Substation Automation concept

1MRK 500 060-BEN


Page 1
Revision: A
Issued: March 2003
Data subject to change without notice

Features • Protection for all applications • Distributed intelligence


• Control with flexible system functions • User-friendly workplaces
• Communication with fibre optics • High performance and availability
• Self-supervision and diagnostic • Step by step implementation possible
• Support of hardware and software • A total substation automation concept
• State of the art microprocessor technology • User friendly software tools

Application General
Substation Automation includes a complete ABB can offer a comprehensive range of
range of flexible object terminals, including numerical object terminals for generation,
all necessary functions for substation control transmission, distribution and industry. These
and substation monitoring systems. All of the state of the art products offer many new pos-
building blocks are based on state of the art sibilities in protection and control. Communi-
numerical technology, compatible with con- cation of load and fault data gives a new
ventional equipment. The new, improved dimension to protection and control. The
technology can thus be implemented step by Substation Automation concept even allows
step from stand-alone protective relays to the connection of existing or new static/elec-
complete coordinated protection and control tromechanical relays.
systems.
Substation Automation concept
1MRK 500 060-BEN
Page 2

However the information from these relays is lines, transformers, etc. are controlled and
limited to data from signal contacts included protected from the lower bay level. A number
in the relays. of dedicated object terminals are provided for
bay level protection and control. This struc-
Separate transducer for voltage and currents ture simplifies future retrofit or expansion;
can however be added to conventional relays. i.e. the installation of additional bays.

Signals from the conventional relays can be The distributed structure increases the avail-
hardwired to the numerical ones. By this ability, because an internal fault will affect
arrangement both existing relays and new only a small part of the equipment. Since the
numerical relays can communicate via a com- most important functions are located at the
mon fibre-optic bus. This makes the concept bay level, the operation of a bay can be main-
suitable for partial retrofit as well as com- tained even if an internal fault occurs at the
pletely new installations. station level. The equipment for each bay is
housed in one or more cubicles which can be
The ABB Substation Automation concept has assembled and tested at the factory. This
five corner stones: reduces on-site erection and commissioning
work. Information is transferred between the
- Protection
two levels via a serial interbay bus.
- Communication
Station-oriented signal collection and the
- Control
serial transmission of information between
- Monitoring the two levels considerably reduces the
- Tools amount of cabling required. Disturbance free
transmission has been achieved by using a
One of the main advantages of ABB Substa- fibre-optic bus.
tion Automation is that it may include build-
ing blocks from various product ranges and ABB has the experience
generations. High performance and total Over the years, ABB has designed and manu-
quality are the major requirements for each factured protective relays and control equip-
building block. ment for substations in power transmission
and distribution systems. The experience thus
Continuity for old and new products includ- gained has served as the basis for designing
ing openness for the future such as for new modern numerical protection and control
sensors or intelligent switchgear. equipment which can ensure more efficient
and reliable operation.
The ABB Substation Automation concept
enables efficient power network management The first commercial microprocessor-based
by providing modular solutions for protec- control system in a substation was installed
tion, control, monitoring and communication by ABB in 1983. Since then, ABB has deliv-
for substations. ered numerous systems throughout the world.
This unique experience has been very valu-
A two-level communication structure able when designing the building blocks of
The entire station is controlled and supervised the today’s Substation Automation concept.
from the higher station level, while individual

Functions Human system interface (HSI): • Interlocking of switching devices within a


bay and between bays
• Operation and supervision of HV equip-
ment • Synchro-check function
• Data presentation • Tap-changer control for voltage regulation
• Engineer’s support • Load transfer for parallel transformers
• System supervision • Switching sequences
Remote control interfacing: • Automatic power restoration
• Adaptation for serial communication with • Load shedding
control centres via various protocols • Autoreclosing
Automatic functions and control sequences: • Control of reactive power
Substation Automation concept
1MRK 500 060-BEN
Page 3

Data acquisition and handling: • Switchgear monitoring


• Remote data acquisition • Transformer monitoring
• Data evaluation Protection functions:
• Energy measurement • Generator protection
• Event list • Line protection
• Alarm list • Busbar protection
• Reports • Transformer protection
• Printed output: event logs, reports • Feeder protection
• Disturbance recording • Motor protection
Condition monitoring: • Protection and Control terminal for Rail-
way power system
• Gas density monitoring (GIS)
• Phasor measurement terminal

Conceptual
structure
5HPRW H 606
ZRUNSODFHZLWK
&$3  606 ([WHUQDOWLPH
V\QFKU RQL]DW LRQ 7&3,3

6WDWLRQ +6, /2123& 1&&


VHU YHU

(YHQW SULQWHU +DUGFRS\


SULQWHU
Modem Dial-up m odem
*DWHZD\

6WDUFRXSOHU 5(5
/21

Modem Dial-up m odem

237,21$/
Fiber optic
trans ceiver 5([ [[ 5([ [[ 5([ [[ 5([ [[ 5([ [[ &$3

63$

/2123&VHU YHUWR
EHXVHG WRJHWKHUZLWK
WKLUG SDUW\+6, en03000029.vsd

Fig. 1 ABB Substation Automation, with 500 series terminals and COMBIFLEX

Protection and Series 100 Terminals The REB 100-series includes the busbar pro-
control Each module in the terminals is based on rack tection. REB 100 is based on the well known
mounted printed board assemblies. Analogue ultra-high speed differential measuring
terminals auxiliary functions can be added in a separate method used in RADSS. This allows CT-satu-
rack. ration as well as sharing of CT-cores with
other protections. One 19” 6U rack can adapt
Series 100 is based on existing stand-alone 12 lines with test switch and 18 lines without.
relays for transmission and generation. The 100
number series is used to describe different hard-
ware combinations of each terminal.
Substation Automation concept
1MRK 500 060-BEN
Page 4

Protection and control Series 200 Terminals These IT based terminals are suited for gener-
terminals (cont’d) The same terminal can be used for more than ation, transmission and distribution applica-
one object and various functions. The selec- tions. A local HMI and PC connection at the
tion is made in the software and choice of front gives fast access to terminal data at
CPU capacity. commissioning and service. In addition listed
terminals below all have two independent
Series 200 is dedicated to complex applica- communication ports for control and monitor-
tions which require many functions included ing.
in one hardware module.
REB 551 Breaker protection terminal
The terminals have unique flexibility - a large REC 561 Bay terminal with a vast array
number of software modules are available for of functions for one or several
system adaption. The terminal can be used for bays at transmission and
more than one object by selecting pretested subtransmission level.
software modules and the appropriate CPU
capacity. RED 521 General differential protec-
tion terminal
REG 216 is designed for generator and trans- REL 501 Line distance protection ter-
former applications. A complete generator minal
transformer block protection unit, including REL 511 Line distance protection ter-
disturbance recording, can be accommodated. minal
It can be divided into sub 1 and sub 2 for
REL 521 Line distance protection ter-
maximum redundancy. A personal computer
minal
can be used for the on-site configuration and
setting of the software library provided. REL 531 Line distance protection ter-
minal
Series 300 Terminals REL 551 Line differential protection
Each terminal is mounted within one compact terminal
case which also has all interfaces. The func- REL 561 Line differential protection
tion selection is made in software and internal terminal
hardware.
REO 517 Protection and Control termi-
REG 316, the numerical generator protection nal for Railway power system
terminal can include all important functions RES 505-C1 Disturbance recording and
required for protection and monitoring of fault location terminal
generators, motors and unit transformers. RES 521 Phasor measurement terminal
RET 521 Transformer protection termi-
The desired functions can be selected from a
nal
comprehensive library.

Series 500 Terminals Several options are available for all terminals
The Substation Automation Concept provides such as e.g., disturbance recorder, event
a full range of numerical protection and con- recorder and breaker related functions. All
trol terminals. terminals can be configured with a large
Depending on the application each terminal is amount of binary inputs and outputs that are
named according to the following designation programmable. These can e.g. be used for
system, “REx 5xx”. control of switchgear equipment.

The letter indicates the terminal type, e.g. L The REO 500 object terminal has a unique
for Line and T for Transformer. The three flexibility. It can be delivered as e.g. a basic
digits indicates in what series the terminal is overcurrent relay or as an integrated protec-
designed. tion and control terminal, depending on
selected options.
The 500-series is the latest serie in state-of-
art-technology terminals for protection, con- Pre-configured terminals (C-terminals) for
trol and monitoring. A common hardware and cost-effective engineering and commission-
software platform is used. ing are also available.
Substation Automation concept
1MRK 500 060-BEN
Page 5

Terminals REL 551 line differential protection terminal


REB 551 breaker protection terminal is used is used for protection of overhead lines and
for breaker related protection and control cables. Phase-segregated current differential
functions in all types of network. The termi- provide excellent sensitivity and phase selec-
nal is specially suitable in 1 1/2 breaker and tion in complex network configurations. The
double breaker switchgears. terminal can perform one-, two- and/or three-
pole tripping.
REC 561 control terminal is used at bay level
in a Substation Control system to control and REL 561 line differential protection terminal
supervise circuit breakers, disconnectors and is used for protection of overhead lines and
earthing switches, in any kind of switchgear/ cables. Phase-segregated current differential
busbar arrangement. Control functions such provide excellent sensitivity and phase selec-
as interlocking, autoreclosing and synchro- tion in complex network configurations. The
check can also be included as well as protec- terminal can perform one-, two- and/or three-
tion and monitoring functions. pole tripping.

RED 521 general differential protection is Charging current compensation can be


used for protection of single and double bus- included in order to increase the sensitivity at
bars, autotransformers, generators etc. The high capacitive currents. A three-zone line
terminal has a typical operating time of 12 ms distance protection can also be included and
and very low CT requirements. the included distance protection can also be
used for series compensated networks.
REL 501 line distance protection terminal is
used for protection of overhead lines and REO 517 protection and control terminal is
cables in high impedance or solidly grounded used for catenary lines as well as overhead
distribution and subtransmission networks. lines and cables feeding the railway power
The terminal can also be used in transmission system. The terminal is available for 16 2/3,
networks up to the highest voltage levels. The 50 and 60 Hz systems.
terminal performs three-pole tripping.
RES 505-C1 disturbance recording and fault
REL 511 line distance protection terminal is location terminal is a stand-alone disturbance
used for protection of overhead lines and recorder and fault locator terminal. It is suit-
cables in high impedance or solidly grounded able for use in any power system application
distribution and subtransmission networks. where the recording (to a high resolution) of
The terminal can also be used in transmission power system voltages, currents and binary
networks up to the highest voltage levels. The signals is required to facilitate analysis of dis-
terminal performs one-, two and/or three-pole turbances that occur in the power system.
tripping.
RES 521 phasor measurement terminal is
REL 521 line distance protection terminal is used for synchronized measurements (GPS)
used for protection of overhead lines and of phase angles between corresponding pha-
cables in solidly grounded networks. The ter- sors in different locations within the power
minal performs one-, two- and/or three-pole system. Increased power transfer, operational
tipping. security and profit can be achieved.

REL 531 high speed line distance protection RET 521 transformer protection terminal is
terminal is used for protection of overhead used for protection of two or three winding
lines and cables in solidly grounded networks power tansformers, generator-transformer
at high requirements for fast operating times blocks and reactors.
(less than one cycle). The terminal is also
suitable for series compensated networks and Voltage regulations for single or parallel
performs one-, two- and/or three-pole trip- transformers with on load tap changers can be
ping. included.

All line distance protection terminals are suit- The above terminals can communicate with a
able for protection of heavily loaded lines and Substation Automation system, see Fig. 1. In
multicircuit lines. The terminals can also be addition to this, local printout from event
used to provide back-up protection for power recorder and disturbance recorder can be
transformers, busbars etc. included separately or as back-up.
Substation Automation concept
1MRK 500 060-BEN
Page 6

Tools CAP 540 Terminal tool box SMS 510 Substation Monitoring
Application
system
CAP 540 is used throughout all stages of nor- Application
mal operation from engineering, parameter The SMS 510 substation monitoring system
setting, commissioning and power system is an overall substation monitoring system
disturbance evaluation. It can also be used to that gives you essential information about
clear front indications, switch setting groups your electrical transmission and distribution
and turn autoreclosure on/off. The engineer- process. This information comprises all mea-
ing work can be done off-line on the PC. sured, recorded and calculated data such as
indications, settings and diagnostic informa-
A disturbance upload and an analyzer tool is tion available in the protection and control
included in the tool box for fault data presen- terminals from ABB. Setting and resetting
tation. facilities for the protection and control termi-
nal are also provided by the product.
Design
The default configuration in the terminals and LIB 520 High voltage software
the pre-configured terminals can easily be modules
adapted to the customer’s needs with the con-
figuration tool. The configuration consists of Application
function blocks, logic gates and timers etc. The high voltage software modules are a
The functions blocks included in a terminal complement to the standard MicroSCADA
are available in a library of functions, where software and provides an easy-to-build and
the engineer can pick a function and connect easy-to-use HSI for supervision, control, dis-
it according to the requirements. turbance collection and SMS functionality in
MicroSCADA.

SMS
SMS510
510 CAP
CAP540
540 LIB
LIB520
520
Navigator
Navigator

Basic package

Parameter
ParameterSetting
Setting Parameter
ParameterSetting
Setting Parameter
ParameterSetting
Setting
MicroSCADA
MicroSCADA

Disturbance
Disturbancehandling Disturbance
DisturbanceUpload Disturbance
DisturbanceUpload
Navigator

handling Upload Upload


Full version
Navigator

Disturbance
DisturbanceEvaluation
Evaluation Voltage
VoltageControl
Control

Configuration
Configuration Option
Option Alarm
Alarm&&Event
Eventhandling
handling

Remote
RemoteConnection
Connection Option
Option On-line
On-lineSupervision
Supervision

Settings
SettingsVisualisation
VisualisationTool
Tool Option
Option On-line
On-lineControl
Control

en03000057.vsd

Fig. 2 CAP 540 basic package and full version


Substation Automation concept
1MRK 500 060-BEN
Page 7

System The system structure is divided into two lev- Station level
structure els; bay level and station level. The bay level Design
consists of distributed terminals, whereas The result of high requirements of availability
operator stations and gateways belong to the is the use of two independent and autono-
station level. mous units on station level; the operators
workplace (HSI) for control and monitoring
Together all units combine control, monitor- of the substation in the station, and the gate-
ing, recording and report generation in a hier- way (GW), for communication with a remote
archy system that supervise its own hard- and control centre. Whenever the independence
software. requirements are lower the function of all
these units can be combined in the HSI.
The entire substation is controlled and super-
vised from the station level, while individual
lines, transformers, etc., are protected, con- Human system interface (HSI)
trolled and monitored from the terminals at Design
bay level. Using a “mouse”, the operator can operate,
control and supervise the substation by mov-
Information is transferred between the two ing the cursor on a color video display unit
control levels via a serial data bus. The sta- (VDU) to symbols or text. The necessary
tion level equipment is connected to the bay information is displayed in windows. Along
level computers via the interbay bus. Bay-ori- with the windows and data, symbolic push-
ented signal collection and the serial trans- buttons of any size can be located anywhere
mission of information between the two on the VDU.
control levels considerably reduces the
amount of cabling required. From the HSI, the operator can also read and
change the settings of all numerical protective
Disturbance-free communication is achieved relays which are connected to the system via
by using fibre-optic links. the fibre-optic bus. This HSI provides the
operator with an excellent overview of the
complete substation, and gives easy access to
the various functions.

5HPRWH 606
ZRUNSODFHZLWK
&$3606
7&3,3

6WDWLRQ +6, 1&&

Modem Dial-up modem


*DWHZD\

6WDUFRXSOHU 5(5
/21

Modem Dial-up modem

Fiber optic
transceiver 5([ [[ 5([ [[ 5([ [[ 5([ [[ 5([ [[

63$
en03000030.vsd

Fig. 3 System structure for transmission and subtransmission voltage applications


Substation Automation concept
1MRK 500 060-BEN
Page 8

Bay level front of the IED) or portable PC provides


Design
easy access and readability. The last ten dis-
Functions related to a particular bay are turbance recordings are stored in the IED
located at the bay level. This is why the bay memory, and a summary for the last distur-
terminals are independent of each other, bance is automatically displayed at IED oper-
which increases the availability. Since the ation.
most important functions are located at the
bay level, the operation of a bay can be main- The setting of the IED is normally done from
tained even if a fault occurs at the substation a portable PC or from the local HMI. Four
level. The equipment for each bay is housed different sets of values can be programmed.
in one or more cubicles which can be assem- Remote setting can in principle be done, but
bled and tested at the factory. This reduces this has to be carefully studied by the user to
on-site erection and commissioning work. prevent outside persons from gaining access
to this possibility.
The protection functions in the bay terminals
are at all time unaffected by the status of the The operator’s workplace monitor can dis-
station level equipment. play all information relevant to the substation
operation. The depth and the detail of infor-
mation is selected by the operator, step by
Communication step, not to create information pollution.
Application
ABB Substation Automation offers a very The engineer’s workplace monitor presents
flexible and open system which can be the information stored in the terminal at trip
designed to combine both the comprehensive operation. All terminal data and settings are
ABB range of terminals, numerical relays accessible and are used for post-fault evalua-
from other manufacturers as well as existing tion and disturbance recording. Once the data
and new conventional relays. Furthermore has been transferred to the data base, the ter-
ABB Substation Automation can communi- minal’s event memory can be reset from the
cate to different types of Network Control master station.
Systems as well as third party HSI’s via an
OPC server. The communication between the different ter-
minals and the operator’s workplace is per-
One of the major differences between numeri- formed via a fibre-optic object bus type LON.
cal technique and conventional technique is All numerical ABB Substation Automation
that numerical technique can store and memo- protection and control IED’s can be con-
rize information, both digital, analogue and nected to this bus.
processed information. To structure and com-
municate the “right” information to the “right” Non LON bus compliant devices such as a
person at the “right” time is essential for the conventional relay may be connected the
overall performance of the system. How we interbay bus via any 500 terminal.
arrange human system interface is a task for
both user and manufacturer. Furthermore, effi- The unique structure in combination with a
cient and safe substation operation requires full range of versatile terminals provides out-
well-structured means of communication that standing flexibility with high availability and
meet the present and future needs of the user. redundancy. It is an “open” system which can
be tailored to the specific need of each user
ABB Substation Automation provides com- and each application. It offers a step by step
munication facilities that can be adapted to implementation, including both new and
the safety and efficiency requirements of existing protection relays.
operators and management, with capabilities
for future expansion as needs increase and For communication with an existing Network
new technology is introduced. Control System a separate Gateway or the
HSI can be used. Today more than 50 differ-
Design ent Protocols have been implemented.
The information is structured on three levels:
operator’s workplace, engineer’s workplace Protocol implementations for any other type
and local human machine interface (HMI) or of Network Control System, not yet included
portable PC. The local HMI (which is a menu in our library, can be quoted on request.
driven alpha-numerical display located on the
Substation Automation concept
1MRK 500 060-BEN
Page 9

Control and Monitoring by ensuring that product and system faults


Application
can be identified without extensive fault-trac-
The traditional control system consists of a ing, so the equipment can be returned to ser-
number of control panels with instruments, vice quickly.
switches, alarm annunciators and other equip-
ment. It also provides a number of sub- Self-supervision of the protection and control
systems such as interlocking, Automatic hardware and software thus reduces mainte-
Voltage Regulation for power transformers, nance costs. The CT and VT circuits, the dc
sequence-of-event recorders, etc. Large space supply and trip circuits, and the communica-
and cabling requirements, extensive mainte- tion links are also monitored continuously,
nance and difficulties in modifying the sys- which further increases the availability.
tem for future expansion are characteristics of
traditional control systems. Messages from the self-supervision system
are available both locally and remotely. This
The ABB Substation Automation concept simplifies fault-tracing and cuts the time for
eliminates these disadvantages. In addition, repair. The resulting reduction in down time
the system provides statistics for the reporting increases the dependability and security.
of history, trends, etc.
Functionality
The main benefit of ABB Substation Auto-
Self-supervision minimizes maintenance and
mation self-supervision is that it covers the
fault tracing. Once the system is programmed
entire system. Moreover, back-up functions
for a specific application, the user can, with
are included, for high reliability.
little effort, modify and add functions him-
self.
With a test interval of two years, the Mean
Time To Repair (MTTR) without supervision
The numerical monitoring and control system
is approximately one year, since a fault will
is the key to safe and efficient substation
not be detected until the next test is per-
operation. This system, which has been
formed. With supervision a fault can nor-
offered by ABB for several years, is thor-
mally be repaired within 24 hours. This
oughly tried and tested.
means that the MTTR will be one day instead
of 365 days - a significant improvement.
The two independent communication inter-
faces in the 500 series allows for a separate
In the system supervision display in the sta-
off-line monitoring system.
tion HSI, according to Fig. 4 below, the fol-
lowing information is presented:
Self-supervision
Application • System configuration
One of the major benefits of microprocessor • Status of installed equipment e.g. IEDs,
technology is that no additional hardware is communication devices etc.
required for self-supervision; a function
which increases the availability and reliability
Substation Automation concept
1MRK 500 060-BEN
Page 10

(en03000035)
Fig. 4 SA System supervision

Workplaces In the ABB Substation Automation concept ferred to the operator. This information is
the human system interface is structured in selected to give a clear and fast view about
workplaces/levels. what is happening. Printout from the distur-
bance recorder modules can be obtained.
The operator’s workplace centrally in the
substation and with remote gateway. Fig. 5a shows an example of pictures which
the operators can select from the monitor.
The protection and control engineer’s
workplace with local and/or remote PC. The single line diagram gives rapid informa-
tion about the status. Each bay, for example a
These workplaces can be used separately or transformer bay can be monitored and load,
combined. The important thing is that the oil temperature, etc. can be logged.
Substation Automation offers this very com- In Fig. 5b the event list is shown which is
prehensive and flexible way of working. continuously updated.

The operator’s workplace Fig. 5c and Fig. 5d shows an example of a


The operator’s workplace is continuously trend logging.
connected to each terminal. Via fibre-optic
cables all information is immediately trans-
Substation Automation concept
1MRK 500 060-BEN
Page 11

Fig. 5a) Single line diagram with


system status

(en03000037)
Fig. 5b) Event list

(en03000038)

Fig. 5c) Trend logging


(en03000039)
Substation Automation concept
1MRK 500 060-BEN
Page 12

Workplaces (cont’d) Fig. 5d) Trends

(en03000036)
Fig. 5 SCS, operators workplace

The protection and control engineer’s installed can be connected to both the front
workplace and rear SPA port. When CAP 540 is installed
The protection and control engineer’s work- on a station local PC automatic upload of dis-
place can be located locally (in the substa- turbance data and transfer of disturbance
tion) and/or remotely. It is possible to call any reports to a remote fax is possible. It is also
station via the local telephone system and possible to only have a modem in the station.
order information to be transferred. Data From the remote CAP 540 PC it is possible to
compression and local expert programs can connect to both stations with a station local
be used to limit this information. PC and stations with only a modem connec-
tion. In order to work with remote IEC
CAP 540 is a software package installed in 61131-3 configuration it is required to only
the workplace, locally and/or remotely, for have a modem connection in the station with-
support to the protection and control engi- out the station local PC. With CAP 540 it is
neer. possible to save disturbance data in
COMTRADE format on a ftp Server. This
CAP 540 architecture requires LAN/WAN connection.
CAP 540 supports the architecture shown in
figure Fig. 6. Computers with CAP 540

Fig. 6 CAP 540 architecture


Substation Automation concept
1MRK 500 060-BEN
Page 13

The CAP 540 Terminal Tool Box offers the edit your parameters in advance and write
user all the necessary functionality in order to them to the terminal later when it is available.
work efficiently with the protection and con-
trol terminals in every step of the terminal life In addition, an simple monitoring function
cycle. The terminal function libraries in the with access to service values is included. The
tools can be automatically adjusted to match simple monitoring functionality lets you
the ordered terminal. upload several power system values like cur-
rents, voltages and frequency. Service values
Parameter setting tool include list of terminal events, current status
With the parameter setting tool, you can read of internal signals, self supervision, LED sta-
parameters from the terminal, edit the param- tus, etc. The tool can also monitor communi-
eter values and write them to a terminal. You cation for the line differential function and
can also change parameter setting groups, display internal measurements from functions
compare terminal and PC-file parameters or like the automatic reclosing function.

Fig. 7 Example parameter view in PST of line protection function

Setting Visualisation Tool be used by test equipment software and con-


Settings Visualisation Tool, SVT, is a tool for tains zone characteristics and trip time.
visualizing PST steady-state parameters for Impedance measurement zones are cut by the
under impedance protection functions. You General Fault Criteria, GFC, (if switched on)
can run SVT while editing parameters in PST in the RIO-file. On the screen these character-
and see the effect of the changes in the termi- istics remain the same, because SVT presents
nal settings. Analysis of the zones can also be settings, rather than operation. It is also possi-
carried out. ble to export a graphical plot to the Clip-
board. A plot displays a part of the impedance
The program allows export of figures avail- plane in accordance to the current scale and
able in SVT to test set software by RIO-for- position. All zones and faults are shown on
mat de-facto standard. This file is supposed to the plot.
Substation Automation concept
1MRK 500 060-BEN
Page 14

Fig. 8 Graphical view/plot

Disturbance handling
After the disturbance list has been uploaded Curve forms and data can then be printed for
the fault data can be uploaded and displayed documentation by the operator.
with the graphical disturbance viewer and
analysis program.

Fig. 9 Disturbance view


Substation Automation concept
1MRK 500 060-BEN
Page 15

Grapichal configuration tool It is also used by the control system construc-


The configuration tool offers a compilation tor that for example adapts the interlocking
check to help the engineer to make a correct logic to the switchgear configuration of the
configuration. station.

The monitoring function provides an on-line The configuration can be printed on a user-
check of all internal signals in a 500-terminal. defined form which gives documentation of
It offers a window into the terminal, where the configuration that matches the terminal
the commissioner can see all changes in sig- completely.
nal status. With this tool, the commissioner
obtains a powerful help.

Fig. 10 User interface in the graphical configuration tool

The Intelligent The Substation Automation concept can be the breakers are installed in panel 1. In panel
terminal adapted to various degrees of requirements 2 the line 2 equipment can be placed and in
and complexity. Fig. 11 shows an example of panel 3 the line 3 equipment can be placed.
a terminal which is appropriate for a 220 kV As an alternative, the subsystem 1 equipment,
line. Main 1 protection is REL 521 and main with main 1 protection for both lines, can be
2 protection is REL 531 which means the dis- placed in cubicle 2 and subsystem 2 equip-
turbance recorder module is included in REL ment in panel 3.
521. For a substation with one and a half
breaker arrangement the panel layout is These line bays are operated through the
shown in Fig. 12. The equipment related to workplaces in Fig. 3.
Substation Automation concept
1MRK 500 060-BEN
Page 16

(97000086)
Fig. 11 Single breaker arrangement, one transmission line and duplicate protection.

(97000087)

Fig. 12 Breaker and a half arrangement with three breakers two transmission line and duplicate
protection per bay.
Substation Automation concept
1MRK 500 060-BEN
Page 17

The intelligent ABB Substation Automation offers a unique For a technical proposal please contact your
station range of state of the art components which nearest ABB representative. The following
management can be combined with conventional relays to information is required:
give total coordinated protection and control.
- One line diagram of the high voltage
system
These products can be used as stand-alone but
can also be upgraded, step by step, to form - Protection, control and monitoring
the “Intelligent substation”. ABB Substation functions included per terminal
Automation offers workplaces for the opera-
- Performance level required for main
tor, relay engineer and service engineer.
functions
These workplaces include software packages
for statistics, setting calculation, disturbance - Functions included per workplace
evaluation, automatic testing and other expert - Existing equipment to be interfaced
programs. with
ABB Substation Automation also offers great - Remote communication required
flexibility and can give technical and eco- The selection of suitable terminals is based
nomical optimum solutions for different on customer requirements on performance
requirements on performance and availabil- and the functions to be included.
ity.
Substation Automation concept
1MRK 500 060-BEN
Page 18

References CAP 540


Terminal Tool box 1MRK 511 112-BEN

LIB 520
High voltage software modules 1MRK 511 126-BEN

REB 100
Busbar protection terminals 1MRK 505 007-BEN

REB 551
Breaker protection terminal 1MRK 505 093-BEN

RED 521
General Differential protection 1MRK 505 031-BEN

REF 541/543/545
Feeder terminals 1MRS 751818-MDS

REG 216
Generator protection terminal 1KHA-000 602-SEN

REG 316
Generator protection terminal 1MRK 502 004-BEN

REM 543/545
Motor and Generator terminals 1MRS 751406-MDS

RE0 517
Multi-functional terminals
for railway application 1MRK 506 135-BEN

RER
LON bus Connection Devices 1MRS 750435-MBG

RES 521
Phasor measurement terminal 1MRK 511 115-BEN

RES 505-C1
Overcurrent protection terminal 1MRK 505 121-BEN

RET 521
Transformer protection terminal 1MRK 504 013-BEN

REx 5xx
Protection, Monitoring and Control
Solution for Transmission Networks 1MRK 500 049-SEN

SMS 510
Substation Monitoring System 1MRS 751973-MBG

Information about our products and tools can be found on internet:


www.abb.com/substationautomation
Substation Automation concept
1MRK 500 060-BEN
Page 19

Manufacturer ABB Automation Technology Products AB


Substation Automation
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation