Académique Documents
Professionnel Documents
Culture Documents
(∆T ) s hL
=
( ∆T ) c k
It can be checked that the term hL/k is dimensionless. This dimensionless quantity is
named as Biot number. If this number is small then (∆T)s will be small and so the temperature
difference in the body is small and so it can be taken as the check for the applicability of
lumped parameter model. If Biot number is less than 0.1, it has been proved that this model
can be used without appreciable error. As this model is simpler to apply, it is worthwhile
checking in all cases for the value of Biot number before attempting the solution. If Bi < 0.1,
then the simpler model can be adopted.
6.2.2. Electrical Analogy: Now going back to equation (6.4), the term (hAs/ρVc) can be used
to visualise an electrical analogy in terms of a
capacitance resistance circuit and the process of heating
V C
1
or cooling as charging and discharging the capacitor is or or R or
hAs T cV 1/hAs
The Biot number has already been defined. It should be noted here that L = V/As
= Volume/Surface area. The value of L can be obtained from the shape of the solid. The quantity
(k/ρc) has already been defined as thermal diffusivity. ατ/L2 is defined as Fourier number. This
number signifies the heat penetration depth in time τ, with respect to the body dimension.
Fourier number should be large for quick heating or cooling. Leaving out the time, higher the
Chapter 6
value of thermal diffusivity or smaller the body dimension, quicker will be the heating up or
cooling down.
The response characteristics of a body with respect to heating or cooling is compared by
using the time required for the temperature difference to drop to 1/e times the original value
(e-base of natural logarithm). This time is called the thermal time constant for the condition
specified. This leads to the condition that the time constant
ρVc
τc = ...(6.6)
hA s
For quick response as in the case of probes for temperature mesurements the time
constant should be small.
Example 6.1: A thermocouple is formed by soldering end-to-end wires of 0.5 mm dia. The
thermal diffusivity of the material is 5.3 × 10–6 m2/s. The conductivity of the material is 19.1
W/mK. The probe initially at 30°C is placed in a fluid at 600°C to measure the temperature of
the fluid. If the convective heat transfer coefficient between the wire and the fluid is 85 W/m2K,
determine the time constant for the probe and also the time taken for it to read 598°C.
206 FUNDAMENTALS OF HEAT AND MASS TRANSFER
−G
F 85 × 2 × 5.3 × 10 I τ
−6
y
In this case the temperature ratio (T – Ts)/(T∞ – Ts) reached a value of 0.99 at Rex1/2
x
Pr1/3 = 5.
Hence the thermal boundary layer was obtained as
δh 5x
δth = 1/3
= 1/ 2 ...(7.19)
Pr Rex Pr 1/3
Also the slope at y = 0 was obtained as 0.332
∂ [(T − Ts )/(T∞ − Ts )]
i.e., = 0.332.
LF y I
∂ MG J . Re 1/ 2 1/ 3 OP
NH x K x Pr
Q y=0
∂T Rex1/ 2 Pr 1/ 3 (T∞ − Ts )
∴ = 0.332
∂y y=0 x
∂T Rex1/ 2 Pr 1/ 3
Heat flux qx = – k = – 0.332 k (T∞ – Ts)
∂y y=0
x
qx k
hx = = 0.332 . Rex1/2 Pr1/3 ...(7.20)
Ts − T∞ x
hx x
∴ = Nux = 0.332 Rex1/2 Pr1/3 ...(7.21)
k
The value of Nusselt number at length L is
NuL = 0.334 ReL1/2 Pr1/3 ...(7.22)
h = 2 h (x = L) ...(7.23)
From experimental results it is found that these equations are applicable if the property
values are used at film temperature (Ts + T∞)/2.
Example 7.9: Air at 20°C and one atmosphere flows over a surface at 100°C with a free stream
Chapter 7
velocity of 6 m/s. Determine the values of Reynolds number, thermal and hydrodynamic
boundary layer thicknesses and the local value and average values of convective heat transfer
coefficients at distances of 0.1, 0.25, 0.5, 0.75, 1, 1.25 m from the leading edge. Also determine
the length at which the flow turns to turbulent taking critical Reynolds number as 5 × 105.
Solution: The temperature at which properties are to be read is (20 + 100)/2 = 60°C for air at
one atmospheric pressure. The following values are read from tables:
ν = 18.97 × 10–6 m2/s, Pr = 0.696,
k = 0.02896 W/mK (these being the required ones for the problem)
302 FUNDAMENTALS OF HEAT AND MASS TRANSFER
u∞ x
Rex = , δx = 5x/Rex1/2, δth x = δx/Pr1/3
ν
Nux = 0.332 Rex1/2 Pr1/3 hx = Nux k/x, hL = 2hL
The calculated values are given below
10.0 INTRODUCTION
In the previous chapters, we discussed heat transfer under forced flow conditions. Though it is
desirable to use forced convection as higher rates of heat transfer coefficient may be obtained by
this method, leading to compact equipments, it is not possible and sometimes not desirable to use
forced convection in the design of several equipments. In these situations, free or natural convection
has to be adopted in designs. Medium size electrical transformers erected in open space cannot
use forced convection. So also steam radiators used for comfort heating.
When a surface is maintained in still fluid at a temperature higher or lower than that of
the fluid, a layer of fluid adjacent to the surface gets heated up or cooled. A density difference is
created between this layer and the still fluid surrounding it. The density difference introduces a
buoyant force causing flow of the fluid near the surface. Heat transfer under such conditions is
known as natural or free convection. Usually a thin layer of flowing fluid forms over the surface.
The fluid beyond this layer is essentially still, and is at a constant temperature of T∞.
The flow velocities encountered in free convection is lower compared to flow velocities in
forced convection. Consequently the value of convection coefficient is lower, generally by one order
of magnitude. Hence for a given rate of heat transfer larger area will be required. As there is no
need for additional devices to force the fluid, this mode is used for heat transfer in simple devices
as well as for devices which have to be left unattended for long periods.
The heat transfer rate is calculated using the general convection equation given below:
Q = h A(Tw – T∞) ...(10.1)
Q—heat transfer in W, h—convection coefficient – W/m2K.
Chapter 10
A—area in m2, Tw—surface temperature
T∞—fluid temperature at distances well removed from the surface (here the stagnant fluid
temperature).
The basic nature of flow and various correlations available for the calculation of convection
coefficient for different flow situations and geometries are discussed in this chapter.
Boundary layer theory is used for the analysis of natural convection also. The example
10.1 brings out the difference in area requirements between natural and forced convection conditions.
Example 10.1: A transformer of 50 kW capacity dissipates by natural convection 1.20 kW of heat
generated inside it. If the value of convective heat transfer coefficient is 5 W/m2K, and if the
temperature of the unit should not exceed 30°C above the ambient level, determine the area
required. In case of forced convection h = 50 W/m2K. Determine the area under this condition.
Solution: Equation 10.1 is suitable for the calculation
Q = h A (Tw – T∞)
or A = Q/h (Tw – T∞)
434
NATURAL CONVECTION 435
Boundary
Chapter 10
TW layer
Stagnant fluid at T ∝
Tw > T ∝ Tw
δx
T
A A
T, u T∝
u
x x
y
δ
y
Using (11.2)
q=
LM 909 × ∆T OP 3
N 16178 3
. × 10 × 4.4 1.7
× 0.013 Q N 1 × 23 × 10 Q −3
q = 1.84334 × ∆T3
Substituting qcr for q, ∆T = 58.8 °C
When surface temp. is 10°C, ∆T = 30°C i.e., 10 – (– 20)
∴ q = 1.84334 × ∆T3 = 0.05 × 106 W/m2
h = 1659 W/m2 K.
Note : Sources for property values of liquids other than water are scarce.
Problem 11.5: n-Butyl alcohol boils on a copper surface at 1 atm. The saturation temperature
is 117.5°C. Determine the critical heat flux and heat flux for excess temperatures of 10, 20,
200°C. Also determine the excess temperature at the critical flux condition.
Solution: The property values are:
σ = 0.0183 N/m, hfg = 591500 J/kg
ρv = 2.3 kg/m3, µv = 0.143 × 10–3 kg/ms
ρ1 = 737 kg/m3, µ1 = 0.39 × 10–3 kg/ms
c1 = 2876 J/kgK, Pr = 6.9, k1 = 0.163 W/mK
Csf = 0.00305, cρν = 1706 J/kgK, kν = 0.02 W/mK
Using equation (11.3)
qcr = 0.149 hfg [σ ggo(ρ1 – ρv) ρv2]1/4
= 0.149 × 591500 [0.0183 × 9.81 × 1 (737 – 2.3)2.32]1/4 = 0.453 × 106 W/m2
Chapter 11
Assuming nucleate boiling and excess temperature ∆Tcr
∆Tcr3
MN h fg pr 1.7 Csf PQ MN g
o σ PQ
= 0.39 × 10–3
L
× 591500 × M
2876 OP LM 9.81 b737 − 2.3g OP 3 0.5
∆Tcr3
N 591500 × 6.9 × 0.00305 Q N 1 0.0183 Q 1.7
= 0.425 M
1 v v v fg pv
hc
MN b g σg µ ∆T PQ = 0.425
o
0.5
v
×M
MN b1 × 0.0183g × 0.143 × 10 × 200 PQ 0.5 −3
= 72.9 W/m2K
502 FUNDAMENTALS OF HEAT AND MASS TRANSFER
LM gbρ
1 − ρv g
1.5
ρv kv3 hfg + 0.68 × cpv ∆T OP 0.25
LM T4
w
4
− Tsat OP
hr = ε σ
hc = 0.425
MN b gσg 0.5
µ v ∆T PQ MN T
w − Tsat PQ
The property values kv and µv should be taken at (Tw + Tsat)/2.
Only a trial solution is possible.
Assuming 1100°C excess temperature, film temp. = 600°C
ρv = 0.252, kv = 0.08176, µv = 33.15 × 10–6 cpv = 2206 J/kgK
Assuming an emisivity of 0.8 (rough surface)
Tw = 1100 + 100 + 273 = 1473 K, Tsat = 373K
0.8 × 5.67
hr = [14.734 – 3.734] = 193.33 W/m2 K
1100
h = 0.425 × M
c
MN −3 0.5
(1 × 58.8 × 10 ) 33.15 × 10 × 1100 −6
PQ
= 155.18 W/m2 K
∴ h = 300.2 W/m2 K ∴ q = 0.33 × 106
This falls short of the critical flux.
Assuming 1900°C excess Temp., Tf = 1000°C
Property values are:
ρv = 0.172, kv = 0.14072, µv = 52.37 × 10–6,
Cpv = 2483
Tw = 2273 K, Tsat = 373 K
HEAT EXCHANGERS 529
Example 12.2: Determine the area required in parallel flow heat exchanger to cool oil from
60°C to 30°C using water available at 20°C. The outlet temperature of the water is 26°C. The
rate of flow of oil is 10 kg/s. The specific heat of the oil is 2200 J/kg K. The overall heat transfer
coefficient U = 300 W/m2 K. Compare the area required for a counter flow exchager.
Solution: The temperature variation for parallel flow is shown in Fig. 12.4 (a).
60°C
T
Ti = 40
30°C
To = 4
26°C
20°C
Inlet A Outlet
Chapter 12
Q = U A (LMTD)
40 − 4
LMTD = = 15.635°C
40
ln
4
6,60,000 = 300 × A × 15.635 ∴ A = 140.71 m2
As can be seen a single tube arrangement is
impractical.
60°C
Counter flow:
The temperature variation is shown in Fig 12.4 (b) Ti = 34
26°C 30°C
34 − 10 To = 10
LMTD = 34 = 19.611°C 20°C
ln T
10
∴ A = 112.18 m2
about 20% less. Inlet A Outlet
The flow rate of water can also be determined as it
Fig. 12.4. (b) Counter flow
will be a necessary data.
Q = mc Cc (Tco – Tci)
6,60,000 = mc × 4180 (26 – 20)
mc = 26.32 kg/s
The counter flow arrangement provides more uniform temperature difference
along the flow and hence a better rate of heat flow. The counter flow type can also be used to
cool or heat over a wider range of temperatures. In the above case by increasing the area or by
reducing flow the hot oil can in the limit be cooled to 20°C. Manipulation in the opposite
direction can get the water heated to 60°C. This is not possible in the parallel flow where the