Zone CFM ....................... Sum of space airflow rates Calculation Months .......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ....................................................... Calculated
Total coil load ............................................................ 0.8 Tons Load occurs at ................................................... Jun 0900
Total coil load .......................................................... 10.2 MBH OA DB / WB .................................................... 105.2 / 85.2 °F
Sensible coil load ...................................................... 7.9 MBH Entering DB / WB .............................................. 74.2 / 63.8 °F
Coil CFM at Jun 0900 .............................................. 409 CFM Leaving DB / WB ............................................... 56.3 / 55.3 °F
Max block CFM ........................................................ 409 CFM Coil ADP ...................................................................... 54.3 °F
Sum of peak zone CFM ........................................... 409 CFM Bypass Factor ........................................................... 0.100
Sensible heat ratio ................................................ 0.776 Resulting RH .................................................................. 59 %
ft²/Ton .................................................................... 271.2 Design supply temp. ................................................... 55.0 °F
BTU/(hr-ft²) .............................................................. 44.3 Zone T-stat Check .................................................... 1 of 1 OK
Water flow @ 16.2 °F rise ...................................... 1.26 gpm Max zone temperature deviation .................................. 0.0 °F
Actual max CFM ...................................................... 409 CFM Fan motor BHP ........................................................... 0.08 BHP
Standard CFM .......................................................... 408 CFM Fan motor kW ............................................................. 0.06 kW
Actual max CFM/ft² ................................................. 1.77 CFM/ft² Fan static ..................................................................... 0.70 in wg