UVIF/ICM/1704/UK

C5 - Communication with the BMS


C5.1 - Communication principles
Halton Foodservice Control Platform (FCP) Building Management System (BMS)
Protocol interface: MODBUS Protocol interface: MODBUS
from Halton's Touch Screen
Protocoles: Use a gateway (to Bacnet, Lon etc)
Support: ETHERNET TCP/IP
Support: ETHERNET TCP/IP
Serial RS485 or RS232
Serial RS485 or RS232

ADDITIONAL CONTROLLERS HOOD / VENTILATED CEILING CONTROLLERS

When they are equipped with one or several of the following technologies:
- Water Wash / Water Mist control cabinets; - Capture RayTM technology;
M.A.R.V.E.L. Other
- VAV controller; - M.A.R.V.E.L. Demand Controlled Ventilation system;
calculator Controllers - KGS duct safety system; - Water Wash / Water Mist technology.
- Auxiliary controller & GSM Module;
LON

RS485

etc Room temp. sensors


...
Exhaust plenum controllers Max

LON T1 T2 T3 T4 EC1 EC2 EC2 EC24


adapter RS485 RS485

HALTON AIR HANDLING UNITS


POLLUSTOP* AEROLYS*
RS485 Fan Fan
COM2 RS232

COM3 RS485

controller controller

Filters Filters
UV-LIGHT WASHING M.A.R.V.E.L. Pollustop
K1 (4 pins) MODBUS RTU RS232 F.O.R.M.(1) controller controller
controller
Touch Screen v6
October 2010

ETHERNET
www.halton.com
* Or Extenso in case of combined
Exit Settings Log off Admin
exhaust/supply AHU
VNC connection to Touch Screen
To BMS (Read only)

To Halton F.O.R.M. server

K5 (4 pins) MODBUS RTU RS485

ITE IES
TS IT
J EC ACIL
RO NF
P
HALTON LTO
HA
OTHERS

Gateway Firewall Firewall


network

network
Private

Private

F.O.R.M.(1)
ETHERNET switch ETHERNET switch server

Building Management System


(BMS)

Refer to the ICMs of the all the systems and technologies that
Halton Customer Service
can be combined with M.A.R.V.E.L.
Authorised Partner
F.O.R.M.(1) Platform

Installation, Commissionning and Maintenance


74 UVI / UVF - Capture Jet™ hood with integrated Capture Ray™ technology
UVIF/ICM/1704/UK
C5.2 - Statuses and values available
Table 1 - Status information available on Halton Foodservice Control Platform
(concerns only the configurations including Halton’s Touch Screen)

CRay = Capture Ray™ technology (UV) KGS = Duct Safety System (grease sensors)
MRV = M.A.R.V.E.L. technology PST = PolluStop (exhaust AHU)
CCW = Water Wash / Water Mist control cabinet ARL = Aerolys (supply AHU)

Version 15 / 32 x byte = 256

Bit Digital status Byte Concerns Controller Description Comments / Range

1 Pressure alarm #1 UV, MRV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
2 Filter Safety alarm #1 UV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
3 UV Safety alarm #1 UV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
4 UV #1 alarm #1 UV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
5 UV #2 alarm #1 UV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
6 UV #3 alarm #1 UV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
7 UV #4 alarm #1 UV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
8 Communication alarm #1 UV, MRV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
9 Actuator Alarm #2 MRV LHC-1.MU1 #1 Exhaust plenum controller 0=Ok, 1=Fault
10 IR activity #2 MRV LHC-1.MU1 #1 Exhaust plenum controller 1=Active
11…20 Same as for bits 1...10 #2...#3 UV, MRV LHC-1.MU1 #2 Exhaust plenum controller Same as for bits 1...10
21…30 Same as for bits 1...10 #3...#4 UV, MRV LHC-1.MU1 #3 Exhaust plenum controller Same as for bits 1...10
31…40 Same as for bits 1...10 #4...#5 UV, MRV LHC-1.MU1 #4 Exhaust plenum controller Same as for bits 1...10
41…50 Same as for bits 1...10 #6...#7 UV, MRV LHC-1.MU1 #5 Exhaust plenum controller Same as for bits 1...10
51…60 Same as for bits 1...10 #6...#8 UV, MRV LHC-1.MU1 #6 Exhaust plenum controller Same as for bits 1...10
61…70 Same as for bits 1...10 #8...#9 UV, MRV LHC-1.MU1 #7 Exhaust plenum controller Same as for bits 1...10
71…80 Same as for bits 1...10 #9...#10 UV, MRV LHC-1.MU1 #8 Exhaust plenum controller Same as for bits 1...10
81…90 Same as for bits 1...10 #11...#12 UV, MRV LHC-1.MU1 #9 Exhaust plenum controller Same as for bits 1...10
91…100 Same as for bits 1...10 #12...#13 UV, MRV LHC-1.MU1 #10 Exhaust plenum controller Same as for bits 1...10
101…110 Same as for bits 1...10 #13...#14 UV, MRV LHC-1.MU1 #11 Exhaust plenum controller Same as for bits 1...10
111…120 Same as for bits 1...10 #14...#15 UV, MRV LHC-1.MU1 #12 Exhaust plenum controller Same as for bits 1...10
121…130 Same as for bits 1...10 #16...#17 UV, MRV LHC-1.MU1 #13 Exhaust plenum controller Same as for bits 1...10
131…140 Same as for bits 1...10 #17...#18 UV, MRV LHC-1.MU1 #14 Exhaust plenum controller Same as for bits 1...10
141…150 Same as for bits 1...10 #18...#19 UV, MRV LHC-1.MU1 #15 Exhaust plenum controller Same as for bits 1...10
151…160 Same as for bits 1...10 #19...#20 UV, MRV LHC-1.MU1 #16 Exhaust plenum controller Same as for bits 1...10
161…170 Same as for bits 1...10 #21...#22 UV, MRV LHC-1.MU1 #17 Exhaust plenum controller Same as for bits 1...10
171…180 Same as for bits 1...10 #22...#23 UV, MRV LHC-1.MU1 #18 Exhaust plenum controller Same as for bits 1...10
188 Comm. alarm #24 MRV CAL-3H Calculator 0=Ok, 1=Fault
191 Grease sensor alarm 1 #24 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
192 Grease sensor alarm 2 #24 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
193 Grease sensor alarm 3 #25 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
194 Grease sensor alarm 4 #25 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
195 Grease sensor alarm 5 #25 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
196 Grease sensor alarm 6 #25 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
197 Grease sensor alarm 7 #25 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
198 Grease sensor alarm 8 #25 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
199 Grease sensor alarm 9 #25 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
200 Grease sensor alarm 10 #25 KGS LHC-1.M4U KGS controller 0=Ok, 1=Fault
201 Filter #1 Dirty #26 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault
202 Filter#1 Overload #26 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault
203 Filter#2 Dirty #26 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault
204 Filter#2 Overload #26 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault
205 Communication Alarm #26 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault
206 T1 comm. alarm #26 MRV LHC-1.TH1 RH & Temp sensors 0=Ok, 1=Fault
207 T2 comm. alarm #26 MRV LHC-1.TH1 RH & Temp sensors 0=Ok, 1=Fault
208 T3 comm. alarm #26 MRV LHC-1.TH1 RH & Temp sensors 0=Ok, 1=Fault
209 T4 comm. alarm #27 MRV LHC-1.TH1 RH & Temp sensors 0=Ok, 1=Fault
211 Water Temp. Warning #27 CCW LHC-1.MU4 WWash & KGS controller 0=Ok, 1=Fault
212 Water Press. Alarm #27 CCW LHC-1.MU4 WWash & KGS controller 0=Ok, 1=Fault
213 Fire Alarm #27 CCW LHC-1.MU4 WWash & KGS controller 0=Ok, 1=Fault
214 Emergency Stop #27 CCW LHC-1.MU4 WWash & KGS controller 0=Ok, 1=Fault

* Exhaust plenum controllers do not play a direct role in the operation plenums equipped with the Capture Ray™ and/or M.A.R.V.E.L.
of the CCW Water Wash Control Cabinet. They can alternatively be technology thus avoiding to connect the valves to the CCW cabinet.
used to control locally the solenoid valves installed on the exhaust

Installation, Commissionning and Maintenance


75 UVI / UVF - Capture Jet™ hood with integrated Capture Ray™ technology
UVIF/ICM/1704/UK
Bit Digital status Byte Concerns Controller Description Comments / Range

215 Detergent Level Warning #27 CCW LHC-1.MU4 WWash 0=Ok, 1=Fault
216 Valve Fault #27 CCW LHC-1.MU4 WWash 0=Ok, 1=Fault
0=Ok, 1=Fault, canceled, no washing
217 Washing successfully #28 CCW LHC-1.MU4 WWash
yet
218 Communication Alarm #28 CCW LHC-1.MU4 WWash 0=Ok, 1=Fault
0=Washing not active and no
219 Wash Request Status #28 CCW LHC-1.MU4 WWash wash request, "1"=washing active
or wash request active
220 Wash Permit HW Status #28 CCW LHC-1.MU4 WWash 0=Inactive, 1=Active
221 Filter#1 Dirty #28 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
222 Filter#1 Overload #28 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
223 Filter#2 Dirty #28 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
224 Filter#2 Overload #28 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
225 Filter#3 Dirty #29 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
226 Filter#3 Overload #29 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
227 Filter#4 Dirty #29 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
228 Filter#4 Overload #29 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
229 Communication Alarm #29 PST LHC-1.MU3 PST filter controller 0=Ok, 1=Fault
231 Fan Stop #29 PST LHC-1.MU2 PST/ARL fan controller 0=Ok, 1=Fault
232 Fire Alarm #29 PST LHC-1.MU2 PST/ARL fan controller 0=Ok, 1=Fault
233 Shutdown #30 PST LHC-1.MU2 PST/ARL fan controller 0=Ok, 1=Fault
234 Inverter Alarm #30 PST LHC-1.MU2 PST/ARL fan controller 0=Ok, 1=Fault
235 Air Proved #30 PST LHC-1.MU2 PST/ARL fan controller 0=Ok, 1=Fault
239 Communication Alarm #30 PST LHC-1.MU2 PST/ARL fan controller 0=Ok, 1=Fault
241 UV lamp maintenance #31 UV LHC-1.MU1 Exhaust plenum controller 0=Ok, 1=Fault
242 UV lamp replacement #31 UV LHC-1.MU1 Exhaust plenum controller 0=Ok, 1=Fault
243 DI5_IN7_ww #31
244 DI5_IN8_ww #31
245 FireAirDamperOK #31 0=Ok, 1=Fault
246 FireAirDamperAlarm #31 0=Ok, 1=Fault
247 ComonAlarm #31 0=Ok, 1=Fault
253 Filter#3 Dirty #32 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault
254 Filter#3 Overload #32 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault
255 Filter#4 Dirty #32 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault
256 Filter#4 Overload #32 ARL LHC-1.M3U ARL filter controller 0=Ok, 1=Fault

Installation, Commissionning and Maintenance


76 UVI / UVF - Capture Jet™ hood with integrated Capture Ray™ technology
UVIF/ICM/1704/UK
Table 2 - Values available on Halton Foodservice Control Platform
(concerns only the configurations with Halton’s Touch Screen)

CRay = Capture Ray™ technology (UV) KGS = Duct Safety System (grease sensors)
MRV = M.A.R.V.E.L. technology PST = PolluStop (exhaust AHU)
CCW = Water Wash / Water Mist control cabinet ARL = Aerolys (supply AHU)
Version 15 / 100 x word

Address Value Concerns Controller / Component Description Range Scale Unit

1 Actual Pressure CRay, MRV LHC-1.MU1 #1 Exhaust plenum controller 0..1000 1:1 Pa
2 Actual AirFlow Cray, MRV LHC-1.MU1 #1 Exhaust plenum controller 0..10000 1:1 m3/h
3 Damper Position MRV LHC-1.MU1 #1 Exhaust plenum controller 0..10000 100:1 %
4 Actual Temperature MRV LHC-1.MU1 #1 Exhaust plenum controller 0..10000 100:1 °C
5 Operating Hours#1 CRay LHC-1.MU1 #1 Exhaust plenum controller 0..65535 1:1 h
6…10 Same as for [1...5] LHC-1.MU1 #2 Exhaust plenum controller Same as for [1...5]
11…15 Same as for [1...5] LHC-1.MU1 #3 Exhaust plenum controller Same as for [1...5]
16…20 Same as for [1...5] LHC-1.MU1 #4 Exhaust plenum controller Same as for [1...5]
21…25 Same as for [1...5] LHC-1.MU1 #5 Exhaust plenum controller Same as for [1...5]
26…30 Same as for [1...5] LHC-1.MU1 #6 Exhaust plenum controller Same as for [1...5]
31…35 Same as for [1...5] LHC-1.MU1 #7 Exhaust plenum controller Same as for [1...5]
36…40 Same as for [1...5] LHC-1.MU1 #8 Exhaust plenum controller Same as for [1...5]
41…45 Same as for [1...5] LHC-1.MU1 #9 Exhaust plenum controller Same as for [1...5]
46…50 Same as for [1...5] LHC-1.MU1 #10 Exhaust plenum controller Same as for [1...5]
51…55 Same as for [1...5] LHC-1.MU1 #11 Exhaust plenum controller Same as for [1...5]
56…60 Same as for [1...5] LHC-1.MU1 #12 Exhaust plenum controller Same as for [1...5]
61…65 Same as for [1...5] LHC-1.MU1 #13 Exhaust plenum controller Same as for [1...5]
66…70 Same as for [1...5] LHC-1.MU1 #14 Exhaust plenum controller Same as for [1...5]
71 Actual AirFlow #15 Cray, MRV LHC-1.MU1 #15 Exhaust plenum controller 0..10000 1:1 m3/h
72 Actual AirFlow #16 Cray, MRV LHC-1.MU1 #16 Exhaust plenum controller 0..10000 1:1 m3/h
73 Actual AirFlow #17 Cray, MRV LHC-1.MU1 #17 Exhaust plenum controller 0..10000 1:1 m3/h
74 Actual AirFlow #18 Cray, MRV LHC-1.MU1 #18 Exhaust plenum controller 0..10000 1:1 m3/h
75 Actual AirFlow #19 Cray, MRV LHC-1.MU1 #19 Ex haust plenum controller 0..10000 1:1 m3/h
76 Actual AirFlow #20 Cray, MRV LHC-1.MU1 #20 Exhaust plenum controller 0..10000 1:1 m3/h
77 Actual AirFlow #21 Cray, MRV LHC-1.MU1 #21 Exhaust plenum controller 0..10000 1:1 m3/h
78 Actual AirFlow #22 Cray, MRV LHC-1.MU1 #22 Exhaust plenum controller 0..10000 1:1 m3/h
79 Actual AirFlow #23 Cray, MRV LHC-1.MU1 #23 Exhaust plenum controller 0..10000 1:1 m3/h
80 Actual AirFlow #24 Cray, MRV LHC-1.MU1 #24 Exhaust plenum controller 0..10000 1:1 m3/h
81 Fan Speed MRV CAL-3H Calculator 0..10000 100:1 %
82 Max damper position MRV CAL-3H Calculator 0..10000 100:1 %
83 Room Temp. #1 MRV LHC-1.TH1 Room temp. Sensor 0..10000 100:1 °C
84 Room Temp. #2 MRV LHC-1.TH1 Room temp. Sensor 0..10000 100:1 °C
85 Room Temp. #3 MRV LHC-1.TH1 Room temp. Sensor 0..10000 100:1 °C
86 Room Temp. #4 MRV LHC-1.TH1 Room temp. Sensor 0..10000 100:1 °C
87 Water Temperature CCW LHC-1.MU4 Water Wash controller 0..10000 100:1 °C
88 Pressure Filter #1 supply ARL LHC-1.M3U ARL Filter controller 0..1000 1:1 Pa
89 FireAirDamperError Alarm damper not closed bit info for dampers 1..16
90 Pressure Filter #2 supply ARL LHC-1.M3U ARL Filter controller 0..1000 1:1 Pa
91 Pressure Filter #3 supply ARL LHC-1.M3U ARL Filter controller 0..1000 1:1 Pa
92 Pressure Filter #4 supply ARL LHC-1.M3U ARL Filter controller 0..1000 1:1 Pa
93 Pressure Filter#1 PST LHC-1.MU3 PST filter controller 0..1000 1:1 Pa
94 Pressure Filter#2 PST LHC-1.MU3 PST filter controller 0..1000 1:1 Pa
95 Pressure Filter#3 PST LHC-1.MU3 PST filter controller 0..1000 1:1 Pa
96 Pressure Filter#4 PST LHC-1.MU3 PST filter controller 0..1000 1:1 Pa
97 Fan Speed PST/ARL LHC-1.MU2 PST/ARL fan controller 0..10000 100:1 %
98 Actual Power PST/ARL LHC-1.MU2 PST/ARL fan controller 0..65535 1:1 kW
99 Airflow PST/ARL LHC-1.MU2 PST/ARL fan controller 0..65535 1:1 m3/h
100 Airflow Set point PST/ARL LHC-1.MU2 PST/ARL fan controller 0..65535 1:1 m3/h

Installation, Commissionning and Maintenance


77 UVI / UVF - Capture Jet™ hood with integrated Capture Ray™ technology