Sheet 1 of 3
Owner
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT
1 AIM
The objective of this calculation is to document the design of the Kandhkot Field Gas Compression Station Project 240 V AC
UPS Electrical System.
2 REFERENCES
1 240V AC UPS Single Line Diagram - DWG-00-E-0008
3 ASSUMPTIONS
1 Power factor is assumed as 0.8 lagging for all connected loads.
CONTRACTOR
Sheet 2 of 3
OWNER CONTRA
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT
EU-5401/ EU-5402 UPS (240 VAC UPS & ED) BUDGET NAMEPLATE
Remarks
Tag Name Description Breaker Rating Duty Volts Amps Watts
1 PCS Cabinet 20 A 2P 1.0 240 14.06 2.7 kW
2 PCS Engg & Operator Stations 16 A 2P 1.0 240 11.98 2.3 kW
3 CSS Engineering & SOE Station 10 A 2P 1.0 240 6.77 1.3 kW
4 CSS Cabinet 50 A 2P 1.0 240 30.21 5.8 kW
5 PAGA System 20 A 2P 1.0 240 15.10 2.9 kW
6 PABX System 6 A 2P 1.0 240 1.50 0.288 kW
7 Weather Monitoring System 6 A 2P 1.0 240 1.04 0.2 kW
8 CCTV system 6 A 2P 1.0 240 2.19 0.42 kW
9 F&G System 6 A 2P 1.0 240 4.69 0.9 kW
10 Bulding fire & smoke system 6 A 2P 1.0 240 4.69 0.9 kW
11 Diesel Generator Panel Controls 6 A 2P 1.0 240 2.60 0.5 kW
12 Flare Ignition System 6 A 2P 1.0 240 2.08 0.4 kW
13 UCP workstation 6 A 2P 1.0 240 2.08 0.4 kW
14 Train A Control Cabinet 16 A 2P 1.0 240 10.42 2 kW
15 Train A Control Cabinet 6 A 2P 1.0 240 0.52 0.1 kW
16 Train B Control Cabinet 16 A 2P 1.0 240 10.42 2 kW
17 Train C Control Cabinet 16 A 2P 1.0 240 10.42 2 kW
Total Current from Single Phase Loads for each UPS 130.77 Amps
Sheet 3 of 3