Vous êtes sur la page 1sur 28

F O R E W O R D

This booklet is intended primarily for the small service station owner and mechanic
who, though n o t normally concerned w i t h car " electrics," are nevertheless required
at some time o r other t o diagnose and correct electrical faults.
W e believe that this booklet w i l l serve t o show you a way in which some o f the m o r e
common faults i n the generator and regulator, on Lucas equipped cars and m o t o r
cycles, can be diagnosed and corrected-in many cases without having t o remove the
units from the vehicle. Quick diagnosis is ensured i f the tests are carried o u t i n t h e
systematic manner outlined herein.
Remember, always commence the tests at the source o f supply-The Generator (Part 1,
Test 1).

Publication No. 1448 Ex. (Fifth Edition) 1963 '~F/1063/L Printed in England
1N DEX OF SYSTEMATIC FAULT LOCATION PROCEDURE

PART 1 PART 2 PART 3 PART 4


Generator Tests for Models: Regulator Tests: Regulator Tests: Regulator Tests:
C39PV C42 Compensated Voltage Con- Current Voltage Control. Current Voltage Control.
trol.
C39Q C45PV-5
Lucas Models: MCRI, MCR2, Lucas Model: RB310 Lucas Model: RB340
C40A C45PV-6 RF95, RF95/3, RF96, RF97, 3 Bobbin Type 3 Bobbin Type
C40/1 C45PVS-6 RBI 0611, RB106/2, RBI 07 w i t h screw type electrical w i t h cam type electrical
and RBI08 adjustment adjustment
C4OAL C47
C40L C48
C4OLQ

Pages 3 - 4 Pages 5 - 9 Pages 10 - 16 Pages 17 - 26

OPrinted i n England
No part of this book may be reproduced without permission.

JOSEPH LUCAS (EXPORT) LTD. . 46 PARK STREET . L O N D O N W.1.


The following tests should be carried out with a good quality Moving Coil Voltmeter. The meter should have a full scale
deflection o f at least 20 volts, with divisions suitable for taking readings t o within 0.5 of a volt. A meter o f this standard will
be suitable for both 6 and 12-volt LUCAS equipped cars, trucks, etc., and 6 volt systems on motor cycles.

ALWAYS CHECK BATTERY C O N D I T I O N BEFORE COMMENCING TESTS


PART 1
GENERATOR TESTS W I T H THE MACHINE IN POSITION ON THE VEHICLE
Inspect generator mounting for tightness of bolts, etc.
lnspect the fan belt for correct tension, adjust i f necessary. If worn o r frayed fit a new belt. Make sure drive
pulleys are correctly aligned.
If the belt and generator mounting are satisfactory and pulleys correctly aligned then proceed t o Test 1.
VOLTMETER CONNECTION I READING ACTION

TEST 1. A. 2-4 volts as generator is run up t o Armature and brush connections O.K.
Disconnect leads from generator. charging speed (approx. 3,000 rev/ proceed t o Test 2.
Connect one lead of voltmeter t o D min) (6 and 12 volt systems).
terminal and the other t o a good
ground. B. Zero volts. Examine brushes and make sure they
Start engine and raise speed until are free in their boxes making good
generator is running at approx. contact on the commutator. If still
3,000 revlmin. no reading fault is in armature,
When vehicle has a positive ground which has t o be replaced.
\
system positive meter lead must be
grounded. C. Rising volts w i t h rising speed. Internal short between D and F ter-
minals, examine field coils and rectify
as necessary o r fit replacement.
VOLTMETER CONNECTION READING ACTION

TEST 2. A. Rising volts w i t h rising speed-full Generator in order, proceed t o Test 3.


Connect meter as i n Test 1. scale reading at fast tick-over.
Link terminals D and F on generator.
Gradually speed up engine t o fast B. 2-4 volts as engine i s revved u p (6 Open circuit i n field coils, rectify as
"tick-over" speed. If an ammeter and 1 2 v o l t systems). necessary o r fit replacement.
is used t o link D and F, reading
should not be more than* 2 amps, C. Z e r o volts. Grounded field coils o r field connection,
when normal voltage o f system i s rectify as necessary o r fit replace-
registered on voltmeter. ment.
"2.5 for C42 w i t h 43 ohm field.
TEST 3. A. 2-4 volts (6 and 1 2 volt systems). D lead from generator t o control box
Reconnect leads o f generator. is in order. Proceed t o Test 4.
Remove leads from D and F terminals
at the control box. B. Z e r o volts. Rewire D lead which is open-circuited,
Connect one side o f voltmeter t o end o r earthed.
o f D lead, the other t o a good
ground, speed generator up t o C. Rising volts w i t h rising speed. Locate short between D and F cables.
approx. 3,000 rev/min.

TEST 4. A. Rising volts w i t h rising speed. Cables from generator t o control b o x


Leave voltmeter connected as i n Test 3. are i n order. Proceed t o Test 5 i n
Join D and F wires together. part 2, 3, o r 4 whichever is applicable.
Gradually speed up engine t o fast
"tick-over" speed. B. Z e r o volts. Earthed F lead.

C. 2-4 volts (6 and 12 volt systems). Open circuit i n field lead between
generator and control bok.
BART 2
M O D E L LRT9 R E G U L A T O R - SINGLE C O N T A C T 2 B O B B I N TYPE
(Used with RF95, 96, RB106/1, MCRZ, etc.)

COMPENSATED VOLTAGE CONTROL TESTS WITH UNIT I N POSITION


O n no account must these tests be made with the battery in circuit.

To isolate the battery from the generator put a piece of dry card between the cut-out points. Remember the output
of the generator, that is the current in amps. flowing from the generator t o the battery i s dependent on the state of charge of
the battery. The generator will give a high output when the battery is in a low state of charge and a low output when the
battery i s fully charged. Regulators must therefore always be set on open-circuit, a condition which is most easily obtained by
inserting the piece of dry card as described above, alternatively, withdraw cables from 'A' and A1 terminals and join together
temporarily.

VOLTMETER CONNECTION READING ACTION


I

TEST 5. A. Battery voltage. Regulator ground connection in good


Reconnect generator leads t o control order. Proceed t o Test 6.
box terminals D and F.
Connect one lead of voltmeter t o ter- B. Less than battery voltage, o r zero Rectify bad ground o r broken ground
minal A, the other t o terminal E on reading. wire between terminal E and chassis.
the control box. Engine stationary.
VOLTMETER CONNECTION READING ACTION

TEST 6. A. W i t h generator running at approx. Regulator in order.


Proceed t o check regulator setting. 3,000 rev/min voltage should remain Proceed t o Test 7.
Remove control box cover. constant w i t h i n the following limits :
Isolate the battery by placing a piece o f Ambient Temp. 6 volt Equip. 12 volt Equip.
d r y card between cut-out contacts, O" O
'' F) 8.0-8-5 16.0-1 6.5
alternatively, remove 'A' and A1 20°C 68°F
cables from terminals and join
together temporarily.
Connect one lead of voltmeter t o ter- - - -

minal D (or frame of regulator) and B. Voltage remains constant, but out- Adjust regulator by turning the adjust-
the other lead t o a good ground. side the given limits. ing screw clockwise t o increase o r
counter-clockwise t o lower the set-
ting. Check setting by raising speed
from zero.

C. Rising volts w i t h rising engine speed Check ' D ' and ' F ' leads for short-
up t o 3,000 revlmin and beyond. circuit, i f O.K. suspect broken shunt
winding i n regulator bobbin. The
ground lead from control box ter-
minal E is common t o both shunt
windings (regulator and cut-out).
Hold a screwdriver near t o p o f the
bobbins and test for magnetic pull.
If there is pull o n the one bobbin
core and not on the other suspect
open circuit on the latter. If no pull on
either checkforopen circuited ground
lead. Replace defective regulator.
--
-.

VOLTMETER CONNECTION READING ACTION

TEST 6 (continued). D. Reading approx. half setting. Suspect regulator contacts not passing
i current causing the contacts resistor
t o be i n circuit the whole time. T o
I test, bridge the contacts w i t h screw-
ARMATURE
FIXING SCREWS /i driver. This closes t h e circuit between
D and F and w e should get rising volts
REGULATOR
w i t h rising speed, thus proving the
FRAME
1
I
contacts are burnt o r corroded.

--

E. Voltage does n o t rise w i t h Check air-gap Settings Types MCRI,


engine speed, o r is erratic. MCR2, RF95, 96, 97, RB106/1. Insert
a 0.020'' feeler gauge between the
crank o f the armature and the L-
shaped frame, and 0.012-0.020" gauge
between the t o p o f the core and the
underside of the brass shim o n the
armature. Loosen the screws holding
FIXED CONTACT 0.006'~0.017" the regulator armature to the t o p o f
BRACKET W I T H ARMATURE the L-shaped frame. Press downwards
PRESSED TO CORE
and backwards. Tighten the screws
and check that clearances are as
Diagram 1. shown i n diagram 1.
VOLTMETER CONNECTION 1 READING ACTION

Types RF95/3, RB106/2, RBI07 and


ALTERNATIVE COPPER RBI 08.
SEPARATION ON Slacken the fixed contact screw and
B O B B I N CORE
unlock armatgre securing screws.
ARMATURE ASSEMBLY FIXED COPUTACT
SECURING SCRiWSz& I-'ADJUSTMEl\T Insert appropriate feeler gauge be-
' IDfi.
m-!i.: SCRE'N DISC TWO WIPE, %urn tween armature and core face. Press
ARMATURE
armature down squarely against the
CORE TYPE OF SEPAPATION S x / gauge and re-tighten securing screws.
DISC OR TWO W I W - - -0.015'
W i t h gauge in position, screw the
AND
fixed contact down until i t just
WPPFR touches the moving contact and
SEPAR4TION
tighten lock nut, see diagram 2.
Diagram 2. Reset the voltage adjusting screw as
described under 6B.

TEST 7. Battery voltage. Proving that circuit from battery


Remove card from between cut-out through ammeter t o A terminal i s
contacts. O.K. Proceed t o Test 8.
Connect voltmeter t o terminal A on
control box and a good ground.
Engine stationary.

TEST 8. A. As cut-out closes the reading should Cut-out i s in order. Proceed t o Test 9.
Leaving voltmeter connected as for increase 0.5 t o 1 volt above battery
Test 7. Start engine and watch voltage, and increase t o the regulator
voltmeter. setting in Test 6.

B. N o voltage o r very low voltage is Clean and adjust cut-out contacts so


recorded when cut-out ~ o i n t sclose. that they meet correctlv.
VOLTMETER CONNECTION 1 READING
I ACTION

TEST 9. A. Cut-out points close when voltage Cut-out is in good order.


Connect one lead of voltmeter t o D is within the following limits :
terminal of regulator or t o the regu-
lator frame itself. 6 volt 12 volt
Other voltmeter lead t o agood ground. 6.3-6-7 12.7-1 3.3

6. Cut-out points close outside above Adjust by turning adjusting screw in


limits. t o increase o r out t o decrease the
setting. Re-test with voltage rising
from zero.

C. Cut-out does not close. Fit replacement unit.

THE F U N C T I O N OF THE FUSES IN T H E AUXlLlARY CIRCUITS


IN 12 VOLT SYSTEMS
Two fuses are incorporated in RF95 control boxes. The main feed i s via the ammeter t o the A terminal of the control
box, then through the series winding in the box t o A1 terminal. Terminal A1 is also the feed t o the ignition switch and from
there t o A3 via internal connections in the control box through the fuse t o A4 terminal. Any accessories connected t o A2 will
w o r k irrespective of the ignition switch position. Accessories connected t o A4 will operate only when the ignition i s switched
on,
The system is similar on RF96, 86106 and RE310612 control boxes, but the fuses are mounted on a separate b a k e
PART 3
MODEL RB310 REGULATOR- SINGLE C O N T A C T 3 B O B B I N TYPE

C U R R E N T VOLTAGE CONTROL REGULATOR TESTS WITH UNIT IN POSilPlON

Instruments required : Moving coil Ammeter 0-40 amperes.


Moving coil Voltmeter 0-20 volts.

The Current Regulator is adjusted, before leaving the factory, t o suit the rated output o f the generator which it is t o
control. I t is important therefore, that the Model o f the generator is carefully noted before commencing the tests. This is
stamped on the yoke of the generator.

fernperature C o r r e c t i o n Factor
Corrections t o be made t o the open-circuit voltage limits when checking o r adjusting settings at temperatures other
than 20°C (68°F) are as follows:-
For every 10°C (18°F) above 20°C,, subtract
0.1 volt f r o m the 6-volt limits
0.2 volt from the 12-volt limits

Conversely, the same corrections must be added for every 10°C below 20°C.

For generator tests, repeat Tests 1 - 4, o f Part 1, then proceed t o Test 5, o n page 11.

page 1 0
!
AMMETER CONNECTION i READING ACTION
I

TEST 5 : Current Regulator. i; A. W i t h generator at full charging


speed, approx." 4,500 revlmin, the
Current regulator i s i n order. Proceed
t o Test 6.
Reconnect ' D ' and F leads t o generator current reading is w i t h i n the follow-
terminals. ing limits: *4,000 revlrnin for C48.
For generator Models:
Remove control box cover. C40/1 12V:20amps.f1 amp.
(with 6" fan).
Short circuit voltage regulator contacts 1 C40/1 12V:22 amps.fl amp.
w i t h a crocodile clip connected (with 5" fan).
across contact plate and frame o f
regulator.
~
I
C42
(Easidrive) 12V:35 amps.& 4 amp.
C40AL 1 2 V : l l amps.&l amp.
Disconnecr. lead frcm terminal B (Bat-
tery) and connect this lead t o nega-
~: C40 L
C40LQ
12V:25 amps. f 14 amps.
12V:25 amps.&lQ amps.
tive ammeter lead. C42 12V:30 amps.& + amp.

Connect positive ammeter lead t o


1 C45PV-5
C45PV-5
6V:33 amps.&l+ amps.
12V:22 amps.* l amp.
terminal B. C45PV-6 12V:25 amps.51 amp.

T o load the generator switch o n head-


C45PVS-6 12V:25 amps.&l amp.
C39Q 32V:19 arnps.&l amp.
~
lights, etc. and start engine. C39PV-2 12V:19 amps.&l amp. 1
I C47
C48
12V:30amps.~l~amps.I
12V:35 amps.&I+ amps.
I
(Do not switch lights o n after start- i
! ing engine otherwise the bulbs may I- -- -

burn out.) Adjust reguiator by turning the adjust-

11- 5. Current remains constant but not


ing screw clockwise t o increase o r
anti-clockwise t o reduce the charging
I w i t h i n limits. rate.
page 11
AMMETER CONNECTION READING ACTION

TEST 5 (continued). C. Current erratic o r cannot be ad- Check air-gap setting (see diagram 3),
justed w i t h i n limits. unlock and screw back fixed contact
CURRENT REGULATOR and current adjustment screws. Slack-
ARMATbRE ASSEMBLY FIXED CONTAC?
en off armature assembly securing
SECURiPIG SCREWS ADJUSTMENT screws. Insert appropriate gauge be-
tween armature and copper disc o n
top o f coil. Press armature d o w n
TENSION
SPRING
_ squarely against gauge and re-tighten
securing screws.
Re-adjust current as i n B and if still n o t
CURRENT A ~ J U S T M E N T SCREW within limits, fit a replacement unit.
AND LOCKING NUT

ALTERNATIVE COPPER
SEPARATION O N

DISC SQUARE

ARMATURE
F-T
GI\UGE
SEPARATION

DlSC
SQUARE

Diagram 3.

page I 2
VOLTMETER CONNECTION READING ACTION

TEST 6 : Voltage Regulator. A. Voltage rises steadily with generator Regulator in order.
running at about* 3,000 rev/min.
Remove test ammeter and leave the B Voltage should remain steady within Proceed t o Test 7.
(Battery) lead disconnected. Also the following limits:
remove clip across contact plate. Ambient Temp. 6 volt C/Box I 2 volt C/Box

Connect voltmeter between D ter-


minal and ground.
VOLTAGE REGULATOR ~ ~

ARMATURE
ASSEMBLY
(REAR VIEW) ALTERNATIVE COPPER W i t h increased speed, voltage does
SEPARATION ON
B O B B I N CORE not increase more than 1-13 volts.
"1,500 rev/min for C47 and C48.
DISC SQUARE
I') i.1 B. Voltage remains constant but out- Adjust regulator by turning the adjust-
side the given limits. ing screw clockwise t o increase and
0 I - METAL
BRIGHT U N P L A T E D A ) anti-clockwise t o decrease the setting.
OR COPPER PLATED ( 6)

ARMATURE

C. Voltage does not rise with engine Check air-gap and adjust in similar
speed o r i s erratic. manner t o Test 5 (C) (see diagram 4).
Re-adjust voltage as i n B above and if
still not within limits, fit replacement
unit.
Diagram 4.

page I 3
ACTION
--
VOLTMETER CONNECTION READING
-
TEST 6 (continued). D. Rising volts w i t h rising engine, Check ' D ' and F ' leads for short-
speed up t o 3,000 rev/min and circuit, if O.K. suspect broken shunt
BOBBIN CORE
FIXED CONTACT beyond. winding i n regulator bobbin. Shunt
\ ADJUSTMENT
windings o n both voltage regulator
and cut-out bobbins are t o common
URE ASSEMBLY
earth. Hold a screwdriver near top
-TENSION SPRING of voltage and cut-out bobbins and
test for magnetic pull.

VOLTAGE ADJUSTMENT SCREW


A N D LOCKING NUT
If no pull check for open circuited
ground !ead o r shunt winding.

If defective fit replacement regulator.

Circuit from battery t o regulator i n


TEST 7. Battery Voltage. order.
Proceed t o Test 8.
Re-connect 5 lead t o regulator. Con-
nect voltmeter t o B terminal and t o
a good ground. Engine stationary.

page 14
VOLTMETER CONNECTION READING ACTION
--
TEST 8. A. As cut-out closes, reading increases Cut-out is in order.
t o 0.5 t o 1.0 volts above battery Proceed t o Test 9.
Leaving voltmeter connected as for voltage and increases as speed i s
Test 7, start engine and slowly increased t o the regulator setting
increase speed and watch voltmeter. voltage in Test 6.

Clean and adjust cut-out contacts so


B. N o voltage o r very l o w voltage is
recorded when cut-out points close. that they meet correctly. With
0.010" gauge between armature and
bobbin core face contacts should be
just touching.

TEST 9. A. Cut-out points close when voltage is Cut-out i n good order and correctly set
within the following limits : Proceed t o FINAL CHECK.
Connect one lead o f voltmeter t o D
terminal o f regulator and other volt- 6 volt 12 volt
meter lead t o a good ground. 6.3-6.7 12-7-1 3-3

B. Cut-out points close outside above


limits. Adjust by turning adjustment screw i n
t o increase o r o u t t o decrease setting.

C. Cut-out does n o t close. Fit replacement unit.

page 15
AMMETER CONNECTION READING ACTION

TEST 10. FINAL CHECK. As speed increases cut-out closes between


12.7-13.3 volts and charging rate builds
Leave voltmeter connected as for up with increasing speed.
Test 9.
Ammeter reading equals maximum rated
Insert ammeter again between terminal output of the generator.
B and A cable as in Test 5.

Steadily increase engine speed and


watch both meters.

Switch on full lighting load.

METRIC EQUIVALENTS
&" dia. =2-38 mm. 0.005" = 0.127 m m. 0.030" = 0.76 m rn.
0.006" = 0-152 rnrn. 0.032" = 0.81 mm.
0.01 0" = 0.25 mm. 0.045" = 1-04 m m.
0-015" = 0.396 mm. 0.049" = 1-24 m m.
0.020" = 0-51 m rn. 0.1 50" = 3-8 m m.
&" dia. = 1-98 mm. 0.025" = 0.635 mm.

page 16
PART 4
M O D E L RB340 R E G U L A T O R - S I N G L E C O N T A C T 3 BOBBIN TYPE
CURRENT VOLTAGE CONTROL REGULATOR TESTS WBTH UNIT IN POSITION
Instruments required : Moving Coil Ammeter 0 - 40 amperes
Moving Coil Voltmeter 0 - 20 volts
Special Tool Part No. 543 817 42

Except for adjustment of the cut-out relay drop-off voltage, which is effected by bending the fixed contact bracket,
electrical settings are made by turning toothed adiustment cams carried o n the front limb o f each magnet frame. A special
t o o l is available for this purpose. Back air gaps are fixed and non-adjustable and the only mechanical settings that may be
required comprise simple adjustments t o the armature-to-bobbin core air gaps.

The Current regulator i s adjusted, before leaving the factory, t o suit the rated output o f the generator which it is t o
control. The nominal setting is rubber-stamped either o n the underside of the '8-8' terminal plate o r o n the cover. In addition
a list o f Lucas generators together w i t h their rated output is given i n the appropriate section o f this booklet. The model
o f t h e generator, which is stamped on the yoke o f the machine can be noted before commencing the tests.

Temperature Correction Factor


Corrections t o be made t o the open-circuit voltage limits when checking o r adjusting settings at temperatures other
than 20°C (68°F) are as follows:-

For every 10°C (18°F)above 20°C subtract 0.2 volt from the 12-volt limits
Conversely, the same corrections must be added for every 10°C below 20°C

For generator tests, repeat Tests 1 - 4, o f Part 1, then proceed t o Test 5, on page 18.
page 17
AMMETER CONNECTION READING ACTION

TEST 5 : Current Regulator. A. Ammeter pointer should be steady Current regulator i s i n order, proceed
Reconnect leads t o D and F on and indicate a current equal t o t o Test 6.
generator. maximum rated output of generator:
Remove control box cover. C40/1 12V:20 amps.&l amp.
Short o u t voltage regulator contacts (with 4h" dia. fan)
w i t h a bulldog clip. C40/1 12Y:22 amps.&l zmp.
Using a suitable 'jumper lead' connect (with 5" dia. fan)
the leads t o the load side o f 0 - 4 0 C45PV-5 12V:22amps.fl amp.
ammeter. C45PV-6 12V:25 amps. fI amp.
Connect other lead o f ammeter t o one C45PVS-6 12V:25 amps.i-1 amp.
of control box terminal blzdes B-B. C39PV-2 12V:19 amps.& I amp.
N o t e : It is important t o ensure that C47 12V:30 amps.&l+ amps.
terminal B-B carries only this C48 12V:35 amps.&l+ amps.
one connection. A l l other C40AL 1 2 V : l l a m p s . i l amp.
load connections (including the C40 L 12V:25 amps.*I amp.
ignition coil feed) must be C40LQ 12V:25 arnps.i-1 amp.
made t o the battery side o f the
ammeter.
C42
C42
22V:30 anips.&1+ amps. SHORT CIRCUITING~
Switch on lights t o ensure generator (Easidrive) 12V:35 amps.&l+ amps. V R CONTACTS.
develops its rated output. - --

Start engine and r u n generator at B. Ammeter pointer remains steady Turn the current adjustment cam until
4,500 rev/min (4,000 rev/min for but current reading outside limits. correct setting is obtained - t u r n i n g
C48). the tool clockwise t o raise the setting
o r anti-clockwise t o lower it.

page 18
AMMETER CONNECTION READING ACTION

TEST 5 (continued). 1 C. A n unsteady reading, i.e. pointer i s


fluctuating more than & 1 amp.
Check for d i r t y contacts, o r foreign
matter i n air gaps.
I
If in order, check air gap setting
between armature and bobbin core
as follows :-
Turn the adjustment cam t o the point giving
minimum lift t o the armature tensioning
spring, by turning the tool t o the fullest
extent anti-clockwise.
Slaclten the adjustable contact loclting nut and
screw back the adjustable contact.
Insert a flat steel feeler gauge of 0.045" (1.04
mm.) thicltness between the armature and
the copper separation on the core face. The
gauge should be inserted as far back as the
two rivet heads on the underside of the
armatu re.
CLIP Retaining the gauge in position and pressing
squarely down on the armature, screw in the
adjustable contact until it just touches the
armature contact.
Re-tighten the loclting nut and withdraw the
gauge.
CURRENT REGULATOR

VOLTAGE REGULATOR
i Carry out the electrical setting procedure.
If still not within limits fit a replacement unit.

page 19
VOLTMETER CONNECTION 1 READING ACTION

TEST 6 : Voltage Regulator. A. Voltmeter reading should be steady Voltage regulator i s in order. Proceed
Remove test ammeter, and leave B-B and lie between the appropriate t o Test 7.
leads disconnected. limits :
N o t e : It will be necessary t o join the Ambient Temp. Setting
ignition and battery feeds to- 10°C (50°F) 14.9 - 15.5 volts
gether with a suitable 'jumper 20°C (68°F) 14-7- 15.3 volts
lead', t o enable the engine t o 30°C (86°F) 14.5 - 15.1 volts
be run. 40°C (104°F) 14.3 - 14.9 volts
Also remove bulldog clip from across
contacts.
Connect voltmeter between D ter- V R AND C.R
minal and ground (earth). ARMATURE TO BOBBIN CORE GAP
Note: A convenient method is t o
withdraw the ignition warning 0.045" 0 - 0 4 9 "
light feed from control box ,,I
t&minal WL and t o clip volt-
meter lead of appropriate pol-
arity t o the small terminal
blade then exposed, this ter-
minal being electrically com-
mon with terminal D.
Start the engine and run the generator
at 1,500 rev/min for C48, 4,500 rev/
min for C42,3,000 rev/min all others.
'\
CONTACT ADJUSTMENT

page 20
VOLTMETER CONNECT1ON 1 READING
I ACTION
-

TEST 6 (continued) B. Voltage reading remains constant Adjust regulator by r o t a t i n g t h e adjust-


b u t outside appropriate limits. m e n t cam. T u r n t h e t o o l clockwise t o
raise t h e setting o r anti-clockwise t o
l o w e r it.
~ - -

C. Rising v o l t s with r i s i n g engine, speed Check D and F leads f o r short-circuit, i f


u p to 3,000 r e v / m i n a n d b e y o n d . O.K. suspect b r o k e n s h u n t w i n d i n g i n
regulator bobbin. Shunt windings o n
b o t h voltage r e g u l a t o r and c u t - o u t
bobbins a r e t o c o m m o n earth. H o l d a
s c r e w d r i v e r near t o p o f voltage and
c u t - o u t bobbins and t e s t f o r magnetic
pull.
EXTERNAL CONNECTIONS SHOWN IN BROKEN LiNE
If n o p u l l check f o r o p e n c i r c u i t e d g r o u n d
,- - - - - - - - - - - - - -.
- - -.
....
. .
-- -.
, lead o r shunt winding.
If defective fit replacement regulator.
Check f o r d i r t y contacts, o r f o r e i g n
D. V o l t m e t e r r e a d i n g m a t t e r i n gaps.
fluctuates, i.e., If i n o r d e r check a i r gap b e t w e e n a r m a t u r e
pointer fluctuating and b o b b i n c o r e face, as follows:
m o r e t h a n 0.3-volt. Turn the adjustment cam t o the point giving
minimum lift t o the armature tensioning
spring, by turning the tool t o the fullest
I , z:: -- --_I extent anti-clockwise.
"E" VOLTAGE
;
Slacken the adjustable contact locking nut and
I ...
..I_.
RELAY REGULATOR

t- - - - - -.: - - - - - - - - - - - - - - - screw back the adjustable contact.


D 0 a.vL insert a flat steel feeler gauge of 0.045" (1.04
-N mm.) thickness between the armature and
U N T i L EARL? i N 1962, THE VR. I CR MLGNLI F W E S WERE LINKED BY A CONNECTOR THROUGH WHICH
the copper separation on the core face. The
(IN THE CONTACTS CLOSE0 P O S I T I @ Y ) T H E FlELD CURRENT PAIIELI. V I A THE C.O. i CR SERIES
WINDINGS, TO TERMINAI'D: gauge should be inserted as far back as the
t w o rivet heads on the underside of the
armature. (continued)

page 21
VOLTMETER C O N N E C T I O N READING ACTION

TEST 6 (continued) D. (continued) Retaining t h e gauge i n position and pressing


squarely d o w n o n t h e armature, screw i n t h e
adjustable contact u n t i l it just touches t h e
armature contact.
Retighten t h e locking n u t and w i t h d r a w t h e
gauge.
C a r r y o u t t h e electrical setting procedure.
If still n o t w i t h i n l i m i t s fit a replacement unit.

TEST 7. Battery voltage. Circuit from battery t o regulator i s in


W i t h engine stationary. Reconnect order.
leads t o B-B terminal o n control box. Proceed t o Test 8.
Connect voltmeter between B-B ter-
minal and ground.

TEST 8. A. As cut-out closes, reading rises t o 0 Cut-out is in order. Proceed t o Test 9.


Leave voltmeter connected as for t o 1.0 volts above battery voltag
Test 7. and continues t o rise as engine spec
Start engine, and slowly increase speed, is steadily increased, u n t i l regulatc
closely watching voltmeter dial. setting voltage, as given i n Test 6,
reached.

B. N o voltage o r very l o w voltage Check for dirty o r burned contacts.


registered when cut-out contac Check for contact alignment.
close. Check that they meet correctly when
armature is pressed down, the moving
contact blade should have a deflection
of 0.01 0" - 0.020".
Armature back stop t o core air gap
should be between 0.035'' - 0.045.

page 22
VOLTMETER CONNECTION READING ACTION
- -- - - ---

TEST 9 : Cut-in Voltage. A. Voltage reading rises steadily and Cut-out i s in order. Proceed t o Final
Connect voltmeter between D on then drops slightly at the instant Check, Test 10.
control box and ground. the contacts close. The cut-in volt-
Switch on headlamps. age i s that which is indicated immedi-
Start engine and slowly increase its ately before the pointer drops back.
speed. Observe the voltmeter I t should occur between the follow-
pointer. ing limits:-
12.6 - 13.4 volts.

B. Cut-out contacts close outside limits. Adjust cut-out by rotating the adjust-
ment cam, t u r n the t o o l clockwise t o
raise the setting o r anti-clockwise t o
lower it.
CUT- OUT Again check cut-in voltage.
Repeat procedure until correct setting
obtained.

C. Cut-out contacts w i l l n o t close. Fit a replacement unit.

ARMATURE TO BOBBIN CORE GAP


(0.035"- 0.045")

page 23
VOLTMETER CONNECTION I READING ACTION

TEST 10 : D r o p off voltage. A. Opening o f contacts. indicated by Control box i n order


W i t h d r a w leads control box B-B the voltmeter pointer dropping t o
terminals. zero, this should occur between the
Connect voltmeter between B-B ter- following limits :
minals and ground. 9.3 - 11.2 volts
Start engine and run up t o 3,000 rev/
min. B. Drop-off occurs outside limits. Adjust Drop-off volts as follows :-
Slowly decelerate and observe volt- Stop engine, and adjust the drop-off
meter pointer. voltage by carefully bending the fixed
contact bracket. Reducing the con-
PHOSPHOR BRONZE
HINGE SPRING tact gap w i l l raise the drop-off
ARMATURE
\ / CONTROL voltage; increasing the gap w i l l lower
the drop-off voltage.
Re-test and, if necessary, readjust until
the correct drop-off setting is
obtained.
Note: W h e n drop-off voltage is correct
the moving contact blade should
have a 'follow through' o r blade
deflection o f 0.010" - 0.020".
The armature back stop, when free,
should give a core gap o f 0.035"
- 0.045", adjust by bending stop w i t h
a suitable tool.

BLADE \ \
FOLLOW-THROUGH'
'B%'TERMINAL FIXED CONTACT
0.010'-0.020") PLATE BRACKET

page 24
RB340 DESIGN DATA (12-volt units)
RESISTOR VALUES
(i) Contacts Resistor : Resistance Identification (ii) Swamp Resistor : Resistance in RESISTANCE OF SHUNT
in Ohms Colour (12-volt Units) Ohms WINDINGS a t 20°C (68°F)
As fitted t o units con- Measured on unit bet- Voltage
trollingl2-voltgenerators ween centre tag and Regulator: 10-8-12-0 ohms
h a v i n g 44 o h m f i e l d base : 13.25 - 14.25 Cut-out : 8.8 - 9.6 ohms
windings : 37- 43 Yellow
Replacement resistor
As fitted t o units con- measured between end
trollingl2-volt generators tags before fitting t o
having 6 ohm field unit : 53 - 57 ADJUSTMENT CAMS
windings : 55 - 65 Red Torque to
(iii) Field Parallel Resist- turn cams : 2 - 4 Ib. in.
ance : (0.023 - 0.046 kg m.)
, As fitted t o units con-
t r o l l i n g model C48
SWAMP RESISTOR CONTACTS RESISTOR generator : 37 - 43
AIR GAPS
Length
Armature back gaps (non- 0-030" - 0.035"
FIELD PARALLLL adjustable) : (0.76 - 0.9 mm.)
RESISTOR
(WHEN FITTED) Armature-to-bobbin core, 0.045" - 0.049"
VR and CR : (1.04 - 1-24 m m.)
'8-13'TERM I N A L
PLATE
Armature-to-bobbin core, 0.035" - 0.045"
Cut-out relay : (0.9 - 1.04 mm.)
8' ,F' 'WL: 'D' 'E'
zB-
'Follow-through'or blade
i
deflection of cut-out reiay 0.01 0" - 0.O2Otc
moving contact : (0.25 -,0.51 mm.)
page 25
CONTACT REPLACEMENT SETS

Contact replacement sets are supplied solely for use overseas, (ii) Discard original armature, clamp plate, and fixed contact
where special service problems are encountered. The fitting of screw and nut, or, when replacing a cut-out relay armature,
these sets involves the replacement of existing rivets w i t h screws. the 'B-B' terminal plate.
The Part Numbers of the sets are 543 820 77-8 and 9 for the
Cut-out Relay, Voltage and Current Regulators, respectively. Each (iii) Loosely assemble replacement parts t o magnet frame, noting
set comprises an Armature Assembly, Clamp,Plate, Fixed Contact that the armature hinge spring has open-ended slotted fixing
Screw and N u t (or, for cut-out relays, a B-B' Terminal Plate holes t o facilitate fitting under the clamp plate.
Assembly), and t w o 5 BA screws with associated spring washers D o not insert the fixed contact screw of the VR o r CR more
and lock nuts (two extra screws, spring washers and lock nuts being than I+ t o 2 turns at this stage.
provided for the cut-out relay t o secure the above terminal plate (iv) When applicable, fit and tighten replacement 'B-B' terminal
assembly). plate, inserting the securing screws from the supper side of
the control box base plate.
IDENTIFICATION OF ARMATURE ASSEMBLIES
(v) Insert a 0.032 (0.81 mm.) feeler gauge approximately half-way
(i) Cut-out relay Moving contact carried on phosphor bronze up the back air gap.
armature : blade.
(vi) Insert a 0,045 (1.04 mm.) feeler gauge in the armature-to-
Phosphor bronze hinge spring unpierced.
bobbin core gap as far back as the t w o tension spring rivets.
Blued steel control spring backed w i t h
bi-metal spring (high expansion side lower- (vii) Press the armature squarely down towards the bobbin core
most). and back towards the magnet frame, firmly trapping both
gauges.
(ii) Voltage regulator Bi-metal hinge spring pierced with central
armature : 0.150 (3.8 mm.) hole. (High expansion (viii) Tighten the armature assembly securing screws.
side of bi-metal uppermost).
(ix) Withdraw gauges and carry out mechanical and electrical
(iii) Current regulator adjustments.
armature : Blued steel hinge spring, unpierced.
ADJUSTMENT SEQUENCE
FITTING ARMATURE ASSEMBLIES After fitting a replacement contact set (or sets), the regulator o r
cut-out relay concerned must be adjusted both mechanically and
(i) Carefully remove existing rivets, using a file, centre-punch, electrically. The order of electrical settings (when all three arma-
twist drill (&" diameter; 2.38 mm.), and a parallel-sided tures have been replaced) being, first, the voltage regulator, secondly
punch (&" diameter; 1.98 mm.), i n that order. the cut-out relay and, thirdly, the current regulator.

page 26

Vous aimerez peut-être aussi