Design Calculation

Issue Date :4-Jul-16

Name of Contractor : SAMSUNG C&T - UEMB JV


Name of Project : MERDEKA PNB 118 PROJECT

Batching Plant : SITE PLANT

1.1 Characteristic Strength (Specified) = 85.00 N/mm2 Compressive Strength at 28 Days


1.2 Free Water / Cement Ratio (A) 0.290
1.3 Margin 15.00 N/mm2

2.1 Admixture Type Dosage Rate Per 100Kg Cement (mL)


Auramix 450W 630±100
Auramix 450R 770±100
2.2 Specific gravity of Cementitious OPC Slag Silica Fume
3.15 2.9 2.2
2.3 Specific Gravity of Combined Agg. (D) 2.61 ( S. S. D. )

3.1 Maximum Aggregate Size (Specified) 20 mm


3.2 Grading of Fine Aggregate B.S. 882:1983
3.3 Proportion of Fine Aggregate (B) 46 %
3.4 Proportion of Coarse Aggregate (C) 54 %

4.1 Workability : Slump Flow (Specified) 600 - 700


4.2 Air Content (Estimated) (E) 2.0 % 20.0 Litres Abs./M3
4.3 Free Water Requirement (F) 151.0 kg/M3 151.0 Litres Abs./M3
4.4 Cementitious Content (G) 520.0 kg/M3 178.2 Litres Abs./M3
4.5 Total Aggregate Content (H) 1699.0 kg/M3 651.0 Litres Abs./M3
4.6 Total Concrete Volume 1000.2 Litres Abs./M3
4.7 Fine Aggregate ( H X B% = J ) 782.0 kg/M3
4.8 Coarse Aggregate ( H X C% = K ) 917.0 kg/M3

5.1 Designed Density of Concrete (F+G+J+K) 2370.0 kg/M3

SUMMARY C85 Flow Special


Specified Flow 600 - 700 mm

Batch Weights (SSD) for one cubic metre of concrete

Cementitious (OPC Kanthan) 208.0 kg/M3


(Slag CIMA) 270.0 kg/M3
(Silica Fume) 42.0 kg/M3
ICE/ Chill Water 151.0 kg/M3
Fine Aggregate (Batang Berjuntai) 782.0 kg/M3
Coarse Aggregate (20mm Hulu Langat) 642.0 kg/M3
(10mm Hulu Langat) 275.0 kg/M3
Admixture : PCE. Admixture (Auramix 450W) 3.28±0.52 litre/M3
Admixture : PCE. Admixture (Auramix 450R) 4.00±0.52 litre/M3

Mix Code: 8553SL8891


Note:
a) Based on specification Section 03 30 00, Proposed 118 Storey Tower
b) 28 Days compressive cube strength compliance
c) 2 hours slump retention
d) Ice/ Chill Water shall be added to achieve target fresh concrete temperature of ≤ 270C. Total Ice and Chill water amount shall
be maintained at 151 kg/m3.
e) Water content declared is exclusive of water content from admixture
Remarks :
The above mix design is submitted for your consideration and may be adjusted / modified according to BS5328/MS
in order to maintain consistency depending on materials quality, weather and site conditions