W-FM 25 Gas butterfly Diffuser
combustion manager stepping motor
Diffuser
setting screw
Typical WG40
4
A hallmark of practical combustion technology
Coded plugs ensure correct electrical connection All components are easily accessible Simple commissioning and diagnosis (W-FM 25)
A safe investment in the future Digital combustion management for Outstanding service
The millionfold success of Weishaupt’s reliability and ease of use Weishaupt has an extensive sales and
reliable and economical compact Weishaupt is a pioneer in the field of sevice network worldwide. Customer
burners is the result of a relentless digital combustion management, which service is available around the clock.
focus on quality and the customer. The greatly simplifies operation and Optimal in-house training at Weishaupt
technology employed by the burners servicing of the burner, ensures ensures our service engineers are of
has been constantly developed and outstanding operational reliability, and – the highest calibre.
improved over decades. last but not least – offers an extremely
attractive price to performance ratio. Proven quality
The latest production methods and Furthermore, this intelligent technology All burners are tested by an
stringent quality checks of all products enables the burner to be integrated independent body and conform to the
ensure Weishaupt’s reputation for with complex automation systems. following standards and EU directives:
quality. You are making a safe
investment in the future. Valve proving as standard with the • Gas Appliance Directive
W-FM10 and W-FM25 combustion 2009/142/EC
Large capacity range managers • EN 676
The large capacity range of 12.5 to The low gas pressure switch is used to • Machinery Directive 2006/42/EC
550 kW makes the burners suitable for check the tightness of the gas valves, • Electromagnetic Compatability
the widest range of heat exchangers. thus providing valve proving without the Directive 2004/108/EC
need for any additional components or • Low Voltage Directive 2006/95/EC
Electronic ignition costs. • Boiler Efficiency Directive
The W-ZG 01 ignition unit used on all 92/42/EEC
Weishaupt W-Seires burners is Gas multifunction assembly
particularly energy efficient and The burner’s gas multifunction Optional conformity:
extremely reliable. assembly incorporates the following WG10 to WG40 ZM-version burners
components/functions: can also be equipped for compliance
• Servo-controlled gas pressure with:
governor for continual gas pressure
• 2 solenoid valves (Class A) • Pressure Equipment Directive
• Filter 97/23/EC
• Gas pressure switch
If the gas pressure falls too low, a low
gas pressure program is started. The
gas pressure switch also provides for
automatic valve proving.
5
Digital combustion management:
reliable and easy to use
The key points: • Suitable for hot-water plant, including
continuous operation (no controlled
• The utilisation of identical units for shutdown and restart every 24 hours)
both gas and oil burners simplifies
commissioning and reduces the • Suitable for air heaters, Group II and
number of spares required III steam boilers, and Group IV steam
boilers (with optional W-FM 25 PO)
• Non-interchangeable plug
connections ensure the correct • The integrated bus connection offers
electrical connection of all the following functions:
components
– Connection to a PC for display of
All Weishaupt W-series burners are • Electrical remote reset is possible the operational sequence and the
fitted as standard with a digital setting of function parameters
combustion manager, whose micro- • Safety ensured through the use of
processors control and monitor all of two microprocessors (reciprocal – Remote monitoring and diagnosis
the burner’s functions. Consequently, monitoring) via a self-dialling modem
Weishaupt burners are easy to use,
precise and reliable. • Vari-coloured LED lamp to indicate – Connection to modern building
burner operational stage and fault management systems
The digital combustion manager also conditions (WG10–WG20 versions
incorporates a bus connection. This LN and Z-LN) – Prepurge time can be set via PC
offers the possibility of interfacing
digitally with other PLCs and • LCD display with interrogation,
automation systems; enabling a servicing and parameter functions.
professional to monitor the operation of The burner can be set directly via the
the burner and diagnose any errors operating keys (WG10–WG40
remotely. version ZM-LN)
Valve proving l l l
6
The right mode of operation
for every heating need
Single and two-stage gas burners
With mechanical compound regulation and
integral gas valve proving
Sliding-two-stage and
modulating gas burners
With electronic compound regulation and
integral gas valve proving
Gas actuator
FG FG
PK PK
IZ IZ
On Off On Off
7
Trustworthy technology
Compact design Electronically controlled air damper
Just one look under the burner’s cover The electronically controlled air damper
is enough to convince anyone of its closes at burner shutdown to hinder the
quality. All the components are clearly cooling-down of the combustion
arranged, the electrical connections are chamber.
obvious and non-interchangeable. The
engineering is typical of Weishaupt and Maintenance position
it makes a good impression. A special bracket enables the burner to
be placed into a maintenance position,
Their compact design means WG providing easy access to the burner and
burners of all ratings can be easily mixing assembly.
installed by one person. Commissioning
costs are reduced to a minimum. Common platform
The common platform principle used
Low-NOx execution with all W-Series burners simplifies the
All WG burners are Low NOx execution provision and storage of spare parts.
as standard. A specially designed
mixing head produces an intensive Interrogation via laptop
internal flue gas recirculation, resulting A special software package and
in exemplary emission levels. connection cables are available for
interrogating the combustion manager.
Sound-attenuated air inlet Combustion optimisation and fault
The transverse fan is sound attenuated analysis can thus be carried out easily
on the suction side. The burners via a laptop computer.
therefore operate particularly quietly.
8
Recirculation reduces emissions Sound-attenuated air inlet
Servicing position for easy access to the fan wheel Electronically controlled air damper
9
Burners with variable speed drive:
economical and quiet
Variable speed drive (VSD) Functionality Benefits:
Whereas a burner motor is usually The Weishaupt W-FM 25 combustion
run at a constant speed, the speed of manager controls the speed of the fan • Energy savings reduce the payback
the motor on VSD-equipped WG30 by means of a frequency convertor, period of the investment
and WG40 burners is variable and varying it in reponse to changes in load
depends on the prevailing burner load. demand. • Reduction in burner noise emissions
The VSD is electronically controlled by
the digital combustion manager. The speed of the fan, which determines • Capacity range identical to that of
the combustion air volume, is monitored the standard, fixed-speed burners
VSD offers the advantages of both during burner operation. The volume of
reduced electrical consumption and a gas that is required for the speed of the • Good price/performance relationship
considerable reduction in noise levels fan/air volume at any given moment is
at partial load. regulated by the gas butterfly valve. • Optimised installation, setting, and
maintenance
The reduced noise levels are of
particular practical benefit. A 10 dB • High-precision, digital control
reduction in the sound level can be
achieved at 50 % burner load, which
equates to a halving of noise emissions.
10
M
FU
P
80
80 600
600
Sound pressure level [ dB(A) ]
5 60
560
SD
hV
70
70 400
4 00
D
10 dB(A) wit VS
th
wi
65 300
3 00
220
60
60
55 100
100
5
500 0
QF 0 5
500 100
100 1 50
150 200 250
250 3 00
300 kW 350 QF 0 5
500 100
100 150
1 50 200 2 50
250 3 00
300 kW 350
QF 0 10
10 20 3
300 4
400 5
500 6
600 70
70 8
800 9
900 % 100
100 QF 0 10
10 20 3
300 40
4 0 50
5 0 60
6 0 70
70 8
800 9
900 % 100
100
11
WG5 capacity and model overview
WG5 capacity graph WG5
Burner Low-pressure supply (flow pressure in mbar into shut-off valve)
mbar Burner type WG5.../1-A LN rating Supply pressure Supply pressure
Rating 12.5–50 kW kW ≤ 50 mbar > 50–300 mbar
W-MF 055 W-MF 055
1,5 Nom. diameter of gas ball valve
½” ½”
1,0
Nat. gas E, LHV = 37.26 MJ/Nm3 (10.35 kWh/Nm3), d = 0.606, Wi = 47.84 MJ/Nm3
0,5 25 12 14
30 11 14
35 11 13
0
40 12 15
45 14 17
-0,5 50 16 19
-1,0 Nat. gas LL, LHV = 31.79 MJ/Nm3 (8.83 kWh/Nm3), d = 0.641, Wi = 39.67 MJ/Nm3
kW 0 10 20 30 40 50 60 25 15 18
30 15 18
35 13 16
40 15 18
Combustion head open Combustion head closed
45 18 21
50 20 23
Burner type Version Operation Valve train Rating Weight CE-PIN Order No.
R/DN - W-MF kW kg
WG5
Natural gas
WG5N/1-A LN Single-stage + actuator ½” 055 12.5–50 kW 12.0 kg CE-0085 AU 0353 232 050 10
LPG
WG5F/1-A LN Single-stage + actuator ½” 055 12.5–50 kW 12.0 kg CE-0085 AU 0353 233 050 11
12
Special equipment WG5N/1-A WG5F/1-A
vers. LN vers. LN
Order No. Order No.
Solenoid valve for air pressure switch test for continuous-run fan or post-purge 240 003 63 240 003 63
Air inlet flange for duct connection, without air pressure switch 240 004 19 240 004 19
Air inlet flange for duct connection, with air pressure switch 240 004 11 240 004 11
Plugged cable for connection of an external solenoid valve 240 003 49 240 003 49
W-St 02/1 actuator for fully automatic air damper control – 240 003 21
ÜB50 high gas pressure switch with connection cable and plug, supplied loose 230 009 88 230 009 88
Motor contactor for boiler controls with fusing <10 A (without tank connection) 230 010 22 230 010 22
Additional FRS governor for gas supply pressures > 50 mbar, with TAE supplied loose 240 003 56 240 003 56
Additional FRS governor for gas supply pressures > 50 mbar, without TAE 240 003 57 240 003 57
13
WG10 capacity and model overview
WG10 capacity graph WG10
Burner Low-pressure supply (flow pressure in mbar into shut-off valve)
mbar Burner type WG10.../0-D ZM-LN
Combustion head WG 10/0-D rating WG10/0-D WG10/0-D WG10/1-D WG10/1-D
Rating 12.5–50 kW kW W-MF 055 W-MF 055 W-MF 507 W-MF 507
Supply press. Supply press. Supply press. Supply press.
1,5 ≤ 50 mbar > 50–300 mbar ≤ 300 mbar ≤ 300 mbar
Nom. diameter of gas ball valve
½” ½” ¾” 1”
1,0
Nat. gas E, LHV = 37.26 MJ/Nm3 (10.35 kWh/Nm3), d = 0.606, Wi = 47.84 MJ/Nm3
0,5 25 12 14 – –
40 12 15 10 10
50 16 19 10 10
0 60 – – 10 10
70 – – 10 10
80 – – 10 10
-0,5 90 – – 11 11
kW 0 10 20 30 40 50 60 100 – – 12 11
110 – – 13 12
Nat. gas LL, LHV = 31.79 MJ/Nm3 (8.83 kWh/Nm3), d = 0.641, Wi = 39.67 MJ/Nm3
WG10 capacity graph 25 15 18 – –
40 15 18 12 12
mbar Burner type WG10.../1-D LN 50 20 23 12 12
Combustion head WG 10-D 60 – – 12 12
Rating 40–110 kW 70 – – 12 12
3,0 80 – – 13 13
90 – – 14 14
2,5 100 – – 15 14
2,0 110 – – 16 15
1,5
LPG*, LHV = 93.20 MJ/Nm3 (25.89 kWh/Nm3), d = 1.555, Wi = 74.73 kWh/Nm3
1,0 25 11 14 – –
0,5 40 10 13 8 –
50 13 15 8 –
0
60 – – 9 –
-0,5 70 – – 9 –
-1,0 80 – – 10 –
kW 0 20 40 60 80 100 120 90 – – 11 –
100 – – 12 –
110 – – 12 –
* The LPG charts are based on propane, but may also be used for butane.
WG10 capacity graph
Capacity graphs certified in accordance with EN 676.
mbar Burner type WG10.../1-D Z-LN and ZM-LN
Combustion head WG 10-D Stated ratings are based on an installation at sea level.
Rating 25–110 kW
For installations at higher altitudes, a reduction in
3,0
capacity of 1 % per 100 m above sea level should be
2,5
taken into account.
2,0
1,5
Note:
1,0
Shaded areas of the valve train table do not meet TRGI ball
0,5
valve sizing requirements. For TRGI compliance use the non-
0
shaded area and note additional price of larger ball valve.
-0,5
-1,0 The combustion chamber pressure in mbar must be
kW 0 20 40 60 80 100 120
added to the minimum gas pressure determined from
the above chart. Minimum gas pressure should not be
less than 15 mbar.
14
Burner type Version Operation Valve train Rating CE-PIN Order No.
R/DN - W-MF kW
WG10
Natural gas
WG10N/0-D ZM-LN Sliding-two-stage or modulating ½” 055 12.5–50 CE-0085 AU 353 232 136 14
WG10N/1-D LN Single-stage with manual air damper control ¾” 507 40–110 CE-0085 BM 0481 232 110 24
WG10N/1-D Z-LN Single or two-stage ¾” 507 25–110 CE-0085 BM 0481 232 123 24
WG10N/1-D ZM-LN Sliding-two-stage or modulating ¾” 507 25–110 CE-0085 BM 0481 232 126 24
LPG
WG10F/0-D ZM-LN Sliding-two-stage or modulating ½” 055 12.5–50 CE-0085 AU 353 233 136 14
WG10F/1-D LN Single-stage with manual air damper control ¾” 507 40–110 CE-0085 BM 0481 233 110 24
WG10F/1-D Z-LN Single or two-stage ¾” 507 25–110 CE-0085 BM 0481 233 113 24
WG10F/1-D ZM-LN Sliding-two-stage or modulating ¾” 507 25–110 CE-0085 BM 0481 233 126 24
W-MF 507 with ball valve & TAE for TRGI 1” 230 010 92 230 010 92 230 010 92 230 010 92
Comb. head extension Natural gas by 100 mm 230 009 31 230 008 49 230 008 49 230 008 49
by 200 mm 230 009 32 230 008 50 230 008 50 230 008 50
by 300 mm 230 009 33 230 008 51 230 008 51 230 008 51
LPG by 100 mm 230 009 34 230 008 52 230 008 52 230 008 52
by 200 mm 230 009 35 230 008 53 230 008 53 230 008 53
by 300 mm 230 009 36 230 008 54 230 008 54 230 008 54
Air inlet flange for duct connection, with air pressure switch 230 011 44 230 009 02 230 011 44 230 009 02
Remote reset 230 011 48 230 007 97 230 011 48 230 007 97
Plugged cable for connection of an external solenoid valve on application 230 007 96 on application 230 007 96
15
WG20 capacity and model overview
WG20 capacity graph WG20
mbar Burner type WG20.../1-C LN Burner Low-pressure supply (flow pressure in mbar into shut-off valve)
Combustion head WG 20-C rating Supply pressure ≤ 300 mbar
Rating 80–200 kW kW W-MF 507 W-MF 507 W-MF 512
Nom. diameter of gas ball valve
3,0 ¾” 1” 1”
2,5
Nat. gas E, LHV = 37.26 MJ/Nm3 (10.35 kWh/Nm3), d = 0.606, Wi = 47.84 MJ/Nm3
2,0
80 – 13 11
1,5 90 – 13 11
1,0 100 – 13 11
110 – 14 12
0,5 120 – 14 13
0 130 – 15 13
-0,5 140 – 15 13
150 – 16 14
-1,0 160 – 16 15
kW 20 60 100 140 180 170 – 16 15
180 – 16 15
190 – 17 16
WG20 capacity graph 200 – 18 16
mbar Burner type WG20/1-C Z-LN and ZM-LN Nat. gas LL, LHV = 31.79 MJ/Nm3 (8.83 kWh/Nm3), d = 0.641, Wi = 39.67 MJ/Nm3
Combustion head WG 20-C 80 – 15 13
Rating 35–200 kW 90 – 15 13
3,0 100 – 15 14
110 – 16 14
2,5 120 – 16 15
2,0 130 – 17 16
1,5 140 – 18 16
150 – 18 17
1,0 160 – 19 17
0,5 170 – 20 18
0 180 – 21 18
190 – 22 19
-0,5 200 – 23 20
-1,0
kW 20 60 100 140 180 LPG*, LHV = 93.20 MJ/Nm3 (25.89 kWh/Nm3), d = 1.555, Wi = 74.73 kWh/Nm3
80 13 – –
90 13 – –
100 13 – –
110 14 – –
120 14 – –
Capacity graphs certified in accordance with EN 676. 130 14 – –
140 14 – –
150 15 – –
Stated ratings are based on an installation at sea level. 160 15 – –
For installations at higher altitudes, a reduction in 170 16 – –
180 17 – –
capacity of 1 % per 100 m above sea level should be 190 18 – –
taken into account. 200 19 – –
* The LPG charts are based on propane, but may also be used for butane.
The combustion chamber pressure in mbar must be
added to the minimum gas pressure determined from
the above chart. Minimum gas pressure should not be
less than 15 mbar.
16
Burner type Version Operation Valve train Rating CE-PIN Order No.
R/DN - W-MF kW
WG20
Natural gas
WG20N/1-C LN Single-stage with manual air damper control 1” 507 80–200 CE-0085 BM 0216 232 210 34
WG20N/1-C Z-LN Single or two-stage 1” 507 35–200 CE-0085 BM 0216 232 213 34
WG20N/1-C ZM-LN Sliding-two-stage or modulating 1” 507 35–200 CE-0085 BM 0216 232 216 34
WG20N/1-C LN Single-stage with manual air damper control 1” 512 80–200 CE-0085 BM 0216 232 210 44
WG20N/1-C Z-LN Single or two-stage 1” 512 35–200 CE-0085 BM 0216 232 213 44
WG20N/1-C ZM-LN Sliding-two-stage or modulating 1” 512 35–200 CE-0085 BM 0216 232 216 44
LPG
WG20F/1-C LN Single-stage with manual air damper control ¾” 507 80–200 CE-0085 BM 0216 233 210 24
WG20F/1-C Z-LN Single or two-stage ¾” 507 35–200 CE-0085 BM 0216 233 213 24
WG20F/1-C ZM-LN Sliding-two-stage or modulating ¾” 507 35–200 CE-0085 BM 0216 233 216 24
Additional ¾” FRS governor for gas supply pressures > 150 mbar 230 011 03 230 011 03 230 011 03
Comb. head extension Natural gas by 100 mm 230 007 80 230 007 80 230 007 80
by 200 mm 230 007 81 230 007 81 230 007 81
by 300 mm 230 007 82 230 007 82 230 007 82
Integral hours-run counter (at initial build only, not available for retrofit) 230 008 01 – 230 008 01
Solenoid valve for air pressure switch test for continuous-run fan or post-purge 230 003 29 230 007 98 230 003 29
Air inlet flange for duct connection, with air pressure switch 230 008 34 230 011 45 230 008 34
Plugged cable for connection of an external solenoid valve 230 007 96 on application 230 007 96
ÜB50 high gas pressure switch with connection cable and plug, supplied loose 230 010 40 – 230 010 40
GW50 high gas pressure switch with connection cable and plug, supplied loose – 230 011 42 –
Motor contactor for boiler controls with fusing <10 A (without tank connection) 230 010 22 230 011 39 230 010 22
W-FM 25 PO combustion manager, 230–240 V (for continuous burner firing > 24 h) – 230 011 34 –
17
WG30 capacity and model overview
WG30 capacity graph WG30
mbar Burner type WG30N/1-C ZM-LN Burner Low-pressure supply (flow pressure in mbar into shut-off valve)
Combustion head WG 30 rating Supply pressure ≤ 300 mbar
Rating 40–350 kW kW W-MF 507 W-MF 512
Nom. diameter of gas ball valve
3,5 ¾” 1” 1” 1½”
3,0
2,5 Nat. gas E, LHV = 37.26 MJ/Nm3 (10.35 kWh/Nm3), d = 0.606, Wi = 47.84 MJ/Nm3
2,0 130 15 15 14 13
1,5 160 17 16 15 14
190 18 17 15 13
1,0 210 19 17 15 13
0,5 240 21 18 15 13
0 270 23 20 16 13
-0,5 300 26 22 17 14
-1,0 350 33 28 20 16
-1,5
Nat. gas LL, LHV = 31.79 MJ/Nm3 (8.83 kWh/Nm3), d = 0.641, Wi = 39.67 MJ/Nm3
kW 0 100 200 300 400
130 18 17 15 14
160 20 19 16 15
190 22 20 17 15
WG30 capacity graph 210 23 21 17 15
240 26 23 18 15
mbar Burner type WG30F/1-C ZM-LN 270 30 25 19 15
Combustion head WG 30/1-LN 300 34 29 21 17
Rating 60–350 kW 350 44 37 26 21
4
LPG*, LHV = 93.20 MJ/Nm3 (25.89 kWh/Nm3), d = 1.555, Wi = 74.73 kWh/Nm3
3 130 13 13 – –
160 14 13 – –
2 190 14 14 – –
210 15 14 – –
1 240 15 14 – –
270 17 16 – –
0 300 18 17 – –
350 21 19 – –
-1
* The LPG charts are based on propane, but may also be used for butane.
-2
kW 0 100 200 300 400
Note:
Shaded areas of the valve train table do not meet TRGI ball
valve sizing requirements. For TRGI compliance use the non-
shaded area and note additional price of larger ball valve.
18
Burner type Version Operation Valve train Rating CE-PIN Order No.
R/DN - W-MF kW
WG30
Natural gas
WG 30N/1-C ZM-LN Sliding-two-stage or modulating ¾” 507 40–350 CE-0085-AU 0064 232 326 21
1” 512 232 326 31
1½” 512 232 326 51
LPG
WG 30F/1-C ZM-LN Sliding-two-stage or modulating ¾” 507 60–350 CE-0085-AU 0064 233 326 21
Additional ¾” FRS governor for gas supply pressures > 150 mbar 230 011 04
W-MF 507 with ball valve & TAE for TRGI 1” 230 010 92
W-MF 507 with ball valve & TAE for TRGI 1½” 230 010 93
Solenoid valve for air pressure switch test for continuous-run fan or post-purge 230 005 43
Air inlet flange for duct connection, with air pressure switch 230 011 46
Motor contactor for boiler controls with fusing <10 A (without tank connection) 230 011 40
GW50 high gas pressure switch with connection cable and plug, supplied loose 230 011 42
W-FM 25 PO combustion manager, 230–240 V (for continuous burner firing > 24 h) 230 011 34
19
WG40 capacity and model overview
WG40 capacity graph WG40
mbar Burner type WG40N/1-A ZM-LN Burner Low-pressure supply (flow pressure in mbar into shut-off valve)
Combustion head WG 40 rating Supply pressure ≤ 300 mbar
Rating 55–550 kW kW W-MF W-MF DMV DMV DMV
507 512 512 525/12 5065/12 5080/12
8 Nom. diameter of gas ball valve
7 ¾” 1” 1½” 2” DN65 DN80
6
5 Nat. gas E, LHV = 37.26 MJ/Nm3 (10.35 kWh/Nm3), d = 0.606, Wi = 47.84 MJ/Nm3
4 240 19 14 12 11 11 11
270 22 14 12 11 11 11
3 300 25 15 13 12 11 11
2 350 30 17 13 12 11 11
1 400 36 19 14 13 12 11
0 450 42 22 15 13 12 11
-1 500 52 27 18 16 14 14
-2 550 61 31 21 18 16 15
kW 0 100 200 300 400 500
Nat. gas LL, LHV = 31.79 MJ/Nm3 (8.83 kWh/Nm3), d = 0.641, Wi = 39.67 MJ/Nm3
240 26 17 15 14 13 13
270 29 18 15 14 13 13
WG40 capacity graph 300 33 19 15 14 13 13
350 40 22 16 14 13 13
mbar Burner type WG40F/1-A ZM-LN 400 49 26 18 16 14 14
Combustion head WG 40 450 60 30 21 18 16 15
Rating 80–550 kW 500 72 35 23 20 17 17
8 550 86 42 27 23 20 19
7
LPG*, LHV = 93.20 MJ/Nm3 (25.89 kWh/Nm3), d = 1.555, Wi = 74.73 kWh/Nm3
6 240 13 11 – – – –
5 270 14 11 – – – –
4 300 16 12 – – – –
3 350 19 14 – – – –
2 400 22 15 – – – –
1 450 26 17 – – – –
500 29 19 – – – –
0 550 33 21 – – – –
-1
-2 * The LPG charts are based on propane, but may also be used for butane.
kW 0 100 200 300 400 500
Combustion head open Combustion head closed Capacity graphs certified in accordance with EN 676.
Do not select a firing rate below 80 kW.
Stated ratings are based on an installation at sea level.
For installations at higher altitudes, a reduction in
capacity of 1 % per 100 m above sea level should be
taken into account.
20
Burner type Version Operation Valve train Rating CE-PIN Order No.
R/DN - W-MF kW
WG40
Natural gas
WG40N/1-A ZM-LN Sliding-two-stage or modulating ¾” 507 55–550 CE-0085-AS 0311 232 416 21
1” 512 232 426 31
1½” 512 232 416 51
2” 520 232 406 61
65 5065 232 416 31
80 5080 232 416 41
LPG
WG40F/1-A ZM-LN Sliding-two-stage or modulating ¾” 507 80–550 CE-0085-AS 0311 233 416 21
Additional ¾” FRS governor for gas supply pressures > 150 mbar 230 011 04
W-MF 507 with ball valve & TAE for TRGI 1” 230 010 92
W-MF 507 with ball valve & TAE for TRGI 1½” 230 010 93
W-MF 512 with ball valve & TAE for TRGI 2” 230 010 96
Solenoid valve for air pressure switch test for continuous-run fan or post-purge 230 005 43
Air inlet flange for duct connection, with air pressure switch 230 011 47
GW50 high gas pressure switch with connection cable and plug for valve trains ≤ 1½”, supplied loose 230 011 42
GW50 high gas pressure switch with connection cable and plug for valve trains ≥ 2”, supplied loose 230 011 43
W-FM 25 PO combustion manager, 230–240 V (for continuous burner firing > 24 h) 230 011 34
21
Technical data
Rp
d1 h3
h1
h2
b1
I2 I1
I3
d3
d4
b2
_$ d2
b3
I4
Burner dimensions
Burner type Dimensions in mm
I1 I2 I3 I4 b1 b2 b3 h1 h2 h3 d1 d2 d3 d4 Rp α°
WG5 135 308 30 103 286 154 143 292 216 154 90 M8 130–150 110 ½” 45°
WG10 140 349 31.5 115 330 165 164 353 270 165 108 M8 150–170 110 ¾” 45°
WG20 140 397 32 158 358 182 178 376 284.5 182 120 M8 170 130 1” 45°
WG30 166 480 62 197 420 226 196 460 342 226 127 M8 170–186 130 1½” 45°
WG40 235 577 72 235 450 245 207 480 360 245 154 M10 186–200 160 1½” 45°
22
Technical data
Burner type Combust. Motor Actuator Air pressure Burner Gas valve train Flame
1
manager switch weight Size Type Weight 1 monitoring
WG5.../1-A
Vers. LN W-FM 05 ECK 02/H – 2/1 W-St 02/1 LGW 3/A1 12.8 kg ½” W-MF 055 2.22 kg Ionisation
230 V, 50 Hz
0.04 kW, cap. 3 μF
WG10.../0-D
Vers. ZM-LN W-FM 25 ECK 02/H – 2/1 STE 4,5 * LGW 3/A1 13.5 kg ½” W-MF 055 2.6 kg Ionisation
230 V, 50 Hz
0.04 kW, cap. 3 μF
WG10.../1-D
Vers. LN W-FM 05 ECK 03/H – 2/1 none LGW 10/A2 13.5 kg ¾” W-MF SLE 507 6 kg Ionisation
Vers. Z-LN W-FM 10 230 V, 50 Hz STD 4,5 ** ¾” W-MF SE 507
Vers. ZM-LN W-FM 25 0.095 kW, cap. 4 μF STE 4,5 * ¾” W-MF SE 507
WG20.../1-C
Vers. LN W-FM 05 ECK 04/1 – 2 none LGW 10/A2 20 kg 1” W-MF SLE 507/512 6 kg / 7 kg Ionisation
Vers. Z-LN W-FM 10 230 V, 50 Hz STD 4,5 ** 1” W-MF SE 507/512
Vers. ZM-LN W-FM 25 0.21 kW, cap. 8 μF STE 4,5 * 1” W-MF SE 507/512
WG30.../1-C
Vers. ZM-LN W-FM 25 ECK 05/1-2 STE 4,5 * LGW 10A2 27 kg ¾” W-MF SE 507 5.5 kg Ionisation
230 V; 50 Hz BO.36/6-01L 1” W-MF SE 512 9.0 kg
2900 rpm 1½” W-MF SE 512 13.5 kg
0.42 kW, cap. 12 μF
WG40.../1-A
Vers. ZM-LN W-FM 25 ECK 06/1-2 STE 4,5 * LGW 10A2 35 kg ¾” W-MF SE 507 5.5 kg Ionisation
230 V; 50 Hz BO.36/6-01L 1” W-MF SE 512 9.0 kg
2900 rpm 1½” W-MF SE 512 13.5 kg
0.62 kW, cap. 16 μF 2” DMV+FRS 520 17.5 kg
DN65 DMV+FRS 5065 50.0 kg
DN80 DMV+FRS 5080 67.0 kg
* Runtime during operation: max. 50 s with full setting movement/min. 25 s with reduced setting movement /Runtime during pre-purge approx. 1–2 s.
** Runtime during operation: approx. 3 s with full setting movement/< 3 s with reduced setting movement/Runtime during pre-purge approx. 3 s.
23
Max Weishaupt GmbH
88475 Schwendi
Tel +49 7353 830
Fax +49 7353 83358
www.weishaupt.de