/2 11/2 11 / 2 21 / 2 3 3
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS 7/ 8 7/8 7/8 2...7/8 2...7/8
Discharge Line ODS 11/8 13 / 8 15 / 8 2...13/8 2...13/8
LEGEND NOTE: Operating weight includes refrigerant operating charge and
ODS — Outside Diameter, Sweat weight of fluid in the heat exchangers.
*30HWA and HL units (condenserless) are shipped with a refrigerant
holding charge. Approximate cooler operating charge is shown.
†60 Hz/50 Hz units.
**With transfer switch set to compressor no. 2 position; 40% with trans-
fer switch set to compressor no. 1 position.

7
Options and accessories
ITEM OPTION* ACCESSORY† Mobility package (30HWA/B only) — Wheels may be
Medium Temperature Brine (30HW)** X factory installed on the unit to aid in transportation of unit
Sound Enclosure Panels X (HW) X to its final installation site. Wheels are rubber type, pivot
Mobility Package (30HW) X (HWA/B) X for easy unit maneuvering, and are lockable for safety.
Non-Fused Disconnect (30HW) X Also available as a field-installed accessory for all 30HW
Part-Wind Start (30HW025-040)** X units.
Hot Gas Bypass X (HW) X (HK,HL)
Proof-of-Flow Switch X Non-fused disconnect (30HW units) — For wiring
Scrolling Marquee Display (50 Hz)†† X convenience, an electrical power disconnect for line and
Vibration Isolators (30HW) X control power may be factory installed.
Compressor Ground Fault Sensor X Part-wind start (30HW025-040 only) — This factory-
Oil Safety Switch X installed option reduces the starting current of the com-
Chillervisor System Manager III X
pressor. This option provides a one-second delay between
Pressure Gage Panel X
Condenser Manifold Package (30HK) X
starting the part-wind and primary compressor windings.
Energy Management Module (EMM) X X As a result, the instantaneous current flow at start-up is
*Factory-installed option.
reduced.
†Field-installed accessory. NOTE: This is a special order item for 30HK,HL units.
**Available as a special order on HK,HL units.
††Scrolling Marquee Display is standard on 60 Hz unit. Hot gas bypass (30HW) — Hot gas bypass control can
be factory installed to reduce chiller capacity. This option
includes a control solenoid valve, a shutoff valve, and nec-
essary controls.
Factory-installed options
NOTE: This is only offered as an accessory on the
Scrolling Marquee display (50 Hz unit) — Clear lan- 30HK,HL units.
guage displays English, Spanish, French, and Portuguese.
Scrolls to allow access to chiller operating parameters Field-installed accessories
(operating status, temperatures, and pressures). (Standard Proof-of-flow switch — The switch connects to a termi-
on 60 Hz unit.) nal strip in the chiller and senses fluid pressure differential
Energy Management Module (EMM) is used for 4 to across the cooler. This accessory is recommended for all
20 mA leaving fluid temperature reset, cooling set point chillers and also works well in conjunction with the Chill-
reset, 4 to 20 mA demand limit and two-step demand ervisor control accessory when up to 4 chillers are applied
limit. Temperature reset lets the unit reset the leaving fluid in a parallel piping arrangement.
temperature to a higher temperature during low load Pressure gage panel — Panel reads suction and dis-
conditions. Temperature reset can also be accomplished charge pressures and includes a shutoff valve for each
based on return fluid, outdoor air or space temperature. gage.
(The EMM option is not required when using entering-
NOTE: For 30HK,HL units, one package is required per
water, outdoor-air, or space temperature for temperature
compressor.
reset. These types of reset are available with the main
board. However, an accessory thermistor is required for Sound enclosure panels (30HK,HL only) — This ac-
outdoor air and/or space temperature reset.) Demand lim- cessory is an acoustically insulated sheet metal enclosure
iting allows the unit capacity to be limited during periods of that is installed around the compressor section and reduces
peak energy usage. Demand limit requires an external 4 to radiated sound levels. Also available as a factory-installed
20 mA signal or a 2-step remote pair of dry contacts. Both option for 30HW units.
the 4 to 20 mA and 2-step demand limit percentage values Vibration isolators — For 30HW units. Isolators are in-
are adjustable. This is also available as a field-installed stalled on the base of the unit to reduce vibration transmis-
accessory. sion from the compressor through the floor. This package
Medium temperature brine (30HW units) — Unit consists of 4 spring isolators with ribbed neoprene pads
may be factory-modified to permit brine operation from sized specifically for each model.
15 to 39 F (–9.4 to 3.9 C) leaving brine temperature. Re- NOTE: The 30HWC,S units each require 2 kits.
frigeration circuit components, such as the expansion de- Compressor ground fault sensor — If a short to
vice and low-pressure safety switch, are modified to permit ground is sensed by this accessory package, the compres-
the low refrigerant flow rates typical of brine duty opera- sor automatically shuts down. This protects the refrigera-
tion. Scrolling marquee display is required with this option. tion system from acid formation typical of a compressor
NOTE: This is a special order item for 30HK,HL units. motor short to ground condition. Compressor shut down
Sound enclosure panels (30HW units) — Units may is initiated when a 2.5 ± 2 amps ground current is sensed
be ordered with acoustically insulated sheet metal enclo- by a toroid installed around the compressor power leads.
sures installed around the compressor section to reduce Oil safety switch — The switch senses pressure differen-
radiated sound levels. Also available as a field-installed tial across the compressor oil pump and shuts down the
accessory. compressor in the event of loss of oil pressure. The safety
NOTE: This is only offered as an accessory on the switch is an accessory for the 30HWB,C,S,HK standard
30HK,HL units. units and is standard on the 30HWA,HL, and all brine
units.

8
Chillervisor System Manager III — This control can be Mobility package — For 30HW units. Wheels may be
used to regulate up to eight 30HK,HL,HW chillers. field installed on the unit to aid in transportation of unit to
Energy Management Module (EMM) is used for 4 to its final installation site. Wheels are rubber type, pivot for
20 mA leaving fluid temperature reset, cooling set point easy unit maneuvering, and are lockable for safety. Also
reset, 4 to 20 mA demand limit and two-step demand available as a factory-installed option on 30HWA/B units.
limit. Temperature reset lets the unit reset the leaving fluid NOTE: The 30HWC,S units require 2 packages each.
temperature to a higher temperature during low load con- Condenser manifold package — For 30HK units. The
ditions. Temperature reset can also be accomplished based manifold provides common water inlet and outlet connec-
on return fluid, outdoor air or space temperature. (The tions and consists of 2 steel manifolds, each in 2 sections.
EMM option is not required when using entering-water, Field welding is required.
outdoor-air, or space temperature for temperature reset.
Hot gas bypass package — For 30HK,HL units.
These types of reset are available with the main board.
However, an accessory thermistor is required for outdoor Allows additional capacity reduction for unit operation be-
low the minimum step of unloading.
air and/or space temperature reset.) Demand limiting al-
lows the unit capacity to be limited during periods of peak
energy usage. Demand limit requires an external 4 to
20 mA signal or a 2-step remote pair of dry contacts. Both
the 4 to 20 mA and 2-step demand limit percentage values
are adjustable. This is also available as a factory-installed
option.

9
Base unit dimensions — 30HWC,S018-040
(fluid-cooled)

UNIT DIMENSIONS — in. (mm)


30HWC,S A B C D E F G
47.50 9.90 14.00 18.15 17.95 6.69 34.20
018
(1206) (251) (356) (461) (456) (170) (869)
48.30 9.90 15.50 18.15 17.95 6.69 34.20
025 (1227) (251) (394) (461) (456) (170) (869)
48.00 10.00 15.80 18.15 17.95 6.69 34.20
028 (1219) (254) (401) (461) (456) (170) (869)
48.20 10.00 15.90 18.15 17.95 6.69 34.20
035
(1224) (254) (404) (461) (456) (170) (869)
47.80 10.00 15.90 18.45 17.36 6.40 34.94
040 (1214) (254) (404) (469) (441) (163) (837)

VOLTAGE MODEL NUMBERS OPERATING WEIGHT


MODEL VOLT-Hz UNIT OPERATING WEIGHT
100 575-60 30HWC,S lbs (kg)
200 380-60 018 1231 (554)
500 208/230-60 025 1358 (611)
600 460-60 028 1484 (668)
900 400-50 035 1508 (679)
040 1702 (766)

DISCONNECT LOCATION — in. (mm) MODEL 30HWC,S (SEE VOLTAGE MODEL NUMBERS TABLE)
(Amps) J K L 018 025 028 035 040
83.11 4.38 3.33 100,200 100,200 100,200 100,200
80 100
(2111) (111) (85) 600,900 600,900 600,900 600,900
85.11 5.00 4.33
100 (2162) (127) (110) 500 500 500 — 200,600,900
89.24 10.00 7.46 — — — 500 500
200 (2267) (254) (189)

WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE — lbs (kg)


Unit Compr. End Control Box End
NOTES: 30HWC,S (4 Places) (4 Places)
1. Operating weight includes weight of water and refrigerant. 018 171 ( 77.6) 136 (61.7)
2. Denotes center of gravity. 025 196 ( 88.9) 144 (65.3)
028 211 ( 95.7) 160 (72.6)
3. Denotes accessory or factory-installed option.
4. Dimensions in ( ) are in millimeters and weights ( ) are in 035 216 ( 98.0) 161 (73.0)
kilograms. 040 240 (108.9) 185 (83.9)

10
Base unit dimensions — 30HK040
(fluid cooled)

STANDARD UNIT
WEIGHT DISTRIBUTION AT MOUNTING HOLES OPERATING DIMENSIONS
UNIT SIZE lbs (kg) WEIGHT in. (mm)
30HK lbs (kg)
1 2 3 4 A B
721 723 716 715 2875
040 50 Hz (327) (328) (325) (325) (1305) 275/16 101/2
710 712 705 703 2830 (693) (267)
040 60 Hz (322) (323) (320) (319) (1284)

NOTES:
1. Standard unit shown with the sound enclosure accessory.
2. Dimensions in ( ) are in millimeters and weights in ( ) are in kilograms.
3. Allow 36″ (914) clearance on all sides unless otherwise noted.

11
Base unit dimensions — 30HK050,060
(fluid-cooled)

STANDARD UNIT
WEIGHT DISTRIBUTION AT MOUNTING HOLES OPERATING DIMENSIONS
UNIT SIZE lbs (kg) WEIGHT in. (mm)
30HK lbs (kg)
1 2 3 4 A B
838 840 832 830 2980
50 Hz (380) (381) (378) (377) (1352)
050
787 789 782 780 2865
60 Hz (357) (358) (355) (354) (1300) 275/16 101/2
853 855 847 845 3020 (693) (267)
50 Hz (387) (388) (385) (384) (1370)
060
838 840 832 830 2980
60 Hz (380) (381) (378) (377) (1352)

NOTES:
1. Standard unit shown with the sound enclosure accessory.
2. Dimensions in ( ) are in millimeters and weights in ( ) are in kilograms.
3. Allow 36″ (914) clearance on all sides unless otherwise noted.

12
Base unit dimensions — 30HWB018-040
(fluid-cooled)

VOLTAGE OPERATING WEIGHT


MODEL NUMBERS UNIT OPERATING WEIGHT
MODEL VOLT-Hz 30HWB lbs (kg)
100 575-60 018 795 (360)
200 380-60 025 950 (431)
500 208/230-60 028 1065 (483)
600 460-60 035 1085 (492)
900 400-50 040 1310 (594)

MODEL 30HWB
DISCONNECT LOCATION — in. (mm) (SEE VOLTAGE MODEL NUMBERS TABLE)
(Amps)
J K L M 018 025 028 035 040
3.33 2.98 14.44 46.50 100,200 100,200 100,200 100,200
80 100
(85) (76) (367) (1181) 600,900 600,900 600,900 600,900
4.33 4.98 14.82 47.50 200,600
100 500 500 500 —
(110) (126) (376) (1207) 900
7.46 11.19 15.82 54.50
200 — — — 500 500
(189) (284) (402) (1384)

UNIT DIMENSIONS — in. (mm)


30HWB A B C D E F G H Z
13.14 18.72 22.02 33.85 11.72 5.75 12.29 17.95 9.28
018 (334) (475) (559) (860) (298) (146) (312) (456) (236)
13.22 18.25 22.10 33.85 11.72 5.75 12.29 17.95 9.28
025 (336) (464) (561) (860) (298) (146) (312) (456) (236)
13.18 17.71 22.39 33.85 11.72 5.75 12.29 17.95 9.28
028 (335) (450) (569) (860) (298) (146) (312) (456) (236)
13.45 17.98 22.68 33.85 11.72 5.75 12.29 17.95 9.28
035 (342) (457) (576) (860) (298) (146) (312) (456) (236)
13.27 17.75 23.44 34.15 11.34 8.22 12.38 17.36 8.22
040 (337) (451) (595) (867) (288) (209) (314) (441) (209)

NOTES:
1. Operating weight includes weight of water and refrigerant. Equal weight distribu-
tion at all four (4) points.
2. Denotes center of gravity.
3. Denotes accessory or factory-installed option.
4. Dimensions in ( ) are in millimeters and weights ( ) are in kilograms.
5. Allow 36″ (914) clearance on all sides unless otherwise specified.

13
Base unit dimensions — 30HWA018-040
(condenserless)

VOLTAGE OPERATING WEIGHT


MODEL NUMBERS
OPERATING
UNIT
MODEL VOLT-Hz WEIGHT
30HWA lbs (kg)
100 575-60
380-60 018 740 (335)
200
025 880 (399)
500 208/230-60
028 960 (435)
600 460-60
400-50 035 975 (442)
900
040 1080 (490)

UNIT DIMENSIONS — in. (mm)


30HWA A B C D E F G
12.58 19.20 20.48 33.85 11.72 5.75 17.95
018 (320) (488) (520) (860) (298) (146) (456)
12.82 18.98 20.57 33.85 11.72 5.75 17.95
025 (326) (482) (522) (860) (298) (146) (456)
12.64 18.31 20.73 33.85 11.72 5.75 17.95
028 (321) (465) (527) (860) (298) (146) (456)
12.87 18.62 20.81 33.85 11.72 5.75 17.95
035 (327) (473) (529) (860) (298) (146) (456)
12.66 18.64 21.30 34.15 11.34 8.22 17.36
040 (322) (473) (541) (867) (288) (209) (441)

MODEL 30HWA (SEE VOLTAGE MODEL


DISCONNECT LOCATION — in. (mm) NUMBERS TABLE)
(Amps)
J K L M 018 025 028 035 040
3.33 2.98 14.44 46.50 100,200100,200 100,200 100,600
80 —
(85) (76) (367) (1181) 600,900600,900 600,900 900
4.33 4.98 14.82 47.50 100,200
100 500 500 — 200
(110) (126) (376) (1207) 600,900
7.46 11.19 15.82 54.50
200 — — 500 500 500
(189) (284) (402) (1384)

NOTES:
1. Operating weight includes weight of water and refrigerant.
Equal weight distribution at all four (4) points.
2. Denotes center of gravity.
3. Denotes accessory or factory-installed option.
4. Dimensions in ( ) are in millimeters and weights ( ) are in kilograms.
5. Allow 36″ (914) clearance on all sides unless otherwise specified.

14
Base unit dimensions — 30HL050,060
(condenserless)

STANDARD UNIT
WEIGHT DISTRIBUTION AT
MOUNTING HOLES OPERATING DIMENSIONS
UNIT SIZE WEIGHT in. (mm)
30HL lbs (kg)
lbs (kg)
1 2 3 4 A B
534 536 531 529 2130
50 Hz (242) (243) (241) (240) (967)
050
519 521 516 514 2070
60 Hz (162) (163) (234) (233) (940) 275/16 101/2
550 551 545 544 2190 (693) (267)
50 Hz (176) (250) (247) (247) (994)
060
534 536 531 529 2130
60 Hz (242) (243) (241) (240) (967)

NOTES:
1. Standard unit shown with the sound enclosure accessory.
2. Dimensions in ( ) are in millimeters and weights in ( ) are in kilograms.
3. Allow 36″ (914) clearance on all sides unless otherwise noted.

15
Application data
Leveling unit exceeded and corrections to capacity, etc. are made. For
To ensure proper oil return, be sure that unit is level, minimum flow rates, see Minimum Cooler and Condenser
particularly in its major lengthwise dimension, as com- Flow Rates and Minimum Loop Volume table. High flow
pressor oil return piping runs in that direction. rate is limited by pressure drop that can be tolerated. If an-
other temperature rise is used, apply LCWT correction as
It should be determined prior to installation if any
given in Capacity Correction and Selection Procedure sec-
special treatment is required to ensure a level tions on pages 18 and 20.
installation.
Minimum cooler flow — The minimum cooler flow
Cooler fluid temperature (maximum cooler temperature rise) for standard units is
1. Maximum sustained leaving chilled-fluid temperature shown in Minimum Cooler and Condenser Flow Rates and
(LCWT) is 60 F (16 C). For sustained operation, Minimum Loop Volume table below. When gpm (L/s) re-
entering-fluid temperature should not exceed 75 F quired is lower (or rise is higher), follow recommendations
(24 C). Unit can start and pull down with up to 95 F below:
(35 C) entering-fluid temperature due to MOP (maxi- a. Multiple smaller chillers may be applied in series,
mum operating pressure) feature of the expansion each providing a portion of the design temperature
valve. rise.
2. Minimum LCWT for standard units is 40 F (4 C). b. Chilled fluid may be recirculated to raise flow rate.
Lower LCWT can be used on medium temperature However, the mixed temperature entering the cooler
brine applications. Refer to Medium Temperature must be maintained at a minimum of at least 5° F
Brine Applications section below. For applications (2.8° C) above the leaving chilled fluid temperature.
with ratings below 40 F (4 C) on standard units, con- c. On 30HK,HL units, special baffling is required to
tact your local Carrier representative. allow minimum flow rate to be reduced to 12%.
Medium Temperature Brine Applications NOTE: Recirculation flow is shown below.
In all brine duty applications, a suitable brine (or antifreeze RECIRCULATION FLOW
and water solution) must be provided to ensure freeze pro-
tection. The solution crystallization point of the brine
should be below the suction temperature of the cooler, and
at least 15° F (8.3° C) below the leaving brine tempera-
ture. The brine solution must also be properly inhibited to
provide suitable corrosion protection.
NOTE: Medium temperature brine is a special order op-
tion on 30HK,HL units.
Condenser (30HWB,C,S and 30HK units)
water temperature
1. Maximum leaving condenser-water temperature is
130 F (54 C) for 30HW 50 Hz units, and 104 F
(40 C) for 60 Hz units and 30HK 50 Hz units. Maximum cooler flow (5 gpm/ton or < 5° F rise
2. Minimum entering condenser-water temperature [0.09 L/s • kW or < 2.7° C rise]) — The maxi-
without condenser flow regulation is 70 F (21 C). mum cooler flow results in practical maximum pressure
drop through cooler.
Cooler and water-cooled condenser flow range The return fluid may bypass the cooler to keep pressure
Ratings and performance data in this publication are for a drop through the cooler within acceptable limits. This per-
cooling temperature rise of 10° F (5.6° C) and are suitable mits a higher ∆T with lower fluid flow through cooler and
for a range from 5 to 15° F (2.8 to 8.3° C) temperature mixing after cooler.
rise without adjustment. Units may be operated at a differ- NOTE: Bypass flow is shown on page 17.
ent temperature range, provided flow limits are not

MINIMUM COOLER AND CONDENSER FLOW RATES AND MINIMUM LOOP VOLUME
LEGEND
MINIMUM
COOLER ARI — Air Conditioning and Refrigeration Institute
COOLER CONDENSER* N — Liters per kW
UNIT SIZE LOOP
VOLUME† V — Gallons per ton
Gal./Min L/s Gal./Min L/s Gal. L *30HWB,C,S, and 30HK only.
30HW018 22.5 1.4 22.5 1.4 44 167 †Minimum system fluid volumes.
30HW025 30.0 1.9 30.0 1.9 59 223 NOTES:
30HW028 37.5 2.4 37.5 2.4 76 288 Gallons = V x ARI capacity in tons.
Liters = N x ARI capacity in kW.
30HW035 45.0 2.8 45.0 2.8 85 322
30HW040 57.0 3.6 57.0 3.6 113 428 APPLICATION V N
30HK040 56.0 3.5 67.0 4.2 120 454 Normal Air Conditioning 3 3.25
30HK,HL050 68.0 4.3 76.0 4.8 148 560 Process Type Cooling 6 to 10 6.5 to 10.8
30HK,HL060 68.0 4.3 83.0 5.2 174 659 Low Ambient Operation 6 to 10 6.5 to 10.8

16
Fouling factor — The factor used to calculate tabulated
BYPASS FLOW ratings was 0.00010 ft2 • hr • F/Btuh (.000018 m2 •
k/W). As fouling factor is increased, unit capacity decreas-
es and compressor power increases. To determine selec-
tions at other fouling factors, use chiller program in the
Electronic Catalog.
30HWA and 30HL remote condenser
requirements
1. Ensure each refrigerant circuit has its own head pres-
sure control.
2. Condenser must provide 15° F (8.3° C) subcooling, a
maximum of 40° F (22.2° C) difference between satu-
rated condensing temperature and outdoor ambient
Variable cooler flow rates — These variable rates may temperature (to prevent overload at high ambient
be applied to standard chillers. However, the unit will at- temperatures), and a minimum of 20° F (11.1° C) dif-
tempt to maintain a constant leaving chilled-fluid tempera- ference (to ensure subcooling).
ture. In such cases, minimum fluid loop volume must be in 3. Do not manifold independent refrigerant circuits into
excess of 3 gallons per ton (3.2 L per kW), and flow rate a single condenser.
must change in steps of less than 10% per minute. Apply
6 gal per ton (6.5 L per kW) fluid loop volume minimum if 4. Condenser should not be located more than 50 ft
flow rate changes more rapidly. (15 m) below chiller to maintain subcooling.
Minimum water-cooled condenser flow — This value 5. Design discharge and liquid piping according to
(maximum rise) is shown in Minimum Cooler and Con- Carrier System Design Manual.
denser Flow Rates and Minimum Loop Volume table on Oversizing chillers
page 16. Condensers may be piped in series. Ensure leav-
Oversizing chillers by more than 15% at design conditions
ing-water temperature does not exceed 104 F (40 C).
must be avoided as the system operating efficiency will be
Chilled fluid loop volume — The chilled fluid loop vol- adversely affected (resulting in greater and/or excessive
ume in circulation must equal or exceed 3 gal per ton of electrical demand and cycling of compressors). When fu-
cooling (3.25 L per kW) for temperature stability and accu- ture expansion of equipment is anticipated, install a single
racy in normal air conditioning applications. (For example, chiller to meet present load requirements and install a sec-
a 30HW040 would require 113 gal [428 L] in circulation ond chiller to meet the additional load demand.
in system loop — see Minimum Cooler and Condenser
It is also recommended that the installation of 2 smaller
Flow Rates and Minimum Loop Volume table on page 16.) chillers be considered where operation at minimum load is
For process jobs where accuracy is vital or for operation at
critical. The operation of a smaller chiller loaded to a
ambient temperature below 32 F (0° C) with low unit load-
greater percent of minimum is preferred to operating a
ing conditions, there should be from 6 to 10 gal per ton single chiller at or near its minimum recommended value.
(6.5 to 10.8 L per kW). To achieve this volume, it is often
necessary to install a tank in the loop. Tank should be baf- Hot gas bypass should not be used as a means to allow
fled to ensure there is no stratification, and that water (or oversizing chillers. Hot gas bypass should be given consid-
brine) entering tank is adequately mixed with liquid in the eration where substantial operating time is anticipated be-
tank. low the minimum unloading step.
NOTE: Tank installation is shown below. Strainers
A strainer with a minimum of 20 mesh must be installed in
both the cooler fluid and condenser water inlet lines on
TANK INSTALLATION 30HWB,C,S and 30HK units, just ahead of and as close
as possible to the cooler and condenser. For 30HWA and
30HL units, this requirement applies only to the cooler.
Parallel chillers
Where chiller capacities greater than can be supplied by a
single 30H chiller are required, or where stand-by capabili-
ty is desired, chillers may be installed in parallel. Units may
be of the same or different sizes. However, cooler and con-
denser flow rates must be balanced to ensure proper flow
to each chiller. The accessory Chillervisor System Manager
III control should be used for proper leaving chilled fluid
temperature control and to ensure proper staging
sequence of up to 8 chillers. Refer to the accessory Chill-
ervisor System Manager III control installation instructions
for further details.

17
Application data (cont)
Series chillers Vibration isolation
Where a large temperature drop (greater than 25 F All compressors are spring isolated. External vibration iso-
[13.9 C]) is desired and higher fluid pressure drop across lation is not generally required, but is available for 30HW
the cooler can be tolerated, chillers may be installed in units as an accessory if desired.
series. The leaving fluid temperature sensors need not be
relocated. However, the cooler minimum entering fluid Cooler and water-cooled condenser freeze
temperature limitations should be considered for the chill- protection
ers located downstream of other chillers. Condensers If chiller or fluid lines are in an area where ambient condi-
should be piped in parallel to maximize capacity and effi- tions fall below 32 F (0° C), it is recommended that an
ciency. This should also minimize condenser pressure drop antifreeze solution be added to protect the unit and fluid
and saturated condensing temperatures. However, if con- piping to a temperature 15° F (8.3° C) below the lowest
densers are piped in series, ensure that the leaving water anticipated ambient temperature. In brine duty applica-
temperature does not exceed 104 F (40 C) for 60 Hz units tions where the leaving cooler fluid temperature is below
or 130 F (54 C) for 50 Hz units. 40 F (4.4 C), the brine solution (antifreeze) option (30HW;
special order on 30HK,HL) should be selected so that the
Energy management freeze point is at least 15° F (8.3° C) below the cooler leav-
ing fluid temperature and below the suction temperature at
Demand limiting and load shedding are popular techniques
the cooler. Corrections to performance as indicated in the
used to reduce peak electric demands typically experienced Capacity Correction and Selection Procedure sections be-
during hot summer days when air conditioning loads are
highest. When utility electricity demands exceed a certain low and on page 20 must be applied.
level, electrical loads are turned off to keep the peak de- Use only antifreeze solutions approved for heat ex-
mands below a prescribed maximum limit. Compressor changer duty. Use of automotive antifreezes is not recom-
unloading will reduce electrical demand while allowing the mended because of the fouling that can occur once their
chiller to operate under part-load capacity and maintain relatively short-lived inhibitor breaks down.
partial chilled fluid cooling. The Energy Management Mod- If not protected with an antifreeze solution, draining
ule can be added to accomplish this. cooler and outdoor piping is recommended if system is not
Electrical demand may be limited by unloading the chill- to be used during freezing weather conditions.
er to a predetermined percentage of the load. One stage Capacity correction (antifreeze)
of unloading can be initiated by a remote signal to signifi-
cantly reduce the chiller power consumption. This power If unit or fluid lines connected to the unit are in an area
reduction applies to the full load power at nominal condi- where ambient temperature falls below 32 F (0° C), it is
tions. The demand limit control should not be cycled less strongly recommended that an appropriate antifreeze solu-
than 10 minutes on and 5 minutes off. tion with suitable corrosion inhibitor be used in the chilled
fluid circuit. Unit performance data based on inhibited eth-
Duty cycling ylene glycol solution must be corrected as shown in the fol-
lowing example (other antifreeze solutions may be suitable
Duty cycling will cycle an electrical load at regular intervals, based on specific application requirements).
regardless of electrical demand. This reduces the electrical
demand by “fooling” demand measuring devices. Duty cy- NOTE: For performance correction factors for systems us-
ing propylene glycol solution, see Propylene Glycol Perfor-
cling of the entire compressor is NOT recommended since mance Correction Factors and Solution Crystallization
motor windings and bearings will be damaged by constant
cycling. Points Graph on page 19.
EXAMPLE — ENGLISH (60 Hz)
Part-wind start (option for 30HW025-040 I. Determine concentration of inhibited ethyl-
units, special order for 30HK,HL units) ene glycol (EG) solution required to protect
Part-wind start is not generally required on 30HK,HL chill- the system to 0° F (at zero flow).
ers due to use of multiple small compressors allowing From Solution Crystallization Point correction curve
smaller load increments, but is available if required. Maxi- on page 19: 35% EG concentration is required for
mum instantaneous current flow should be used in deter- solution crystallization at 0° F.
mining need. Consider the 30HWB040 unit selected in the Selec-
The instantaneous current flow experienced during chill- tion Procedure section on page 20.
er start-up is a function of the compressor motor locked II. Correct unit capacity.
rotor amps (LRA). The LRA draw occurs briefly when the
compressor is started and can lead to a peak in the electri- On Capacity Correction curve on page 19, read
cal demand. Chillers with part-wind compressors have 0.99 correction factor at 35% concentration.
2 sets of compressor motor windings (per compressor) to Corrected Capacity = 0.99 x Rated Capacity
allow for reduced instantaneous current flow during com- = 0.99 x 35.9
pressor start-up.
= 35.5 Tons

18
III. Correct cooler water flow rate (Gpm).
ETHYLENE GLYCOL PERFORMANCE
CORRECTION FACTORS AND SOLUTION On Cooler Flow Correction curve on this page, read
CRYSTALLIZATION POINTS 1.11 correction factor at 35% concentration.
Correction factors apply to published chilled water Cooler Water Flow Tons x 24 35.5 x 24
performance ratings from 40 to 60 F = =
(4.4 to 15.6 C) LCWT. (at corrected capacity) ∆T 10
= 85.3 Gpm
Cooler Water Flow
= 1.11 x 85.3 = 94.7 Gpm
(35% EG)
IV. Correct cooler pressure drop.
On Cooler Pressure Drop Correction curve on this
page, read 1.30 correction factor at 35%
concentration.
On Cooler Pressure Drop curve, (page 22) for
94.7 gpm of water, Pressure Drop =7.0 ft of water.
For 35% EG solution,
= 1.30 x 7.0
Pressure Drop
= 9.1 ft of water
EXAMPLE — SI (50 Hz)
I. Determine concentration of inhibited ethyl-
ene glycol (EG) solution required to protect
the system to –17.8 C (at zero flow).
From Solution Crystallization Point correction curve
at left: 35% EG concentration is required for solu-
tion crystallization at –17.8 C.
Consider the 30HWB040 unit selected in the Selec-
tion Procedure example.
II. Correct unit capacity.
PROPYLENE GLYCOL PERFORMANCE On Capacity Correction curve on this page, read
CORRECTION FACTORS AND SOLUTION 0.99 correction factor at 35% concentration.
CRYSTALLIZATION POINTS
Correction factors apply to published chilled water Corrected Capacity = 0.99 x Rated Capacity
performance ratings from 40 to 60 F = 0.99 x 112.1
(4.4 to 15.6 C) LCWT.
= 111.0 kW
III. Correct cooler water flow rate (L/s).
On Cooler Flow Correction curve on this page, read
1.11 correction factor at 35% concentration.
Cooler Water Flow kW x .239
=
(at corrected capacity) ∆T
111.0 x .239
=
5.6
= 4.7 L/s
Cooler Water Flow
= 1.11 x 4.7 = 5.26 L/s
(35% EG)
IV. Correct cooler pressure drop.
On Cooler Pressure Drop Correction curve on this
page, read 1.30 correction factor at 35%
concentration.
On Cooler Pressure Drop curve (page 22), for
5.5 L/s of water, Pressure Drop = 20.0 kPa.
For 35% EG solution,
= 1.30 x 20.0
Pressure Drop
= 26.0 kPa

19
Selection procedure (with example)
ENGLISH (60 Hz) SI (50 Hz)
NOTE: Contact your local Carrier representative for a NOTE: Contact your local Carrier representative for a
computer selection (based on the Reciprocating Chiller Se- computer selection (based on the Reciprocating Chiller Se-
lection program of Carrier’s electronic catalog), or follow lection program of Carrier’s electronic catalog), or follow
the procedure below. the procedure below.
I. Determine unit size and operating conditions I. Determine unit size and operating conditions
required to meet given capacity at given required to meet given capacity at given
conditions. conditions.
Given: Given:
Capacity. . . . . . . . . . . . . . . . . . . . . . . . . 35 Tons Capacity. . . . . . . . . . . . . . . . . . . . . . . . . 125 kW
Leaving Chilled Water Temp (LCWT) . . . . . . .44 F Leaving Chilled Water Temp (LCWT) . . . . . . . 7 C
Cooler Water Temp Rise . . . . . . . . . . . . . . . 10° F Cooler Water Temp Rise . . . . . . . . . . . . . . 5.6° C
Condenser Entering Water Temp . . . . . . . . . .85 F Condenser Entering Water Temp . . . . . . . . . 30 C
Condenser Water Temp Rise . . . . . . . . . . . . 10° F Condenser Water Temp Rise . . . . . . . . . . . 5.6° C
Fouling Factor (Cooler and Fouling Factor (Cooler and
Condenser . . . . . . . . . . . . . . . . . . . . . . .00010 Condenser . . . . . . . . . . . . . . . . . . . . . .000018
NOTE: For other than 10° F temperature rise, data NOTE: For other than 5.6° C temperature rise, data
corrections must be made; also, on some units a corrections must be made; also, on some units a
change of controls is necessary. change of controls is necessary.
II. Choose appropriate condenser based on con- II. Choose appropriate condenser based on con-
denser water conditions and specific job denser water conditions and specific job
requirements. requirements.
UNIT 30 CONDENSER TYPE UNIT 30 CONDENSER TYPE
Condenserless or combined with matched Condenserless or combined with matched
HWA,HL Carrier air-cooled condenser. HWA,HL Carrier air-cooled condenser.
HWB Brazed-plate condenser. HWB Brazed-plate condenser.
Shell-and-tube condenser with copper Shell-and-tube condenser with copper tubes
HWC,HK HWC,HK
tubes (mechanically-cleanable condenser). (mechanically cleanable condenser).
Shell-and-tube condenser with cupro-nickel Shell-and-tube condenser with cupro-nickel
tubes and tube sheets and zinc anodes tubes and tube sheets and zinc anodes
HWS (suitable for sea coast applications). HWS (suitable for sea coast applications).
Mechanically cleanable. Mechanically cleanable.
FOR 30HWB,C, or HK Fluid-Cooled Condenser: FOR 30HWB,C, or HK Fluid-Cooled Condenser:
Enter the appropriate Performance Data table at Enter the appropriate Performance Data table at
44 F LCWT and 85 F Condenser Entering Water 7 C LCWT and 30 C Condenser Entering Water
Temperature. Read down the capacity column to a Temperature. Read down the capacity column to a
capacity that equals or exceeds the given capacity. capacity that equals or exceeds the given capacity.
Read across to obtain the operating conditions Read across to obtain the operating conditions
required to obtain the listed capacity. Use cooler required to obtain the listed capacity. Use cooler
and condenser pressure drop curves to determine and condenser pressure drop curves to determine
the respective pressure drops. Final unit selection the respective pressure drops. Final unit selection
should be based on present and future job require- should be based on present and future job require-
ments and the economics of the job. ments and the economics of the job.
NOTE: For 30HWS, contact your local Carrier NOTE: For 30HWS, contact your local Carrier
representative. representative.
FOR 30HWA and 30HL Condenserless: FOR 30HWA and HL Condenserless:
Use same method. For remote condenser data, Use same method. For remote condenser data,
refer to appropriate Carrier condenser Product Data refer to appropriate Carrier condenser Product Data
literature. literature.
Contact your local Carrier representative for a com- Contact your local Carrier representative for a com-
puter selection of chiller system combinations with puter selection of chiller system combinations with
Carrier air-cooled condensers other than those Carrier air-cooled condensers other than those
shown in Performance Data tables. shown in Performance Data tables.
III. From Cooling Capacities table on page 26 III. From Cooling Capacity table on page 38 and
and pressure drop curves on page 22, deter- pressure drop curves on page 22, determine
mine operating data for selected unit. operating data for selected unit.
Unit . . . . . . . . . . . . . . . . . . . . . . . . . 30HWB040 Unit . . . . . . . . . . . . . . . . . . . . . . . . . 30HWB040
Capacity. . . . . . . . . . . . . . . . . . . . . . . . 35.9 tons Capacity. . . . . . . . . . . . . . . . . . . . . . . .112.1 kW
Compressor Motor Power Input . . . . . . . .35.2 kW Compressor Motor Power Input . . . . . . . .30.0 kW
Cooler Water Flow . . . . . . . . . . . . . . . . 86.1 gpm Cooler Water Flow . . . . . . . . . . . . . . . . . .4.8 L/s
Cooler Pressure Drop . . . . . . . . . . .6.5 ft of water Cooler Pressure Drop . . . . . . . . . . . . . . 16.9 kPa
Condenser Water Flow . . . . . . . . . . . . 108.7 gpm Condenser Water Flow . . . . . . . . . . . . . . .6.0 L/s
Condenser Pressure Drop . . . . . . . .8.8 ft of water Condenser Pressure Drop . . . . . . . . . . . 21.8 kPa

20
Performance data
Ratings
1. All performance data are based on: LCWT CORRECTION FACTORS
a. Cooler water temperature rise of 10° F (5.6° C). ENGLISH
When more accuracy is desired, correct LCWT
(leaving chilled-water temperature) by amount
determined from LCWT Correction curve on this
page before entering Performance Data tables.
b. Cooler fouling factor of .00010 ft2 • hr • F/Btu
(.000018m2 • K/W) (same for condenser on
30HWB,C,S).
c. 10° F (5.6° C) subcooling.
d. Refrigerant 22.
2. When corrected LCWT is used, cooler pressure drop
must also be corrected for the new LCWT:
a. Enter Performance Data table at corrected LCWT.
By interpolation, determine corrected Capacity
(tons or kW), saturated discharge temperature (in NOTE: For rise above 10° F, ADD correction to design LCWT;
Performance Data tables on pages 28, 32, 36, below 10° F, SUBTRACT.
and 40 for 30HWA and HL condenserless units),
and kW (compressor motor power input at rated
SI
voltage).
b. Calculate:
corrected corrected capacity (tons) x 24
=
gpm temperature rise (°F)
corrected corrected capacity (kW) x .239
=
L/s temperature rise (°C)
c. Enter Cooler Pressure Drop curve on page 22 at
corrected gpm (L/s) and find pressure drop.
Combining 30HWA and HL units with remote con-
densers which have greater than (less than) the 10° F
(5.6° C) subcooling in the ratings, increases (de-
creases) system capacity. To adjust capacity, multiply
capacity ratings by 0.96; then adjust this result
upward by 0.4% for each degree F (0.7% for each
degree C) of available subcooling.
NOTE: For rise above 5.6° C, ADD correction to design LCWT;
3. Contact your local Carrier representative for 30HWS below 5.6° C, SUBTRACT.
cooling capacity data and for assistance in 30HWS LCWT — Leaving Chilled-Water Temperature
applications.

21
Performance data (cont)
COOLER PRESSURE DROP — 30HW UNITS COOLER PRESSURE DROP — 30HK,HL UNITS

NOTE: Ft of water = 2.31 x change in psig.

22
CONDENSER PRESSURE DROP — CONDENSER PRESSURE DROP —
30HWC AND 30HWS UNITS 30HWB UNITS

CONDENSER PRESSURE DROP —


30HK

NOTE: Ft of water = 2.31 x change in psig.

23
Performance data (cont)
ARI RATINGS (60 Hz only)

COOLER COOLER CONDENSER CONDENSER


CAPACITY INPUT PRESSURE PRESSURE
UNIT FLOW FLOW
POWER DROP DROP EER IPLV
30 (kW)
Tons kW Gpm L/s Ft of Kpa Gpm L/s Ft of kPa
Water Water
HWB018 14.8 52.0 13.4 35.5 2.2 6.2 18.5 44.3 2.8 17.1 51.2 13.2 18.3
HWB025 19.6 69.1 17.0 47.2 3.0 7.0 21.0 58.9 3.7 18.6 55.4 13.8 19.0
HWB028 25.4 89.2 23.2 60.9 3.8 8.8 26.1 76.0 4.8 19.7 58.7 13.1 17.6
HWB035 28.5 100.3 25.8 68.5 4.3 11.0 32.8 85.6 5.4 20.5 61.2 13.3 17.3
HWB040 35.9 126.3 35.2 86.2 5.4 6.6 19.6 107.7 6.8 8.6 25.8 12.2 15.0
HWC018 15.8 55.7 13.2 38.0 2.4 7.1 21.1 47.5 3.0 8.1 24.3 14.4 19.8
HWC025 19.9 69.8 16.2 47.7 3.0 7.2 21.4 59.6 3.8 13.4 40.0 14.7 20.1
HWC028 25.4 89.3 21.8 60.9 3.8 8.8 26.1 76.2 4.8 11.7 35.0 14.0 18.2
HWC035 28.1 98.9 25.4 67.5 4.3 10.7 31.9 84.4 5.3 14.5 43.3 13.3 16.7
HWC040 37.7 132.7 34.6 90.6 5.7 7.2 21.5 113.2 7.1 9.4 28.0 13.1 16.1
HK040 41.2 144.9 34.2 98.7 6.2 13.4 40.0 123.6 7.8 6.1 18.2 14.4 20.2
HK050 50.5 177.6 43.6 121.0 7.6 11.5 34.2 151.5 9.6 7.3 21.8 13.9 18.1
HK060 58.8 206.7 52.8 140.9 8.9 15.4 45.8 176.1 11.1 8.1 24.0 13.4 18.0
LEGEND 3. IPLV is a single number part-load efficiency value calculated from
ARI — Air Conditioning and Refrigeration Institute (U.S.A.) the system full-load efficiency values and corrected for a typical
EER — Energy Efficiency Ratio (Capacity [Btuh] ÷ Input Power [W]) building air-conditioning application.
IPLV — Integrated Part-Load Value 4. All data in this table is rated (60 Hz only) in accordance with ARI
Standard 550/590-98 as represented in the Reciprocating Chiller
NOTES: Selection Program (E-Cat) version 2.11.
1. Rated (60 Hz only) in accordance with ARI Standard 550/590-98
at standard rating conditions.
2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving water temperature: 44 F (6.7 C) Rated in accordance with
Flow: 2.4 gpm (.15 L/s) R ARI Standard 550/590-98.
Condenser Conditions:
Entering water temperature: 85 F (29.4 C)
Flow: 3 gpm per ton (0.054 L/s per kW) 60 Hz Only
Fouling Factor (Cooler and Condenser):
0.00010 hr x sq ft x F per Btuh
(0.000018 m2 x k per W)

24
Performance data,
30HWC,HK water-cooled — English
COOLING CAPACITIES — 60 Hz
CONDENSER ENTERING WATER TEMPERATURE (F)
75 80 85 90
LCWT UNIT UNIT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
(F) 30 SIZE Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
Cap Cap Cap Cap
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
018 14.5 12.0 34.8 42.5 14.1 12.5 33.8 41.9 13.8 13.1 32.9 41.4 13.4 13.6 32.0 40.8
025 19.3 15.3 46.3 56.2 18.7 16.0 44.9 55.2 18.2 16.6 43.5 54.2 17.6 17.2 42.0 53.2
HWC 028 25.0 20.8 60.0 73.4 24.3 21.7 58.1 72.1 23.5 22.6 56.3 70.9 22.8 23.4 54.6 69.8
035 28.0 23.2 66.9 81.9 27.2 24.1 65.1 80.7 26.4 25.0 63.3 79.5 25.7 25.9 61.4 78.3
40 040 35.0 31.8 83.8 104.2 34.1 32.9 81.6 102.8 33.2 34.0 79.5 101.4 32.3 35.0 77.3 100.0
040 40.3 30.7 96.5 116.3 39.1 32.2 93.5 114.4 37.8 33.6 90.5 112.4 36.5 35.0 87.4 110.2
HK 050 49.3 39.1 118.1 143.3 47.9 40.9 114.6 141.1 46.4 42.7 111.0 138.7 44.9 44.3 107.4 136.3
060 57.4 47.4 137.4 168.0 55.8 49.5 133.6 165.6 54.2 51.5 129.7 163.1 52.5 53.5 125.7 160.5
018 15.1 12.1 36.1 43.8 14.7 12.7 35.1 43.3 14.3 13.2 34.2 42.7 13.9 13.8 33.2 42.2
025 20.1 15.4 48.1 58.1 19.5 16.2 46.7 57.1 18.9 16.8 45.2 56.1 18.3 17.5 43.8 55.1
HWC 028 26.0 21.1 62.2 75.8 25.2 22.0 60.4 74.6 24.4 22.9 58.5 73.3 23.7 23.7 56.7 72.1
035 29.0 23.5 69.6 84.7 28.3 24.5 67.7 83.5 27.5 25.4 65.8 82.3 26.7 26.3 63.9 81.0
42 040 36.4 32.3 87.2 107.9 35.5 33.5 84.9 106.5 34.5 34.6 82.7 105.1 33.6 35.7 80.5 103.6
040 42.0 30.9 100.6 120.6 40.7 32.5 97.6 118.6 39.5 34.0 94.5 116.6 38.1 35.5 91.4 114.4
HK 050 51.4 39.4 123.2 148.6 49.9 41.3 119.6 146.3 48.4 43.2 115.9 143.9 46.9 44.9 112.3 141.4
060 59.8 47.9 143.2 174.0 58.1 50.1 139.2 171.5 56.4 52.2 135.2 169.0 54.8 54.2 131.2 166.3
018 15.6 12.2 37.4 45.2 15.2 12.8 36.4 44.6 14.8 13.4 35.4 44.1 14.4 14.0 34.4 43.5
025 20.9 15.6 50.0 60.1 20.2 16.3 48.5 59.0 19.6 17.0 47.0 58.1 19.0 17.7 45.5 57.0
HWC 028 26.9 21.3 64.6 78.2 26.1 22.3 62.7 77.0 25.4 23.2 60.8 75.8 24.6 24.1 58.9 74.4
035 30.1 23.8 72.2 87.5 29.3 24.8 70.3 86.3 28.5 25.8 68.4 85.1 27.7 26.7 66.5 83.8
44 040 37.8 32.8 90.6 111.6 36.9 34.0 88.4 110.2 35.9 35.2 86.1 108.7 35.0 36.3 83.8 107.3
040 43.7 31.2 104.8 124.9 42.4 32.8 101.7 122.9 41.1 34.3 98.6 120.8 39.8 35.9 95.4 118.7
HK 050 53.5 39.8 128.3 153.9 52.0 41.7 124.7 151.6 50.5 43.6 121.0 149.2 48.9 45.5 117.2 146.7
060 62.2 48.3 149.0 180.0 60.5 50.6 145.0 177.5 58.8 52.8 140.9 175.0 57.0 55.0 136.7 172.3
018 15.9 12.3 38.1 45.9 15.5 12.9 37.1 45.3 15.0 13.5 36.1 44.8 14.6 14.1 35.1 44.2
025 21.3 15.7 51.0 61.0 20.6 16.4 49.4 60.0 20.0 17.1 48.0 59.0 19.4 17.8 46.5 58.0
HWC 028 27.4 21.4 65.7 79.5 26.6 22.4 63.8 78.2 25.8 23.3 61.9 77.0 25.0 24.2 60.0 75.6
035 30.7 23.9 73.6 88.9 29.9 25.0 71.7 87.7 29.1 26.0 69.7 86.5 28.3 26.9 67.8 85.2
45 040 38.5 33.1 92.4 113.5 37.6 34.3 90.1 112.1 36.6 35.5 87.8 110.6 35.6 36.6 85.5 109.1
040 44.6 31.3 107.0 127.1 43.3 32.9 103.8 125.1 42.0 34.5 100.7 123.0 40.6 36.1 97.5 120.9
HK 050 54.6 39.9 130.9 156.6 53.1 41.9 127.2 154.3 51.5 43.9 123.5 151.9 49.9 45.8 119.7 149.4
060 63.4 48.5 152.0 183.1 61.7 50.9 147.9 180.6 59.9 53.1 143.8 178.0 58.2 55.3 139.6 175.4
018 16.2 12.3 38.8 46.6 15.7 12.9 37.7 46.0 15.3 13.6 36.7 45.5 14.9 14.2 35.7 44.9
025 21.6 15.8 51.9 62.0 21.0 16.5 50.4 61.1 20.4 17.2 48.9 60.0 19.7 18.0 47.4 59.0
HWC 028 27.9 21.6 66.9 80.7 27.1 22.6 65.0 79.5 26.3 23.5 63.1 78.2 25.5 24.4 61.2 76.9
035 31.2 24.1 75.0 90.4 30.4 25.1 73.0 89.2 29.6 26.1 71.1 87.9 28.8 27.1 69.1 86.6
46 040 39.3 33.3 94.2 115.5 38.3 34.6 91.8 114.0 37.3 35.8 89.5 112.5 36.3 37.0 87.2 111.0
040 45.5 31.4 109.1 129.3 44.2 33.0 106.0 127.2 42.8 34.7 102.8 125.2 41.5 36.3 99.5 123.0
HK 050 55.7 40.1 133.6 159.3 54.1 42.1 129.9 157.0 52.6 44.1 126.1 154.5 51.0 46.0 122.3 152.0
060 64.6 48.7 155.0 186.2 62.9 51.1 150.8 183.7 61.1 53.4 146.7 181.1 59.4 55.7 142.4 178.4
018 16.7 12.4 40.2 48.1 16.3 13.1 39.1 47.5 15.9 13.7 38.1 46.9 15.4 14.3 37.0 46.3
025 22.4 15.9 53.8 64.0 21.8 16.7 52.3 63.1 21.2 17.5 50.8 62.1 20.5 18.2 49.3 61.0
HWC 028 28.9 21.8 69.3 83.2 28.1 22.8 67.3 82.0 27.2 23.8 65.4 80.7 26.4 24.8 63.4 79.4
035 32.4 24.4 77.8 93.4 31.6 25.5 75.8 92.2 30.7 26.5 73.8 90.8 29.9 27.5 71.8 89.5
48 040 40.8 33.8 97.8 119.4 39.8 35.1 95.4 117.9 38.8 36.4 93.0 116.3 37.8 37.6 90.6 114.8
040 47.3 31.6 113.5 133.7 46.0 33.3 110.3 131.7 44.6 35.0 107.0 129.6 43.2 36.6 103.7 127.4
HK 050 57.9 40.4 139.0 164.8 56.3 42.5 135.2 162.5 54.7 44.6 131.3 160.0 53.1 46.6 127.4 157.5
060 67.1 49.1 161.1 192.5 65.4 51.6 156.8 189.9 63.6 54.0 152.6 187.3 61.8 56.3 148.2 184.6
018 17.3 12.5 41.6 49.6 16.9 13.2 40.5 49.0 16.4 13.8 39.4 48.3 16.0 14.5 38.4 47.7
025 23.2 16.1 55.8 66.1 22.6 16.9 54.3 65.1 21.9 17.7 52.7 64.1 21.3 18.4 51.1 63.0
HWC 028 29.9 22.1 71.8 85.8 29.0 23.1 69.7 84.5 28.2 24.1 67.7 83.2 27.4 25.1 65.7 81.9
035 33.6 24.6 80.7 96.4 32.8 25.8 78.7 95.1 31.9 26.9 76.6 93.9 31.0 27.9 74.5 92.5
50 040 42.3 34.3 101.6 123.5 41.3 35.6 99.2 121.9 40.2 36.9 96.6 120.3 39.2 38.2 94.1 118.7
040 49.1 31.8 118.0 138.3 47.8 33.5 114.7 136.2 46.4 35.3 111.4 134.1 45.0 37.0 108.0 131.9
HK 050 60.2 40.7 144.6 170.6 58.6 42.9 140.7 168.2 56.9 45.0 136.6 165.6 55.2 47.1 132.6 163.0
060 69.7 49.5 167.3 198.9 67.9 52.1 163.0 196.3 66.1 54.6 158.6 193.7 64.2 57.0 154.2 190.9
018 18.9 12.7 45.3 53.4 18.4 13.4 44.2 52.7 17.9 14.1 43.0 52.1 17.4 14.8 41.9 51.4
025 25.3 16.5 60.8 71.4 24.7 17.4 59.3 70.3 24.0 18.2 57.6 69.3 23.3 19.0 56.0 68.2
HWC 028 32.5 22.7 78.1 92.5 31.6 23.8 76.0 91.2 30.7 24.9 73.8 89.8 29.8 26.0 71.7 88.4
035 36.6 25.3 88.1 104.1 35.8 26.5 85.9 102.8 34.9 27.7 83.8 101.5 34.0 28.8 81.6 100.2
55 040 46.3 35.4 111.3 133.8 45.2 36.9 108.7 132.2 44.1 38.4 106.0 130.6 43.0 39.7 103.4 128.9
040 53.9 32.2 129.5 150.1 52.5 34.1 126.1 147.9 51.0 36.0 122.6 145.8 49.5 37.9 119.0 143.4
HK 050 66.1 41.3 158.9 185.2 64.4 43.7 154.8 182.7 62.7 46.0 150.6 180.1 60.9 48.3 146.4 177.5
060 76.4 50.2 183.7 215.6 74.5 53.1 179.0 212.9 72.6 55.8 174.4 210.2 70.6 58.5 169.7 207.3
018 20.5 12.8 49.3 57.4 20.0 13.6 48.0 56.7 19.5 14.4 46.8 56.0 19.0 15.1 45.6 55.3
025 27.5 16.9 66.1 76.8 26.8 17.8 64.5 75.8 26.1 18.7 62.8 74.7 25.4 19.6 61.1 73.6
HWC 028 35.2 23.3 84.7 99.4 34.3 24.5 82.4 98.0 33.3 25.7 80.2 96.6 32.4 26.8 78.0 95.2
035 39.8 25.9 95.8 112.2 38.9 27.2 93.6 110.9 38.0 28.5 91.3 109.5 37.0 29.7 89.0 108.1
60 040 50.5 36.5 121.5 144.6 49.4 38.2 118.7 142.9 48.2 39.7 115.9 141.2 47.0 41.2 113.1 139.5
040 58.3 32.5 140.2 160.9 56.7 34.6 136.4 158.4 55.1 36.6 132.5 155.9 53.2 38.5 128.1 152.8
HK 050 71.8 41.7 172.8 199.2 69.9 44.3 168.2 196.4 67.9 46.7 163.3 193.2 65.8 49.2 158.3 189.9
060 83.3 50.8 200.5 232.6 81.2 53.8 195.3 229.6 79.0 56.8 190.1 226.4 76.8 59.7 184.8 223.1

(See Legend on page 26.)

25
Performance data,
30HWB water-cooled — English
COOLING CAPACITIES — 60 Hz (cont)
CONDENSER ENTERING WATER TEMPERATURE (F)
75 80 85 90
LCWT UNIT UNIT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
(F) 30 SIZE Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
Cap Cap Cap Cap
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
018 14.5 12.0 34.8 42.5 14.1 12.5 33.8 41.9 13.8 13.1 32.9 41.4 13.4 13.6 32.0 40.8
025 19.3 15.3 46.3 56.2 18.7 16.0 44.9 55.2 18.2 16.6 43.5 54.2 17.6 17.2 42.0 53.2
40 HWB 028 25.0 20.8 60.0 73.4 24.3 21.7 58.1 72.1 23.5 22.6 56.3 70.9 22.8 23.4 54.6 69.8
035 28.0 23.2 66.9 81.9 27.2 24.1 65.1 80.7 26.4 25.0 63.3 79.5 25.7 25.9 61.4 78.3
040 35.0 31.8 83.8 104.2 34.1 32.9 81.6 102.8 33.2 34.0 79.5 101.4 32.3 35.0 77.3 100.0
018 15.1 12.1 36.1 43.8 14.7 12.7 35.1 43.3 14.3 13.2 34.2 42.7 13.9 13.8 33.2 42.2
025 20.1 15.4 48.1 58.1 19.5 16.2 46.7 57.1 18.9 16.8 45.2 56.1 18.3 17.5 43.8 55.1
42 HWB 028 26.0 21.1 62.2 75.8 25.2 22.0 60.4 74.6 24.4 22.9 58.5 73.3 23.7 23.7 56.7 72.1
035 29.0 23.5 69.6 84.7 28.3 24.5 67.7 83.5 27.5 25.4 65.8 82.3 26.7 26.3 63.9 81.0
040 36.4 32.3 87.2 107.9 35.5 33.5 84.9 106.5 34.5 34.6 82.7 105.1 33.6 35.7 80.5 103.6
018 15.6 12.2 37.4 45.2 15.2 12.8 36.4 44.6 14.8 13.4 35.4 44.1 14.4 14.0 34.4 43.5
025 20.9 15.6 50.0 60.1 20.2 16.3 48.5 59.0 19.6 17.0 47.0 58.1 19.0 17.7 45.5 57.0
44 HWB 028 26.9 21.3 64.6 78.2 26.1 22.3 62.7 77.0 25.4 23.2 60.8 75.8 24.6 24.1 58.9 74.4
035 30.1 23.8 72.2 87.5 29.3 24.8 70.3 86.3 28.5 25.8 68.4 85.1 27.7 26.7 66.5 83.8
040 37.8 32.8 90.6 111.6 36.9 34.0 88.4 110.2 35.9 35.2 86.1 108.7 35.0 36.3 83.8 107.3
018 15.9 12.3 38.1 45.9 15.5 12.9 37.1 45.3 15.0 13.5 36.1 44.8 14.6 14.1 35.1 44.2
025 21.3 15.7 51.0 61.0 20.6 16.4 49.4 60.0 20.0 17.1 48.0 59.0 19.4 17.8 46.5 58.0
45 HWB 028 27.4 21.4 65.7 79.5 26.6 22.4 63.8 78.2 25.8 23.3 61.9 77.0 25.0 24.2 60.0 75.6
035 30.7 23.9 73.6 88.9 29.9 25.0 71.7 87.7 29.1 26.0 69.7 86.5 28.3 26.9 67.8 85.2
040 38.5 33.1 92.4 113.5 37.6 34.3 90.1 112.1 36.6 35.5 87.8 110.6 35.6 36.6 85.5 109.1
018 16.2 12.3 38.8 46.6 15.7 12.9 37.7 46.0 15.3 13.6 36.7 45.5 14.9 14.2 35.7 44.9
025 21.6 15.8 51.9 62.0 21.0 16.5 50.4 61.1 20.4 17.2 48.9 60.0 19.7 18.0 47.4 59.0
46 HWB 028 27.9 21.6 66.9 80.7 27.1 22.6 65.0 79.5 26.3 23.5 63.1 78.2 25.5 24.4 61.2 76.9
035 31.2 24.1 75.0 90.4 30.4 25.1 73.0 89.2 29.6 26.1 71.1 87.9 28.8 27.1 69.1 86.6
040 39.3 33.3 94.2 115.5 38.3 34.6 91.8 114.0 37.3 35.8 89.5 112.5 36.3 37.0 87.2 111.0
018 16.7 12.4 40.2 48.1 16.3 13.1 39.1 47.5 15.9 13.7 38.1 46.9 15.4 14.3 37.0 46.3
025 22.4 15.9 53.8 64.0 21.8 16.7 52.3 63.1 21.2 17.5 50.8 62.1 20.5 18.2 49.3 61.0
48 HWB 028 28.9 21.8 69.3 83.2 28.1 22.8 67.3 82.0 27.2 23.8 65.4 80.7 26.4 24.8 63.4 79.4
035 32.4 24.4 77.8 93.4 31.6 25.5 75.8 92.2 30.7 26.5 73.8 90.8 29.9 27.5 71.8 89.5
040 40.8 33.8 97.8 119.4 39.8 35.1 95.4 117.9 38.8 36.4 93.0 116.3 37.8 37.6 90.6 114.8
018 17.3 12.5 41.6 49.6 16.9 13.2 40.5 49.0 16.4 13.8 39.4 48.3 16.0 14.5 38.4 47.7
025 23.2 16.1 55.8 66.1 22.6 16.9 54.3 65.1 21.9 17.7 52.7 64.1 21.3 18.4 51.1 63.0
50 HWB 028 29.9 22.1 71.8 85.8 29.0 23.1 69.7 84.5 28.2 24.1 67.7 83.2 27.4 25.1 65.7 81.9
035 33.6 24.6 80.7 96.4 32.8 25.8 78.7 95.1 31.9 26.9 76.6 93.9 31.0 27.9 74.5 92.5
040 42.3 34.3 101.6 123.5 41.3 35.6 99.2 121.9 40.2 36.9 96.6 120.3 39.2 38.2 94.1 118.7
018 18.9 12.7 45.3 53.4 18.4 13.4 44.2 52.7 17.9 14.1 43.0 52.1 17.4 14.8 41.9 51.4
025 25.3 16.5 60.8 71.4 24.7 17.4 59.3 70.3 24.0 18.2 57.6 69.3 23.3 19.0 56.0 68.2
55 HWB 028 32.5 22.7 78.1 92.5 31.6 23.8 76.0 91.2 30.7 24.9 73.8 89.8 29.8 26.0 71.7 88.4
035 36.6 25.3 88.1 104.1 35.8 26.5 85.9 102.8 34.9 27.7 83.8 101.5 34.0 28.8 81.6 100.2
040 46.3 35.4 111.3 133.8 45.2 36.9 108.7 132.2 44.1 38.4 106.0 130.6 43.0 39.7 103.4 128.9
018 20.5 12.8 49.3 57.4 20.0 13.6 48.0 56.7 19.5 14.4 46.8 56.0 19.0 15.1 45.6 55.3
025 27.5 16.9 66.1 76.8 26.8 17.8 64.5 75.8 26.1 18.7 62.8 74.7 25.4 19.6 61.1 73.6
60 HWB 028 35.2 23.3 84.7 99.4 34.3 24.5 82.4 98.0 33.3 25.7 80.2 96.6 32.4 26.8 78.0 95.2
035 39.8 25.9 95.8 112.2 38.9 27.2 93.6 110.9 38.0 28.5 91.3 109.5 37.0 29.7 89.0 108.1
040 50.5 36.5 121.5 144.6 49.4 38.2 118.7 142.9 48.2 39.7 115.9 141.2 47.0 41.2 113.1 139.5
LEGEND
ARI — Air Conditioning and Refrigeration Institute (U.S.A.)
Cap — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

26
Performance data, 30HWA,HL in combination
with 09DK air-cooled condenser — English
COOLING CAPACITIES — 60 Hz (cont)
CONDENSER ENTERING WATER TEMPERATURE (F)
REMOTE 85 95 105 115 125
LCWT UNIT UNIT Cooler Cooler Cooler Cooler Cooler
COND
(F) 30 SIZE Input Flow Input Flow Input Flow Input Flow Input Flow
09DK Cap Cap Cap Cap Cap
kW Rate kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
018 020 13.4 13.6 32.0 12.6 14.6 30.2 11.9 15.5 28.4 11.1 16.4 26.6 * * *
025 028 17.3 16.8 41.5 16.2 17.9 38.8 15.0 19.0 36.0 13.8 19.8 33.1 12.6 20.6 30.2
HWA 028 028 22.3 23.5 53.5 20.9 24.9 50.1 19.6 26.3 46.8 18.2 27.5 43.5 * * *
40 035 034 24.6 25.3 58.9 23.1 26.8 55.4 21.6 28.2 51.7 20.1 29.3 48.1 18.5 30.3 44.4
040 044 31.3 34.8 74.9 29.5 36.7 70.7 27.8 38.5 66.5 26.1 40.1 62.4 24.3 41.6 58.2
050 028,024 44.2 46.1 105.8 41.3 48.7 98.8 38.3 51.1 91.8 * * * * * *
HL
060 034,034 53.1 53.6 127.1 49.9 57.0 119.4 46.6 60.0 111.6 43.3 62.6 103.6 * * *
018 020 13.8 13.8 33.1 13.1 14.9 31.3 12.3 15.8 29.5 11.5 16.8 27.6 * * *
025 028 18.0 17.1 43.1 16.8 18.3 40.3 15.7 19.3 37.5 14.4 20.3 34.5 13.2 21.1 31.6
HWA 028 028 23.1 23.9 55.4 21.7 25.5 52.0 20.3 26.8 48.5 18.9 28.1 45.2 * * *
42 035 034 25.5 25.7 61.2 24.0 27.3 57.6 22.5 28.8 53.9 20.9 30.0 50.1 * * *
040 044 32.5 35.5 77.8 30.7 37.5 73.6 28.9 39.4 69.3 27.1 41.1 65.0 * * *
050 028,024 46.0 47.1 110.1 43.0 49.8 103.0 40.0 52.3 95.9 45.2 64.1 108.2 * * *
HL
060 034,034 55.2 54.6 132.3 51.9 58.1 124.4 48.6 61.3 116.4 * * * * * *
018 020 14.3 14.1 34.3 13.5 15.1 32.4 12.7 16.1 30.5 12.0 17.1 28.7 * * *
025 028 18.7 17.3 44.8 17.5 18.6 41.9 16.3 19.7 39.0 15.0 20.7 36.0 13.8 21.6 33.0
HWA 028 028 23.9 24.4 57.4 22.5 25.9 53.9 21.0 27.4 50.4 19.6 28.7 46.9 * * *
44 035 034 26.5 26.2 63.5 25.0 27.9 59.8 23.4 29.4 56.1 21.8 30.7 52.2 * * *
040 044 33.7 36.2 80.8 31.9 38.3 76.5 30.1 40.2 72.1 28.2 42.0 67.7 * * *
050 028,024 47.8 48.1 114.7 44.8 51.0 107.4 41.7 53.6 100.0 47.1 65.6 112.9 * * *
HL
060 034,034 57.4 55.6 137.6 54.0 59.3 129.5 50.6 62.6 121.3 * * * * * *
018 020 14.6 14.2 34.9 13.8 15.2 33.0 13.0 16.3 31.1 12.2 17.2 29.2 * * *
025 028 19.0 17.5 45.6 17.8 18.8 42.8 16.6 19.9 39.8 15.4 20.9 36.8 14.1 21.8 33.7
HWA 028 028 24.3 24.6 58.4 22.9 26.2 54.9 21.4 27.7 51.3 19.9 29.0 47.8 * * *
45 035 034 27.0 26.4 64.7 25.4 28.1 61.0 23.8 29.7 57.2 22.2 31.0 53.3 * * *
040 044 34.3 36.5 82.3 32.5 38.7 78.0 30.7 40.7 73.5 28.8 42.5 69.0 * * *
050 028,024 48.8 48.5 117.0 45.7 51.5 109.6 42.6 54.2 102.1 * * * * * *
HL
060 034,034 58.5 56.1 140.3 55.1 59.9 132.1 51.6 63.3 123.8 48.1 66.3 115.3 * * *
018 020 14.8 14.3 35.5 14.0 15.4 33.6 13.2 16.4 31.7 12.4 17.4 29.7 * * *
025 028 19.4 17.6 46.5 18.2 18.9 43.6 16.9 20.1 40.6 15.7 21.2 37.6 14.4 22.1 34.4
HWA 028 028 24.8 24.9 59.5 23.3 26.5 55.8 21.8 27.9 52.3 20.3 29.3 48.7 * * *
46 035 034 27.4 26.7 65.8 25.9 28.4 62.1 24.3 30.0 58.3 22.7 31.4 54.4 * * *
040 044 35.0 36.9 83.9 33.1 39.1 79.4 31.3 41.1 75.0 29.4 43.0 70.5 * * *
050 028,024 49.7 49.0 119.3 46.6 52.1 111.8 43.5 54.8 104.2 * * * * * *
HL
060 034,034 59.6 56.6 143.0 56.2 60.4 134.7 52.6 63.9 126.3 49.1 67.1 117.7 * * *
018 020 15.3 14.5 36.8 14.5 15.6 34.7 13.6 16.7 32.8 12.8 17.7 30.8 * * *
025 028 20.1 17.9 48.2 18.8 19.2 45.2 17.6 20.5 42.2 16.3 21.6 39.1 * * *
HWA 028 028 25.6 25.3 61.5 24.1 27.0 57.8 22.6 28.5 54.2 21.0 30.0 50.5 * * *
48 035 034 28.4 27.1 68.2 26.8 28.9 64.4 25.2 30.6 60.5 23.6 32.1 56.5 * * *
040 044 36.3 37.6 87.0 34.4 39.9 82.4 32.4 42.0 77.9 30.5 44.0 73.2 * * *
050 028,024 51.6 50.0 123.9 48.5 53.2 116.3 45.2 56.1 108.6 * * * * * *
HL
060 034,034 61.9 57.6 148.6 58.3 61.6 140.0 54.7 65.3 131.4 * * * * * *
018 020 15.8 14.7 38.0 15.0 15.9 36.0 14.1 17.0 33.9 13.3 18.0 31.9 * * *
025 028 20.8 18.2 49.8 19.5 19.6 46.8 18.2 20.9 43.8 16.9 22.0 40.6 * * *
HWA 028 028 26.5 25.8 63.6 24.9 27.5 59.9 23.3 29.1 56.0 21.8 30.6 52.3 * * *
50 035 034 29.5 27.6 70.7 27.8 29.5 66.7 26.1 31.2 62.8 24.5 32.7 58.7 * * *
040 044 37.6 38.3 90.2 35.6 40.6 85.5 33.6 42.9 80.8 31.7 44.9 76.1 * * *
HL 050 028,024 53.6 51.1 128.7 50.3 54.3 120.9 47.0 57.3 113.0 * * * * * *
060 034,034 64.2 58.6 154.2 60.6 62.8 145.5 56.9 66.6 136.6 * * * * * *
018 020 17.2 15.3 41.3 16.3 16.6 39.1 15.4 17.7 36.9 14.4 18.9 34.7 * * *
025 028 22.6 18.9 54.3 21.3 20.4 51.1 19.9 21.8 47.9 18.6 23.1 44.6 * * *
HWA 028 028 28.7 27.0 69.1 27.1 28.8 65.0 25.4 30.5 61.1 * * * * * *
55 035 034 32.1 28.8 77.1 30.4 30.8 73.0 28.6 32.7 68.7 26.8 34.4 64.3 * * *
040 044 41.0 40.1 98.6 38.9 42.7 93.6 36.8 45.1 88.5 34.7 47.3 83.3 * * *
050 028,024 58.7 53.6 141.0 55.2 57.2 132.7 * * * * * * * * *
HL 060 034,034 70.2 61.1 168.7 66.4 65.7 159.5 62.5 69.9 150.1 * * * * * *
018 020 18.6 15.9 44.6 17.6 17.2 42.3 16.6 18.5 40.0 * * * * * *
025 028 24.5 19.6 58.9 23.1 21.2 55.6 21.7 22.7 52.2 20.3 24.2 48.8 * * *
HWA 028 028 31.1 28.2 74.7 29.3 30.1 70.5 27.6 32.0 66.3 * * * * * *
60 035 034 34.8 30.0 83.7 33.0 32.2 79.4 31.2 34.3 74.9 29.2 36.2 70.4 * * *
040 044 44.6 41.9 107.3 42.4 44.7 102.0 40.1 47.4 96.5 37.9 49.9 91.1 * * *
050 028,024 62.8 55.7 151.0 58.8 59.4 141.5 * * * * * * * * *
HL
060 034,034 76.0 63.5 182.9 71.7 68.4 172.6 67.4 72.8 162.1 * * * * * *
LEGEND *Operation not recommended with condenser identified. Contact your Carrier rep-
Cap — Capacity, Tons of Refrigeration resentative for an alternate equipment selection.
COND — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

27
Performance data,
30HWA,HL condenserless — English
COOLING CAPACITIES — 60 Hz (cont)
SATURATED DISCHARGE TEMPERATURE (F)
95 110 120 135
LCWT UNIT UNIT Cooler Cooler Cooler Cooler
(F) 30 SIZE Input Flow Input Flow Input Flow Input Flow
Cap THR Cap THR Cap THR Cap THR
kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm)
018 13.9 11.9 33.3 17.0 12.7 13.6 30.4 16.2 11.9 14.7 28.5 15.7 10.7 16.2 25.5 14.9
025 18.0 15.1 43.2 22.0 16.2 17.2 38.8 20.7 15.0 18.5 35.8 19.7 13.0 20.0 31.1 18.2
HWA 028 23.9 20.4 57.2 29.2 21.5 23.2 51.6 27.6 20.0 24.9 47.8 26.4 17.7 27.1 42.4 24.7
40 035 25.6 22.7 61.3 31.5 23.2 25.6 55.6 29.9 21.6 27.2 51.8 28.7 19.2 29.4 45.9 26.8
040 32.2 31.9 77.2 40.5 29.5 35.4 70.5 38.6 27.6 37.4 66.1 37.3 24.8 40.2 59.4 35.2
HL 050 50.3 39.2 120.4 60.4 45.7 44.6 109.3 57.2 42.5 47.8 101.8 54.9 37.6 51.8 90.1 51.0
060 58.6 47.4 140.3 70.9 53.5 53.7 128.2 67.4 50.1 57.4 119.8 64.9 44.7 62.1 107.0 60.8
018 14.5 12.0 34.7 17.6 13.2 13.8 31.6 16.8 12.4 14.9 29.6 16.2 11.1 16.5 26.6 15.4
025 18.8 15.2 45.0 22.7 16.9 17.4 40.5 21.4 15.6 18.7 37.5 20.5 13.6 20.4 32.7 18.9
HWA 028 24.8 20.6 59.5 30.2 22.4 23.5 53.7 28.5 20.8 25.2 49.9 27.4 18.5 27.6 44.2 25.6
42 035 26.6 22.9 63.8 32.6 24.2 25.9 58.1 30.9 22.6 27.7 54.1 29.8 20.1 29.9 48.0 27.8
040 33.6 32.3 80.5 41.9 30.7 35.9 73.6 40.0 28.8 38.1 69.0 38.7 25.9 41.0 62.1 36.5
050 52.5 39.4 125.7 62.7 47.8 45.1 114.4 59.4 44.5 48.5 106.7 57.1 39.5 52.8 94.7 53.2
HL
060 61.1 47.7 146.4 73.4 55.9 54.3 133.9 70.0 52.4 58.3 125.4 67.4 46.9 63.3 112.3 63.3
018 15.0 12.0 36.0 18.1 13.7 13.9 32.9 17.3 12.9 15.1 30.9 16.8 11.6 16.7 27.7 15.9
025 19.5 15.3 46.8 23.5 17.7 17.6 42.4 22.2 16.3 19.0 39.1 21.2 14.3 20.8 34.3 19.7
HWA 028 25.8 20.7 61.9 31.2 23.3 23.7 55.9 29.5 21.7 25.6 52.1 28.3 19.3 28.0 46.2 26.5
44 035 27.7 23.1 66.4 33.7 25.3 26.2 60.6 32.0 23.6 28.1 56.5 30.8 21.0 30.5 50.3 28.9
040 35.0 32.6 83.8 43.4 32.0 36.4 76.8 41.4 30.1 38.7 72.0 40.1 27.1 41.8 64.9 37.9
HL 050 54.7 39.6 131.2 65.0 49.9 45.5 119.7 61.7 46.6 49.1 111.7 59.3 41.5 53.8 99.5 55.4
060 63.6 48.0 152.6 76.1 58.3 54.9 139.9 72.6 54.7 59.1 131.2 70.0 49.1 64.5 117.7 65.8
018 15.3 12.0 36.7 18.4 14.0 13.9 33.5 17.6 13.1 15.2 31.5 17.1 11.8 16.8 28.3 16.2
025 19.9 15.3 47.7 23.9 18.0 17.7 43.2 22.6 16.7 19.1 40.0 21.6 14.6 20.9 35.1 20.1
HWA 028 26.3 20.7 63.1 31.7 23.8 23.8 57.0 30.0 22.1 25.7 53.1 28.8 19.7 28.2 47.2 27.0
45 035 28.2 23.1 67.7 34.2 25.8 26.3 61.8 32.6 24.1 28.3 57.7 31.4 21.5 30.7 51.4 29.4
040 35.7 32.8 85.6 44.2 32.7 36.7 78.4 42.2 30.7 39.0 73.6 40.8 27.7 42.2 66.4 38.6
HL 050 55.9 39.7 134.0 66.1 51.0 45.8 122.3 62.9 47.7 49.4 114.3 60.5 42.5 54.2 101.9 56.5
060 64.9 48.1 155.7 77.4 59.6 55.2 142.9 73.9 55.9 59.5 134.1 71.3 50.2 65.0 120.5 67.1
018 15.6 12.0 37.4 18.7 14.3 14.0 34.2 17.9 13.4 15.2 32.1 17.3 12.0 16.9 28.9 16.4
025 20.3 15.4 48.7 24.3 18.4 17.8 44.1 23.0 17.0 19.2 40.8 22.0 15.0 21.1 35.9 20.4
HWA 028 26.8 20.8 64.3 32.2 24.3 23.9 58.2 30.5 22.6 25.9 54.2 29.3 20.1 28.5 48.2 27.4
46 035 28.8 23.2 69.1 34.8 26.3 26.5 63.1 33.2 24.6 28.4 59.0 31.9 21.9 31.0 52.6 30.0
040 36.4 32.9 87.3 44.9 33.4 36.9 80.0 42.9 31.3 39.3 75.2 41.5 28.3 42.6 67.8 39.3
HL 050 57.0 39.7 136.8 67.3 52.1 46.0 125.0 64.0 48.7 49.8 116.9 61.6 43.5 54.7 104.4 57.7
060 66.3 48.2 158.9 78.7 60.8 55.5 145.9 75.2 57.1 59.8 137.0 72.6 51.4 65.6 123.3 68.4
018 16.2 12.1 38.8 19.3 14.8 14.1 35.5 18.4 13.9 15.4 33.3 17.9 12.5 17.1 30.0 16.9
025 21.1 15.4 50.6 25.1 19.1 17.9 45.9 23.8 17.8 19.4 42.7 22.8 15.7 21.4 37.6 21.2
HWA 028 27.8 20.9 66.8 33.2 25.2 24.2 60.5 31.5 23.5 26.2 56.4 30.3 20.9 28.9 50.1 28.3
48 035 29.9 23.3 71.8 35.9 27.4 26.7 65.7 34.3 25.6 28.8 61.5 33.1 22.9 31.5 55.0 31.1
040 37.9 33.2 90.8 46.4 34.7 37.4 83.4 44.4 32.6 39.9 78.4 43.0 29.5 43.4 70.8 40.7
050 59.4 39.8 142.6 69.7 54.4 46.4 130.5 66.4 50.9 50.3 122.2 64.0 45.6 55.6 109.4 60.0
HL
060 68.9 48.3 165.4 81.4 63.4 56.0 152.2 77.9 59.6 60.6 143.0 75.3 53.7 66.7 129.0 71.0
018 16.8 12.1 40.2 19.9 15.4 14.2 36.9 19.0 14.4 15.5 34.6 18.4 13.0 17.4 31.3 17.5
025 21.9 15.5 52.5 25.9 19.9 18.0 47.8 24.6 18.5 19.6 44.4 23.6 16.4 21.8 39.3 22.0
HWA 028 28.9 21.0 69.3 34.3 26.2 24.4 62.9 32.5 24.4 26.4 58.6 31.3 21.8 29.3 52.3 29.4
50 035 31.1 23.4 74.6 37.1 28.5 27.0 68.3 35.4 26.7 29.1 64.0 34.2 23.9 32.0 57.4 32.2
040 39.4 33.5 94.5 48.0 36.1 37.8 86.8 45.9 34.0 40.5 81.6 44.5 30.8 44.1 73.8 42.2
050 61.8 39.9 148.5 72.2 56.7 46.7 136.1 68.8 53.2 50.9 127.6 66.3 47.7 56.5 114.6 62.3
HL
060 71.7 48.4 172.1 84.2 66.0 56.4 158.5 80.6 62.1 61.2 149.2 78.0 56.1 67.7 134.8 73.7
018 18.3 12.1 44.0 21.4 16.8 14.4 40.4 20.5 15.8 15.8 38.0 19.9 14.3 17.8 34.4 18.9
025 24.0 15.5 57.6 28.0 21.9 18.3 52.6 26.6 20.4 20.1 49.1 25.6 18.2 22.5 43.7 24.0
HWA 028 31.6 21.1 75.9 37.0 28.7 24.8 69.0 35.1 26.8 27.1 64.5 33.9 24.0 30.3 57.7 31.9
55 035 34.0 23.5 81.8 40.1 31.3 27.5 75.2 38.4 29.4 29.9 70.7 37.1 26.5 33.2 63.6 35.1
040 43.2 34.0 103.9 52.0 39.8 38.9 95.7 49.9 37.5 41.9 90.2 48.4 34.0 46.0 81.8 45.9
050 68.1 39.9 163.8 78.5 62.7 47.4 150.8 75.0 59.0 52.0 141.8 72.5 53.3 58.4 128.0 68.4
HL 060 78.8 48.5 189.4 91.4 72.8 57.3 175.1 87.7 68.7 62.7 165.2 85.0 62.4 70.1 150.0 80.5
018 19.9 12.0 48.0 23.0 18.3 14.5 44.1 22.1 17.3 16.0 41.5 21.4 15.7 18.3 37.7 20.4
025 26.1 15.5 62.9 30.2 24.0 18.5 57.6 28.8 22.5 20.5 54.0 27.7 20.1 23.1 48.4 26.1
HWA 028 34.4 21.1 82.8 39.9 31.4 25.1 75.6 37.9 29.4 27.7 70.7 36.6 26.4 31.2 63.5 34.5
60 035 37.1 23.5 89.4 43.2 34.3 27.9 82.5 41.5 32.3 30.5 77.7 40.2 29.2 34.3 70.3 38.1
040 47.4 34.4 114.0 56.3 43.7 39.8 105.2 54.0 41.3 43.1 99.3 52.4 37.5 47.7 90.3 49.9
050 74.5 39.6 179.2 84.7 68.3 47.7 164.4 80.7 63.9 52.8 153.8 77.6 57.2 59.6 137.5 72.6
HL
060 86.4 48.1 207.7 98.8 79.7 57.8 191.8 94.7 75.1 63.8 180.7 91.6 68.0 71.9 163.6 86.6
LEGEND NOTE: Performance based on 15 F subcooling.
Cap — Capacity, Tons of Refrigeration
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)
THR — Total Heat of Rejection, Tons of Refrigeration

28
Performance data,
30HWC,HK water-cooled — English
COOLING CAPACITIES — 50 Hz
CONDENSER ENTERING WATER TEMPERATURE (F)
75 80 85 90
LCWT UNIT UNIT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
(F) 30 SIZE Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
Cap Cap Cap Cap
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
018 13.6 9.6 32.6 38.9 13.3 10.2 31.8 38.4 12.9 10.8 30.9 38.0 12.6 11.4 30.1 37.6
025 17.1 12.1 41.0 48.9 16.6 12.7 39.8 48.1 16.1 13.3 38.5 47.2 15.6 13.9 37.2 46.3
HWC 028 21.6 16.1 51.6 62.0 20.8 16.8 49.8 60.7 20.1 17.5 48.0 59.4 19.3 18.1 46.3 58.1
035 23.7 19.0 56.7 68.9 23.0 19.8 55.0 67.8 22.2 20.6 53.2 66.6 21.5 21.3 51.5 65.3
40 040 32.3 26.4 77.4 94.4 31.5 27.4 75.4 93.1 30.6 28.5 73.3 91.8 29.8 29.4 71.3 90.5
040 41.2 33.5 98.6 120.2 40.0 35.1 95.7 118.4 38.8 36.6 92.8 116.5 37.6 38.1 89.9 114.6
HK 050 48.8 39.4 116.7 142.2 47.4 41.2 113.4 140.1 46.0 43.0 110.1 137.9 44.6 44.7 106.7 135.7
060 62.1 59.4 148.6 186.7 60.4 61.6 144.6 184.2 58.7 63.7 140.5 181.6 57.0 65.8 136.4 179.0
018 14.1 9.7 33.8 40.0 13.8 10.3 33.0 39.6 13.4 10.9 32.1 39.2 13.0 11.5 31.2 38.8
025 17.8 12.2 42.6 50.6 17.3 12.9 41.4 49.7 16.7 13.5 40.1 48.9 16.2 14.1 38.8 48.0
HWC 028 22.6 16.3 54.1 64.7 21.8 17.0 52.3 63.3 21.0 17.7 50.4 61.9 20.3 18.4 48.6 60.6
035 24.7 19.2 59.3 71.6 24.0 20.0 57.5 70.5 23.3 20.9 55.7 69.2 22.5 21.6 54.0 68.0
42 040 33.7 26.7 80.7 97.9 32.8 27.8 78.5 96.4 31.9 28.9 76.4 95.1 31.0 29.9 74.4 93.7
040 42.9 33.8 102.7 124.4 41.6 35.4 99.8 122.6 40.4 37.0 96.8 120.8 39.2 38.6 93.8 118.8
HK 050 50.8 39.7 121.7 147.3 49.4 41.6 118.3 145.2 48.0 43.5 114.9 143.0 46.5 45.3 111.4 140.7
060 64.6 60.1 154.8 193.3 62.8 62.5 150.6 190.7 61.1 64.7 146.4 188.0 59.3 66.9 142.2 185.4
018 14.6 9.7 35.0 41.3 14.2 10.4 34.2 40.9 13.9 11.0 33.3 40.4 13.5 11.6 32.4 40.0
025 18.5 12.3 44.3 52.2 18.0 13.0 43.0 51.4 17.4 13.6 41.8 50.6 16.9 14.2 40.4 49.6
HWC 028 23.7 16.5 56.7 67.4 22.9 17.3 54.8 66.0 22.1 18.0 52.9 64.6 21.3 18.7 51.0 63.2
035 25.8 19.4 62.0 74.4 25.1 20.3 60.2 73.2 24.3 21.1 58.3 72.0 23.6 21.9 56.5 70.7
44 040 35.0 27.0 83.9 101.3 34.1 28.2 81.8 99.9 33.2 29.3 79.7 98.6 32.3 30.3 77.4 97.1
040 44.6 34.1 106.9 128.8 43.3 35.8 103.9 126.9 42.1 37.4 100.9 125.1 40.8 39.1 97.8 123.1
HK 050 52.9 40.0 126.8 152.5 51.4 42.0 123.3 150.4 50.0 44.0 119.8 148.2 48.5 45.8 116.2 145.9
060 67.2 60.9 161.0 200.0 65.4 63.4 156.7 197.3 63.6 65.7 152.4 194.6 61.8 68.0 148.1 191.9
018 14.9 9.7 35.6 41.9 14.5 10.4 34.8 41.5 14.1 11.0 33.9 41.0 13.8 11.7 33.0 40.6
025 18.8 12.4 45.2 53.1 18.3 13.0 43.9 52.3 17.8 13.7 42.6 51.4 17.2 14.3 41.2 50.5
HWC 028 24.2 16.6 58.0 68.7 23.4 17.4 56.1 67.3 22.6 18.1 54.2 65.9 21.8 18.8 52.2 64.5
035 26.4 19.4 63.3 75.8 25.6 20.4 61.5 74.6 24.9 21.3 59.7 73.4 24.1 22.1 57.8 72.1
45 040 35.7 27.2 85.6 103.0 34.8 28.3 83.4 101.7 33.9 29.5 81.3 100.3 33.0 30.5 79.0 98.8
040 45.5 34.2 109.0 131.0 44.2 35.9 106.0 129.1 42.9 37.6 102.9 127.2 41.6 39.3 99.8 125.3
HK 050 53.9 40.2 129.4 155.1 52.5 42.2 125.8 153.0 51.0 44.2 122.3 150.8 49.5 46.1 118.6 148.5
060 68.5 61.3 164.2 203.4 66.7 63.8 159.8 200.7 64.8 66.2 155.4 198.0 63.0 68.5 151.1 195.2
018 15.1 9.7 36.3 42.5 14.7 10.4 35.4 42.1 14.4 11.1 34.5 41.7 14.0 11.7 33.6 41.2
025 19.2 12.4 46.0 54.0 18.6 13.1 44.7 53.1 18.1 13.7 43.4 52.3 17.5 14.4 42.1 51.4
HWC 028 24.8 16.7 59.4 70.1 23.9 17.5 57.4 68.7 23.1 18.3 55.4 67.3 22.3 19.0 53.5 65.8
035 27.0 19.5 64.7 77.2 26.2 20.5 62.9 76.0 25.4 21.4 61.0 74.8 24.6 22.2 59.1 73.5
46 040 36.4 27.3 87.2 104.8 35.5 28.5 85.1 103.4 34.5 29.7 82.9 102.0 33.6 30.8 80.6 100.5
040 46.4 34.3 111.2 133.2 45.1 36.1 108.1 131.3 43.8 37.8 105.0 129.4 42.5 39.5 101.9 127.5
HK 050 55.0 40.3 132.0 157.8 53.5 42.4 128.4 155.7 52.0 44.4 124.8 153.5 50.5 46.3 121.2 151.2
060 69.8 61.6 167.5 206.8 68.0 64.2 163.0 204.1 66.1 66.7 158.5 201.3 64.2 69.0 154.1 198.5
018 15.6 9.7 37.5 43.8 15.3 10.4 36.6 43.3 14.9 11.1 35.7 42.9 14.5 11.8 34.8 42.5
025 19.9 12.5 47.8 55.8 19.4 13.2 46.4 54.9 18.8 13.9 45.0 54.0 18.2 14.5 43.7 53.2
HWC 028 25.9 16.9 62.1 73.0 25.0 17.7 60.1 71.5 24.2 18.5 58.1 70.0 23.4 19.3 56.0 68.5
035 28.1 19.7 67.5 80.1 27.4 20.7 65.6 78.9 26.6 21.6 63.7 77.7 25.7 22.5 61.8 76.4
48 040 37.8 27.6 90.7 108.3 36.8 28.8 88.4 106.9 35.9 30.0 86.2 105.5 35.0 31.2 83.9 104.1
040 48.2 34.6 115.6 137.7 46.9 36.4 112.5 135.8 45.5 38.2 109.3 133.9 44.2 40.0 106.1 131.9
HK 050 57.2 40.6 137.3 163.2 55.7 42.7 133.6 161.1 54.2 44.8 130.0 158.8 52.6 46.8 126.2 156.5
060 72.6 62.4 174.1 213.8 70.6 65.0 169.5 211.1 68.7 67.6 164.9 208.2 66.8 70.1 160.3 205.3
018 16.2 9.8 38.8 45.1 15.8 10.5 37.9 44.6 15.4 11.2 37.0 44.2 15.0 11.9 36.0 43.7
025 20.6 12.6 49.5 57.6 20.1 13.3 48.2 56.7 19.5 14.0 46.8 55.9 18.9 14.7 45.4 54.9
HWC 028 27.1 17.1 65.0 75.9 26.2 17.9 62.8 74.4 25.3 18.8 60.7 72.8 24.4 19.6 58.7 71.3
035 29.3 19.8 70.4 83.1 28.5 20.9 68.5 81.9 27.7 21.9 66.5 80.6 26.9 22.8 64.5 79.3
50 040 39.2 27.9 94.1 111.9 38.3 29.2 91.8 110.5 37.3 30.4 89.5 109.1 36.3 31.6 87.3 107.6
040 50.0 34.8 120.1 142.3 48.7 36.7 116.9 140.4 47.3 38.6 113.7 138.4 46.0 40.4 110.4 136.4
HK 050 59.4 40.8 142.7 168.7 57.9 43.0 139.0 166.6 56.3 45.2 135.2 164.3 54.7 47.3 131.4 162.0
060 75.3 63.0 180.9 221.0 73.4 65.8 176.1 218.1 71.4 68.5 171.4 215.3 69.4 71.1 166.7 212.4
018 17.5 9.8 42.1 48.4 17.1 10.6 41.1 47.9 16.7 11.3 40.2 47.4 16.3 12.1 39.2 47.0
025 22.5 12.7 54.1 62.2 21.9 13.5 52.7 61.4 21.3 14.2 51.3 60.5 20.7 15.0 49.9 59.5
HWC 028 30.1 17.5 72.4 83.5 29.2 18.4 70.1 81.9 28.2 19.3 67.8 80.3 27.3 20.2 65.6 78.6
035 32.5 20.2 78.0 90.9 31.6 21.3 75.9 89.6 30.7 22.4 73.9 88.2 29.8 23.5 71.7 86.8
55 040 42.9 28.5 103.2 121.3 41.9 29.9 100.7 119.8 40.9 31.3 98.3 118.3 39.9 32.6 95.9 116.8
040 54.8 35.2 131.8 154.2 53.4 37.3 128.4 152.2 52.0 39.3 125.1 150.3 50.6 41.3 121.6 148.2
HK 050 65.2 41.3 156.7 183.0 63.6 43.7 152.8 180.7 61.9 46.1 148.8 178.4 60.2 48.4 144.8 176.0
060 82.5 64.6 198.4 239.3 80.4 67.7 193.3 236.4 78.3 70.6 188.3 233.4 76.2 73.5 183.3 230.3
018 18.9 9.8 45.6 51.8 18.5 10.6 44.6 51.3 18.1 11.4 43.5 50.9 17.7 12.2 42.5 50.4
025 24.5 12.8 58.9 67.1 23.9 13.7 57.5 66.2 23.3 14.5 56.0 65.3 22.6 15.3 54.5 64.3
HWC 028 33.4 17.9 80.3 91.6 32.4 18.9 77.9 89.9 31.4 19.9 75.4 88.2 30.3 20.9 73.0 86.4
035 35.8 20.4 86.1 99.0 34.9 21.6 83.9 97.7 34.0 22.8 81.7 96.3 33.0 24.0 79.4 94.9
60 040 46.8 29.0 112.7 131.1 45.8 30.6 110.1 129.5 44.7 32.0 107.5 128.0 43.6 33.5 104.9 126.4
040 59.3 35.5 142.7 165.2 57.8 37.7 139.0 162.9 56.2 39.9 135.2 160.6 54.5 42.0 131.2 158.1
HK 050 70.5 41.5 169.7 196.0 68.7 44.2 165.3 193.4 66.9 46.7 160.9 190.8 65.0 49.3 156.4 188.0
060 90.2 66.0 216.9 258.6 87.9 69.4 211.4 255.4 85.7 72.6 206.2 252.4 83.4 75.7 200.6 249.0

(See Legend on page 30.)

29
Performance data,
30HWB water-cooled — English
COOLING CAPACITIES — 50 Hz (cont)
CONDENSER ENTERING WATER TEMPERATURE (F)
75 80 85 90
LCWT UNIT UNIT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
(F) 30 SIZE Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
Cap Cap Cap Cap
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
018 12.8 9.7 30.5 36.8 12.4 10.2 29.8 36.4 12.1 10.8 29.0 36.0 11.8 11.3 28.2 35.6
025 17.0 12.8 40.7 49.0 16.5 13.4 39.4 48.1 16.0 14.0 38.2 47.3 15.4 14.5 36.9 46.4
40 HWB 028 22.2 17.2 53.1 64.2 21.5 17.9 51.4 63.0 20.8 18.7 49.9 62.0 20.2 19.4 48.3 60.9
035 24.6 19.2 58.9 71.3 23.9 20.1 57.3 70.3 23.3 20.9 55.7 69.2 22.6 21.6 54.0 68.1
040 30.8 26.7 73.8 91.0 30.0 27.7 71.9 89.8 29.2 28.7 69.9 88.5 28.4 29.6 68.0 87.2
018 13.3 9.8 31.7 38.0 12.9 10.3 30.9 37.6 12.6 10.9 30.1 37.2 12.2 11.5 29.3 36.7
025 17.7 12.9 42.4 50.7 17.1 13.5 41.0 49.8 16.6 14.1 39.8 49.0 16.1 14.7 38.5 48.1
42 HWB 028 23.0 17.3 55.1 66.3 22.3 18.2 53.5 65.2 21.6 19.0 51.8 64.1 21.0 19.7 50.2 63.0
035 25.6 19.5 61.2 73.8 24.9 20.3 59.6 72.7 24.2 21.1 57.9 71.6 23.5 21.9 56.3 70.5
040 32.1 27.1 76.9 94.3 31.3 28.2 74.9 93.0 30.4 29.1 72.9 91.7 29.6 30.1 70.9 90.4
018 13.7 9.8 32.9 39.2 13.4 10.5 32.1 38.8 13.0 11.0 31.2 38.3 12.7 11.6 30.4 37.9
025 18.3 13.0 44.0 52.4 17.8 13.7 42.8 51.6 17.3 14.3 41.4 50.6 16.7 14.9 40.1 49.8
44 HWB 028 23.9 17.5 57.2 68.5 23.2 18.4 55.5 67.4 22.5 19.2 53.8 66.2 21.8 20.0 52.2 65.2
035 26.5 19.7 63.6 76.3 25.8 20.6 62.0 75.2 25.1 21.4 60.3 74.1 24.4 22.2 58.5 73.0
040 33.4 27.5 80.0 97.6 32.5 28.6 77.9 96.3 31.7 29.6 75.9 95.0 30.8 30.6 73.8 93.6
018 14.0 9.9 33.5 39.8 13.6 10.5 32.6 39.4 13.3 11.1 31.8 39.0 12.9 11.7 30.9 38.5
025 18.7 13.1 44.8 53.2 18.2 13.8 43.5 52.4 17.6 14.4 42.2 51.6 17.0 15.0 40.8 50.6
45 HWB 028 24.3 17.6 58.3 69.6 23.6 18.5 56.6 68.5 22.9 19.3 54.9 67.3 22.2 20.1 53.2 66.2
035 27.0 19.8 64.8 77.5 26.3 20.7 63.1 76.5 25.6 21.6 61.4 75.4 24.9 22.4 59.7 74.2
040 34.0 27.7 81.6 99.3 33.2 28.8 79.5 98.0 32.3 29.9 77.4 96.7 31.4 30.9 75.3 95.3
018 14.2 9.9 34.1 40.5 13.9 10.5 33.2 40.0 13.5 11.2 32.4 39.6 13.1 11.8 31.5 39.1
025 19.0 13.2 45.7 54.1 18.5 13.8 44.4 53.3 17.9 14.5 43.0 52.4 17.4 15.1 41.7 51.5
46 HWB 028 24.7 17.7 59.4 70.7 24.0 18.6 57.6 69.6 23.3 19.4 55.9 68.4 22.6 20.2 54.2 67.3
035 27.5 19.9 66.1 78.8 26.8 20.8 64.4 77.7 26.1 21.7 62.6 76.6 25.4 22.6 60.9 75.5
040 34.7 27.9 83.2 101.0 33.8 29.0 81.1 99.7 32.9 30.1 79.0 98.3 32.0 31.1 76.9 97.0
018 14.7 10.0 35.3 41.7 14.3 10.7 34.4 41.3 14.0 11.3 33.5 40.8 13.6 11.9 32.7 40.4
025 19.8 13.3 47.4 55.9 19.2 13.9 46.1 55.0 18.6 14.6 44.7 54.2 18.1 15.3 43.4 53.2
48 HWB 028 25.7 17.9 61.6 73.0 24.9 18.8 59.8 71.8 24.2 19.6 58.0 70.6 23.4 20.5 56.2 69.5
035 28.6 20.1 68.6 81.4 27.8 21.0 66.8 80.3 27.1 22.0 65.1 79.2 26.4 22.9 63.3 78.0
040 36.0 28.3 86.5 104.5 35.1 29.4 84.3 103.1 34.2 30.5 82.1 101.8 33.3 31.6 80.0 100.4
018 15.2 10.1 36.5 43.0 14.8 10.8 35.6 42.5 14.5 11.4 34.7 42.1 14.1 12.0 33.8 41.6
025 20.5 13.4 49.2 57.7 19.9 14.1 47.8 56.8 19.3 14.8 46.4 55.9 18.8 15.4 45.0 55.0
50 HWB 028 26.6 18.0 63.8 75.4 25.8 19.0 62.0 74.2 25.0 19.9 60.1 72.9 24.3 20.7 58.3 71.7
035 29.6 20.3 71.1 84.0 28.9 21.3 69.3 83.0 28.1 22.2 67.5 81.8 27.4 23.2 65.7 80.6
040 37.4 28.6 89.8 108.0 36.5 29.8 87.6 106.7 35.6 31.0 85.4 105.3 34.6 32.1 83.1 103.8
018 16.5 10.2 39.8 46.3 16.1 11.0 38.8 45.8 15.7 11.7 37.8 45.3 15.3 12.4 36.9 44.8
025 22.4 13.6 53.8 62.4 21.8 14.4 52.4 61.5 21.2 15.1 50.9 60.6 20.6 15.8 49.4 59.6
55 HWB 028 29.0 18.4 69.6 81.3 28.2 19.4 67.7 80.1 27.3 20.4 65.7 78.8 26.5 21.3 63.8 77.6
035 32.3 20.7 77.7 90.9 31.5 21.8 75.8 89.7 30.8 22.8 73.9 88.6 30.0 23.9 72.0 87.4
040 41.0 29.5 98.5 117.2 40.0 30.8 96.1 115.8 39.0 32.1 93.8 114.3 38.0 33.3 91.4 112.8
018 18.0 10.3 43.2 49.8 17.5 11.1 42.2 49.2 17.1 11.8 41.2 48.7 16.7 12.6 40.1 48.2
025 24.3 13.9 58.5 67.3 23.7 14.7 57.0 66.4 23.1 15.5 55.5 65.4 22.5 16.2 54.0 64.5
60 HWB 028 31.4 18.8 75.6 87.6 30.6 19.9 73.6 86.2 29.7 20.9 71.6 84.9 28.9 22.0 69.5 83.6
035 35.2 21.1 84.7 98.1 34.4 22.3 82.8 96.9 33.6 23.4 80.8 95.7 32.7 24.5 78.7 94.5
040 44.8 30.3 107.8 127.0 43.8 31.7 105.3 125.4 42.7 33.2 102.7 123.9 41.6 34.5 100.1 122.2
LEGEND
Cap — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

30
Performance data, 30HWA,HL in combination
with 09DK air-cooled condenser — English
COOLING CAPACITIES — 50 Hz (cont)
CONDENSER ENTERING WATER TEMPERATURE (F)
REMOTE 85 95 105 115 125
LCWT UNIT UNIT Cooler Cooler Cooler Cooler Cooler
COND
(F) 30 SIZE Input Flow Input Flow Input Flow Input Flow Input Flow
09DK Cap Cap Cap Cap Cap
kW Rate kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
018 024 12.0 10.7 28.6 11.3 11.7 27.0 10.6 12.7 25.4 10.0 13.6 23.8 9.3 14.5 22.2
025 028 15.4 14.0 36.8 14.3 15.0 34.3 13.3 15.9 31.9 12.3 16.8 29.3 11.2 17.4 26.7
HWA 028 028 20.0 19.3 47.8 18.7 20.6 44.8 17.4 21.8 41.7 16.2 22.9 38.7 14.9 23.8 35.8
40 035 034 21.8 20.9 52.1 20.5 22.3 49.0 19.1 23.5 45.8 17.8 24.6 42.5 16.4 25.5 39.2
040 044 27.7 29.1 66.2 26.1 30.9 62.5 24.6 32.4 58.8 23.0 33.9 55.1 21.5 35.2 51.4
050 034,034 45.6 43.9 109.2 42.9 46.9 102.6 40.0 49.6 95.8 37.2 52.0 89.0 * * *
HL
060 034,034 57.2 66.6 136.9 54.0 70.2 129.1 50.7 73.5 121.4 47.5 76.5 113.6 * * *
018 024 12.4 10.8 29.7 11.7 11.9 28.1 11.0 12.9 26.4 10.3 13.9 24.8 9.6 14.8 23.1
025 028 16.0 14.2 38.2 14.9 15.2 35.7 13.9 16.2 33.2 12.8 17.1 30.6 11.7 17.8 28.0
HWA 028 028 20.7 19.6 49.6 19.4 21.0 46.5 18.1 22.2 43.4 16.8 23.3 40.3 * * *
42 035 034 22.6 21.2 54.2 21.3 22.7 51.0 19.9 24.0 47.7 18.5 25.1 44.4 17.1 26.1 41.0
040 044 28.8 29.7 68.9 27.2 31.5 65.1 25.6 33.1 61.3 24.0 34.7 57.5 22.4 36.1 53.7
050 034,034 47.5 44.6 113.7 44.6 47.8 107.0 41.7 50.7 100.0 38.8 53.2 93.0 * * *
HL
060 034,034 59.4 68.0 142.4 56.1 71.8 134.3 52.7 75.2 126.3 * * * * * *
018 024 12.8 11.0 30.8 12.1 12.1 29.1 11.4 13.1 27.4 10.7 14.1 25.7 10.0 15.1 24.0
025 028 16.6 14.4 39.7 15.5 15.5 37.2 14.4 16.5 34.6 13.3 17.5 32.0 12.2 18.2 29.3
HWA 028 028 21.4 20.0 51.3 20.1 21.4 48.2 18.8 22.6 45.1 17.5 23.8 41.9 * * *
44 035 034 23.5 21.6 56.3 22.1 23.1 53.0 20.7 24.5 49.7 19.3 25.7 46.3 17.9 26.7 42.8
040 044 29.9 30.2 71.7 28.3 32.1 67.8 26.6 33.9 63.8 25.0 35.5 59.9 23.3 36.9 55.9
050 034,034 49.4 45.3 118.4 46.5 48.7 111.4 43.5 51.7 104.3 40.5 54.4 97.1 * * *
HL
060 034,034 61.7 69.5 148.0 58.3 73.4 139.6 54.8 77.0 131.4 * * * * * *
018 024 13.1 11.0 31.3 12.4 12.2 29.6 11.7 13.2 27.9 10.9 14.2 26.2 10.2 15.2 24.5
025 028 16.9 14.5 40.5 15.8 15.6 37.9 14.7 16.7 35.3 13.6 17.6 32.6 12.5 18.4 29.9
HWA 028 028 21.8 20.1 52.3 20.5 21.6 49.1 19.1 22.9 45.9 17.8 24.1 42.7 * * *
45 035 034 23.9 21.8 57.4 22.5 23.3 54.0 21.1 24.7 50.7 19.7 25.9 47.2 18.2 27.0 43.7
040 044 30.5 30.5 73.1 28.8 32.4 69.1 27.2 34.2 65.1 25.5 35.9 61.1 23.8 37.4 57.1
050 034,034 50.3 45.7 120.7 47.4 49.1 113.7 44.4 52.2 106.5 41.4 55.0 99.2 * * *
HL
060 034,034 62.9 70.2 150.8 59.4 74.2 142.4 55.9 77.8 134.0 * * * * * *
018 024 13.3 11.1 31.9 12.6 12.3 30.2 11.9 13.3 28.5 11.1 14.4 26.7 10.4 15.4 24.9
025 028 17.2 14.6 41.2 16.1 15.8 38.6 15.0 16.8 36.0 13.9 17.8 33.3 12.8 18.6 30.6
HWA 028 028 22.2 20.3 53.2 20.8 21.7 50.0 19.5 23.1 46.7 18.2 24.3 43.6 * * *
46 035 034 24.4 21.9 58.5 23.0 23.5 55.1 21.5 24.9 51.7 20.1 26.2 48.2 18.6 27.3 44.7
040 044 31.1 30.8 74.5 29.4 32.7 70.5 27.7 34.6 66.4 26.0 36.3 62.4 24.3 37.8 58.3
050 034,034 51.3 46.1 123.1 48.4 49.5 116.0 45.3 52.7 108.7 42.3 55.5 101.4 * * *
HL
060 034,034 64.1 70.9 153.7 60.5 75.0 145.2 56.9 78.7 136.6 * * * * * *
018 024 13.8 11.3 33.0 13.0 12.4 31.3 12.3 13.6 29.5 11.5 14.6 27.7 10.8 15.6 25.9
025 028 17.8 14.8 42.8 16.7 16.0 40.1 15.6 17.1 37.5 14.5 18.1 34.7 13.3 19.0 31.9
HWA 028 028 23.0 20.6 55.1 21.6 22.1 51.8 20.2 23.5 48.5 18.8 24.8 45.2 * * *
48 035 034 25.3 22.3 60.6 23.9 23.9 57.2 22.4 25.4 53.7 20.9 26.7 50.2 19.4 27.9 46.5
040 044 32.3 31.3 77.4 30.5 33.4 73.2 28.8 35.3 69.1 27.0 37.0 64.9 25.3 38.7 60.7
050 034,034 53.3 46.8 127.9 50.3 50.4 120.6 47.2 53.7 113.2 44.0 56.7 105.7 * * *
HL
060 034,034 66.5 72.3 159.5 62.8 76.6 150.7 59.2 80.5 142.0 * * * * * *
018 024 14.2 11.4 34.2 13.5 12.6 32.4 12.7 13.8 30.6 12.0 14.9 28.7 11.2 15.9 26.9
025 028 18.5 15.0 44.4 17.4 16.3 41.7 16.2 17.4 38.9 15.0 18.5 36.1 13.9 19.4 33.3
HWA 028 028 23.8 21.0 57.1 22.3 22.5 53.6 20.9 23.9 50.2 19.5 25.3 46.9 * * *
50 035 034 26.2 22.6 62.9 24.7 24.3 59.4 23.3 25.9 55.8 21.7 27.3 52.1 * * *
040 044 33.5 31.9 80.3 31.7 34.0 76.1 29.9 36.0 71.8 28.1 37.8 67.5 * * *
HL 050 034,034 55.3 47.5 132.9 52.2 51.3 125.4 49.1 54.7 117.8 45.8 57.9 110.0 * * *
060 034,034 68.9 73.8 165.4 65.1 78.2 156.4 61.4 82.2 147.4 * * * * * *
018 024 15.5 11.8 37.2 14.7 13.1 35.3 13.9 14.3 33.3 13.1 15.5 31.4 * * *
025 028 20.1 15.5 48.4 19.0 16.9 45.6 17.8 18.1 42.7 16.5 19.3 39.8 * * *
HWA 028 028 25.8 21.9 62.1 24.3 23.5 58.4 22.8 25.1 54.8 21.3 26.5 51.2 * * *
55 035 034 28.5 23.5 68.6 27.0 25.3 64.9 25.4 27.1 61.2 23.9 28.6 57.3 * * *
040 044 36.6 33.2 87.9 34.7 35.6 83.3 32.8 37.8 78.8 30.9 39.8 74.2 * * *
050 034,034 60.6 49.3 145.7 57.3 53.4 137.7 53.9 57.3 129.6 50.5 60.8 121.4 * * *
HL
060 034,034 75.2 77.6 180.8 71.2 82.4 171.2 67.2 86.8 161.5 * * * * * *
018 024 16.7 12.1 40.2 15.9 13.5 38.2 15.1 14.8 36.2 14.2 16.1 34.1 * * *
025 028 21.8 16.0 52.5 20.6 17.5 49.6 19.4 18.9 46.6 18.1 20.2 43.6 * * *
HWA 028 028 28.0 22.7 67.2 26.4 24.5 63.4 24.8 26.2 59.6 23.2 27.8 55.7 * * *
60 035 034 31.0 24.3 74.6 29.4 26.3 70.7 27.7 28.2 66.7 26.1 30.0 62.7 * * *
040 044 39.9 34.6 95.9 37.8 37.2 90.9 35.8 39.6 86.1 33.8 41.8 81.3 * * *
050 034,034 65.2 50.8 156.8 61.5 55.1 148.0 57.6 59.0 138.5 * * * * * *
HL
060 034,034 81.7 81.3 196.4 77.1 86.3 185.5 * * * * * * * * *
LEGEND *Operation not recommended with condenser identified. Contact your Carrier rep-
Cap — Capacity, Tons of Refrigeration resentative for an alternate equipment selection.
COND — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

31
Performance data,
30HWA,HL condenserless — English
COOLING CAPACITIES — 50 Hz (cont)
SATURATED DISCHARGE TEMPERATURE (F)
95 110 120 135
LCWT UNIT UNIT Cooler Cooler Cooler Cooler
(F) 30 SIZE Input Flow Input Flow Input Flow Input Flow
Cap THR Cap THR Cap THR Cap THR
kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm)
018 12.8 9.7 30.6 15.3 11.8 11.4 28.2 14.7 11.1 12.4 26.5 14.3 10.0 13.9 24.0 13.6
025 16.6 12.8 39.8 19.9 15.0 14.6 35.9 18.8 13.9 15.7 33.3 18.0 12.2 17.0 29.2 16.6
HWA 028 22.1 17.1 53.0 26.6 20.0 19.4 47.9 25.0 18.6 20.9 44.6 24.0 16.6 22.7 39.8 22.5
40 035 23.6 19.2 56.4 28.5 21.5 21.6 51.5 27.1 20.1 23.0 48.1 26.0 17.9 24.7 42.9 24.3
040 29.8 27.1 71.2 36.8 27.3 30.1 65.4 35.1 25.7 31.8 61.5 33.9 23.3 34.2 55.7 32.1
HL 050 49.6 39.8 118.7 59.9 45.2 45.2 108.3 56.9 42.3 48.3 101.2 54.8 37.7 52.3 90.3 51.3
060 63.6 59.0 152.2 78.9 58.3 65.7 139.6 75.3 54.8 69.8 131.2 72.9 49.6 75.1 118.8 69.0
018 13.3 9.7 31.9 15.8 12.2 11.5 29.3 15.2 11.5 12.6 27.6 14.8 10.4 14.1 25.0 14.1
025 17.3 12.9 41.4 20.6 15.7 14.8 37.5 19.5 14.5 15.9 34.8 18.6 12.8 17.3 30.6 17.3
HWA 028 23.0 17.2 55.1 27.4 20.8 19.7 49.9 25.9 19.4 21.1 46.5 24.9 17.4 23.1 41.6 23.3
42 035 24.5 19.3 58.7 29.5 22.4 21.8 53.7 28.1 21.0 23.3 50.3 27.0 18.8 25.2 44.9 25.3
040 31.0 27.4 74.3 38.1 28.5 30.5 68.3 36.4 26.8 32.4 64.3 35.2 24.3 34.9 58.3 33.4
050 51.7 40.0 123.9 62.1 47.3 45.7 113.2 59.1 44.2 49.0 106.0 56.9 39.6 53.3 94.8 53.4
HL
060 66.3 59.6 158.7 81.7 60.8 66.7 145.7 78.1 57.2 70.9 137.1 75.6 51.8 76.6 124.2 71.7
018 13.8 9.8 33.1 16.3 12.7 11.6 30.4 15.7 12.0 12.7 28.7 15.3 10.9 14.3 26.1 14.6
025 18.0 13.0 43.1 21.4 16.3 15.0 39.1 20.2 15.2 16.1 36.4 19.4 13.4 17.7 32.1 18.0
HWA 028 23.9 17.3 57.3 28.4 21.7 19.9 52.0 26.8 20.2 21.4 48.5 25.8 18.1 23.5 43.4 24.2
44 035 25.5 19.4 61.2 30.5 23.4 22.1 56.0 29.1 21.9 23.7 52.5 28.0 19.7 25.7 47.1 26.3
040 32.3 27.7 77.4 39.5 29.7 31.0 71.2 37.7 28.0 32.9 67.1 36.5 25.4 35.5 60.9 34.6
HL 050 53.9 40.2 129.2 64.3 49.4 46.2 118.3 61.3 46.2 49.7 110.9 59.1 41.5 54.3 99.4 55.5
060 69.0 60.1 165.4 84.6 63.4 67.6 152.0 80.9 59.7 72.1 143.1 78.3 54.1 78.0 129.8 74.3
018 14.0 9.8 33.7 16.6 12.9 11.6 31.0 15.9 12.2 12.8 29.3 15.5 11.1 14.4 26.6 14.8
025 18.3 13.0 44.0 21.7 16.7 15.0 40.0 20.6 15.5 16.2 37.2 19.7 13.7 17.8 32.9 18.3
HWA 028 24.4 17.4 58.4 28.9 22.2 20.0 53.1 27.3 20.7 21.5 49.5 26.2 18.5 23.7 44.3 24.6
45 035 26.0 19.5 62.4 31.1 23.9 22.2 57.2 29.6 22.4 23.8 53.6 28.5 20.1 25.9 48.2 26.8
040 33.0 27.8 79.1 40.2 30.3 31.2 72.8 38.4 28.6 33.2 68.6 37.2 26.0 35.9 62.3 35.3
050 55.0 40.3 131.9 65.4 50.4 46.4 120.9 62.4 47.3 50.0 113.4 60.2 42.4 54.8 101.8 56.6
HL
060 70.4 60.4 168.8 86.0 64.7 68.0 155.2 82.3 60.9 72.6 146.1 79.7 55.3 78.7 132.6 75.7
018 14.3 9.8 34.3 16.8 13.2 11.7 31.7 16.2 12.4 12.8 29.8 15.8 11.3 14.5 27.1 15.1
025 18.7 13.0 44.9 22.1 17.0 15.1 40.7 20.9 15.8 16.3 38.0 20.1 14.0 18.0 33.6 18.7
HWA 028 24.8 17.4 59.6 29.3 22.6 20.1 54.1 27.8 21.0 21.7 50.4 26.6 18.9 23.9 45.3 25.1
46 035 26.5 19.5 63.6 31.6 24.3 22.3 58.4 30.1 22.8 24.0 54.8 29.0 20.5 26.2 49.2 27.3
040 33.6 28.0 80.7 40.9 31.0 31.4 74.3 39.1 29.2 33.4 70.0 37.9 26.5 36.2 63.7 35.9
HL 050 56.1 40.4 134.6 66.6 51.5 46.6 123.5 63.6 48.3 50.3 115.9 61.3 43.4 55.2 104.2 57.7
060 71.8 60.6 172.3 87.5 66.0 68.5 158.4 83.8 62.2 73.1 149.3 81.2 56.5 79.5 135.5 77.1
018 14.8 9.8 35.6 17.4 13.7 11.7 32.9 16.7 12.9 13.0 31.0 16.3 11.8 14.7 28.2 15.6
025 19.4 13.1 46.6 22.8 17.7 15.2 42.6 21.7 16.5 16.5 39.6 20.8 14.7 18.2 35.2 19.4
HWA 028 25.8 17.5 61.9 30.3 23.5 20.2 56.3 28.7 21.9 21.9 52.7 27.6 19.7 24.2 47.2 25.9
48 035 27.6 19.6 66.1 32.6 25.3 22.5 60.8 31.2 23.8 24.3 57.1 30.1 21.4 26.6 51.4 28.3
040 35.0 28.2 84.0 42.3 32.3 31.8 77.4 40.5 30.4 33.9 73.0 39.2 27.7 36.9 66.5 37.2
050 58.4 40.5 140.2 68.9 53.7 47.0 128.9 65.9 50.4 50.9 121.0 63.6 45.4 56.2 109.0 60.0
HL
060 74.7 61.1 179.3 90.5 68.8 69.3 165.1 86.7 64.8 74.2 155.6 84.0 58.9 80.9 141.4 79.9
018 15.4 9.8 36.9 17.9 14.2 11.8 34.1 17.3 13.4 13.1 32.3 16.8 12.2 14.9 29.3 16.1
025 20.2 13.1 48.4 23.6 18.4 15.3 44.2 22.4 17.2 16.7 41.3 21.5 15.3 18.5 36.8 20.1
HWA 028 26.8 17.5 64.2 31.3 24.4 20.4 58.5 29.7 22.8 22.2 54.7 28.5 20.5 24.6 49.2 26.8
50 035 28.6 19.7 68.7 33.7 26.3 22.7 63.3 32.2 24.8 24.6 59.5 31.1 22.4 27.0 53.7 29.4
040 36.4 28.4 87.4 43.7 33.6 32.2 80.6 41.9 31.7 34.4 76.1 40.6 28.9 37.5 69.3 38.6
050 60.8 40.5 146.0 71.3 55.9 47.4 134.3 68.2 52.6 51.5 126.3 65.9 47.5 57.0 114.0 62.2
HL
060 77.7 61.5 186.5 93.6 71.6 70.0 171.8 89.7 67.5 75.2 162.1 87.0 61.4 82.2 147.5 82.7
018 16.8 9.8 40.3 19.3 15.5 11.9 37.3 18.6 14.7 13.3 35.3 18.1 13.4 15.3 32.3 17.4
025 22.1 13.2 53.1 25.5 20.3 15.6 48.7 24.3 19.0 17.1 45.7 23.4 17.0 19.1 41.0 22.0
HWA 028 29.3 17.6 70.4 33.8 26.8 20.8 64.3 32.1 25.1 22.7 60.3 31.0 22.6 25.4 54.3 29.2
55 035 31.4 19.8 75.4 36.5 29.0 23.1 69.7 35.0 27.3 25.2 65.7 33.9 24.8 28.0 59.6 32.0
040 40.0 28.8 96.2 47.5 37.0 33.0 89.0 45.6 35.0 35.6 84.1 44.2 32.0 39.1 76.9 42.1
050 67.0 40.5 160.9 77.4 61.8 48.1 148.6 74.3 58.3 52.7 140.1 71.9 52.9 59.0 127.0 68.1
HL 060 85.4 62.2 205.3 101.5 78.9 71.8 189.6 97.5 74.5 77.6 179.1 94.6 68.0 85.5 163.4 90.1
018 18.3 9.7 43.9 20.8 16.9 12.0 40.7 20.0 16.1 13.5 38.6 19.5 14.7 15.6 35.4 18.7
025 24.1 13.1 58.0 27.5 22.2 15.7 53.5 26.3 20.9 17.4 50.3 25.4 18.8 19.7 45.3 23.9
HWA 028 32.0 17.6 76.9 36.5 29.3 21.0 70.4 34.7 27.5 23.2 66.1 33.5 24.9 26.1 59.8 31.6
60 035 34.3 19.7 82.5 39.4 31.8 23.4 76.4 37.8 30.0 25.7 72.3 36.7 27.4 28.9 65.8 34.8
040 43.9 29.1 105.6 51.4 40.7 33.8 97.8 49.4 38.5 36.6 92.7 48.0 35.3 40.5 84.9 45.8
050 72.7 40.2 175.0 83.1 67.0 48.4 161.2 79.6 63.1 53.5 151.8 76.9 56.8 60.2 136.6 72.4
HL
060 93.7 62.5 225.3 109.8 86.7 73.1 208.5 105.6 81.8 79.6 196.7 102.4 74.3 88.2 178.7 97.1
LEGEND NOTE: Performance based on 15 F subcooling.
Cap — Capacity, Tons of Refrigeration
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)
THR — Total Heat of Rejection, Tons of Refrigeration

32
Performance data,
30HWC,HK water-cooled — SI
COOLING CAPACITIES — 60 Hz
CONDENSER ENTERING WATER TEMPERATURE (C)
25 30 35
LCWT UNIT UNIT Cooler Cond Cooler Cond Cooler Cond
(C) 30 SIZE Input Flow Flow Input Flow Flow Input Flow Flow
Cap Cap Cap
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
018 53.4 12.0 2.3 2.8 50.8 13.1 2.2 2.7 48.3 14.1 2.1 2.7
025 66.8 14.7 2.9 3.5 63.0 15.9 2.7 3.4 59.2 17.0 2.5 3.2
HWC 028 84.5 19.7 3.6 4.4 79.2 21.1 3.4 4.3 74.0 22.3 3.2 4.1
035 93.4 23.1 4.0 5.0 88.3 24.7 3.8 4.8 83.0 26.1 3.6 4.6
4 040 125.9 31.6 5.4 6.7 120.0 33.6 5.2 6.5 114.1 35.5 4.9 6.4
040 137.7 31.1 5.9 7.2 129.8 33.7 5.6 7.0 121.8 36.1 5.2 6.7
HK 050 168.6 39.7 7.2 8.9 159.3 42.8 6.8 8.6 149.8 45.6 6.4 8.3
060 196.4 48.1 8.4 10.4 186.2 51.7 8.0 10.1 175.9 54.9 7.6 9.8
018 55.1 12.1 2.4 2.9 52.5 13.2 2.3 2.8 49.9 14.3 2.1 2.7
025 69.1 14.8 3.0 3.6 65.4 16.1 2.8 3.5 61.5 17.2 2.6 3.3
HWC 028 88.1 20.0 3.8 4.6 82.7 21.4 3.6 4.4 77.3 22.7 3.3 4.3
035 97.2 23.3 4.2 5.1 91.9 25.0 3.9 5.0 86.5 26.5 3.7 4.8
5 040 130.5 32.0 5.6 6.9 124.5 34.1 5.3 6.7 118.3 36.1 5.1 6.6
040 143.0 31.4 6.1 7.4 135.0 34.1 5.8 7.2 126.8 36.6 5.4 7.0
HK 050 175.0 40.0 7.5 9.2 165.6 43.3 7.1 8.9 155.9 46.3 6.7 8.6
060 203.7 48.5 8.8 10.7 193.3 52.3 8.3 10.4 182.8 55.7 7.9 10.1
018 56.8 12.1 2.4 2.9 54.2 13.3 2.3 2.9 51.5 14.4 2.2 2.8
025 71.5 15.0 3.1 3.7 67.7 16.2 2.9 3.6 63.7 17.4 2.7 3.5
HWC 028 91.8 20.3 3.9 4.8 86.2 21.7 3.7 4.6 80.7 23.1 3.5 4.4
035 101.1 23.6 4.3 5.3 95.7 25.3 4.1 5.1 90.2 26.9 3.9 5.0
6 040 135.1 32.4 5.8 7.1 129.0 34.6 5.5 7.0 122.6 36.6 5.3 6.8
040 148.3 31.6 6.4 7.7 140.2 34.4 6.0 7.4 131.9 37.0 5.7 7.2
HK 050 181.7 40.4 7.8 9.4 172.0 43.7 7.4 9.2 162.2 46.9 7.0 8.9
060 211.2 49.0 9.1 11.1 200.6 52.9 8.6 10.8 189.8 56.5 8.2 10.5
018 58.6 12.2 2.5 3.0 55.9 13.4 2.4 3.0 53.2 14.5 2.3 2.9
025 74.0 15.1 3.2 3.8 70.1 16.4 3.0 3.7 66.1 17.6 2.8 3.6
HWC 028 95.6 20.5 4.1 4.9 89.9 22.1 3.9 4.8 84.2 23.5 3.6 4.6
035 105.1 23.9 4.5 5.5 99.6 25.7 4.3 5.3 93.9 27.4 4.0 5.2
7 040 139.8 32.8 6.0 7.3 133.5 35.0 5.7 7.2 127.1 37.2 5.5 7.0
040 153.8 31.9 6.6 7.9 145.5 34.8 6.3 7.7 137.0 37.5 5.9 7.4
HK 050 188.4 40.7 8.1 9.8 178.6 44.2 7.7 9.5 168.5 47.4 7.2 9.2
060 218.8 49.4 9.4 11.4 207.9 53.5 8.9 11.1 197.0 57.2 8.5 10.8
018 60.4 12.3 2.6 3.1 57.7 13.5 2.5 3.0 54.9 14.6 2.4 3.0
025 76.5 15.2 3.3 3.9 72.5 16.6 3.1 3.8 68.5 17.8 2.9 3.7
HWC 028 99.5 20.8 4.3 5.1 93.6 22.4 4.0 4.9 87.8 23.9 3.8 4.8
035 109.2 24.1 4.7 5.7 103.5 26.0 4.5 5.5 97.8 27.7 4.2 5.3
8 040 144.6 33.1 6.2 7.6 138.2 35.5 5.9 7.4 131.7 37.7 5.7 7.2
040 159.4 32.1 6.9 8.2 151.0 35.1 6.5 7.9 142.3 37.9 6.1 7.7
HK 050 195.2 41.0 8.4 10.1 185.2 44.6 8.0 9.8 175.0 48.0 7.5 9.5
060 226.5 49.8 9.7 11.8 215.5 54.0 9.3 11.5 204.3 57.9 8.8 11.2
018 62.3 12.3 2.7 3.2 59.5 13.6 2.6 3.1 56.6 14.8 2.4 3.0
025 79.0 15.3 3.4 4.0 75.0 16.7 3.2 3.9 70.9 18.0 3.1 3.8
HWC 028 103.6 21.0 4.5 5.3 97.5 22.7 4.2 5.1 91.5 24.2 3.9 4.9
035 113.4 24.3 4.9 5.9 107.6 26.3 4.6 5.7 101.7 28.1 4.4 5.5
9 040 149.5 33.5 6.4 7.8 142.9 35.9 6.2 7.6 136.3 38.2 5.9 7.4
040 165.1 32.3 7.1 8.4 156.5 35.4 6.7 8.2 147.7 38.3 6.4 7.9
HK 050 202.2 41.3 8.7 10.4 192.0 45.0 8.3 10.1 181.6 48.6 7.8 9.8
060 234.5 50.2 10.1 12.1 223.2 54.5 9.6 11.8 211.7 58.6 9.1 11.5
018 64.2 12.4 2.8 3.3 61.3 13.7 2.6 3.2 58.4 14.9 2.5 3.1
025 81.6 15.4 3.5 4.1 77.5 16.8 3.3 4.0 73.4 18.2 3.2 3.9
HWC 028 107.7 21.3 4.6 5.5 101.4 23.0 4.4 5.3 95.3 24.6 4.1 5.1
035 117.7 24.5 5.1 6.1 111.8 26.6 4.8 5.9 105.7 28.5 4.6 5.7
10 040 154.4 33.8 6.7 8.0 147.8 36.3 6.4 7.8 141.0 38.7 6.1 7.7
040 170.9 32.5 7.4 8.7 162.1 35.6 7.0 8.4 153.2 38.7 6.6 8.2
HK 050 209.5 41.6 9.0 10.7 198.9 45.4 8.6 10.4 188.4 49.1 8.1 10.1
060 242.5 50.5 10.4 12.5 231.0 55.1 10.0 12.2 219.3 59.3 9.4 11.9
018 70.0 12.5 3.0 3.5 67.0 13.9 2.9 3.4 63.9 15.2 2.8 3.4
025 89.6 15.7 3.9 4.5 85.3 17.2 3.7 4.4 80.9 18.8 3.5 4.3
HWC 028 120.7 22.0 5.2 6.1 113.9 23.9 4.9 5.9 107.2 25.7 4.6 5.7
035 131.2 25.1 5.7 6.7 124.9 27.4 5.4 6.5 118.4 29.6 5.1 6.3
13 040 169.9 34.9 7.3 8.7 162.9 37.6 7.0 8.5 155.7 40.2 6.7 8.4
040 188.9 33.0 8.1 9.5 179.7 36.4 7.8 9.2 170.3 39.7 7.3 9.0
HK 050 231.8 42.3 10.0 11.7 220.8 46.5 9.5 11.4 209.4 50.6 9.0 11.1
060 268.0 51.4 11.6 13.6 255.7 56.4 11.0 13.3 243.2 61.2 10.5 13.0
018 76.2 12.6 3.3 3.8 72.9 14.1 3.1 3.7 69.7 15.5 3.0 3.6
025 98.1 15.8 4.2 4.9 93.7 17.5 4.0 4.8 89.1 19.2 3.8 4.6
HWC 028 134.8 22.7 5.8 6.7 127.3 24.8 5.5 6.5 120.1 26.7 5.2 6.3
035 145.7 25.5 6.3 7.3 138.9 28.1 6.0 7.1 132.0 30.5 5.7 6.9
16 040 186.1 35.8 8.0 9.5 178.7 38.8 7.7 9.3 171.1 41.7 7.4 9.1
040 203.4 33.3 8.8 10.1 192.4 36.9 8.3 9.8 181.3 40.3 7.8 9.5
HK 050 250.5 42.7 10.8 12.5 237.5 47.2 10.2 12.2 224.3 51.5 9.7 11.8
060 292.2 52.1 12.6 14.7 278.4 57.5 12.0 14.3 264.5 62.5 11.4 14.0
(See Legend on page 34.)

33
Performance data,
30HWB water-cooled — SI
COOLING CAPACITIES — 60 Hz (cont)
CONDENSER ENTERING WATER TEMPERATURE (C)
25 30 35
LCWT UNIT UNIT Cooler Cond Cooler Cond Cooler Cond
(C) 30 SIZE Input Flow Flow Input Flow Flow Input Flow Flow
Cap Cap Cap
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
018 49.8 12.1 2.1 2.6 47.4 13.1 2.0 2.6 44.9 14.1 1.9 2.5
025 66.1 15.5 2.8 3.5 62.4 16.6 2.7 3.4 58.5 17.7 2.5 3.2
4 HWB 028 85.7 21.1 3.7 4.5 81.0 22.6 3.5 4.4 76.5 24.0 3.3 4.3
035 95.8 23.5 4.1 5.1 91.0 25.1 3.9 4.9 86.1 26.5 3.7 4.8
040 119.9 32.1 5.1 6.5 114.2 34.0 4.9 6.3 108.6 35.8 4.7 6.1
018 51.4 12.3 2.2 2.7 49.0 13.3 2.1 2.6 46.6 14.3 2.0 2.6
025 68.5 15.6 2.9 3.6 64.7 16.9 2.8 3.5 60.9 18.0 2.6 3.4
5 HWB 028 88.7 21.3 3.8 4.7 83.8 22.9 3.6 4.5 79.1 24.4 3.4 4.4
035 99.1 23.7 4.3 5.2 94.2 25.4 4.0 5.1 89.3 26.9 3.8 4.9
040 124.2 32.5 5.3 6.7 118.4 34.5 5.1 6.5 112.7 36.4 4.8 6.3
018 53.1 12.4 2.3 2.8 50.6 13.4 2.2 2.7 48.1 14.4 2.1 2.7
025 70.9 15.8 3.0 3.7 67.0 17.0 2.9 3.6 63.1 18.2 2.7 3.5
6 HWB 028 91.6 21.5 3.9 4.8 86.6 23.2 3.7 4.7 81.8 24.7 3.5 4.5
035 102.5 24.0 4.4 5.4 97.6 25.7 4.2 5.2 92.5 27.3 4.0 5.1
040 128.6 33.0 5.5 6.9 122.7 35.1 5.3 6.7 116.8 37.0 5.0 6.5
018 54.8 12.5 2.4 2.9 52.2 13.6 2.2 2.8 49.6 14.6 2.1 2.7
025 73.4 16.0 3.2 3.8 69.4 17.2 3.0 3.7 65.4 18.5 2.8 3.6
7 HWB 028 94.6 21.8 4.1 5.0 89.6 23.5 3.9 4.8 84.6 25.1 3.6 4.7
035 106.0 24.3 4.6 5.5 100.9 26.1 4.3 5.4 95.8 27.7 4.1 5.3
040 133.1 33.5 5.7 7.1 127.1 35.6 5.5 6.9 121.0 37.6 5.2 6.7
018 56.6 12.6 2.4 2.9 53.9 13.7 2.3 2.9 51.3 14.8 2.2 2.8
025 75.8 16.1 3.3 3.9 71.8 17.4 3.1 3.8 67.7 18.7 2.9 3.7
8 HWB 028 97.6 22.0 4.2 5.1 92.5 23.8 4.0 4.9 87.4 25.4 3.8 4.8
035 109.6 24.6 4.7 5.7 104.4 26.4 4.5 5.6 99.1 28.1 4.3 5.4
040 137.7 33.9 5.9 7.3 131.5 36.1 5.7 7.1 125.3 38.2 5.4 7.0
018 58.5 12.7 2.5 3.0 55.7 13.8 2.4 3.0 52.9 14.9 2.3 2.9
025 78.3 16.3 3.4 4.0 74.3 17.6 3.2 3.9 70.1 18.9 3.0 3.8
9 HWB 028 100.8 22.3 4.3 5.2 95.5 24.1 4.1 5.1 90.4 25.7 3.9 4.9
035 113.3 24.8 4.9 5.9 107.9 26.7 4.6 5.7 102.5 28.5 4.4 5.6
040 142.4 34.4 6.1 7.5 136.1 36.7 5.9 7.3 129.7 38.8 5.6 7.2
018 60.3 12.8 2.6 3.1 57.5 13.9 2.5 3.0 54.7 15.1 2.4 3.0
025 80.8 16.4 3.5 4.1 76.7 17.8 3.3 4.0 72.6 19.2 3.1 3.9
10 HWB 028 103.9 22.5 4.5 5.4 98.6 24.3 4.2 5.2 93.3 26.1 4.0 5.1
035 117.0 25.1 5.0 6.1 111.6 27.1 4.8 5.9 106.0 28.9 4.6 5.7
040 147.4 34.8 6.3 7.8 140.8 37.2 6.1 7.6 134.3 39.4 5.8 7.4
018 66.1 13.0 2.9 3.4 63.1 14.3 2.7 3.3 60.1 15.5 2.6 3.2
025 88.7 16.9 3.8 4.5 84.4 18.4 3.6 4.4 80.1 19.9 3.5 4.3
13 HWB 028 113.8 23.2 4.9 5.8 108.2 25.2 4.7 5.7 102.5 27.1 4.4 5.5
035 128.5 25.8 5.5 6.6 122.8 28.0 5.3 6.4 117.0 30.1 5.0 6.3
040 162.5 36.1 7.0 8.5 155.5 38.8 6.7 8.3 148.5 41.3 6.4 8.1
018 72.2 13.2 3.1 3.6 69.0 14.6 3.0 3.6 65.8 15.9 2.8 3.5
025 97.0 17.3 4.2 4.9 92.5 19.0 4.0 4.8 87.9 20.5 3.8 4.6
16 HWB 028 124.0 23.9 5.4 6.3 118.1 26.0 5.1 6.1 112.2 28.1 4.8 6.0
035 140.6 26.5 6.1 7.1 134.6 28.9 5.8 7.0 128.6 31.1 5.5 6.8
040 178.5 37.4 7.7 9.2 171.0 40.3 7.4 9.0 163.6 43.0 7.1 8.8
LEGEND
Cap — Capacity, kW
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

34
Performance data, 30HWA,HL in combination
with 09DK air-cooled condenser — SI
COOLING CAPACITIES — 60 Hz (cont)
CONDENSER ENTERING WATER TEMPERATURE (C)
REMOTE 30 35 40 45 50
LCWT UNIT UNIT Cooler Cooler Cooler Cooler Cooler
COND
(C) 30 SIZE Input Flow Input Flow Input Flow Input Flow Input Flow
09DK Cap Cap Cap Cap Cap
kW Rate kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s) (L/s)
018 020 46.1 13.6 2.0 43.7 14.5 1.9 41.4 15.3 1.8 39.1 16.1 1.7 36.7 16.9 1.6
025 028 59.7 16.8 2.6 56.1 17.8 2.4 52.4 18.7 2.2 48.6 19.5 2.1 44.9 20.2 1.9
HWA 028 028 76.8 23.5 3.3 72.5 24.8 3.1 68.2 26.0 2.9 63.9 27.1 2.7 59.7 28.1 2.6
4 035 034 84.8 25.3 3.6 80.0 26.6 3.4 75.3 27.8 3.2 70.5 28.9 3.0 65.7 29.7 2.8
040 044 107.6 34.7 4.6 102.2 36.4 4.4 96.8 38.0 4.2 91.4 39.4 3.9 85.9 40.8 3.7
050 * * * * * * * * * * * * * * * *
HL
060 * * * * * * * * * * * * * * * *
018 020 47.5 13.8 2.0 45.1 14.7 1.9 42.8 15.6 1.8 40.4 16.4 1.7 38.0 17.2 1.6
025 028 61.8 17.0 2.7 58.1 18.1 2.5 54.4 19.1 2.3 50.5 19.9 2.2 46.7 20.6 2.0
HWA 028 028 79.4 23.9 3.4 74.9 25.2 3.2 70.5 26.4 3.0 66.1 27.6 2.8 * * *
5 035 034 87.7 25.7 3.8 83.0 27.1 3.6 78.1 28.3 3.4 73.2 29.5 3.1 68.2 30.4 2.9
040 044 111.5 35.3 4.8 105.9 37.1 4.5 100.3 38.8 4.3 94.8 40.3 4.1 89.2 41.7 3.8
050 028,024 157.5 46.9 6.7 148.2 49.3 6.3 138.8 51.5 5.9 * * * * * *
HL
060 034,034 189.4 54.5 8.1 179.1 57.6 7.6 168.6 60.4 7.2 158.0 62.8 6.7 * * *
018 020 49.0 14.0 2.1 46.6 15.0 2.0 44.1 15.8 1.9 41.7 16.7 1.8 39.2 17.5 1.7
025 028 63.9 17.3 2.7 60.2 18.4 2.6 56.3 19.4 2.4 52.4 20.3 2.3 48.5 21.0 2.1
HWA 028 028 82.0 24.3 3.5 77.4 25.6 3.3 72.8 26.9 3.1 68.3 28.1 2.9 * * *
6 035 034 90.6 26.1 3.9 85.8 27.6 3.7 81.0 28.9 3.5 75.9 30.0 3.3 70.9 31.1 3.0
040 044 115.3 36.0 5.0 109.7 37.8 4.7 103.9 39.5 4.5 98.2 41.1 4.2 92.5 42.6 4.0
050 028,024 163.2 47.8 7.0 153.8 50.3 6.6 144.2 52.6 6.2 * * * * * *
HL
060 034,034 196.2 55.4 8.4 185.6 58.6 7.9 174.9 61.5 7.5 164.0 64.1 7.0 * * *
018 020 50.6 14.2 2.2 48.1 15.2 2.1 45.6 16.1 2.0 43.0 17.0 1.9 * * *
025 028 66.0 17.6 2.8 62.2 18.7 2.7 58.4 19.7 2.5 54.4 20.7 2.3 50.4 21.5 2.2
HWA 028 028 84.5 24.7 3.6 79.9 26.1 3.4 75.2 27.4 3.2 70.6 28.6 3.0 * * *
7 035 034 93.6 26.5 4.0 88.7 28.0 3.8 83.8 29.4 3.6 78.7 30.7 3.4 73.5 31.7 3.2
040 044 119.3 36.6 5.1 113.5 38.5 4.9 107.7 40.3 4.6 101.8 42.0 4.4 95.9 43.5 4.1
050 028,024 169.2 48.7 7.2 159.5 51.3 6.8 149.7 53.7 6.4 * * * * * *
HL
060 034,034 203.0 56.3 8.7 192.3 59.6 8.2 181.4 62.7 7.7 170.2 65.5 7.3 * * *
018 020 52.1 14.4 2.2 49.6 15.4 2.1 47.0 16.4 2.0 44.4 17.2 1.9 * * *
025 028 68.2 17.8 2.9 64.4 19.0 2.8 60.4 20.1 2.6 56.4 21.0 2.4 52.3 21.9 2.3
HWA 028 028 87.3 25.1 3.8 82.4 26.6 3.5 77.7 27.9 3.3 73.0 29.2 3.1 * * *
8 035 034 96.7 26.9 4.2 91.7 28.5 3.9 86.6 29.9 3.7 81.5 31.2 3.5 76.2 32.4 3.3
040 044 123.2 37.2 5.3 117.3 39.2 5.0 111.4 41.1 4.8 105.5 42.8 4.5 99.3 44.4 4.3
050 028,024 175.2 49.6 7.5 165.3 52.3 7.1 155.2 54.8 6.6 * * * * * *
HL
060 034,034 210.1 57.2 9.0 199.1 60.7 8.5 187.9 63.9 8.0 176.5 66.8 7.5 * * *
018 020 53.8 14.7 2.3 51.1 15.7 2.2 48.5 16.6 2.1 45.9 17.6 2.0 * * *
025 028 70.4 18.1 3.0 66.5 19.3 2.9 62.5 20.4 2.7 58.4 21.4 2.5 54.3 22.3 2.3
HWA 028 028 89.9 25.5 3.9 85.1 27.0 3.7 80.2 28.4 3.5 75.3 29.7 3.2 * * *
9 035 034 99.8 27.3 4.3 94.7 29.0 4.1 89.6 30.5 3.9 84.3 31.8 3.6 * * *
040 044 127.3 37.9 5.5 121.2 39.9 5.2 115.2 41.9 5.0 109.1 43.7 4.7 103.0 45.4 4.4
050 028,024 181.2 50.5 7.7 171.1 53.3 7.3 160.9 55.9 6.9 * * * * * *
HL
060 034,034 217.3 58.1 9.3 206.0 61.7 8.8 194.6 65.0 8.3 183.0 68.1 7.8 * * *
018 020 55.4 14.9 2.4 52.7 15.9 2.3 49.9 16.9 2.2 47.3 17.8 2.0 * * *
025 028 72.5 18.3 3.1 68.6 19.6 3.0 64.6 20.7 2.8 60.4 21.8 2.6 56.2 22.8 2.4
HWA 028 028 92.6 25.9 4.0 87.7 27.5 3.8 82.7 28.9 3.6 77.8 30.3 3.4 * * *
10 035 034 103.0 27.8 4.4 97.8 29.5 4.2 92.5 31.0 4.0 87.2 32.4 3.8 * * *
040 044 131.4 38.5 5.7 125.2 40.6 5.4 119.0 42.6 5.1 112.8 44.5 4.9 * * *
HL 050 028,024 187.4 51.4 8.0 177.1 54.3 7.6 166.7 57.1 7.1 * * * * * *
060 034,034 224.6 59.0 9.6 213.1 62.8 9.1 201.4 66.2 8.6 189.5 69.4 8.1 * * *
018 020 60.5 15.5 2.6 57.5 16.6 2.5 54.7 17.7 2.4 51.8 18.7 2.2 * * *
025 028 79.5 19.1 3.4 75.3 20.5 3.2 71.0 21.7 3.1 66.8 22.9 2.9 * * *
HWA 028 028 101.2 27.2 4.4 95.8 28.9 4.1 90.5 30.5 3.9 85.3 32.0 3.7 * * *
13 035 034 112.9 29.1 4.9 107.5 30.9 4.6 101.9 32.6 4.4 96.2 34.2 4.1 * * *
040 044 144.6 40.5 6.2 137.8 42.8 5.9 131.1 45.0 5.7 124.3 47.1 5.4 * * *
050 028,024 206.6 54.2 8.8 195.7 57.5 8.4 * * * * * * * * *
HL 060 034,034 247.3 61.8 10.6 235.2 66.0 10.1 222.7 69.8 9.5 * * * * * *
018 020 65.7 16.1 2.8 62.7 17.3 2.7 59.6 18.5 2.6 56.5 19.6 2.4 * * *
025 028 86.8 19.9 3.7 82.4 21.4 3.6 77.9 22.7 3.4 73.3 24.1 3.2 * * *
HWA 028 028 109.9 28.6 4.7 104.4 30.4 4.5 98.8 32.1 4.3 * * * * * *
16 035 034 123.3 30.4 5.3 117.6 32.4 5.1 111.7 34.3 4.8 105.5 36.1 4.6 * * *
040 044 158.2 42.5 6.8 151.2 45.1 6.5 144.0 47.5 6.2 136.7 49.8 5.9 * * *
050 028,024 219.5 56.1 9.4 206.9 59.4 8.9 * * * * * * * * *
HL
060 034,034 267.7 64.2 11.5 254.0 68.6 10.9 239.9 72.6 10.3 * * * * * *
LEGEND *Operation not recommended with condenser identified. Contact your Carrier rep-
Cap — Capacity, kW resentative for an alternate equipment selection.
COND — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

35
Performance data,
30HWA,HL condenserless — SI
COOLING CAPACITIES — 60 Hz (cont)
SATURATED DISCHARGE TEMPERATURE (C)
35 45 50 55
LCWT UNIT UNIT Cooler Cooler Cooler Cooler
(C) 30 SIZE Input Flow Input Flow Input Flow Input Flow
Cap THR Cap THR Cap THR Cap THR
kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s)
018 53.0 11.9 2.3 63.8 48.0 13.9 2.1 60.6 45.5 14.8 2.0 59.0 43.0 15.7 1.8 57.3
025 68.5 15.0 2.9 82.2 60.9 17.4 2.6 76.8 56.8 18.5 2.4 73.6 52.7 19.4 2.3 70.3
HWA 028 90.5 20.3 3.9 109.0 80.7 23.4 3.5 102.1 76.0 24.9 3.3 98.6 71.2 26.1 3.1 95.0
4 035 97.1 22.6 4.2 117.7 87.4 25.8 3.8 110.9 82.3 27.2 3.5 107.1 77.2 28.4 3.3 103.0
040 122.2 31.6 5.2 151.0 110.9 35.5 4.8 143.2 105.2 37.2 4.5 139.1 99.6 38.8 4.3 135.0
HL 050 175.0 39.0 7.5 210.5 155.6 45.3 6.7 196.9 145.6 48.0 6.3 189.4 135.5 50.4 5.8 181.4
060 204.0 47.3 8.8 247.1 182.8 54.6 7.8 232.4 171.8 57.7 7.4 224.3 160.7 60.5 6.9 215.7
018 54.8 11.9 2.4 65.7 49.7 14.0 2.1 62.4 47.1 15.0 2.0 60.8 44.6 15.9 1.9 59.0
025 71.0 15.1 3.1 84.8 63.2 17.6 2.7 79.2 59.0 18.7 2.5 76.1 54.9 19.7 2.4 72.9
HWA 028 93.7 20.4 4.0 112.3 83.7 23.7 3.6 105.3 78.8 25.2 3.4 101.7 73.8 26.5 3.2 98.0
5 035 100.7 22.8 4.3 121.4 90.7 26.1 3.9 114.5 85.6 27.6 3.7 110.7 80.4 28.9 3.5 106.7
040 126.8 31.9 5.4 155.9 115.2 36.0 4.9 148.0 109.4 37.9 4.7 143.8 103.6 39.5 4.4 139.6
050 181.9 39.3 7.8 217.7 162.2 45.8 7.0 203.9 152.0 48.7 6.5 196.3 141.6 51.3 6.1 188.3
HL
060 211.9 47.6 9.1 255.2 190.2 55.2 8.2 240.4 179.0 58.5 7.7 232.3 167.6 61.5 7.2 223.6
018 56.7 12.0 2.4 67.6 51.4 14.1 2.2 64.3 48.8 15.1 2.1 62.6 46.3 16.1 2.0 60.9
025 73.6 15.2 3.2 87.4 65.6 17.8 2.8 81.8 61.6 19.0 2.6 78.8 57.3 20.0 2.5 75.5
HWA 028 97.0 20.5 4.2 115.7 86.8 24.0 3.7 108.6 81.7 25.5 3.5 104.9 76.9 26.9 3.3 101.4
6 035 104.3 22.9 4.5 125.1 94.2 26.4 4.0 118.2 88.9 28.0 3.8 114.4 83.6 29.4 3.6 110.3
040 131.5 32.3 5.7 160.8 119.5 36.5 5.1 152.8 113.6 38.5 4.9 148.6 107.6 40.2 4.6 144.3
HL 050 189.0 39.5 8.1 224.9 168.9 46.3 7.3 211.0 158.5 49.4 6.8 203.4 147.9 52.1 6.4 195.3
060 219.9 47.8 9.5 263.4 197.8 55.8 8.5 248.6 186.4 59.3 8.0 240.3 174.7 62.5 7.5 231.6
018 58.6 12.0 2.5 69.5 53.2 14.2 2.3 66.2 50.5 15.3 2.2 64.4 47.9 16.3 2.1 62.7
025 76.1 15.3 3.3 90.1 68.1 18.0 2.9 84.5 63.9 19.2 2.7 81.4 59.5 20.3 2.6 78.0
HWA 028 100.3 20.7 4.3 119.1 89.9 24.2 3.9 111.9 84.7 25.8 3.6 108.2 79.6 27.3 3.4 104.5
7 035 107.9 23.0 4.6 128.9 97.7 26.7 4.2 122.0 92.4 28.4 4.0 118.2 86.9 29.8 3.7 114.1
040 136.2 32.6 5.9 165.9 124.0 37.0 5.3 157.7 117.9 39.0 5.1 153.4 111.8 40.9 4.8 149.0
050 196.2 39.6 8.4 232.3 175.7 46.8 7.6 218.3 165.1 50.0 7.1 210.6 154.3 52.9 6.6 202.4
HL
060 228.1 48.0 9.8 271.8 205.5 56.4 8.8 256.8 193.9 60.1 8.3 248.6 182.0 63.4 7.8 239.7
018 60.6 12.0 2.6 71.5 55.0 14.3 2.4 68.1 52.3 15.4 2.2 66.3 49.5 16.4 2.1 64.5
025 78.8 15.4 3.4 92.8 70.6 18.2 3.0 87.2 66.4 19.4 2.9 84.1 62.1 20.6 2.7 80.8
HWA 028 103.7 20.8 4.5 122.6 93.0 24.4 4.0 115.3 87.8 26.1 3.8 111.5 82.6 27.7 3.6 107.7
8 035 111.7 23.2 4.8 132.8 101.3 27.0 4.4 125.9 95.9 28.7 4.1 122.0 90.3 30.3 3.9 117.9
040 141.1 32.8 6.1 171.0 128.6 37.5 5.5 162.7 122.3 39.6 5.3 158.4 116.1 41.6 5.0 153.9
HL 050 203.6 39.7 8.8 239.8 182.7 47.2 7.9 225.7 171.9 50.6 7.4 217.9 160.9 53.6 6.9 209.7
060 236.4 48.2 10.2 280.3 213.4 56.9 9.2 265.3 201.6 60.8 8.7 256.9 189.4 64.3 8.2 248.0
018 62.6 12.1 2.7 73.5 56.9 14.4 2.4 70.0 54.1 15.6 2.3 68.2 51.3 16.6 2.2 66.4
025 81.5 15.4 3.5 95.5 73.2 18.3 3.2 89.9 68.9 19.6 3.0 86.8 64.5 20.8 2.8 83.4
HWA 028 107.2 20.8 4.6 126.2 96.3 24.7 4.1 118.7 90.9 26.4 3.9 114.9 85.6 28.0 3.7 111.1
9 035 115.5 23.3 5.0 136.7 104.9 27.3 4.5 129.7 99.4 29.1 4.3 125.9 93.8 30.7 4.0 121.7
040 146.1 33.1 6.3 176.2 133.3 38.0 5.7 167.8 126.8 40.2 5.5 163.4 120.4 42.2 5.2 158.9
050 211.2 39.8 9.1 247.4 189.8 47.6 8.2 233.2 178.8 51.1 7.7 225.4 167.6 54.3 7.2 217.0
HL
060 245.0 48.4 10.5 289.0 221.5 57.4 9.5 273.8 209.4 61.5 9.0 265.4 197.1 65.2 8.5 256.4
018 64.6 12.1 2.8 75.6 58.8 14.5 2.5 72.0 55.9 15.7 2.4 70.2 53.0 16.8 2.3 68.3
025 84.2 15.5 3.6 98.3 75.8 18.5 3.3 92.6 71.5 19.8 3.1 89.5 67.0 21.1 2.9 86.2
HWA 028 110.7 20.9 4.8 129.8 99.6 24.9 4.3 122.2 94.1 26.7 4.1 118.3 88.6 28.3 3.8 114.4
10 035 119.4 23.4 5.1 140.7 108.6 27.5 4.7 133.7 103.0 29.4 4.4 129.8 97.3 31.1 4.2 125.6
040 151.2 33.3 6.5 181.6 138.0 38.4 5.9 173.0 131.5 40.7 5.7 168.5 124.9 42.8 5.4 163.9
050 218.9 39.9 9.4 255.2 197.2 48.0 8.5 240.8 185.9 51.7 8.0 232.9 174.5 55.0 7.5 224.6
HL
060 253.7 48.4 10.9 297.8 229.8 57.9 9.9 282.5 217.5 62.1 9.4 274.0 204.8 66.1 8.8 265.0
018 70.9 12.1 3.1 81.9 64.7 14.8 2.8 78.2 61.6 16.1 2.7 76.2 58.6 17.3 2.5 74.3
025 92.7 15.5 4.0 106.9 84.0 18.8 3.6 101.1 79.4 20.4 3.4 98.0 74.8 21.8 3.2 94.6
HWA 028 121.8 21.1 5.3 141.0 109.9 25.4 4.7 133.0 104.0 27.4 4.5 129.0 98.2 29.3 4.2 124.9
13 035 131.6 23.5 5.7 153.0 120.3 28.2 5.2 145.9 114.4 30.3 4.9 141.9 108.4 32.2 4.7 137.7
040 167.1 33.9 7.2 198.0 153.0 39.6 6.6 189.1 146.0 42.2 6.3 184.4 138.9 44.7 6.0 179.6
050 243.1 39.9 10.5 279.4 220.1 48.9 9.5 264.6 208.2 53.0 9.0 256.4 196.0 56.9 8.5 247.8
HL 060 281.0 48.5 12.1 325.1 255.7 59.0 11.0 309.4 242.6 63.9 10.5 300.7 229.2 68.3 9.9 291.4
018 77.7 12.0 3.4 88.6 71.0 15.0 3.1 84.6 67.7 16.3 2.9 82.6 64.4 17.7 2.8 80.5
025 101.7 15.5 4.4 115.8 92.6 19.1 4.0 110.0 87.8 20.8 3.8 106.8 83.0 22.4 3.6 103.4
HWA 028 133.5 21.1 5.8 152.6 120.8 25.9 5.2 144.4 114.6 28.1 4.9 140.1 108.4 30.2 4.7 135.9
16 035 144.4 23.5 6.2 165.8 132.5 28.7 5.7 158.6 126.3 31.0 5.5 154.6 120.0 33.2 5.2 150.3
040 184.1 34.3 7.9 215.3 169.0 40.7 7.3 206.0 161.5 43.6 7.0 201.1 153.9 46.3 6.6 196.1
050 265.2 39.6 11.4 301.2 237.8 49.3 10.3 282.7 223.8 53.7 9.7 272.7 209.5 57.8 9.0 262.2
HL
060 308.4 48.1 13.3 352.2 279.8 59.7 12.1 334.1 265.1 65.0 11.4 324.2 250.0 69.9 10.8 313.6
LEGEND
Cap — Capacity, kW
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)
THR — Total Heat of Rejection
NOTE: Performance based on 9.4 C subcooling.

36
Performance data,
30HWC,HK water-cooled — SI
COOLING CAPACITIES — 50 Hz
CONDENSER ENTERING WATER TEMPERATURE (C)
25 30 35
LCWT UNIT UNIT Cooler Cond Cooler Cond Cooler Cond
(C) 30 SIZE Input Flow Flow Input Flow Flow Input Flow Flow
Cap Cap Cap
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
018 46.7 9.8 2.0 2.4 44.6 10.9 1.9 2.4 42.4 12.0 1.8 2.3
025 58.6 12.3 2.5 3.0 55.3 13.4 2.4 2.9 51.9 14.4 2.2 2.8
HWC 028 73.3 16.3 3.1 3.8 68.7 17.5 2.9 3.7 64.2 18.5 2.8 3.5
035 80.8 19.2 3.5 4.3 76.3 20.6 3.3 4.1 71.7 21.9 3.1 4.0
4 040 110.7 26.7 4.8 5.8 105.4 28.5 4.5 5.7 100.2 30.1 4.3 5.5
040 140.8 34.0 6.0 7.4 133.3 36.7 5.7 7.2 125.5 39.2 5.4 7.0
HK 050 166.8 40.0 7.2 8.8 158.0 43.1 6.8 8.6 149.1 46.0 6.4 8.3
060 212.5 59.9 9.1 11.6 201.9 63.8 8.7 11.3 191.3 67.3 8.2 11.0
018 48.3 9.9 2.1 2.5 46.0 11.0 2.0 2.4 43.8 12.1 1.9 2.4
025 60.7 12.4 2.6 3.1 57.3 13.5 2.5 3.0 53.9 14.5 2.3 2.9
HWC 028 76.5 16.5 3.3 4.0 71.8 17.7 3.1 3.8 67.1 18.9 2.9 3.7
035 84.1 19.4 3.6 4.4 79.5 20.9 3.4 4.3 74.8 22.2 3.2 4.1
5 040 114.8 27.0 4.9 6.0 109.4 28.9 4.7 5.9 104.0 30.6 4.5 5.7
040 146.1 34.3 6.3 7.7 138.3 37.1 5.9 7.5 130.5 39.7 5.6 7.2
HK 050 173.1 40.3 7.4 9.1 164.1 43.6 7.1 8.8 155.1 46.6 6.7 8.6
060 220.3 60.7 9.5 11.9 209.4 64.7 9.0 11.6 198.5 68.4 8.5 11.3
018 49.8 9.9 2.1 2.5 47.5 11.1 2.0 2.5 45.3 12.2 1.9 2.4
025 62.8 12.5 2.7 3.2 59.5 13.6 2.6 3.1 55.9 14.7 2.4 3.0
HWC 028 79.8 16.7 3.4 4.1 74.9 18.0 3.2 4.0 70.1 19.2 3.0 3.8
035 87.5 19.6 3.8 4.6 82.8 21.1 3.6 4.4 78.0 22.5 3.4 4.3
6 040 119.0 27.3 5.1 6.2 113.4 29.2 4.9 6.1 107.8 31.0 4.6 5.9
040 151.4 34.6 6.5 7.9 143.6 37.5 6.2 7.7 135.6 40.2 5.8 7.5
HK 050 179.6 40.6 7.7 9.4 170.5 44.0 7.3 9.1 161.1 47.2 6.9 8.9
060 228.3 61.4 9.8 12.3 217.1 65.6 9.3 12.0 205.9 69.4 8.9 11.7
018 51.4 10.0 2.2 2.6 49.1 11.2 2.1 2.6 46.7 12.3 2.0 2.5
025 64.9 12.6 2.8 3.3 61.6 13.8 2.6 3.2 58.0 14.9 2.5 3.1
HWC 028 83.2 16.9 3.6 4.3 78.1 18.2 3.4 4.1 73.1 19.5 3.1 3.9
035 91.0 19.8 3.9 4.7 86.2 21.4 3.7 4.6 81.3 22.8 3.5 4.4
7 040 123.3 27.6 5.3 6.4 117.6 29.6 5.1 6.3 111.8 31.5 4.8 6.1
040 156.9 34.8 6.7 8.2 148.9 37.9 6.4 7.9 140.8 40.7 6.1 7.7
HK 050 186.2 40.9 8.0 9.7 176.9 44.5 7.6 9.4 167.4 47.7 7.2 9.2
060 236.4 62.1 10.2 12.7 224.9 66.5 9.7 12.4 213.4 70.5 9.2 12.1
018 53.0 10.0 2.3 2.7 50.7 11.2 2.2 2.6 48.3 12.4 2.1 2.6
025 67.2 12.7 2.9 3.4 63.8 13.9 2.7 3.3 60.1 15.0 2.6 3.2
HWC 028 86.7 17.1 3.7 4.4 81.5 18.5 3.5 4.3 76.3 19.8 3.3 4.1
035 94.6 20.0 4.1 4.9 89.6 21.6 3.9 4.7 84.6 23.1 3.6 4.6
8 040 127.6 27.9 5.5 6.6 121.8 30.0 5.2 6.5 115.9 31.9 5.0 6.3
040 162.5 35.1 7.0 8.4 154.3 38.3 6.6 8.2 146.1 41.2 6.3 8.0
HK 050 192.9 41.2 8.3 10.0 183.4 44.9 7.9 9.7 173.7 48.3 7.5 9.5
060 244.8 62.8 10.5 13.1 233.0 67.3 10.0 12.8 221.2 71.5 9.5 12.4
018 54.6 10.0 2.4 2.8 52.2 11.3 2.2 2.7 49.8 12.5 2.1 2.7
025 69.5 12.8 3.0 3.5 65.9 14.0 2.8 3.4 62.3 15.2 2.7 3.3
HWC 028 90.3 17.3 3.9 4.6 84.9 18.7 3.7 4.4 79.6 20.0 3.4 4.2
035 98.3 20.1 4.2 5.0 93.2 21.8 4.0 4.9 88.1 23.4 3.8 4.8
9 040 132.0 28.1 5.7 6.8 126.1 30.3 5.4 6.7 120.0 32.3 5.2 6.5
040 168.2 35.3 7.2 8.7 159.9 38.6 6.9 8.5 151.5 41.7 6.5 8.2
HK 050 199.8 41.5 8.6 10.3 190.1 45.3 8.2 10.0 180.2 48.8 7.8 9.8
060 253.4 63.5 10.9 13.5 241.2 68.2 10.4 13.1 229.1 72.6 9.9 12.8
018 56.3 10.0 2.4 2.8 53.9 11.3 2.3 2.8 51.4 12.6 2.2 2.7
025 71.8 12.8 3.1 3.6 68.2 14.1 2.9 3.5 64.5 15.3 2.8 3.4
HWC 028 93.9 17.4 4.0 4.8 88.4 18.9 3.8 4.6 82.9 20.3 3.6 4.4
035 102.0 20.3 4.4 5.2 96.9 22.1 4.2 5.1 91.6 23.7 3.9 4.9
10 040 136.5 28.4 5.9 7.0 130.5 30.6 5.6 6.9 124.3 32.8 5.4 6.7
040 174.0 35.5 7.5 8.9 165.5 38.9 7.1 8.7 157.0 42.1 6.8 8.5
HK 050 206.8 41.7 8.9 10.6 197.0 45.6 8.5 10.3 186.8 49.3 8.0 10.1
060 262.1 64.2 11.3 13.9 249.7 69.0 10.8 13.5 237.2 73.5 10.2 13.2
018 61.5 10.1 2.7 3.1 58.9 11.5 2.5 3.0 56.3 12.8 2.4 2.9
025 78.9 13.0 3.4 3.9 75.2 14.4 3.2 3.8 71.3 15.7 3.1 3.7
HWC 028 105.4 17.9 4.5 5.3 99.4 19.6 4.3 5.1 93.5 21.1 4.0 4.9
035 113.9 20.6 4.9 5.7 108.3 22.6 4.7 5.6 102.7 24.5 4.4 5.4
13 040 150.6 29.1 6.5 7.7 144.1 31.6 6.2 7.5 137.7 33.9 5.9 7.3
040 192.3 36.1 8.3 9.7 183.3 39.8 7.9 9.5 174.2 43.3 7.5 9.3
HK 050 228.7 42.3 9.9 11.6 218.2 46.6 9.4 11.3 207.6 50.7 9.0 11.0
060 289.4 66.0 12.5 15.1 276.1 71.4 11.9 14.8 262.7 76.4 11.3 14.4
018 66.9 10.1 2.9 3.3 64.1 11.6 2.8 3.2 61.4 13.0 2.7 3.2
025 86.5 13.2 3.7 4.3 82.5 14.7 3.6 4.2 78.5 16.1 3.4 4.0
HWC 028 117.9 18.3 5.1 5.8 111.4 20.2 4.8 5.6 105.0 21.9 4.5 5.4
035 126.6 20.9 5.5 6.3 120.6 23.1 5.2 6.1 114.7 25.2 4.9 6.0
16 040 165.5 29.7 7.1 8.3 158.6 32.5 6.8 8.2 151.7 35.1 6.5 8.0
040 207.6 36.4 9.0 10.4 196.8 40.3 8.5 10.1 185.8 44.0 8.0 9.8
HK 050 247.6 42.6 10.7 12.4 235.1 47.2 10.1 12.1 222.5 51.6 9.6 11.7
060 317.4 67.6 13.7 16.4 302.1 73.4 13.0 16.0 286.8 78.9 12.4 15.6
(See Legend on page 38.)

37
Performance data,
30HWB water-cooled — SI
COOLING CAPACITIES — 50 Hz (cont)
CONDENSER ENTERING WATER TEMPERATURE (C)
25 30 35
LCWT UNIT UNIT Cooler Cond Cooler Cond Cooler Cond
(C) 30 SIZE Input Flow Flow Input Flow Flow Input Flow Flow
Cap Cap Cap
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
018 43.8 9.8 1.9 2.3 41.7 10.8 1.8 2.2 39.6 11.8 1.7 2.2
025 58.1 13.0 2.5 3.0 54.9 14.0 2.4 2.9 51.5 15.0 2.2 2.8
4 HWB 028 75.8 17.4 3.3 4.0 71.7 18.7 3.1 3.8 67.5 20.0 2.9 3.7
035 84.3 19.5 3.6 4.4 80.0 20.9 3.4 4.3 75.6 22.2 3.2 4.2
040 105.6 27.0 4.5 5.6 100.5 28.7 4.3 5.5 95.5 30.2 4.1 5.3
018 45.2 9.9 1.9 2.3 43.2 11.0 1.9 2.3 41.0 12.0 1.8 2.3
025 60.2 13.1 2.6 3.1 56.9 14.2 2.4 3.0 53.5 15.2 2.3 2.9
5 HWB 028 78.5 17.6 3.4 4.1 74.0 19.0 3.2 4.0 69.9 20.3 3.0 3.8
035 87.2 19.7 3.7 4.6 82.9 21.1 3.6 4.4 78.5 22.5 3.4 4.3
040 109.5 27.3 4.7 5.8 104.3 29.1 4.5 5.7 99.1 30.7 4.3 5.5
018 46.8 10.0 2.0 2.4 44.6 11.1 1.9 2.4 42.4 12.1 1.8 2.3
025 62.4 13.2 2.7 3.2 59.0 14.3 2.5 3.1 55.5 15.4 2.4 3.0
6 HWB 028 81.1 17.8 3.5 4.2 76.9 19.2 3.3 4.1 72.4 20.5 3.1 4.0
035 90.3 19.9 3.9 4.7 85.9 21.4 3.7 4.6 81.4 22.8 3.5 4.4
040 113.5 27.7 4.9 6.0 108.1 29.5 4.6 5.9 102.8 31.2 4.4 5.7
018 48.3 10.1 2.1 2.5 46.1 11.2 2.0 2.4 43.8 12.3 1.9 2.4
025 64.5 13.3 2.8 3.3 61.1 14.5 2.6 3.2 57.5 15.6 2.5 3.1
7 HWB 028 83.9 17.9 3.6 4.3 79.4 19.4 3.4 4.2 74.8 20.8 3.2 4.1
035 93.4 20.1 4.0 4.8 88.9 21.7 3.8 4.7 84.3 23.1 3.6 4.6
040 117.5 28.1 5.1 6.2 112.1 30.0 4.8 6.0 106.6 31.7 4.6 5.9
018 49.8 10.2 2.1 2.6 47.5 11.3 2.0 2.5 45.2 12.4 1.9 2.5
025 66.7 13.4 2.9 3.4 63.2 14.6 2.7 3.3 59.6 15.7 2.6 3.2
8 HWB 028 86.6 18.1 3.7 4.5 82.0 19.6 3.5 4.3 77.6 21.1 3.3 4.2
035 96.6 20.3 4.2 5.0 92.0 21.9 4.0 4.9 87.3 23.5 3.8 4.7
040 121.7 28.4 5.2 6.4 116.1 30.4 5.0 6.2 110.5 32.2 4.8 6.1
018 51.4 10.3 2.2 2.6 49.1 11.4 2.1 2.6 46.8 12.5 2.0 2.5
025 68.9 13.5 3.0 3.5 65.4 14.8 2.8 3.4 61.8 15.9 2.7 3.3
9 HWB 028 89.4 18.2 3.9 4.6 84.8 19.8 3.6 4.5 80.1 21.3 3.4 4.3
035 99.8 20.5 4.3 5.1 95.2 22.2 4.1 5.0 90.4 23.7 3.9 4.9
040 125.9 28.8 5.4 6.6 120.2 30.8 5.2 6.4 114.5 32.7 4.9 6.3
018 53.0 10.4 2.3 2.7 50.6 11.5 2.2 2.6 48.2 12.7 2.1 2.6
025 71.2 13.6 3.1 3.6 67.6 14.9 2.9 3.5 63.9 16.1 2.8 3.4
10 HWB 028 92.4 18.4 4.0 4.7 87.5 20.0 3.8 4.6 82.8 21.6 3.6 4.4
035 103.1 20.7 4.4 5.3 98.4 22.4 4.2 5.1 93.5 24.1 4.0 5.0
040 130.2 29.1 5.6 6.8 124.4 31.2 5.4 6.6 118.5 33.2 5.1 6.5
018 58.0 10.5 2.5 2.9 55.5 11.8 2.4 2.9 52.9 13.1 2.3 2.8
025 78.4 13.9 3.4 3.9 74.6 15.3 3.2 3.8 70.7 16.6 3.0 3.7
13 HWB 028 101.4 18.9 4.4 5.1 96.3 20.6 4.2 5.0 91.2 22.3 3.9 4.8
035 113.4 21.2 4.9 5.7 108.4 23.1 4.7 5.6 103.2 24.9 4.5 5.5
040 143.8 30.1 6.2 7.4 137.5 32.4 5.9 7.2 131.2 34.7 5.7 7.1
018 63.4 10.6 2.7 3.2 60.7 12.0 2.6 3.1 57.9 13.4 2.5 3.0
025 85.8 14.2 3.7 4.3 81.9 15.7 3.5 4.2 77.8 17.1 3.4 4.1
16 HWB 028 110.8 19.3 4.8 5.6 105.3 21.2 4.5 5.4 100.0 23.1 4.3 5.3
035 124.4 21.6 5.4 6.2 119.1 23.7 5.1 6.1 113.6 25.7 4.9 6.0
040 158.3 31.0 6.8 8.1 151.6 33.6 6.5 7.9 144.7 36.0 6.2 7.7
LEGEND
Cap — Capacity, kW
COND — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

38
Performance data, 30HWA,HL in combination
with 09DK air-cooled condenser — SI
COOLING CAPACITIES — 50 Hz (cont)
CONDENSER ENTERING WATER TEMPERATURE (C)
REMOTE 30 35 40 45 50
LCWT UNIT UNIT Cooler Cooler Cooler Cooler Cooler
COND
(C) 30 SIZE Input Flow Input Flow Input Flow Input Flow Input Flow
09DK Cap Cap Cap Cap Cap
kW Rate kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s) (L/s)
018 024 41.2 10.7 1.8 39.1 11.6 1.7 37.1 12.5 1.6 35.0 13.3 1.5 32.8 14.1 1.4
025 028 52.8 14.0 2.3 49.6 14.9 2.1 46.4 15.7 2.0 43.1 16.5 1.9 39.7 17.1 1.7
HWA 028 028 68.7 19.3 3.0 64.7 20.4 2.8 60.8 21.5 2.6 56.9 22.5 2.4 53.0 23.4 2.3
4 035 034 74.9 20.9 3.2 70.8 22.1 3.0 66.6 23.2 2.9 62.4 24.2 2.7 58.0 25.0 2.5
040 044 95.2 29.1 4.1 90.4 30.6 3.9 85.6 32.0 3.7 80.7 33.3 3.5 75.8 34.5 3.3
050 * * * * * * * * * * * * * * * *
HL
060 * * * * * * * * * * * * * * * *
018 024 42.6 10.9 1.8 40.5 11.8 1.7 38.3 12.7 1.6 36.2 13.6 1.6 34.0 14.4 1.5
025 028 54.8 14.2 2.4 51.4 15.1 2.2 48.1 16.0 2.1 44.8 16.8 1.9 41.3 17.4 1.8
HWA 028 028 71.0 19.6 3.1 67.0 20.8 2.9 62.9 21.9 2.7 58.9 22.9 2.5 55.0 23.8 2.4
5 035 034 77.6 21.2 3.3 73.4 22.5 3.2 69.1 23.6 3.0 64.8 24.6 2.8 60.3 25.5 2.6
040 044 98.7 29.6 4.2 93.7 31.2 4.0 88.7 32.6 3.8 83.8 34.0 3.6 78.8 35.2 3.4
HL 050 034,034 162.7 44.6 6.9 153.9 47.4 6.6 144.8 49.9 6.2 135.6 52.1 5.8 * * *
060 034,034 203.9 67.7 8.7 193.5 71.0 5.0 183.1 74.1 7.8 172.7 76.9 7.4 * * *
018 024 44.0 11.0 1.9 41.8 12.0 1.8 39.6 12.9 1.7 37.4 13.8 1.6 35.2 14.6 1.5
025 028 56.6 14.4 2.4 53.3 15.4 2.3 49.9 16.3 2.1 46.5 17.1 2.0 43.0 17.8 1.8
HWA 028 028 73.3 19.9 3.2 69.2 21.1 3.0 65.1 22.3 2.8 61.0 23.3 2.6 56.9 24.3 2.4
6 035 034 80.3 21.5 3.5 76.0 22.9 3.3 71.7 24.0 3.1 67.3 25.1 2.9 62.7 26.1 2.7
040 044 102.2 30.1 4.4 97.1 31.7 4.2 92.0 33.3 4.0 86.9 34.7 3.7 81.7 36.0 3.5
050 034,034 168.7 45.2 7.2 159.6 48.1 6.8 150.4 50.8 6.4 141.0 53.2 6.0 * * *
HL
060 034,034 211.0 69.0 9.0 200.3 72.4 8.5 189.6 75.6 8.1 178.9 78.5 7.6 * * *
018 024 45.4 11.1 2.0 43.2 12.1 1.9 40.9 13.1 1.8 38.7 14.0 1.7 36.4 14.9 1.6
025 028 58.6 14.6 2.5 55.2 15.6 2.4 51.7 16.5 2.2 48.2 17.4 2.1 44.7 18.1 1.9
HWA 028 028 75.6 20.2 3.3 71.5 21.5 3.1 67.3 22.7 2.9 63.1 23.8 2.7 58.9 24.8 2.5
7 035 034 83.1 21.9 3.6 78.6 23.2 3.4 74.2 24.5 3.2 69.7 25.6 3.0 65.2 26.6 2.8
040 044 105.8 30.6 4.6 100.6 32.3 4.3 95.3 33.9 4.1 90.1 35.4 3.9 84.8 36.7 3.6
050 034,034 174.7 45.9 7.5 165.4 48.9 7.1 156.0 51.7 6.7 146.4 54.2 6.2 * * *
HL
060 034,034 218.4 70.3 9.3 207.2 73.8 8.8 196.3 77.1 8.4 185.3 80.2 7.9 * * *
018 024 46.8 11.3 2.0 44.6 12.3 1.9 42.3 13.3 1.8 40.0 14.2 1.7 37.6 15.1 1.6
025 028 60.5 14.8 2.6 57.1 15.8 2.5 53.7 16.8 2.3 50.0 17.7 2.2 46.5 18.5 2.0
HWA 028 028 78.0 20.5 3.4 73.8 21.8 3.2 69.5 23.0 3.0 65.3 24.2 2.8 61.0 25.2 2.6
8 035 034 85.9 22.2 3.7 81.4 23.6 3.5 76.8 24.9 3.3 72.3 26.1 3.1 67.6 27.1 2.9
040 044 109.4 31.1 4.7 104.1 32.9 4.5 98.7 34.5 4.2 93.4 36.1 4.0 87.9 37.5 3.8
050 034,034 180.9 46.6 7.7 171.4 49.7 7.3 161.8 52.6 6.9 152.1 55.2 6.5 * * *
HL
060 034,034 225.8 71.6 9.6 214.5 75.3 9.2 203.1 78.7 8.7 * * * * * *
018 024 48.3 11.4 2.1 46.0 12.4 2.0 43.6 13.5 1.9 41.3 14.4 1.8 38.9 15.4 1.7
025 028 62.6 14.9 2.7 59.1 16.0 2.5 55.5 17.1 2.4 51.9 18.0 2.2 48.2 18.8 2.1
HWA 028 028 80.6 20.8 3.5 76.2 22.2 3.3 71.7 23.4 3.1 67.4 24.6 2.9 * * *
9 035 034 88.7 22.5 3.8 84.2 24.0 3.6 79.5 25.3 3.4 74.9 26.5 3.2 70.0 27.6 3.0
040 044 113.3 31.6 4.9 107.7 33.4 4.6 102.2 35.2 4.4 96.7 36.8 4.2 91.2 38.3 3.9
050 034,034 187.2 47.2 8.0 177.5 50.5 7.6 167.1 53.5 7.2 157.7 56.3 6.7 * * *
HL
060 034,034 233.3 72.9 10.0 221.7 76.7 9.5 210.1 80.3 9.0 * * * * * *
018 024 49.8 11.5 2.1 47.4 12.6 2.0 45.0 13.7 1.9 42.6 14.7 1.8 40.2 15.6 1.7
025 028 64.5 15.1 2.8 61.0 16.3 2.6 57.4 17.3 2.5 53.8 18.3 2.3 50.0 19.2 2.2
HWA 028 028 83.1 21.1 3.6 78.5 22.5 3.4 74.0 23.8 3.2 69.6 25.0 3.0 * * *
10 035 034 91.6 22.8 3.9 87.0 24.3 3.7 82.3 25.7 3.5 77.4 27.0 3.3 72.6 28.2 3.1
040 044 117.1 32.1 5.0 111.5 34.0 4.8 105.7 35.8 4.6 100.1 37.5 4.3 94.4 39.0 4.1
HL 050 034,034 193.6 47.9 8.3 183.7 51.3 7.8 173.7 54.4 7.4 163.5 57.3 7.0 * * *
060 034,034 240.9 74.3 10.3 229.1 78.2 9.8 217.2 81.9 9.3 * * * * * *
018 024 54.4 11.9 2.3 51.9 13.1 2.2 49.4 14.2 2.1 46.8 15.3 2.0 44.2 16.4 1.9
025 028 70.8 15.7 3.1 67.2 16.9 2.9 63.4 18.1 2.7 59.5 19.2 2.6 55.5 20.2 2.4
HWA 028 028 90.9 22.1 3.9 86.0 23.6 3.7 81.2 25.0 3.5 76.5 26.3 3.3 * * *
13 035 034 100.5 23.7 4.3 95.6 25.4 4.1 90.7 27.0 3.9 85.6 28.4 3.7 80.5 29.8 3.5
040 044 128.8 33.6 5.6 122.8 35.7 5.3 116.8 37.7 5.0 110.8 39.6 4.8 104.7 41.4 4.5
050 034,034 213.5 49.9 9.1 203.0 53.6 8.7 192.4 57.1 8.2 181.5 60.3 7.8 * * *
HL 060 034,034 264.9 78.4 11.3 252.2 82.7 10.8 239.5 86.8 10.2 * * * * * *
018 024 59.3 12.3 2.6 56.6 13.6 2.4 53.9 14.8 2.3 51.2 15.9 2.2 * * *
025 028 77.3 16.3 3.3 73.5 17.6 3.2 69.5 18.8 3.0 65.6 20.1 2.8 61.4 21.2 2.6
HWA 028 028 99.0 23.1 4.3 93.9 24.7 4.1 88.9 26.2 3.8 83.8 27.7 3.6 * * *
16 035 034 110.0 24.7 4.7 104.8 26.5 4.5 99.5 28.2 4.3 94.1 29.8 4.1 * * *
040 044 141.4 35.1 6.1 134.9 37.4 5.8 128.4 39.6 5.5 121.9 41.7 5.3 * * *
050 034,034 228.7 51.3 9.8 216.4 55.1 9.3 204.0 58.7 8.7 191.6 61.9 8.2 * * *
HL
060 034,034 287.5 82.2 12.3 273.1 86.7 11.7 258.7 90.9 11.1 * * * * * *
LEGEND *Operation not recommended with condenser identified. Contact your Carrier rep-
Cap — Capacity, kW resentative for an alternate equipment selection.
COND — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

39
Performance data,
30HWA,HL condenserless — SI
COOLING CAPACITIES — 50 Hz (cont)
SATURATED DISCHARGE TEMPERATURE (C)
35 45 50 55
LCWT UNIT UNIT Cooler Cooler Cooler Cooler
(C) 30 SIZE Input Flow Input Flow Input Flow Input Flow
Cap THR Cap THR Cap THR Cap THR
kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s)
018 44.5 9.7 1.9 53.3 40.3 11.6 1.7 50.9 38.1 12.6 1.6 49.6 36.0 13.4 1.5 48.2
025 57.9 12.8 2.5 69.5 51.1 14.9 2.2 64.6 47.6 15.8 2.0 62.0 44.0 16.6 1.9 59.1
HWA 028 77.1 17.1 3.3 92.6 68.3 19.8 2.9 86.3 64.0 21.0 2.7 83.1 59.8 22.1 2.6 79.9
4 035 82.0 19.1 3.5 99.4 73.4 21.9 3.2 93.3 69.0 23.1 3.0 90.0 64.3 24.1 2.8 86.3
040 103.6 27.0 4.4 128.2 93.4 30.4 4.0 121.1 88.4 31.9 3.8 117.4 83.4 33.3 3.6 113.7
HL 050 172.5 39.7 7.4 208.7 154.4 45.9 6.6 196.2 145.1 48.6 6.2 189.3 135.6 50.9 5.8 181.9
060 221.4 58.7 9.5 274.9 199.4 66.6 8.6 260.0 188.6 70.0 8.1 252.3 177.7 73.2 7.6 244.3
018 46.2 9.7 2.0 55.0 41.8 11.7 1.8 52.5 39.5 12.7 1.7 51.1 37.3 13.6 1.6 49.7
025 59.9 12.9 2.6 71.6 53.1 15.1 2.3 66.8 49.6 16.0 2.1 64.1 45.9 16.8 2.0 61.2
HWA 028 79.8 17.2 3.4 95.4 70.9 20.0 3.0 89.1 66.5 21.3 2.9 85.8 62.2 22.4 2.7 82.6
5 035 85.1 19.2 3.7 102.6 76.3 22.2 3.3 96.5 71.8 23.4 3.1 93.1 67.2 24.5 2.9 89.6
040 107.6 27.3 4.6 132.4 97.1 30.8 4.2 125.2 91.9 32.4 3.9 121.4 86.7 33.9 3.7 117.6
HL 050 179.3 39.9 7.7 215.6 160.7 46.4 6.9 203.0 151.2 49.3 6.5 196.0 141.5 51.8 6.1 188.6
060 229.8 59.3 9.9 283.8 207.2 67.5 8.9 268.7 196.0 71.1 8.4 260.8 184.9 74.4 7.9 252.6
018 47.7 9.7 2.1 56.6 43.2 11.8 1.9 54.0 41.0 12.8 1.8 52.7 38.7 13.8 1.7 51.2
025 62.3 13.0 2.7 74.1 55.2 15.2 2.4 69.1 51.6 16.2 2.2 66.4 47.9 17.1 2.1 63.5
HWA 028 82.7 17.3 3.6 98.4 73.5 20.2 3.2 91.9 69.0 21.5 3.0 88.6 64.6 22.7 2.8 85.3
6 035 88.2 19.3 3.8 105.8 79.2 22.4 3.4 99.6 74.6 23.7 3.2 96.2 70.1 25.0 3.0 92.8
040 111.6 27.5 4.8 136.7 100.9 31.3 4.3 129.3 95.5 32.9 4.1 125.5 90.2 34.5 3.9 121.6
HL 050 186.1 40.1 8.0 222.6 167.2 46.9 7.2 209.9 157.5 49.9 6.8 202.9 147.6 52.6 6.3 195.4
060 238.4 59.8 10.2 292.8 215.2 68.4 9.3 277.5 203.7 72.2 8.8 269.4 192.3 75.7 8.3 261.1
018 49.4 9.8 2.1 58.2 44.7 11.9 1.9 55.5 42.4 13.0 1.8 54.2 40.1 13.9 1.7 52.8
025 64.4 13.0 2.8 76.3 57.3 15.4 2.5 71.3 53.7 16.4 2.3 68.6 49.9 17.4 2.1 65.7
HWA 028 85.6 17.3 3.7 101.3 76.2 20.4 3.3 94.8 71.6 21.8 3.1 91.4 67.0 23.1 2.9 88.0
7 035 91.4 19.4 3.9 109.1 82.3 22.7 3.5 102.9 77.6 24.1 3.3 99.5 72.8 25.3 3.1 95.8
040 115.8 27.8 5.0 141.0 104.7 31.7 4.5 133.6 99.3 33.4 4.3 129.7 93.8 35.0 4.0 125.7
HL 050 193.2 40.3 8.3 229.8 173.9 47.4 7.5 217.0 163.9 50.6 7.0 209.9 153.8 53.4 6.6 202.4
060 247.2 60.3 10.6 302.1 223.4 69.2 9.6 286.4 211.6 73.2 9.1 278.2 199.8 76.9 8.6 269.8
018 51.0 9.8 2.2 59.9 46.3 12.0 2.0 57.3 43.9 13.1 1.9 55.8 41.5 14.1 1.8 54.4
025 66.7 13.1 2.9 78.6 59.5 15.5 2.6 73.6 55.8 16.6 2.4 70.9 51.9 17.6 2.2 68.0
HWA 028 88.5 17.4 3.8 104.4 78.9 20.6 3.4 97.7 74.1 22.0 3.2 94.1 69.6 23.4 3.0 90.8
8 035 94.6 19.5 4.1 112.4 85.3 22.9 3.7 106.2 80.5 24.4 3.5 102.7 75.7 25.7 3.3 99.0
040 120.0 28.0 5.2 145.5 108.7 32.1 4.7 137.9 103.1 33.9 4.4 134.0 97.5 35.6 4.2 129.9
HL 050 200.4 40.4 8.6 237.1 180.6 47.9 7.8 224.2 170.5 51.2 7.3 217.1 160.1 54.2 6.9 209.5
060 256.2 60.7 11.0 311.5 231.8 70.1 10.0 295.6 219.7 74.2 9.5 287.2 207.6 78.1 8.9 278.6
018 52.7 9.8 2.3 61.6 47.9 12.1 2.1 58.9 45.4 13.2 2.0 57.4 43.0 14.3 1.9 56.0
025 69.0 13.1 3.0 81.0 61.7 15.6 2.7 75.9 57.9 16.8 2.5 73.2 54.0 17.8 2.3 70.3
HWA 028 91.6 17.5 3.9 107.5 81.7 20.8 3.5 100.7 77.0 22.3 3.3 97.3 72.1 23.7 3.1 93.7
9 035 97.9 19.6 4.2 115.8 88.5 23.1 3.8 109.5 83.6 24.6 3.6 106.0 78.6 26.1 3.4 102.3
040 124.3 28.2 5.4 150.0 112.8 32.5 4.9 142.3 107.0 34.4 4.6 138.3 101.2 36.2 4.4 134.1
HL 050 207.7 40.5 8.9 244.6 187.6 48.3 8.1 231.5 177.2 51.7 7.6 224.3 166.7 54.9 7.2 216.6
060 265.5 61.1 11.4 321.1 240.4 70.9 10.4 304.9 228.0 75.2 9.8 296.4 215.5 79.3 9.3 287.6
018 54.4 9.8 2.3 63.3 49.5 12.2 2.1 60.6 47.1 13.3 2.0 59.2 44.5 14.4 1.9 57.6
025 71.4 13.1 3.1 83.4 64.0 15.7 2.8 78.3 60.1 16.9 2.6 75.5 56.2 18.0 2.4 72.6
HWA 028 94.7 17.5 4.1 110.6 84.6 20.9 3.6 103.7 79.7 22.5 3.4 100.2 74.7 23.9 3.2 96.5
10 035 101.3 19.7 4.4 119.2 91.7 23.3 3.9 112.9 86.7 24.9 3.7 109.4 81.6 26.4 3.5 105.7
040 128.8 28.4 5.5 154.6 116.9 32.9 5.0 146.8 111.0 34.9 4.8 142.7 105.1 36.7 4.5 138.5
HL 50 215.2 40.5 9.3 252.1 194.7 48.6 8.4 239.0 184.1 52.3 7.9 231.7 173.3 55.6 7.5 224.0
60 274.9 61.5 11.8 330.9 249.2 71.6 10.7 314.4 236.4 76.2 10.2 305.8 223.6 80.4 9.6 296.8
018 59.8 9.8 2.6 68.7 54.5 12.4 2.4 65.8 51.9 13.6 2.2 64.2 49.2 14.8 2.1 62.6
025 78.8 13.2 3.4 90.8 71.0 16.0 3.1 85.6 67.0 17.4 2.9 82.8 62.8 18.6 2.7 79.8
HWA 028 104.4 17.6 4.5 120.4 93.6 21.4 4.0 113.1 88.3 23.1 3.8 109.4 83.1 24.7 3.6 105.6
13 035 111.8 19.8 4.8 129.8 101.7 23.8 4.4 123.4 96.4 25.7 4.2 119.8 91.1 27.4 3.9 116.0
040 142.7 28.9 6.2 169.0 129.9 33.9 5.6 160.8 123.5 36.2 5.3 156.5 117.2 38.3 5.1 152.0
HL 050 238.8 40.5 10.3 275.7 217.0 49.5 9.4 262.1 205.8 53.7 8.9 254.6 194.3 57.5 8.4 246.6
060 304.6 62.2 13.1 361.3 276.9 73.7 11.9 344.0 263.1 78.8 11.3 334.9 249.3 83.7 10.7 325.4
018 65.5 9.7 2.8 74.3 59.9 12.5 2.6 71.2 57.0 13.8 2.5 69.6 54.2 15.1 2.3 67.9
025 86.6 13.1 3.7 98.5 78.4 16.3 3.4 93.2 74.2 17.7 3.2 90.3 69.9 19.1 3.0 87.3
HWA 028 114.7 17.6 4.9 130.7 103.2 21.7 4.5 123.0 97.5 23.6 4.2 119.1 91.9 25.5 4.0 115.1
16 035 123.0 19.7 5.3 140.9 112.3 24.2 4.8 134.3 106.8 26.3 4.6 130.7 101.1 28.2 4.4 126.7
040 157.5 29.1 6.8 184.1 143.8 34.7 6.2 175.5 137.0 37.3 5.9 170.9 130.1 39.7 5.6 166.2
HL 050 259.5 40.1 11.2 296.1 234.5 50.0 10.1 280.0 221.2 54.4 9.5 270.8 207.8 58.5 9.0 261.1
060 336.3 62.6 14.5 393.2 304.5 75.2 13.1 373.0 288.6 80.9 12.5 362.3 272.8 86.2 11.8 351.2
LEGEND NOTE: Performance based on 9.4 C subcooling.
Cap — Capacity, kW
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)
THR — Total Heat of Rejection, kW

40
Electrical data — 30HWB,HWC,HWS,HK
fluid-cooled units
UNIT COMPRESSOR (ea)
UNIT SIZE Volts Voltage* ICF LRA
30- Rec
Nameplate MCA MOCP RLA
Hz Min Max PW XL Fuse PW XL
(3 ph)
208/230 60 187 253 62 — 266 110 80 49 — 266
380 60 342 418 35 — 145 60 45 28 — 145
HWB,C,S018 460 60 414 508 28 — 120 50 35 23 — 120
575 60 518 632 24 — 96 40 30 19 — 96
380/415 50 342 440 34 — 115 60 45 27 — 115
208/230 60 187 253 72 170 283 125 90 57 170 283
380 60 342 418 43 85 142 70 60 34 85 142
HWB,C,S025 460 60 414 508 34 85 142 60 45 27 85 142
575 60 518 632 28 59 98 45 35 22 59 98
380/415 50 342 440 38 104 173 60 45 30 104 173
208/230 60 187 253 89 268 446 150 110 71 268 446
380 60 342 418 54 134 223 90 70 43 134 223
HWB,C,S028 460 60 414 508 44 134 223 70 60 35 134 223
575 60 518 632 35 98 164 60 45 28 98 164
380/415 50 342 440 54 134 223 90 70 43 134 223
208/230 60 187 253 102 268 446 175 125 81 268 446
380 60 342 418 59 134 223 100 80 47 134 223
HWB,C,S035 460 60 414 508 48 134 223 80 60 38 134 223
575 60 518 632 39 98 164 60 50 31 98 164
380/415 50 342 440 54 152 253 90 70 43 152 253
208/230 60 187 253 145 414 690 250 175 116 414 690
380 60 342 418 84 207 345 150 110 67 207 345
HWB,C,S040 460 60 414 508 69 207 345 110 90 55 207 345
575 60 518 632 55 165 276 90 70 44 165 276
380/415 50 342 440 78 207 345 125 100 62 207 345
208/230 60 187 253 129 † 340 175 150 57 † 283
460 60 414 518 59 † 168 80 70 26 † 142
HK040 575 60 518 632 54 † 122 70 60 24 † 98
400 50 342 440 71 † 249 100 90 36/26** † 223/142**
208/230 60 187 253 161 † 503 225 200 83/57** † 446/283**
460 60 414 518 75 † 249 110 90 39/26** † 223/142**
HK050 575 60 518 632 73 † 188 110 90 39/24** † 164/ 98**
400 50 342 440 81 † 259 110 100 36 † 223
208/230 60 187 253 187 † 529 250 225 83 † 446
460 60 414 518 88 † 262 125 100 39 † 223
HK060 575 60 518 632 88 † 203 125 100 39 † 164
400 50 342 440 131 † 403 175 150 58 † 345
(See Legend and Notes on page 43.)

41
Electrical data —
30HWA and HL condenserless units
UNIT COMPRESSOR (ea)
UNIT SIZE Volts Voltage* ICF LRA
30- Rec
Nameplate MCA MOCP RLA
Hz Min Max PW XL Fuse PW XL
(3 ph)
208/230 60 187 253 72 — 266 125 90 57 — 266
380 60 342 418 40 — 145 70 50 32 — 145
HWA018 460 60 414 508 34 — 120 60 45 27 — 120
575 60 518 632 28 — 96 45 35 22 — 96
380/415 50 342 440 34 — 115 60 45 27 — 115
208/230 60 187 253 79 207 345 125 100 63 207 345
380 60 342 418 47 104 173 80 60 37 104 173
HWA025 460 60 414 508 38 104 173 60 45 30 104 173
575 60 518 632 30 72 120 50 40 24 72 120
380/415 50 342 440 38 104 173 60 45 30 104 173
208/230 60 187 253 107 268 446 175 150 85 268 446
380 60 342 418 60 134 223 100 80 48 134 223
HWA028 460 60 414 508 54 134 223 90 70 43 134 223
575 60 518 632 42 98 164 70 50 33 98 164
380/415 50 342 440 54 134 223 90 70 43 134 223
208/230 60 187 253 119 304 506 200 150 95 304 506
380 60 342 418 67 152 253 110 80 53 152 253
HWA035 460 60 414 508 54 152 253 90 70 43 152 253
575 60 518 632 44 106 176 70 60 35 106 176
380/415 50 342 440 54 152 253 90 70 43 152 253
208/230 60 187 253 167 414 690 300 200 133 414 690
380 60 342 418 95 207 345 150 125 76 207 345
HWA040 460 60 414 508 78 207 345 125 100 62 207 345
575 60 518 632 63 165 276 110 80 50 165 276
380/415 50 342 440 78 207 345 125 100 62 207 345
208/230 60 187 253 190 † 571 250 225 100/65** † 506/345**
460 60 414 508 84 † 282 125 100 44/29** † 253/173**
HL050 575 60 518 632 75 † 203 110 90 38/27** † 176/120**
400 50 342 440 99 † 297 125 110 44 † 253
208/230 60 187 253 225 † 606 300 250 100 † 506
460 60 414 508 99 † 297 125 110 44 † 253
HL060 575 60 518 632 86 † 214 110 100 38 † 176
400 50 342 440 138 † 406 175 175 61 † 345
(See Legend and Notes on page 43.)

42
Electrical data (cont)
LEGEND FOR ELECTRICAL DATA
ICF — Maximum instantaneous current flow during starting. NEC — National Electrical Code (U.S.A.)
For single-compressor units, ICF is the compressor PW — Part wind
LRA. Rec Fuse — Recommended dual element fuse amps (150\ of
kcmil — Thousand circular mils compressor RLA). Size up to the next standard fuse
LRA — Locked rotor amps. First value is for part-wind start. size.
Larger value is the full LRA. RLA — Rated load amps
MCA — Minimum circuit amps (for wire sizing). Complies XL — Across the line
with NEC, Section 430-24. *Supply Range — Units are suitable for use on electrical systems
MFA — Maximum fuse amps (225% of compressor RLA).
Size down to the next standard fuse size. where voltage supplied to the unit terminals is not below or above the
listed range limits.
MOCP — Maximum Overcurrent Protection †Contact your local Carrier representative for part-wind details.
**Compressor no. 1/compressor no. 2.

NOTES FOR ELECTRICAL DATA


1. All units have one field power terminal block. 7. Across-the-line start is standard on all units. Part-wind start is
2. Maximum incoming wire size: available as a factory-installed option on 30HW025-040 sizes (not
a. 350 kcmil for unit sizes 040-060; 208/230-3-60 and 230-3-50 available on 30HW018 size).
voltages.
b. 2/0 for all other unit sizes; all voltages.
3. Additional control circuit power is not required.
4. Any field modification of factory wiring must be in compliance with
all applicable codes. Field-installed power wires must be rated
75 C minimum.
5. Use copper, copper-clad aluminum, or aluminum conductors for
field wiring.
6. Control circuit power supply is 115-v single phase for 50- and (30HWA,B,C and 30HK,HL
60-Hz units. Control power is supplied by the factory-installed 60 Hz Only)
control transformer.

43
Control sequence
The controls consist of 115-v and 24-v control circuits. Off cycle
The 24-v circuit provides control power for the During an off cycle, the crankcase heater remains ener-
ComfortLink™ microprocessor control, all safeties, the gized. However, the heater will remain on during safety trip
compressor unloaders, interlock relays, and the accessory conditions.
ground current sensor. The 115-v circuit powers the com-
pressor contactor(s), crankcase heater(s), and the time- Start-up
delay relay for the optional part-wind start contactor (if When the unit Enable/Off/Remote switch is set to the
installed). ENABLE position, the 24-v control circuit will be ener-
gized. When there is a call for cooling and all safety devices
Microprocessor are satisfied, the compressor will start unloaded after a
The ComfortLink microprocessor controls overall unit delay of 2 to 5 seconds. The low pressure and oil pressure
operation. Its central executive routine controls a number safety switches (if so equipped) will be bypassed, and the
of processes simultaneously. These include internal timers, compressor unloaders will remain energized during a
reading inputs, analog to digital conversions, fan control, 2-minute time delay after the compressor has been started.
display control, diagnostic control, output relay control,
demand limit, capacity control, head pressure control, and Capacity control
temperature reset. Some processes are updated almost The 30HW018 and 028-040 units have 3 standard stages
continuously, others every 2 to 3 seconds, and some every of capacity control, the 30HW025 units have 2 standard
30 seconds. stages of capacity control, and the 30HK,HL units have 4
The microprocessor routine is started by switching the standard stages of capacity control. The standard capacity
Emergency ON-OFF switch (switch 2) to ON position. staging is provided by electrically actuated suction cut-off
unloaders. One additional stage of capacity control can be
Standard Quickset display (standard on 50 Hz provided by the optional hot gas bypass.
unit) When the leaving fluid temperature rises above the set
Standard control includes a simple single set point dial and point, the control will begin to add stages of capacity by
an alarm light. starting a compressor. The control uses a leaving-water
temperature control with entering water compensation
routine and will add additional stages of capacity as
required to meet the required load. If the unit is equipped
20° 30° with hot gas bypass, the hot gas bypass solenoid and com-
0° 40°
pressor unloader for the circuit will be energized as the first
-10°
-20°
-0° stage of capacity. When the leaving-fluid temperature
50°
-10° starts falling below the set point, the control will remove
-20° -30°
F C 20°
stages of capacity to match the degrease in building load.
70°
Automatic lead/lag control (30HK,HL)
ALARM STATUS SETPOINT This standard feature will automatically switch compressor
no. 1 from being energized by stage 1 of the temperature
controller to being energized by stage 2 of the temperature
controller (or vice versa depending on current stage). The
switch takes place each time stage 1 is satisfied.
Scrolling Marquee Display (standard on 60 Hz
unit; factory-installed option on 50 Hz unit) Safeties
An optional four-digit alphanumeric display shows all of Loss of charge — This safety will lock out the compres-
the ComfortLink control codes (with expandable clear lan- sor if the refrigerant pressure falls below the minimum per-
guage), plus set points, time of day, and temperatures. mittable level. See base unit installation instructions for
low-pressure switch settings.
High-pressure cutout — This protection will lock out
the compressor if the compressor discharge pressure rises
MODE above the cutout setting. See base unit installation instruc-
Run Status
Service Test
tions for pressure settings.
Temperature
Pressures Compressor circuit breakers — These circuit breakers
Setpoints
Inputs Alarm Status
protect against compressor overload, locked rotor condi-
Outputs tions, and primary power single phasing.
Configuration
ESCAPE ENTER
Time Clock Sensor failure protection — This feature recognizes if
Operating Modes
Alarms the leaving fluid sensor is not functioning correctly and will
lock out the unit.

44
Freeze protection Factory-installed optional controls
This safety feature is provided by monitoring of the leaving Hot gas bypass (30HW) — The hot gas bypass will pro-
fluid temperature and from the low-pressure switch. If the vide an additional stage of capacity control for operation
leaving chilled-fluid temperature falls to approximately 6 F down to 10% of full load capacity. The hot gas solenoid is
(3.3 C) below the leaving fluid set point, the compressor energized when the compressor is started.
will rapidly unload and shut off. NOTE: This is available as a field-installed accessory on
Loss-of-flow protection — Loss-of-flow protection is 30HK,HL units.
provided by monitoring the required accessory proof-of- Part-wind start (30HW025-040) — A one-second,
flow switch. time-delay relay will allow the full motor windings to ener-
Ground current safety — This sensor opens when a gize after the partial windings have started the compressor.
current-to-ground condition greater than 2.5 ± 2 amps is This reduces the instantaneous current flow during com-
sensed in the compressor windings (accessory ground cur- pressor start-up.
rent sensor required). NOTE: This is available as a special-order item on
Diagnostics (with optional display) 30HK,HL units.
Microprocessor may be put through service test (see Con- Capacity Control Steps
trols, Start-Up, Operation, Service and Troubleshooting lit- Refer to the Capacity Control Steps tables below for
erature) without additional equipment or tools. Service test capacity control steps for standard units.
confirms microprocessor is functional, informs observer
NOTE: If the optional factory-installed hot gas bypass is
through display the condition of each sensor and switch in
chiller, and allows observer to check for proper operation used, there will be one more stage of unloading added and
the units will be able to operate down to 10% of full load
of control and compressor(s).
capacity.
Default settings
To facilitate quick start-ups, all chillers with ComfortLink™
controls are pre-configured with a default setting that CAPACITY CONTROL STEPS — 30HW
assumes stand-alone operation supplying 44 F (6.7 C) UNIT CONTROL PERCENT OPERATING
chilled water. 30HW STEPS DISPLACEMENT CYLINDERS
Configuration setting will be based on any options or 1 33 2
018 2 67 4
accessories included with the unit at the time of manufac-
3 100 6
turing. Date and time are set to U.S.A. central time zone 1 50 2
and will need reconfiguring based on location and local 025
2 100 4
time zone. If operation based on occupancy scheduling is 1 33 2
desired, this will also need to be set during installation. 028 2 67 4
3 100 6
Remote alarm 1 33 2
A 24-v alarm signal will be provided to a remote location in 035 2 67 4
the event of a lockout condition. 3 100 6
1 33 2
Demand limit switch 040 2 67 4
Demand limiting can be accomplished through switch 3 100 6
input or by a field-supplied 4 to 20 mA signal. For either
case, the Energy Management Module option (also avail-
able as an accessory) is required. The field supplied, nor-
mally open contacts (single or pair) can be used to reduce
the total chiller electrical demand during times of peak
usage. This is accomplished by reducing the number of
capacity stages. In a similar manner, a field-supplied 4 to
20 mA signal can also be used to reduce the total capacity
of the chillers.

45
Control sequence (cont)
CAPACITY CONTROL STEPS — 30HK,HL
SEQUENCE A SEQUENCE B
UNIT CONTROL
30 STEPS Operating Cylinders Operating Cylinders
% Disp. % Disp.
Total Ckt 1 Ckt 2 Total Ckt 1 Ckt 2
1 25 2 2 — 25 2 — 2
HK040 2 50 4 2 2 50 4 2 2
3 75 6 4 2 75 6 2 4
4 100 8 4 4 100 8 4 4
1 40 4 4 — 20 2 — 2
HK,HL050 2 60 6 4 2 60 6 4 2
3 80 8 6 2 80 8 4 4
4 100 10 6 4 100 10 6 4
1 33 4 4 — 33 4 — 4
HK,HL060 2 66 8 4 4 66 8 4 4
3 88 10 6 4 88 10 4 6
4 100 12 6 6 100 12 6 6
LEGEND NOTES:
Disp. — Displacement 1. All compressors are designated from left to right when viewed
from front of unit. Circuits are also designated from left to right.
2. If accessory hot gas bypass is installed, the hot gas bypass valve
will be opened (energized) only on control step no. 1.

46
Typical piping (fluid-cooled 30HWB shown)

NOTES:
1. Chiller must be installed levelly to maintain proper compressor oil return.
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installa-
tion. Wiring and piping shown are for a quick overview of system and are not in accordance with recognized
standards.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE
(American Society of Heating, Refrigeration, and Air Conditioning Engineers) handbook for details.
5. See Application Data section on page 16 for minimum system fluid volume. This system may require the addition of
a holding tank to ensure adequate volume.

47
Typical piping (air-cooled 30HWA with remote
09DK unit shown)
NOTES:
1. Chiller must be installed levelly to maintain proper com-
pressor oil return.
2. Wiring and piping shown are general points-of-connection
guides only and are not intended for a specific installation.
Wiring and piping shown are for a quick overview of sys-
tem and are not in accordance with recognized standards.
3. All wiring must comply with applicable local and national
codes.
4. All piping must follow standard piping techniques. Refer to
Carrier System Design Manual part 3, Carrier E20-II®
software Refrigerant Piping program, or appropriate
ASHRAE (American Society of Heating, Refrigeration,
and Air Conditioning Engineers) handbook for details on
proper piping sizes and design.
5. See Application Data section on page 16 for minimum
system fluid volume. This system may require the addition
of a holding tank to ensure adequate volume.
6. Hot gas lines should rise above refrigerant level in con-
denser circuit. Double riser may be required; check com-
pressor minimum capacity.
7. Trap should be installed on hot gas lines to prevent con-
denser oil and refrigerant vapor migration from accumulat-
ing on compressor heads during off cycle.
8. Pitch all horizontal lines downward in the direction of
refrigerant flow.
9. For piping lengths greater than 50 ft, provide support to
liquid and gas lines near the connections to the condenser
coil.
10. For pressure relief requirements, see latest revision of
ASHRAE Standard 15, Safety Code for Mechanical
Refrigeration.

48
Guide specifications
Water-Cooled and Condenserless discharge shutoff valves, oil sight glass, and a
Reciprocating Chillers refrigerant suction gas-cooled motor.
3. Each shall be mounted on spring vibration isola-
HVAC Guide Specifications tors with an isolation efficiency of no less than
Size Range: 15 to 60 Tons (53 to 210 kW) 95%.
Carrier Model Number: 30HW018-040 4. Each compressor shall have a crankcase heater,
30HK040-060 muffler, and suction cutoff unloaders.
30HL050,060
5. Speed not to exceed 1750 rpm (29.2 r/s) for
Part 1 — General 60 Hz units, and 1450 rpm (24.2 r/s) for
1.01 SYSTEM DESCRIPTION 50 Hz units.
Microprocessor controlled water-cooled (HWB,HWC, 6. Shall be same manufacturer as chiller.
HWS,HK) or condenserless (HWA,HL) liquid chiller D. Cooler:
utilizing serviceable, semi-hermetic type compressor.
1. 30HW: Single-pass ANSI type 316, stainless-
1.02 QUALITY ASSURANCE steel, brazed-plate construction.
A. The 30HWB,HWC,HK 60-Hz unit performance shall 30HK,HL: Single-pass, shell-and-tube type with
be rated per ARI (U.S.A.) Standard 550/590-98 at removeable heads and multiple internal
standard rating conditions. All other unit performance polypropylene baffles. Seamless copper tubes
shall be based on ARI Standard 550/590-98. shall be rolled into tube sheets.
B. Unit construction shall comply with ANSI/ASHRAE 2. Direct expansion refrigerant circuit.
15, latest revision Safety Standard, NEC, and appli-
3. Equipped with grooved-end-type fluid connec-
cable ASME codes (U.S.A. codes).
tions at least 8 in. (203 mm) above floor level.
C. Unit shall be certified in accordance with ISO 9002
manufacturing quality standard. 4. Insulated with 3/4-in. (19 mm) closed cell foam
or equivalent.
D. Unit shall be UL listed and UL, Canada certified
5. Cooler shall be tested and stamped according to
(30HWA,HWB,HWC,HK 60-Hz units only) (U.S.A.
standards). ASME code (U.S.A.) for working pressures of
430 psig (2965 kPa) on the refrigerant side for
1.03 DELIVERY, STORAGE AND HANDLING 30HW units and 235 psig (1620 kPa) for
Unit shall be shipped factory-assembled with all pip- 30HK,HL units. Cooler shall have a maximum
ing and wiring, precharged with a complete operat- of 300 psig (2069 kPa) fluid-side working pres-
ing charge (30HWB,HWC,HWS,HK) or a holding sure for 30HW units and 150 psig (1034 kPa)
charge (30HWA,HL) of R-22 and shall be stored for 30HK,HL units.
and handled according to manufacturer’s E. Condenser (30HWC,30HK):
recommendations.
1. Water-cooled shell-and-tube type with seamless,
Part 2 — Products integrally-finned copper tubes and removable
2.01 EQUIPMENT heads (2 condensers on 30HK units).
A. General: 2. Design and construction shall provide positive
Single-piece liquid chiller consisting of compres- subcooling of liquid refrigerant.
sor(s), direct expansion cooler, condenser(s) 3. Each unit shall be equipped with a pressure
(30HWB,HWC,HWS,HK), controls, safeties, and relief device, purge cock, and liquid line shutoff
any hardware required before start-up. valve.
B. Unit Cabinet: 4. Condenser shall be tested and stamped in
1. Frame shall be of heavy-gage galvanized steel accordance with ASME code for refrigerant-
with an electrostatically applied baked enamel side working pressure of 365 psig (2517 kPa)
finish. for 30HWC units and 385 psig (2655 kPa) for
30HK units. Condenser shall have a maximum
2. The 30HW units shall pass through a standard
water-side working pressure of 300 psig
30-in. (762 mm) door and shall not exceed (2069 kPa) for 30HWC units and 250 psig
36 in. (914 mm) in length (30HWA,B). The
(1724 kPa) for 30HK units.
30HK,HL units shall not exceed 36 in.
(762 mm) in width. F. Condenser (30HWB):
C. Compressor: 1. Single-pass, water-cooled, ANSI type 316,
stainless-steel brazed-plate construction that
1. Reciprocating, serviceable, semi-hermetic type
shall provide positive subcooling of liquid
only. refrigerant.
2. Equipped with an automatically reversible oil
pump, operating oil charge, suction and

49
Guide specifications (cont)
2. Condensers shall be tested and stamped per 2) Pumpout at beginning and end of every
ASME code for working pressures of 430 psig circuit cycle.
(2965 kPa) on the refrigerant side. Condenser 3) Capacity control based on leaving chilled
shall have a maximum of 300 psig (2069 kPa) fluid temperature and compensated by
water-side working pressure. rate of change of return-fluid temperature.
3. Equipped with grooved-end-type water connec- 4) Limiting of the chilled fluid temperature
tions at least 25 in. (635 mm) above floor level. pulldown rate at start-up to 1° F (.56° C)
per minute to prevent excessive demand
4. Each condenser has a liquid line shutoff valve.
spikes (charges) at start-up.
G. Condenser (30HWS): 2. Safeties:
1. Water-cooled shell-and-tube type with seamless,
a. Unit shall be equipped with sensors and all
integrally-finned 90/10 cupro-nickel tubes and
necessary components in conjunction with
tube sheets with removable heads and zinc the control system to provide the unit with
anodes.
the following protections:
2. Design and construction shall provide positive
1) Loss of refrigerant charge protection.
subcooling of liquid refrigerant. 2) Low fluid flow detection.
3. Each unit shall be equipped with a pressure 3) Low chilled fluid temperature protection.
relief device, purge cock, and liquid line shutoff 4) Low control voltage (to unit) protection.
valve. 5) High-pressure switch.
4. Condenser shall be tested and stamped in b. Compressors shall be equipped with the fol-
accordance with ASME code for refrigerant- lowing manual-reset type protections:
side working pressure of 365 psig (2517 kPa).
1) Pressure overload.
Condenser shall have a maximum water-side 2) Electrical overload through the use of
working pressure of 300 psig (2069 kPa).
definite-purpose contactors and cali-
5. Heads shall include replaceable zinc anodes for brated, ambient compensated, mag-
condenser corrosion protection. netic trip circuit breakers. Circuit
H. Refrigerant Components: breakers shall open all 3 phases in the
Each chiller shall contain the following: high side event of an overload in any one phase
pressure relief device; liquid, suction, and discharge (single-phasing condition).
shutoff valves; sight glass; filter drier; thermostatic J. Operating Characteristics:
expansion valve; and charging valve. 1. Unit shall be capable of starting with up to 95 F
→ I. Controls and Safeties: (35 C) fluid temperature entering the cooler.
1. Controls: 2. Unit shall be capable of operating with variable
a. Unit controls shall include the following min- cooler fluid flow.
imum components: K. Electrical Requirements:
1) Microprocessor. 1. Single-point electrical power connection with
2) Power and control circuit terminal terminal block. Shall include power for control
blocks. circuit.
3) ON/OFF control switch. 2. Control points shall be accessed through termi-
4) Single set point dial (50 Hz unit) or nal block.
Scrolling Marquee Display (60 Hz unit). L. Special Features:
NOTE: Scrolling Marquee Display shall
1. Oil Safety Switch (standard on HWA,HL, and
be available as a factory-installed option
brine units, field-installed accessory on
for 50 Hz unit. HWB,HWC,HWS,HK standard units):
5) Thermistor installed to measure satu-
This switch senses differential oil pressure and
rated condensing temperature, cooler
prevents unit operation at low oil pressures.
saturation temperature, compressor
return gas temperature, and cooler 2. Hot Gas Bypass:
entering and leaving fluid temperatures. This factory-installed option (30HW) or field-
6) Terminal block for temporary and/or installed accessory (30HK,HL) shall permit
permanent interface to the Carrier chiller unloading capacity down to 10% of max-
Comfort Network or similar building sys- imum loaded capacity.
tem control. 3. Pressure Gage Panel:
b. Unit controls shall be capable of performing This field-installed accessory shall include both
the following functions: suction and discharge pressure gages with shut-
1) Automatic circuit lead/lag (30HK,HL off valves.
only).

50 403
4. Sound Enclosure Panels: 13. Condenser Manifold Package (HK only):
This acoustic package shall be either factory This field-installed accessory shall provide com-
(30HW units only) or field installed and shall mon fluid inlet and outlet connections.
entirely enclose the compressor section to → 14. Scrolling Marquee Display (standard on 60 Hz
reduce radiated sound by approximately 5 dBA. unit; available as a factory-installed option for
5. Mobility Package (30HW units only): 50 Hz unit):
This package shall be either factory (30HWA,B a. Single leaving water temperature set point
only) or field installed and shall include 4 swivel potentiometer.
wheels for easy unit mobility. b. The diagnostic display module shall be capa-
NOTE: The 30HWC,S units require 2 packages. ble of indicating the safety lockout condition
6. Vibration Isolators (30HW units only): by displaying a code for which an explana-
tion may be scrolled at the display. Informa-
Vibration isolators shall be field installed before tion included for display shall be:
the unit is set into its final location and shall
reduce vibration transmission through the 1) Compressor lockout.
mounting area of the chiller. 2) Loss of charge.
3) Low fluid flow.
7. Multi-Chiller Control: 4) Low oil pressure.
The multi-chiller control shall be field installed, 5) Cooler freeze protection.
and shall sequence up to 8 chillers in parallel. 6) Thermistor malfunction.
8. Proof-of-Flow Switch: 7) Entering and leaving-fluid temperature.
This field-installed accessory shall sense fluid 8) All set points.
pressure differential across the chiller, and shall 9) Time of day.
be compatible with the multi-chiller control c. Display module, in conjunction with the
accessory. microprocessor, must also be capable of dis-
9. Compressor Ground Fault Sensor: playing the output (results) of a service test.
Service test shall verify operation of every
Ground-current sensing shall deenergize the switch, thermistor, fan, and compressor
compressor on sensing of a 2.5 ± 2 amps before chiller is started.
current imbalance from primary to ground to
prevent formation of acids from motor burnout. 15. Energy Management Module (EMM):
It shall be a field-installed accessory. EMM shall be capable of:
10. Part-Wind Start (option on 30HW025-040; a. Leaving temperature reset form space tem-
special order on HK040-060 and HL050,060): perature, outdoor temperature, or 4 to 20 mA
Part-wind start shall be factory installed to signal.
reduce compressor inrush current. b. Demand limit or load shed via field supplied
11. Non-Fused Disconnect (30HW units only): 4 to 20 mA signal or 2-step discrete contact
closure.
The non-fused disconnect shall be factory
installed and shall disconnect all power to the
unit (including control circuit power).
12. Medium Temperature Brine (30HW units only):
Special modifications shall be made at the fac-
tory to permit operation with leaving chilled
fluid temperatures between 15 to 39 F (–9.4 to
3.9 C).
NOTE: This is a special order for 30HK,HL
units.

403 51
Carrier Corporation • Syracuse, New York 13221 403 10-99
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 New Book 3 Pg 52 Catalog No. 523-057 Printed in U.S.A. PC 903 Form 30H-7PD
Tab 5c Tab RC1 Replaces: 30H-6PD

Vous aimerez peut-être aussi