Vous êtes sur la page 1sur 120

Internal Use Only

http://biz.lgservice.com

System
Indoor Unit R410A
SERVICE MANUAL R410A
MODEL : ARNU Series
URNU Series

CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Air Conditioner Service Manual

TABLE OF CONTENTS
Part 1 General Information ....................................................................................................... 3
Model Names ...............................................................................................................................4
External Appearance...................................................................................................................5
Nomenclature...............................................................................................................................6

Part 2 Indoor Units ...................................................................................................................... 7


Ceiling Mounted Cassette Type (1 way)........................................................................................8
Ceiling Mounted Cassette Type (2 way)......................................................................................16
Ceiling Mounted Cassette Type (4 way)(1)..................................................................................21
Ceiling Mounted Cassette Type (4 way)(2)..................................................................................27
Art Cool Type(Mirror)...................................................................................................................34
Art Cool Type(Gallery).................................................................................................................45
Ceiling Concealed Duct Type (Low static)...................................................................................55
Ceiling Concealed Duct Type (Built in)........................................................................................61
Ceiling Concealed Duct Type (High static)..................................................................................67
Wall Mounted Type......................................................................................................................76
Ceiling & Floor Ceiling Suspended..............................................................................................87
Floor Standing Type.....................................................................................................................94
Vertical Air Handling Unit...........................................................................................................101

Part 3 Trouble shooting guide...............................................................................109

Copyright ©2010 LG Electronics. Inc. All right reserved. - 2-


Only for training and service purposes
LGE Internal Use Only
Part 1
General Information

1. Model Names .............................................4

2. External Appearance.................................5

3. Nomenclature.............................................6

Copyright ©2010 LG Electronics. Inc. All right reserved. - 3-


Only for training and service purposes
LGE Internal Use Only
Model Names

1. Model Names
Capacity(Btu/h(kW))
Chassis
Category 7.5 9.6 12.3 15.4 19.1 24.2 28.0 30.0 36.2 42.0 48.1 54.0 76.4 95.5
Name
(2.2) (2.8) (3.6) (4.5) (5.6) (7.1) (8.2) (8.8) (10.6) (12.3) (14.1) (15.8) (22.4) (28.0)
ARNU07ARNU09ARNU12ARNU15
SE 3SE*2 3SE*2 3SE*2 3SE*2
Wall Mounted
(General) ARNU18ARNU24
S5 3S5*2 3S5*2
ARNU07ARNU09ARNU12ARNU15
SE 3SE*2 3SE*2 3SE*2 3SE*2
ART
Mirror
COOL ARNU18ARNU24
S8 3S8*2 3S8*2
ARNU07ARNU09ARNU12
1 Way TJ 3TJ*2 3TJ*2 3TJ*2
ARNU18ARNU24
2 Way TL 3TL*2 3TL*2
ARNU07ARNU09ARNU12
TR 3TR*2 3TR*2 3TR*2
Ceiling ARNU15ARNU18
TQ 3TQ*2 3TQ*2
Cassette
ARNU24ARNU28
4 Way TP 3TP*2 3TP*2
ARNU36
TN 3TN*2
ARNU42ARNU48
TM 3TM*2 3TM*2
ARNU07ARNU09ARNU12ARNU15ARNU18ARNU24
BH 3BHA2 3BHA2 3BHA2 3BHA2 3BHA2 3BHA2
ARNU28 ARNU36ARNU42
BG 3BGA2 3BGA2 3BGA2
High Static
ARNU483
BR BRA2
URNU76URNU96
Ceiling B8 3B8A2 3B8A2
Concealed
ARNU07ARNU09ARNU12ARNU15
Duct B1 3B1G2 3B1G2 3B1G2 3B1G2
Low Static
ARNU18ARNU24
B2 3B2G2 3B2G2
ARNU07ARNU09ARNU12ARNU15
B3 3B3G2 3B3G2 3B3G2 3B3G2
Built In
ARNU18ARNU24
B4 3B4G2 3B4G2
ARNU09ARNU12
Ceiling & Floor VE 3VEA2 3VEA2
ARNU18
Ceiling Suspended VJ 3VJA2
ARNU07ARNU09ARNU12ARNU15
CE 3CEA2 3CEA2 3CEA2 3CEA2
With Case
ARNU18ARNU24
CF 3CFA2 3CFA2
Floor
Standing ARNU07ARNU09ARNU12ARNU15
CE 3CEU2 3CEU2 3CEU2 3CEU2
Without
Case ARNU18ARNU24
CF 3CFU2 3CFU2
ARNU18ARNU24 ARNU30ARNU36
NJ 3NJA2 3NJA2 3NJA2 3NJA2
Vertical AHU
ARNU42ARNU48 ARNU54
NK 3NKA2 3NKA2 3NKA2
h *ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable))
*Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma

Copyright ©2010 LG Electronics. Inc. All right reserved. - 4-


Only for training and service purposes
LGE Internal Use Only
External Appearance

2. External Appearance
Ceiling Cassette- 1Way Ceiling Concealed Duct - High Static
ARNU073TJ*2 ARNU073BHA2 ARNU363BGA2
ARNU093TJ*2 ARNU093BHA2 ARNU423BGA2
ARNU123TJ*2 ARNU123BHA2 ARNU483BRA2
ARNU153BHA2 URNU763B8A2
ARNU183BHA2 URNU963B8A2
* A:Basic, C:Plasma
ARNU243BHA2
ARNU283BGA2

Ceiling Cassette- 4Way


ARNU073TR*2 ARNU243TP*2
Wall Mounted
ARNU073SE*2 ARNU153SE*2
ARNU093TR*2 ARNU283TP*2
ARNU093SE*2 ARNU183S5*2
ARNU123TR*2 ARNU363TN*2
ARNU123SE*2 ARNU243S5*2
ARNU153TQ*2 ARNU423TM*2
ARNU183TQ*2 ARNU483TM*2
* A:Basic, L:Plasma
* A:Basic, C:Plasma

Ceiling Concealed Duct - Low Static ART COOL Mirror


ARNU073B1G2 ARNU153B1G2 ARNU073SE*2 * R:Mirror
ARNU093B1G2 ARNU183B2G2 ARNU093SE*2 V:Silver
ARNU123B1G2 ARNU243B2G2 ARNU123SE*2 B : Blue
ARNU153SE*2
ARNU183S8*2
ARNU243S8*2

Ceiling Concealed Duct – Built-in Floor Standing


ARNU073B3G2 ARNU153B3G2 With case
ARNU093B3G2 ARNU183B4G2 ARNU073CEA2
ARNU123B3G2 ARNU243B4G2 ARNU093CEA2
ARNU123CEA2
ARNU153CEA2
ARNU183CFA2
ARNU243CFA2
Ceiling & Floor
ARNU093VEA2 Without case
ARNU123VEA2 ARNU073CEU2
ARNU093CEU2
ARNU123CEU2
Ceiling Suspended ARNU153CEU2
ARNU183VJA2 ARNU183CFU2
ARNU243VJA2 ARNU243CFU2

Ceiling Cassette -2Way Vertical AHU


ARNU183TL*2 ARNU183NJA2
ARNU243TL*2 ARNU243NJA2
ARNU303NJA2
ARNU363NJA2
ARNU423NKA2
* A:Basic, C:Plasma ARNU483NKA2
ARNU543NKA2

Copyright ©2010 LG Electronics. Inc. All right reserved. - 5-


Only for training and service purposes
LGE Internal Use Only
Nomenclature

3. Nomenclature
ARN U 07 3 TJ A 2

Generation
Combinations of functions
A: Basic function
L: Neo Plasma(Wall Mounted)
C:Plasma(Ceiling Cassette)
G: Low Static
U: Floor Standing without Case
ART COOL Type Panel Color
B:Blue R:Mirror V: Silver

Chassis Name

Electrical Ratings
1:1Ø, 115V, 60Hz 2: 1Ø, 220V, 60Hz
6:1Ø, 220 - 240V, 50Hz 7: 1Ø, 100V, 50/60Hz
3:1Ø, 208/230V, 60Hz

Total Cooling Capacity in Btu/h Class


EX) 18,000 Btu/h Class → '18'

Combination of Inverter Type and


Cooling Only or Heat Pump
N: AC Inverter and H/P V: AC Inverter and C/O
U: DC Inverter and H/P and C/O
System with
Indoor Unit using R410A
❈ LGETA:U Ex) URN

Copyright ©2010 LG Electronics. Inc. All right reserved. - 6-


Only for training and service purposes
LGE Internal Use Only
Part 2
Indoor Units

Ceiling Cassette
1 Way.................................................................................8
2 Way...............................................................................13
4 Way(1)...........................................................................20
4 Way(2)...........................................................................23
Art Cool Series
ART COOLMiror..............................................................34
ART COOL Gallery..........................................................45
Ceiling Concealed Duct
Low Static........................................................................55
Built In..............................................................................62
High Static........................................................................67
Wall Mounted(General)
Wall Mounted...................................................................76
Ceiling & Floor
Ceiling & Floor
Ceiling Suspended...........................................................87
Floor Standing
Floor Standing..................................................................94
Vertical Air Handling Unit................................................117

Copyright ©2010 LG Electronics. Inc. All right reserved. - 7-


Only for training and service purposes
LGE Internal Use Only
Ceiling Mounted Cassette Type (1Way)

1. Functions......................................................................................9
2. Operation Details........................................................................10
3. Dimensions.................................................................................12

Copyright ©2010 LG Electronics. Inc. All right reserved. - 8-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C(76°F).

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.
• Built-in drain pump automatically drains water.
High head Drain pump
• A standard drain-head height of up to 700mm(27-9/16inch) is
possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 9-


Only for training and service purposes
LGE Internal Use Only
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

INDOOR FAN Selected Low Selected Low Selected


Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2010 LG Electronics. Inc. All right reserved. - 10-


Only for training and service purposes
LGE Internal Use Only
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36 °C(96 °F)

33 °C(92 °F)

25 °C(76 °F)
20 °C(68 °F)

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan StopLow Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2
n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C(76°F).
• The operation diagram is as following.

Pipe
temperature

35°C(94 °F)
30°C(86 °F)
27°C(80 °F)
25°C(76 °F)

22°C(72 °F)
LO
LOW

Indoor fan OFF LOW


SELECTED
LOW LOLOW
FAN
speed
COMP ON

Copyright ©2010 LG Electronics. Inc. All right reserved. - 11-


Only for training and service purposes
LGE Internal Use Only
Ceiling Cassette 1-way
Dimensions

ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2

Only for training and service purposes


(unit : mm)

8. 572
6. 602
Number Name Descripition

8. 601
3. Dimensions

861 88 1 Liquid pipe connection Unit size(7k, 9k, 12k):ø6.35


1012 2 Gas pipe connection Unit size(7k, 9k, 12k):ø12.7

Copyright ©2010 LG Electronics. Inc. All right reserved.


453
320.5 27 3 Air suction grill
4 Air discharge grill

Note

3. 861
5. 69
1. Unit should be installed in compliance with the installation manual

4. 75
in the product box.
2. Unit shall be grounded in accordance with the local regulations or

- 12-
1,100 applicable national codes.
(Panel Name: PT-UUC)
881(Air outlet Hole)

005
43

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: TU

LGE Internal Use Only


Ceiling Cassette 1-way
ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2

3. 453
354
8. 572
3. 602

Only for training and service purposes


8. 601
(unit : mm)
861 88
Number Name Descripition
1012
1 Liquid pipe connection Unit size(7k, 9k, 12k):ø6.35
453 2 Gas pipe connection Unit size(7k, 9k, 12k):ø12.7

Copyright ©2010 LG Electronics. Inc. All right reserved.


320.5 27
3 Air suction grill
4 Air discharge grill

3. 861
5. 69
Note

4. 75
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or

- 13-
1100
applicable national codes.
109.5 109.5 (Panel Name: PT-UUD)

5. 64

005
43
711

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: TU

LGE Internal Use Only


Dimensions
Ceiling Cassette 1-way
Dimensions

ARNU18GTT*2
ARNU24GTT*2

8. 354

Only for training and service purposes


(unit : mm)

5. 742
Number Name Descripition

6. 081
1 Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52

3. 56
1176.4
2 Gas pipe connection Unit size(18k):ø12.7, (24k):ø15.88

Copyright ©2010 LG Electronics. Inc. All right reserved.


65.1
1332 453.8 3 Air suction grill
4 Air discharge grill

Note
1. Unit should be installed in compliance with the installation manual

8. 371
19
in the product box.

1. 69
2. Unit shall be grounded in accordance with the local regulations or

- 14-
7. 13
applicable national codes.

4. 75 6. 02
1,420 (Panel Name: PT-UTC)
1,201(Air Outlet Hole)

005
43

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: TT

LGE Internal Use Only


Ceiling Cassette 1-way
ARNU18GTT*2
ARNU24GTT*2

8. 354
5. 742

Only for training and service purposes


6. 081
(unit : mm)
1176.4 65.1 Number Name Descripition

3. 56
1332 1 Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52
2 Gas pipe connection Unit size(18k):ø12.7, (24k):ø15.88

Copyright ©2010 LG Electronics. Inc. All right reserved.


3 Air suction grill
453.8
4 Air discharge grill
22.3 335 96.5

Note
1. Unit should be installed in compliance with the installation manual

8. 371
231

19
1. 79
75
in the product box.
Ø14
2. Unit shall be grounded in accordance with the local regulations or

- 15-
4. 75
7. 13
2. 51

6. 02
applicable national codes.

1420 (Panel Name: PT-UTD)


109.5 109.5

5. 64
005
44

43
76, Seongsan-dong, Changwon City, Gyeongnam,
641-713, Korea CHASSIS CODE: TT

LGE Internal Use Only


Dimensions
Ceiling Mounted Cassette Type (2Way)

1. Functions....................................................................................17
2. Operation Details........................................................................18
3. Dimensions.................................................................................20

Copyright ©2010 LG Electronics. Inc. All right reserved. - 16-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

• The indoor fan does not rotate until the evaporator pip-
Hot-start Control (Heating)
ing temperature will be reached at 25°C(76°F).

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.

High head Drain pump • Built-in drain pump automatically drains water.
• A standard drain-head height of up to 700mm
(27-9/16inch) is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 17-


Only for training and service purposes
LGE Internal Use Only
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))
Thermo. OFF
(SET TEMPERATURE
More than More than
-0.5°C(33°F))
3 minutes 3 minutes

INDOOR FAN Selected Low Selected Low Selected


Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2010 LG Electronics. Inc. All right reserved. - 18-


Only for training and service purposes
LGE Internal Use Only
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36 °C(96 °F)

33 °C(92 °F)

25 °C(76 °F)
20 °C(68 °F)

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan StopLow Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C(76°F).
• The operation diagram is as following.

Pipe
temperature

35°C(94 °F)
30°C(86 °F)
27°C(80 °F)
25°C(76 °F)

22°C(72 °F)
LO
LOW

Indoor fan OFF LOW


SELECTED
LOW LOLOW
FAN
speed
COMP ON

Copyright ©2010 LG Electronics. Inc. All right reserved. - 19-


Only for training and service purposes
LGE Internal Use Only
Ceiling Cassette 2-way
Dimensions

ARNU183TL*2
ARNU243TL*2

A
830(32-11/16) B
47.9(1-7/8)

Only for training and service purposes


[Unit : mm(inch)]
Number Name Descripition
1 Liquid pipe connection (18k) ø6.35(1/4), (24k)ø9.52(3/8)
3. Dimensions

) 61/ 31- 01( 572


2 Gas pipe connection (18k) ø12.7(1/2), (24k)ø15.88(5/8)

Copyright ©2010 LG Electronics. Inc. All right reserved.


3 Air suction grill

) 61/ 11- 12( 055


4 Air discharge grill
1

) 4/ 3- 2( 5. 96
Note
1. Unit should be installed in compliance with the installation manual
889.2(35) in the product box.
TL 2. Unit shall be grounded in accordance with the local regulations or

- 20-
A 225(8-7/8) applicable national codes.
B 126.5(5)

1050(41-5/16)
28.5(1-1/8)

) 61/ 3- 52( 046


3

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: TL
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Ceiling Mounted Cassette Type (4Way) (1)

1. Functions....................................................................................22
2. Operation Details........................................................................23
3. Dimensions.................................................................................25

Copyright ©2010 LG Electronics. Inc. All right reserved. - 21-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C(76°F).

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.

High head Drain pump • Built-in drain pump automatically drains water.
• A standard drain-head height of up to 700mm
(27-9/16inch) is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Swirl Swing Control • It is operating swirl swing

Copyright ©2010 LG Electronics. Inc. All right reserved. - 22-


Only for training and service purposes
LGE Internal Use Only
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

INDOOR FAN Selected Low Selected Low Selected


Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

n Swirl Swing Control Vane 2


Vane 2, 4 is almost vane closed while vane1, 3 is opened.
Vane 1, 3 and vane 2,4 turn over minutely

Vane 1 Vane 3

Vane 4

Copyright ©2010 LG Electronics. Inc. All right reserved. - 23-


Only for training and service purposes
LGE Internal Use Only
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36 °C(96 °F)

33 °C(92 °F)

25 °C(76 °F)
20 °C(68 °F)

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan StopLow Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C(76°F).
• The operation diagram is as following.

Pipe
temperature

35°C(94 °F)
30°C(86 °F)
27°C(80 °F)
25°C(76 °F)

22°C(72 °F)
LO
LOW

Indoor fan OFF LOW


SELECTED
LOW LOLOW
FAN
speed
COMP ON

Copyright ©2010 LG Electronics. Inc. All right reserved. - 24-


Only for training and service purposes
LGE Internal Use Only
R3
Ceiling Cassette 4-way
5

ARNU05GTR*2

821
4R20 ARNU07GTR*2
69
517
ARNU09GTR*2
4
5
ARNU12GTR*2

Only for training and service purposes


(unit : mm)
6
Number Name Descripition

007
715
075

325
3. Dimensions

1 Liquid pipe connection Unit size(5k, 7k, 9k, 12k):ø6.35

) elli r Gt el nI ( 673
2 Gas pipe connection Unit size(5k, 7k, 9k, 12k):ø12.7

Copyright ©2010 LG Electronics. Inc. All right reserved.


3 Drain pipe connection VP25(Φ32)
4 Power supply connection
461
5 Air discharge grill
380(Air outlet hole) 570
473 2 1
6 Air suction grill
700 165
Note

- 25-
1. Unit should be installed in compliance with the installation manual

5. 95
412
in the product box.

97

5. 22
5. 48
84
2. Unit shall be grounded in accordance with the local regulations or

35
5.43
3019 63 applicable national codes.
142.5
570
3
Branch Duct Connection

• REQUIRED SPACE

B
CEILING OPENING
500mm or more*

500mm or more*
500mm or more*

500mm or more*

A ARROW VIEW B ARROW VIEW


A

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: TR

LGE Internal Use Only


Dimensions
R3
5 Ceiling Cassette 4-way
ARNU15GTQ*2
Dimensions

471
4R20
ARNU18GTQ*2
68

517
4
5

Only for training and service purposes


(unit : mm)
Number Name Descripition
6

007
715
075

325
1 Liquid pipe connection Unit size(15k, 18k):Ø6.35

) elli r Gt el nI ( 673
2 Gas pipe connection Unit size(15k, 18k):Ø12.7

Copyright ©2010 LG Electronics. Inc. All right reserved.


3 Drain pipe connection VP25(Φ32)
4 Power supply connection
461 5 Air discharge grill
570

2 1
6 Air suction grill
380(Air outlet hole)
473
Note
700

- 26-
165
1. Unit should be installed in compliance with the installation manual

5. 95
in the product box.

652

5. 22
97
2. Unit shall be grounded in accordance with the local regulations or

521
5. 59
49
67

84
applicable national codes.
3019 63
142.5
570

3 Branch Duct Connection

• REQUIRED SPACE 500mm or more*

CEILING OPENING

B
500mm or more*
500mm or more*

500mm or more*

A
A ARROW VIEW B ARROW VIEW

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: TQ

LGE Internal Use Only


Ceiling Mounted Cassette Type (4Way) (2)

1. Functions....................................................................................28
2. Operation Details........................................................................29
3. Dimensions.................................................................................31

Copyright ©2010 LG Electronics. Inc. All right reserved. - 27-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C(76°F).

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.
• Built-in drain pump automatically drains water.
High head Drain pump • A standard drain-head height of up to 700mm
(27-9/16inch) is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Swirl Swing Control • It is operating swirl swing

Copyright ©2010 LG Electronics. Inc. All right reserved. - 28-


Only for training and service purposes
LGE Internal Use Only
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

INDOOR FAN Selected Low Selected Low Selected


Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2010 LG Electronics. Inc. All right reserved. - 29-


Only for training and service purposes
LGE Internal Use Only
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36 °C(96 °F)

33 °C(92 °F)

25 °C(76 °F)
20 °C(68 °F)

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan StopLow Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C(76°F).
• The operation diagram is as following.

Pipe
temperature

35°C(94 °F)
30°C(86 °F)
27°C(80 °F)
25°C(76 °F)

22°C(72 °F)
LO
LOW

Indoor fan OFF LOW


SELECTED
LOW LOLOW
FAN
speed
COMP ON

Copyright ©2010 LG Electronics. Inc. All right reserved. - 30-


Only for training and service purposes
LGE Internal Use Only
4-R20
Ceiling Cassette 4-way
5
804
ARNU21GTP*2
ARNU24GTP*2

451
402
6
ARNU28GTP*2

059

Only for training and service purposes


) elli r Gt el nI( 416
787 (unit : mm)
Number Name Descripition
1 Liquid pipe connection Unit size(24k, 28k):ø9.52
3. Dimensions

500(Air outlet Hole)


737
950
2 Gas pipe connection Unit size(24k, 28k):ø15.88

Copyright ©2010 LG Electronics. Inc. All right reserved.


52
3 Drain pipe connection VP25(Φ32)
4 Power supply connection
5 Air discharge grill

176
486
048
870-920(CEILINGOPENINGSPACE)
786(SUSPENSIONPOSITION) 6 Air suction grill

003
SSEL RO
Note

024
393
024
) NO

) NO
1. Unit should be installed in compliance with the installation manual

- 31-
) ECAPS GN
Ceiling opening A in the product box.

I TI SOP NO

I TI SOPNO
2. Unit shall be grounded in accordance with the local regulations or

I NEPOGN
787
applicable national codes.

I SNEPSUS( 286

I SNEPSUS( 966
840

I LI EC( 029- 078


475
B

71 OUTDOORAIRINTAKE BRANCHDUCT
1 92 92 92 92 CONNECTION • REQUIRED SPACE
(DIRECTCONNECTION) 4 BRANCHDUCT
31 35 CONNECTION 50
350 500mm or more*
165

97

62
23 05

26
97

500mm or more*
204
500mm or more*
05

17
65 40
28
99

06
ø70 13-ø3, 3Hole
108 60 53.5 80

5. 14
2 840 3 165 165 500mm or more*
13-ø3, 3 Hole 10
Branch Duct Connection 350

A ARROW VIEW

B ARROW VIEW

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: TP

LGE Internal Use Only


Dimensions
4-R20
Ceiling Cassette 4-way
5
840
Dimensions

591
ARNU36GTN*2

642
6

059
) elli r Gt el nI( 416

Only for training and service purposes


(unit : mm)
Number Name Descripition
500(Air outlet Hole) 1 Liquid pipe connection Unit size(36k):ø9.52
737
950 2 Gas pipe connection Unit size(36k):ø15.88

Copyright ©2010 LG Electronics. Inc. All right reserved.


3 Drain pipe connection VP25(Φ32)

52
4 Power supply connection
870-920(CEILINGOPENINGSPACE) 5 Air discharge grill
786(SUSPENSIONPOSITION)

003
SSEL RO
6 Air suction grill
Note

024
393
024
) NO
1. Unit should be installed in compliance with the installation manual

) NO

- 32-
) ECAPS GN
Ceiling opening A in the product box.

I TI SOP NO

I TI SOP NO
2. Unit shall be grounded in accordance with the local regulations or

I NEPOGN
applicable national codes.

I SNEPSUS( 286

I SNEPSUS( 966
I LI EC( 029- 078
475
B

71 OUTDOORAIRINTAKE
31 35 (DIRECTCONNECTION)
4 BRANCHDUCT
1 350 CONNECTION 92 92 92 92 • REQUIRED SPACE
165 BRANCHDUCT

44
CONNECTION
500mm or more*
34

08
ø70
06

17
04
642

001
001

500mm or more*
06

141

500mm or more*

701
301

25
87
13-ø3, 3Hole
110 60 80 3
2 840 53.5 13-ø3, 3 Hole

165 10 165 500mm or more*


Branch Duct Connection
350

A ARROW VIEW

B ARROW VIEW

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: TN

LGE Internal Use Only


4-R20
Ceiling Cassette 4-way
5

ARNU42GTM*2
ARNU48GTM*2
840

732

059
882

) elli r Gt el nI( 416

Only for training and service purposes


(unit : mm)
Number Name Descripition
1 Liquid pipe connection Unit size(42k, 48k):ø9.52
500(Air outlet Hole)
737 2 Gas pipe connection Unit size(42k, 48k):ø15.88
950

Copyright ©2010 LG Electronics. Inc. All right reserved.


3 Drain pipe connection VP25(Φ32)

52
4 Power supply connection
5 Air discharge grill
870-920(CEILINGOPENINGSPACE)
786(SUSPENSIONPOSITION) 6 Air suction grill

003
SSEL RO
Note

- 33-
1. Unit should be installed in compliance with the installation manual

024
393
024
) NO

) NO
Ceiling opening in the product box.

) ECAPS GN
A

I TI SOPNO

I TI SOPNO
2. Unit shall be grounded in accordance with the local regulations or

I NEPOGN
applicable national codes.

I SNEPSUS( 286

I SNEPSUS( 966
I LI EC( 029- 078
475
B
71
OUTDOORAIRINTAKE 92 92 92 92
31 35 350
4
(DIRECTCONNECTION) • REQUIRED SPACE
1
165
BRANCHDUCT

001
67

CONNECTION 500mm or more*


631

57
011
06

ø70
001

500mm or more*
06

500mm or more*

17
BRANCHDUCTCONNECTION

48
53.5
13-ø3, 3Hole 3 13-ø3, 3Hole
500mm or more*
2 165 10 165
Branch Duct Connection
350

A ARROW VIEW

B ARROW VIEW

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: TM

LGE Internal Use Only


Dimensions
Art Cool Type(Mirror)

1. Functions....................................................................................35
2. Operation Details........................................................................36
3. Dimensions.................................................................................43

Copyright ©2010 LG Electronics. Inc. All right reserved. - 34-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Functions
Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature


• Room temperature sensor. (THERMISTOR)

Room temperature control


• Maintains the room temperature in accordance with the Setting Temp.

Starting Current Control


• Indoor fan is delayed for 5 sec at the starting.

Indoor Fan Speed Control


• High, Med, Low, CHAOS

Operation indication Lamps (LED)


Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.
Defrost Mode : Lights up during Defrost Mode or Hot Start operation.

Soft Dry Operation Mode


• Intermittent operation of fan at low speed.

Sleep Mode Auto Control


• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic • Both the indoor and outdoor fan stops dur-
ing defrosting.
• The fan is switched to intermittent or irregular operation
• The fan speed is automatically switched from high to low speed. Hot-start Control (Heating)

Airflow Direction Control • The indoor fan does not rotate until the
evaporator pipe temperature will be reached
• The louver can be set at the desired position or swing
up and down automatically. at 28°C(82°F).

Copyright ©2010 LG Electronics. Inc. All right reserved. - 35-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
• When the intake air temperature reaches 0.5°C(33°F) below the setting temp, the compressor and the outdoor
fan stop.
• When it reaches 0.5°C(33°F)above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C (33°F)
Compressor OFF Temp => Setting Temp-0.5°C(33°F)
• While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.

n Healthy Dehumidification Mode


• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp-1°C(34°F)
18°C(64°F) ≤ Intake Air Temp < 24°C(76°F) => Intake Air Temp-0.5°C(33°F)
Intake Air Temp < 18°C(64°F) => 18°C(64°F)
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C(33°F)
Compressor OFF Temp. => Setting Temp-0.5°C(33°F)
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

n Heating Mode Operation

Copyright ©2010 LG Electronics. Inc. All right reserved. - 36-


Only for training and service purposes
LGE Internal Use Only
Operation Details

• When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.
When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2˚C(36°F)
Themo OFF Temp. => Setting Temp.+4°C(39°F)
• While in compressor on, when above 38°C(100°F), it operates with setting airflow speed (while in sleep mode,
with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C (92°F), when above
35°C(94°F) , it operates with the low airflow speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.

n Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.

n Fuzzy Operation (Outdoor unit C/O Model)


• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the
setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compres-
sor is turned on.
Compressor ON Temp => Setting Temp+0.5°C(33°F)
Compressor OFF Temp => Setting Temp+0.5°C(33°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp
Intake Air Temp<18°C(64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-
ature
n Fuzzy Operation (Outdoor unit H/P Model)
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C(76°F) ≤ Inatake Air Temp => Fuzzy Operation for Cooling
21°C(70°F)≤ Inatake Air Temp<24°C(76°F) => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C(70°F) => Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 37-


Only for training and service purposes
LGE Internal Use Only
Operation Details

1) Fuzzy Operation for Cooling


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more
below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the
compressor is turned on.
Compressor ON Temp. => Setting Temp+0.5°C(33°F)
Compressor OFF Temp. => Setting Temp+0.5°C(33°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp
Intake Air Temp<18°C(64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

2) Fuzzy Operation for Dehumidification


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more
below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the
compressor is turned on.
Compressor ON Temp. => Setting Temp+0.5°C(33°F)
Compressor OFF Temp. => Setting Temp+0.5°C(33°F)

• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp < 26°C(78°F)=> Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp
Intake Air Temp < 18°C(64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 38-


Only for training and service purposes
LGE Internal Use Only
Operation Details
3) Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37°F) or more
above the setting temp, the compressor is turned off. When below the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp + 2°C(36°F)
Compressor OFF Temp => Setting Temp + 4°C(39°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
20°C(68°F) ≤ Intake Air Temp => Intake Air Temp + 0.5°C(33°F)
Intake Air Temp < 20°C(68°F) => 20°C(68°F)

• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
n Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.

n On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.

n Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 39-


Only for training and service purposes
LGE Internal Use Only
Operation Details
n Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation
is carried out according to the set time.

n Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C(34°F) After another 30 min elapse, it increases by 1°C(34°) again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.

n Chaos Swing Mode


• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.

n Chaos Natural Wind Mode


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.”

n Jet Cool Mode Operation (Outdoor unit C/O Model)


• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F).
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

n Jet Cool Mode Operation (Outdoor unit H/P Model)


• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F).
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

n Auto Restarting Operation


• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory

Copyright ©2010 LG Electronics. Inc. All right reserved. - 40-


Only for training and service purposes
LGE Internal Use Only
Operation Details
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)

n Forced Operation (Outdoor unit C/O Model)


• To operate the appliance by force in case that the remote controller is lost, the forced operation button is on
the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• The forced operation is carried out in cooling mode with the setting temperature 22°C(72°F) and the high
speed of airflow.

n Forced Operation (Outdoor unit H/P Model)


• To operate the appliance by force in case that the remote controller is lost, the forced operation selection
switch is on the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation
condition is set according to the intake air temperature as follows.
24°C(76°F) ≤ Intake Air Temp => Cooling Mode Operation, 22°C(72°F), High Speed
21°C(70°F) ≤ Intake Air Temp < 24°C(76°F) => Dehumidification Operation, 23°C(74°F), High Speed
Intake Air Temp < 21°C(70°F) => Heating Mode Operation, 24°C(76°F), High Speed

n Test Operation Control


• To check the condition of the installation when installing the appliance, the appliance is operated at cooling
mode, high speed of airflow, compressor-on for 18 min without controlling the room temperature.
• After supplying power to the main body, keep pressing the forced operation button for about 3 seconds.
• While in test operation, a key can be input by the remote controller.
When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, Jet
Cool) is input by the remote controller, the test operation is canceled and the appliance is operated according
to the setting by the remote controller.

n Protection of the evaporator pipe from frosting


• In the temperrature of the indoor pipe is below 0°C(32°F) after 7 minutes from starting the compressor, the
compressor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the tem-
perature of the indoor pipe is over 7°C(45°F), the compressor and the outdoor fan are reoperated.
• Outdoor fan motor stops when indoor pipe temperature is blow 3°C(37°F) and restarts at the pipe temperature
above 6°C(43°F) or after 90 seconds, if the pipe temperature does not rise to 6°C(43°F), outdoor fan motor
runs continuously at even below 3°C(37°F).

Copyright ©2010 LG Electronics. Inc. All right reserved. - 41-


Only for training and service purposes
LGE Internal Use Only
Operation Details
n Buzzer Sounding Operation
• When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds.
• When the appliance-pause key is input by the remote controller, the long “beep—” sounds.

n Air Cleaner Operation


• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 42-


Only for training and service purposes
LGE Internal Use Only
ART COOL Mirror
H ARNU073SE*2
2 ARNU093SE*2
ARNU123SE*2
ARNU153SE*2
D

Only for training and service purposes


W [Unit : mm(inch)]
Model W H D
1
ARNU073SE*2
3. Dimensions

ARNU093SE*2 915 282 169


ARNU123SE*2 (36) (11-1/8) (5-5/8)

Copyright ©2010 LG Electronics. Inc. All right reserved.


ARNU153SE*2

) 2/ 1- 6( 561
169(5-5/8)
915(36) [Unit : mm(inch)]
Number Name Descripition
1 Air discharge grill
2 Air suction grill

- 43-
Note

) 61/ 1- 2( 35

) 8/ 1- 11( 282
) 8/ 1- 11( 282
1. Unit should be installed in compliance with the installation manual
in the product box.
51(2-1/16)
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

567(22-3/8)

) 2/ 1- 01( 562

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: SE
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Dimensions
ART COOL Mirror
3
Dimensions

ARNU18GS8*2
ARNU24GS8*2

Only for training and service purposes


1

(unit : mm)
No. Part Name Remark

992
4 1 Front panel

Copyright ©2010 LG Electronics. Inc. All right reserved.


2 2 Display & signal receiver

01
36
53
1107 3 Air suction grille
200
4 Knockout hole
5 Installation plate

39

- 44-
84
72
58 122

804

Note
1. Unit should be installed in compliance with the installation manual
in the product box.

182 2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: S8

LGE Internal Use Only


ArtCoolGallery

1. Functions....................................................................................46
2. Operation Details........................................................................47
3. Dimensions.................................................................................54

Copyright ©2010 LG Electronics. Inc. All right reserved. - 45-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Functions
Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature


• Room temperature sensor. (THERMISTOR)

Room temperature control


• Maintains the room temperature in accordance with the Setting Temp.

Starting Current Control


• Indoor fan is delayed for 5 sec at the starting.

Indoor Fan Speed Control


• High, Med, Low, CHAOS

Operation indication Lamps (LED)


Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.
Defrost Mode : Lights up during Defrost Mode or Hot Start operation.

Soft Dry Operation Mode


• Intermittent operation of fan at low speed.

Sleep Mode Auto Control


• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic • Both the indoor and outdoor fan stops dur-
ing defrosting.
• The fan is switched to intermittent or irregular operation
• The fan speed is automatically switched from high to low speed. Hot-start Control (Heating)

Airflow Direction Control • The indoor fan does not rotate until the
evaporator pipe temperature will be reached
• The louver can be set at the desired position or swing at 28°C(82°F).
up and down automatically.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 46-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
• When the intake air temperature reaches 0.5°C(33°F) below the setting temp, the compressor and the outdoor
fan stop.
• When it reaches 0.5°C(33°F)above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C (33°F)
Compressor OFF Temp => Setting Temp-0.5°C(33°F)
• While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 47-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Healthy Dehumidification Mode


• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C(78°F) ≤ Intake Air Temp => 25°C
24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp-1°C
18°C(64°F) ≤ Intake Air Temp < 24°C(76°F) => Intake Air Temp-0.5°C(33°F)
Intake Air Temp < 18°C(64°F) => 18°C(64°F)
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C(33°F)
Compressor OFF Temp. => Setting Temp-0.5°C(33°F)
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

n Heating Mode Operation


• When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.
When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2˚C(36°F)
Themo OFF Temp. => Setting Temp.+4°C(39°F)
• While in compressor on, when above 38°C(100°F), it operates with setting airflow speed (while in sleep mode,
with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(92°F) , when above
35°C(94°F) , it operates with the low airflow speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.

n Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.

n Fuzzy Operation (Outdoor unit C/O Model)


• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the
setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compres-
sor is turned on.
Compressor ON Temp => Setting Temp+0.5°C(33°F)
Compressor OFF Temp => Setting Temp+0.5°C(33°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp
Intake Air Temp<18°C(64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-

Copyright ©2010 LG Electronics. Inc. All right reserved. - 48-


Only for training and service purposes
LGE Internal Use Only
Operation Details

ature

n Fuzzy Operation (Outdoor unit H/P Model)


• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C(76°F) ≤ Inatake Air Temp => Fuzzy Operation for Cooling
21°C(70°F) ≤ Inatake Air Temp<24°C(76°F) => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C(70°F) => Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1) Fuzzy Operation for Cooling


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more
below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the
compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C(33°F)
Compressor OFF Temp => Setting Temp+0.5°C(33°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp
Intake Air Temp < 18°C(64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

2) Fuzzy Operation for Dehumidification


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the com-
pressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C(33°F)
Compressor OFF Temp => Setting Temp+0.5°C(33°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 49-


Only for training and service purposes
LGE Internal Use Only
Operation Details
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp
Intake Air Temp < 18°C (64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.

3) Fuzzy Operation for Heating


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37°F) or more
above the setting temp, the compressor is turned off. When below the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp + 2°C(36°F)
Compressor OFF Temp => Setting Temp + 4°C(39°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
20°C(68°F) ≤ Intake Air Temp => Intake Air Temp + 0.5°C(33°F)
Intake Air Temp < 20°C(68°F) => 20°C(68°F)

• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
n Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.

n On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.

n Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 50-


Only for training and service purposes
LGE Internal Use Only
Operation Details
n Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation
is carried out according to the set time.

n Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C(34°F) After another 30 min elapse, it increases by 1°C(34°F) again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.

n Chaos Swing Mode


• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.

n Chaos Natural Wind Mode


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.”

n Jet Cool Mode Operation (Outdoor unit C/O Model)


• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F)
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

n Jet Cool Mode Operation (Outdoor unit H/P Model)


• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F)
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

n Auto Restarting Operation


• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory

Copyright ©2010 LG Electronics. Inc. All right reserved. - 51-


Only for training and service purposes
LGE Internal Use Only
Operation Details
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)

n Forced Operation (Outdoor unit C/O Model)


• To operate the appliance by force in case that the remote controller is lost, the forced operation button is on
the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• The forced operation is carried out in cooling mode with the setting temperature 22°C(72°F) and the high
speed of airflow.

n Forced Operation (Outdoor unit H/P Model)


• To operate the appliance by force in case that the remote controller is lost, the forced operation selection
switch is on the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation
condition is set according to the intake air temperature as follows.
24°C(76°F) ≤ Intake Air Temp => Cooling Mode Operation, 22°C(72°F), High Speed
21°C(70°F) ≤ Intake Air Temp < 24°C(76°F) => Dehumidification Operation, 23°C(74°F), High Speed
Intake Air Temp < 21°C(70°F) => Heating Mode Operation, 24°C(76°F), High Speed

n Test Operation Control


• To check the condition of the installation when installing the appliance, the appliance is operated at cooling
mode, high speed of airflow, compressor-on for 18 min without controlling the room temperature.
• After supplying power to the main body, keep pressing the forced operation button for about 3 seconds.
• While in test operation, a key can be input by the remote controller.
When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, Jet
Cool) is input by the remote controller, the test operation is canceled and the appliance is operated according
to the setting by the remote controller.

n Protection of the evaporator pipe from frosting


• In the temperrature of the indoor pipe is below 0°C(32°F) after 7 minutes from starting the compressor, the
compressor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the tem-
perature of the indoor pipe is over 7°C(45°F), the compressor and the outdoor fan are reoperated.
• Outdoor fan motor stops when indoor pipe temperature is blow 3°C(37°F) and restarts at the pipe temperature
above 6°C or after 90 seconds, if the pipe temperature does not rise to 6°C(43°F), outdoor fan motor runs con-
tinuously at even below 3°C(37°F).

Copyright ©2010 LG Electronics. Inc. All right reserved. - 52-


Only for training and service purposes
LGE Internal Use Only
Operation Details
n Buzzer Sounding Operation
• When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds.
• When the appliance-pause key is input by the remote controller, the long “beep—” sounds.

n Air Cleaner Operation


• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 53-


Only for training and service purposes
LGE Internal Use Only
2 ART COOL Gallery
W D
Dimensions

ARNU073SF*2
ARNU093SF*2
ARNU123SF*2

Only for training and service purposes


[Unit : mm(inch)]
1 Model W H D

1 ARNU073SF*2
3. Dimensions

600 600 146


ARNU093SF*2 (23-5/8) (23-5/8) (5-11/16)
ARNU123SF*2

Copyright ©2010 LG Electronics. Inc. All right reserved.


[Unit : mm(inch)]
Pipe Hole
Number Name Descripition
1 Air discharge grill
2 Air suction grill
1
Hanger Hole Note

- 54-
500(19-5/8) 1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

) 8/ 5- 02( 525
Fix Hole

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: SF
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Ceiling Concealed Duct Type (Low static)

1. Funtions......................................................................................56
2. Operation Details........................................................................57
3. Dimensions.................................................................................60

Copyright ©2010 LG Electronics. Inc. All right reserved. - 55-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

• Although the air-conditioner is turned off by a power failure, it is restarted auto-


Auto Restart
matically previous operation mode after power supply.

• Both the indoor and outdoor fan stops during defrosting.


Deice (defrost) control (Heating)
• Hot start after defrost ends.

• The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25°C(76°F).

• A standard drain-head height of up to 700mm(27-9/16inch)


High head height Drain pump
is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 56-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature


Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))

Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

Selecting Selecting Selecting


INDOOR FAN Low Low
fan speed fan speed fan speed

COMPRESSOR ON OFF ON OFF ON

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2010 LG Electronics. Inc. All right reserved. - 57-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C(104°F)


Heat-Exchanger
temperature T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C(37 °F)
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - WhileAthe indoor Heat-Exchanger temperature is higher than 40 °C(104 °F), fan operates
at low speed, when it becomes lower than 40 °C(104 °F) fan stops.
- For eluminating
B latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To beCoperated "Low" except initial Hotstart operation

High Static Low Static Convertible


Chassis BH BG BR B1 B2 CE CF VE VJ
Hotstart On T On 19°C(66°F)19°C(66°F)19°C(66°F)19°C(66°F)
19°C(66°F)
19°C(66°F)
19°C(66°F) 26°C(78°F) 26°C(78°F)
Hotstart Off T Off 22°C(72°F)22°C(72°F)22°C(72°F)22°C(72°F)
22°C(72°F)
22°C(72°F)
22°C(72°F) 27°C(80°F) 27°C(80°F)
Low temperatureT LT 25°C(76°F)25°C(76°F)25°C(76°F)25°C(76°F)
25°C(76°F)
25°C(76°F)
25°C(76°F) 28°C(82°F) 28°C(82°F)
Setting Temperature T ST 27°C(80°F)27°C(80°F)27°C(80°F)27°C(80°F)
27°C(80°F)
27°C(80°F)
27°C(80°F) 30°C(86°F) 30°C(86°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 58-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F).

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2010 LG Electronics. Inc. All right reserved. - 59-


Only for training and service purposes
LGE Internal Use Only
Ceiling Concealed Duct (Low Static)
Dimensions

ARNU073B1G2
ARNU093B1G2
ARNU123B1G2
ARNU153B1G2
ARNU183B2G2

Only for training and service purposes


ARNU243B2G2
5 13(1/2)
D
[Unit : mm(inch)]
3. Dimensions

A B C D

Copyright ©2010 LG Electronics. Inc. All right reserved.


ARNU073B1G2
190(7-7/16)
ARNU093B1G2 820 728 856 794
65(2-1/2) 60(2-3/8)
ARNU123B1G2 (32-5/16) (28-11/16) (33-11/16) (31-5/16)

) 61/ 5- 6( 161 ) 2/ 1( 41
ARNU153B1G2
1
ARNU183B2G2 1100 1008 1131 1072
2 ARNU243B2G2 (43-5/16) (39-11/16) (44-9/16) (42-3/16)

) 2/ 1- 8( 612

) 8/ 7- 01( 772

- 60-
[Unit : mm(inch)]

)21/11(42

) 8/ 5- 22( 575
Number Name Descripition

) 61/ 1- 51( 383


Unit size(7k,9k,12k,18k):ø6.35(1/4)
3 1 Liquid pipe connection Unit size(24k):ø9.52(3/8)
Unit size(7k,9k,12k,18k):ø12.7(1/2)
2 Gas pipe connection Unit size(24k):ø15.88(5/8)
3 Drain pipe connection
C
4
4 Power supply connection
6

) 4/ 3( 81
5 Air discharge
6 Air suction

) 6( 451

) 61/ 7- 7( 091
Note

18(3/4) B 1. Unit should be installed in compliance with the installation manual


in the product box.
A
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B1/B2
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Ceiling Concealed Duct Type (Built in)

1. Funtions......................................................................................62
2. Operation Details........................................................................63
3. Dimensions.................................................................................66

Copyright ©2010 LG Electronics. Inc. All right reserved. - 61-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

• Although the air-conditioner is turned off by a power failure, it is restarted auto-


Auto Restart
matically previous operation mode after power supply.

• Both the indoor and outdoor fan stops during defrosting.


Deice (defrost) control (Heating)
• Hot start after defrost ends.

• The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25°C(76°F).

• A standard drain-head height of up to 700mm(27-9/16inch)


High head height Drain pump
is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 62-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature


Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))

Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

Selecting Selecting Selecting


INDOOR FAN Low Low
fan speed fan speed fan speed

COMPRESSOR ON OFF ON OFF ON

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2010 LG Electronics. Inc. All right reserved. - 63-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C(104°F)


Heat-Exchanger
temperature T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C(37 °F)
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - WhileAthe indoor Heat-Exchanger temperature is higher than 40 °C(104 °F), fan operates
at low speed, when it becomes lower than 40 °C(104 °F) fan stops.
- For eluminating
B latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To beCoperated "Low" except initial Hotstart operation

High Static Low Static Convertible


Chassis BH BG BR B1 B2 CE CF VE VJ
Hotstart On T On 19°C(66°F)19°C(66°F)19°C(66°F)19°C(66°F)
19°C(66°F)
19°C(66°F)
19°C(66°F) 26°C(78°F) 26°C(78°F)
Hotstart Off T Off 22°C(72°F)22°C(72°F)22°C(72°F)22°C(72°F)
22°C(72°F)
22°C(72°F)
22°C(72°F) 27°C(80°F) 27°C(80°F)
Low temperatureT LT 25°C(76°F)25°C(76°F)25°C(76°F)25°C(76°F)
25°C(76°F)
25°C(76°F)
25°C(76°F) 28°C(82°F) 28°C(82°F)
Setting Temperature T ST 27°C(80°F)27°C(80°F)27°C(80°F)27°C(80°F)
27°C(80°F)
27°C(80°F)
27°C(80°F) 30°C(86°F) 30°C(86°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 64-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F).

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2010 LG Electronics. Inc. All right reserved. - 65-


Only for training and service purposes
LGE Internal Use Only
With Suction Grille B3/B4 Ceiling Concealed Duct (Built in)
With Suction Grille & Suction Canvas
Dimensions

ARNU073B3G2+PBSGB30(Accessory), PBSC30(Accessory)
ARNU093B3G2+PBSGB30(Accessory), PBSC30(Accessory)
ARNU123B3G2+PBSGB30(Accessory), PBSC30(Accessory)
ARNU153B3G2+PBSGB30(Accessory), PBSC30(Accessory)
190(7-7/16)
6 ARNU183B4G2+PBSGB40(Accessory), PBSC40(Accessory)
65(2-1/2)60(2-3/8)

Only for training and service purposes


ARNU243B4G2+PBSGB40(Accessory), PBSC40(Accessory)

) 8/ 7- 01( 772
3. Dimensions

) 2/ 1- 8( 612 )21/11(42

) 8/ 5- 22( 575
) 4/ 1- 51( 883

) 4/ 1- 51( 883

Copyright ©2010 LG Electronics. Inc. All right reserved.


1

) 61/ 5- 42( 816


3
5

A_1 With Suction Grille


4

2_ B
) 61/ 7- 7( 091

- 66-
A_2

) 61/ 31- 9( 052


C_2 [Unit : mm(inch)]
With Suction Grille & Suction Canvas Number Name Descripition
Unit size(7k,9k,12k,18k):ø6.35(1/4)
1 Liquid pipe connection Unit size(24k):ø9.52(3/8)
Unit size(7k,9k,12k,18k):ø12.7(1/2)
2 Gas pipe connection Unit size(24k):ø15.88(5/8)

) 61/ 7- 7( 091
3 Drain pipe connection
Btu/h A_1 4 Power supply connection
7,9,12k 820(32-5/16)

) x a M() 61/ 11- 91( 005


5 Air discharge

3_ C
18,24k 1100(43-5/16)
6 Air suction
A_3 B_3
A_2 B_2 C_2
PBSGB30 910(35-13/16) 359(14-1/8) 56(2-3/16) Note
PBSGB40 1188(46-13/16) 359(14-1/8) 56(2-3/16)
1. Unit should be installed in compliance with the installation manual
A_3 B_3 C_3 in the product box.
PBSC30 821(32-5/16) 274(10-11/16) 42~250(1-9/16~9-13/16) 2. Unit shall be grounded in accordance with the local regulations or
PBSC40 1100(43-5/16) 274(10-11/16) 42~250(1-9/16~9-13/16) applicable national codes.

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B3/B4
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Ceiling Concealed Duct Type (High Static)

1. Funtions......................................................................................68
2. Operation Details........................................................................69
3. Dimensions.................................................................................72

Copyright ©2010 LG Electronics. Inc. All right reserved. - 67-


Only for training and service purposes
LGE Internal Use Only
Funtion

1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

• Although the air-conditioner is turned off by a power failure, it is restarted auto-


Auto Restart
matically previous operation mode after power supply.

• Both the indoor and outdoor fan stops during defrosting.


Deice (defrost) control (Heating)
• Hot start after defrost ends.

• The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25°C(76°F)

• A standard drain-head height of up to 700mm(27-9/16inch)


High head height Drain pump
is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 68-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature


Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))

Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

Selecting Selecting Selecting


INDOOR FAN Low Low
fan speed fan speed fan speed

COMPRESSOR ON OFF ON OFF ON

Copyright ©2010 LG Electronics. Inc. All right reserved. - 69-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C(104°F)


Heat-Exchanger
temperature T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C(37 °F)
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - WhileAthe indoor Heat-Exchanger temperature is higher than 40 °C(104 °F), fan operates
at low speed, when it becomes lower than 40 °C(104 °F) fan stops.
- For eluminating
B latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To beCoperated "Low" except initial Hotstart operation

High Static Low Static Convertible


Chassis BH BG BR B1 B2 CE CF VE VJ
Hotstart On T On 19°C(66°F)19°C(66°F)19°C(66°F)19°C(66°F)
19°C(66°F)
19°C(66°F)
19°C(66°F) 26°C(78°F) 26°C(78°F)
Hotstart Off T Off 22°C(72°F)22°C(72°F)22°C(72°F)22°C(72°F)
22°C(72°F)
22°C(72°F)
22°C(72°F) 27°C(80°F) 27°C(80°F)
Low temperatureT LT 25°C(76°F)25°C(76°F)25°C(76°F)25°C(76°F)
25°C(76°F)
25°C(76°F)
25°C(76°F) 28°C(82°F) 28°C(82°F)
Setting Temperature T ST 27°C(80°F)27°C(80°F)27°C(80°F)27°C(80°F)
27°C(80°F)
27°C(80°F)
27°C(80°F) 30°C(86°F) 30°C(86°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 70-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F).

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2010 LG Electronics. Inc. All right reserved. - 71-


Only for training and service purposes
LGE Internal Use Only
4 Ceiling Concealed Duct (High Static)
745(29-3/8) 115(4-1/2)
Dimensions

ARNU073BHA2
ARNU093BHA2

) 4/ 3( 02 ) 8/ 7- 6( 571
ARNU123BHA2
ARNU153BHA2

Only for training and service purposes


6 51(2-1/16) 101(3-15/16)
49(15/16) ARNU183BHA2
932(36-11/16) 70(2-3/4) 31(1-3/13)
24(15/16) ARNU243BHA2
29(1-1/8)

) 8/ 7- 1( 84

) 61/ 51- 1( 05
114(4-1/2)
3. Dimensions

R3

) 61/ 1- 2( 25
.7 5

) 8/ 7- 8( 422
) 31/ 7- 6( 561
/ 8)
60(2-3

) 41( 553

Copyright ©2010 LG Electronics. Inc. All right reserved.


) 41( 553
3

) 61/ 11- 71( 054

) 61/ 11- 71( 054


) 61/ 51- 3( 001
1
47(1-7/8) 2

) 4/ 1- 5( 331
47(1-7/8)
21(7/8)

) 61/ 9- 5( 041
260(10-1/4)

) 61/ 31- 4( 321


87(3-7/16) 30(1-3/16)
750(29-1/2)
5

882(34-3/4) 108(4-3/13)

- 72-
65(2-9/16) [Unit : mm(inch)]
Number Name Descripition
Unit size(7k,9k,12k,18k):ø6.35(1/4)
1 Liquid pipe connection

) 5( 721
Unit size(24k):ø9.52(3/8)

) 4/ 1- 01( 062
) 4/ 1- 6( 851
) 61/ 51- 2( 57
Unit size(7k,9k,12k,18k):ø12.7(1/2)

601
) 8/ 1- 4(
2 Gas pipe connection Unit size(24k):ø15.88(5/8)
3 Drain pipe connection
64(2-1/2) 243(9-9/16) 212(8-3/8) 243(9-9/16) 119(4-11/16)
4 Power supply connection
5 Air discharge
6 Air suction

Note
1. Unit should be installed in compliance with the installation manual

) 61/ 11- 71( 054


in the product box.
2. Unit shall be grounded in accordance with the local regulations or
882(34-3/4) applicable national codes.

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BH
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


1,043(41) 115(4-1/2) 4 Ceiling Concealed Duct (High Static)
ARNU283BGA2
ARNU363BGA2

) 4/ 3( 02 ) 8/ 5- 8( 022
ARNU423BGA2

Only for training and service purposes


6
1,230(48-7/16) 102(4)
51(2-1/16) 32(1-3/13)
23(15/16)

) 61/ 51- 1( 05
152(5-7/8)

Copyright ©2010 LG Electronics. Inc. All right reserved.


ø1
0 0

) 31/ 7- 6( 561

) 8/ 7- 8( 422
/ 8)

) 8/ 7- 1( 74 ) 61/ 1- 2(35
3
60(2-

) 61/ 11- 71( 054


) 61/ 51- 3( 001
1

) 41( 553 ) 61/ 7- 3( 78


) 61/ 9- 5( 041
2
3
49(15/16)
29(1-3/8) 75(2-15/16)

) 61/ 31- 4( 221


87(3-7/16) 261(10-1/4)
830(32-11/16)

- 73-
5
1,182(46-5/8) 108(4-3/13)

[Unit : mm(inch)]
Number Name Descripition

) 61/ 5- 7( 681
1 Liquid pipe connection Unit size(28k,36k,42k):ø9.52(3/8)

) 61/ 11- 11( 892


2 Gas pipe connection Unit size(28k,36k,42k):ø15.88(5/8)

) 4/ 1- 6( 851 ) 61/ 7- 4( 311


232(1-1/4) 243(9-9/16) 232(1-1/4) 243(9-9/16) 232(1-1/4) 3 Drain pipe connection
4 Power supply connection
5 Air discharge
6 Air suction
Note

) 61/ 11- 71( 054


1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
1,182(46-1/2) applicable national codes.

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BG
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com

LGE Internal Use Only


www.lgeaircon.com
Dimensions
Ceiling Concealed Duct (High Static)
4
1,092(43) 120(4-3/4)
Dimensions

) 1( 52
ARNU483BRA2

) 21( 303
[Unit : mm(inch)]

Only for training and service purposes


6 101(3-15/16)
1,284(50-9/16)
83(3-1/4) Number Name Descripition
1,230(48-7/16) 115(4-9/16) 26(1)
1 Liquid pipe connection Unit size(48k):ø9.52(3/8)

R6
198(7-3/4) 2 Gas pipe connection Unit size(48k):ø15.88(5/8)
0

) 4/ 3- 8( 122

) 61/ 31- 2( 27
)61/ 31- 4(321
) 3 Drain pipe connection

) 4/ 1- 21( 213

Copyright ©2010 LG Electronics. Inc. All right reserved.


- /38
(2
60 3

) 61/ 9- 3( 09
4 Power supply connection

) 61/ 3- 32( 095

) 4/ 3- 81( 774
1 5 Air discharge
2

) 61/ 11- 5( 441


6 Air suction
135(5-5/16)
50(1-15/16)

) 61/ 31- 4( 221


118(4-5/8) 114(4-7/16) 190(7-7/16)

) 61/ 3- 2( 65

) 31/ 3- 1( 23
260(10-1/4)
1,004(39-9/16) Note
5

- 74-
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

) 8/ 5- 6( 861

) 51( 083
) 61/ 9- 5( 041
) 4/ 1- 7( 581
241(9-1/2) 279(11) 241(9-1/2) 279(11) 215(8-1/2)

) 61/ 3- 32( 095


1,230(48-7/16)

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BR
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Ceiling Concealed Duct (High Static)
1,396(54-15/16) 115(4-9/16) 4
URNU763B8A2

)4/ 3( 02
URNU963B8A2
2

)8/ 3-71( 044


70(2-3/4)
6 120(4-3/4)

Only for training and service purposes


3
/16)
1,622(63-11/13) 40(5-9
460(18-1/13) (3-7/8) 1
99
1,562(61-7/13)
1

)2/ 1-2(46
58(2-1/4)
18(3/4)

)8/3-2(06

Copyright ©2010 LG Electronics. Inc. All right reserved.


)4/3-2(07 )8/7-4(221
109(4-1/4) [Unit : mm(inch)]
68(2-5/8)

)72(886
) 22( 065
358(14) Number Name Descripition
1 Liquid pipe connection Unit size(76k,96k):ø9.52(3/8)
1,220(48) Unit size(76k):ø19.05(3/4)
2 Gas pipe connection Unit size(96k):ø22.2(7/8)

)31/ 7-2(46
)61/ 3-1(03
5
3 Drain pipe connection

- 75-
4 Power supply connection
5 Air discharge
6 Air suction

)31/ 7- 21( 813


)31/ 1-81(064
)61/ 7-11(092 161
) 8/ 3- 6(
293(11-7/13) 329(12-15/16) 320(12-5/8) 329(12-15/16)
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

) 72( 886
1,562(61-1/2)

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B8
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Dimensions
Wall Mountedd Type

1. Functions....................................................................................77
2. Operation Details........................................................................78
3. Dimensions.................................................................................85

Copyright ©2010 LG Electronics. Inc. All right reserved. - 76-


Only for training and service purposes
LGE Internal Use Only
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature


• Room temperature sensor. (THERMISTOR)

Room temperature control


• Maintains the room temperature in accordance with the Setting temperature

Starting Current Control


• Indoor fan is delayed for 5 sec at the starting.

Indoor Fan Speed Control

• High, Med, Low, CHAOS

Operation indication Lamps (LED)


Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.
Defrost Mode : Lights up during Defrost Mode or Hot Start operation.
Temperature : Indicate the setting temperature.

Soft Dry Operation Mode

• Intermittent
Sleep Mode operation of fan at low speed.
Auto Control

• The fan is switched to low(Cooling), med(Heating) speed. Defrost(Deice) control (Heating)


• The unit will
Natural Airbe stopped
Control byafter 1, 2,Logic
CHAOS 3, 4, 5, 6, 7 hours.
• Both the indoor and outdoor fan stops dur-
ing defrosting.
Hot-start Control (Heating)
• The fan is switched to intermittent or irregular operation
• The fan speed
Airflow is automatically
Direction Control switched from high to low speed. • The indoor fan does not rotate until the
evaporator pipe temperature will be reached
at 28°C(82°F).

• The louver can be set at the desired position or swing


up and down automatically.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 77-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
Function of Controls
DISPLAY
(1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer(on/off) and Sleep timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
• When the intake air temperature reaches 0.5°C(33°F) below the setting temp, the compressor and the outdoor
fan stop.
• When it reaches 0.5°C(33°F)above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C (33°F)
Compressor OFF Temp => Setting Temp-0.5°C(33°F)
• While in compressor running, operating with the airflow speed set by the remote controller. While in com-
pressor not running, operating with the low airflow speed regardless of the setting.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 78-


Only for training and service purposes
LGE Internal Use Only
Operation Details
n Healthy Dehumidification Mode
• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp-1°C(34°F)
18°C(64°F) ≤ Intake Air Temp < 24°C(76°F) => Intake Air Temp-0.5°C (33°F)
Intake Air Temp < 18°C(64°F) => 18°C(64°F)
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C (33°F)
Compressor OFF Temp. => Setting Temp-0.5°C(33°F)
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

n Heating Mode Operation


• When the intake air temp reaches +3°Cabove the setting temp, the compressor is turned off. When below the
setting temp, the compressor is turned on.
Thermo ON Temp. => Setting Temp. +2°C(36°F)
Thermo OFF Temp. => Setting Temp. +4°C(39°F)
• While in compressor on, when above 38°C(100°F) , it operates with or setting airflow speed (while in sleep
mode, with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(92°F) , when above
35°C(94°F) , it operates with the low airflow speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.

n Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost the outdoor unit.

n Fuzzy Operation (Outdoor unit C/O Model)


• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C(33°F)or more below the set-
ting temp, the compressor is turned off. When 0.5°C (33°F) or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C (33°F)
Compressor OFF Temp => Setting Temp+0.5°C(33°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 79-


Only for training and service purposes
LGE Internal Use Only
Operation Details

26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)


24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C (33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp
Intake Air Temp<18°C(64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-
ature

n Fuzzy Operation (Outdoor unit H/P Model)


• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C(76°F) ≤ Inatake Air Temp => Fuzzy Operation for Cooling
21°C(70°F) ≤ Inatake Air Temp<24°C(76°F) => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C(70°F) => Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1) Fuzzy Operation for Cooling


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F)or more
below the setting temp, the compressor is turned off. When 0.5°C(33°F)or more above the setting temp, the
compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C (33°F)
Compressor OFF Temp => Setting Temp+0.5°C(33°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C (33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F)=> Intake Air Temp
Intake Air Temp < 18°C(64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

2) Fuzzy Operation for Dehumidification


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F)or more
below the setting temp, the compressor is turned off. When 0.5°C(33°F)or more above the setting temp, the
compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C (33°F)
Compressor OFF Temp => Setting Temp+0.5°C(33°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 80-


Only for training and service purposes
LGE Internal Use Only
Operation Details

• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F)
22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C (33°F)
18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp
Intake Air Temp < 18°C(64°F) => 18°C(64°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.

3) Fuzzy Operation for Heating


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37°F) or more
above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned
on.
Compressor ON Temp => Setting Temp. +2°C(36°F)
Compressor OFF Temp => Setting Temp. +4°C(39°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C(68°F) ≤ Intake Air Temp => Intake Air Temp + 0.5°C (33°F)
Intake Air Temp < 20°C(68°F) => 20°C(68°F)

• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.

n Airflow Speed Selection


• The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.

n On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.

n Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 81-


Only for training and service purposes
LGE Internal Use Only
Operation Details
n Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation is
carried out according to the set time.

n Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C(34°F) After another 30 min elapse, it increases by 1°C(34°F) again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.

n Chaos Swing Mode


• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.

n Chaos Natural Wind Mode


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.”

n Jet Cool Mode Operation (Outdoor unit C/O Model)


• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F)
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• During the JET COOL function at any moment, the A/C starts to blow the cool air with side louvers closed at
extremely high speed for 30 minutes setting the room temp. automatically to 18°C.

n Jet Cool Mode Operation (Outdoor unit H/P Model)


• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other
mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F)
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• During the JET HEAT function at any moment, the A/C starts to blow the hot air with side louvers closed at
extremely high speed for 60 minutes setting the room temp. automatically to 30°C(86°F).

n Auto Restarting Operation


• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF

Copyright ©2010 LG Electronics. Inc. All right reserved. - 82-


Only for training and service purposes
LGE Internal Use Only
Operation Details
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)

n Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.

Heat pump Model


Cooling Model
Room Temp. ≥ 24°C(76°F)
21°C(70°F) ≤ Room Temp. <Room
24°C(76°F)
Temp. < 21°C(70°F)
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor Fan Speed High High High High
Setting Temperature22°C(72°F) 22°CC(72°F) 23°C(74°F) 24°C(76°F)

• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.

n Test operation
• During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-
perature and resets in 18±1 minutes.
•During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, Press and hold ON/OFF button 3~5 seconds, then the buzzer sound 1 "beep".
• If you want to stop the operation, re-press the button.

n Protection of the evaporator pipe from frosting


• If the indoor pipe temp is below 0°C(32F) in 7 min. after the compressor operates without any pause while in
cooling cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor
evaporator pipe from frosting.
• When the indoor pipe temp is 7°C(45°F) or higher after 3 min. pause of the compressor, the compressor and
the outdoor fan is turned on according to the condition of the room temperature.

n Buzzer Sounding Operation


• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
• When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the
remote control signal cannot be received.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 83-


Only for training and service purposes
LGE Internal Use Only
Operation Details
n Air Cleaner Operation
• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 84-


Only for training and service purposes
LGE Internal Use Only
Wall Mounted
PIPING/WIRING PIPING/WIRING ARNU07GSE*2
DIRECTION DIRECTION
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2
(unit : mm)

Only for training and service purposes


Model W H D
ARNU07GSE*2
ARNU09GSE*2 895 282 165
3. Dimensions

ARNU12GSE*2
ARNU15GSE*2

Copyright ©2010 LG Electronics. Inc. All right reserved.


(unit : mm)
PIPING DIRECTION
Number Name Descripition
1 Front panel
2 Air discharge
3 Air suction
4 Liquid pipe Ø6.35 Flare connection

- 85-
567
5 Gas pipe Ø12.7 Flare connection
6 Drain pipe External dia. Ø17
7 Right side piping/wiring connection

562
8 Left side piping/wiring connection
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
PIPE AND DRAIN DIMENSION 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

※Required space(unit:mm)
Lower than 2.3m
More than 200 mm

More than 100 mm

More than 100 mm


Higher than eye-level

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: SE

LGE Internal Use Only


Dimensions
Wall Mounted

PIPING/WIRING PIPING/WIRING ARNU18GS5*2


Dimensions

DIRECTION DIRECTION
ARNU24GS5*2

(unit : mm)
Model W H D

Only for training and service purposes


ARNU18GS5*2 1090 300 178
ARNU24GS5*2

(unit : mm)

Copyright ©2010 LG Electronics. Inc. All right reserved.


Number Name Descripition
PIPING DIRECTION
1 Front panel
2 Air discharge
3 Air suction
4 Liquid pipe Ø6.35 Flare connection
5 Gas pipe Ø12.7 Flare connection
6 Drain pipe External dia. Ø17

- 86-
804
7 Right side piping/wiring connection
8 Left side piping/wiring connection

182
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
PIPE AND DRAIN DIMENSION applicable national codes.

※Required space(unit:mm)
Lower than 2.3m
More than 200 mm

More than 100 mm

More than 100 mm


Higher than eye-level

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: S5

LGE Internal Use Only


Ceiling & Floor
Ceiling Suspended

1. Funtions......................................................................................88
2. Operation Details........................................................................89
3. Dimensions.................................................................................92

Copyright ©2010 LG Electronics. Inc. All right reserved. - 87-


Only for training and service purposes
LGE Internal Use Only
Function

1. Function
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C(76°F).

• A standard drain-head height of up to 700mm(27-9/16inch)


High head height Drain pump
is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 88-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature


Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))

Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

Selecting Selecting Selecting


INDOOR FAN Low Low
fan speed fan speed fan speed

COMPRESSOR ON OFF ON OFF ON

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2010 LG Electronics. Inc. All right reserved. - 89-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C(104°F)


Heat-Exchanger
temperature T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C(37 °F)
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - WhileAthe indoor Heat-Exchanger temperature is higher than 40 °C(104 °F), fan operates
at low speed, when it becomes lower than 40 ° °
C(104 F) fan stops.
- For eluminating
B latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To beCoperated "Low" except initial Hotstart operation

High Static Low Static Convertible


Chassis BH BG BR B1 B2 CE CF VE VJ
Hotstart On T On 19°C(66°F)19°C(66°F)19°C(66°F)19°C(66°F)
19°C(66°F)
19°C(66°F)
19°C(66°F) 26°C(78°F) 26°C(78°F)
Hotstart Off T Off 22°C(72°F)22°C(72°F)22°C(72°F)22°C(72°F)
22°C(72°F)
22°C(72°F)
22°C(72°F) 27°C(80°F) 27°C(80°F)
Low temperatureT LT 25°C(76°F)25°C(76°F)25°C(76°F)25°C(76°F)
25°C(76°F)
25°C(76°F)
25°C(76°F) 28°C(82°F) 28°C(82°F)
Setting Temperature T ST 27°C(80°F)27°C(80°F)27°C(80°F)27°C(80°F)
27°C(80°F)
27°C(80°F)
27°C(80°F) 30°C(86°F) 30°C(86°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 90-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F).

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2010 LG Electronics. Inc. All right reserved. - 91-


Only for training and service purposes
LGE Internal Use Only
Ceiling & Floor
Dimensions

ARNU09GVEA2
ARNU12GVEA2
(unit : mm)
Model W H D

Only for training and service purposes


ARNU09GVEA2 900 490 200
ARNU12GVEA2
3. Dimensions

(unit : mm)
Number Name Descripition

Copyright ©2010 LG Electronics. Inc. All right reserved.


1 Liquid pipe ø6.35 Flare connection
2 Gas pipe ø12.7 Flare connection
3 Suction gille
4 Discharge grille
5 Suspension bracket
6 Right side drain hose hole
7 Left side drain hose hole

- 92-
8 Wiring connection Slit hole
9 Piping connection Slit hole
10 Signal receiver & Operation indicator

Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

※Required space(unit:mm)
587 More than 200mm
More than 200mm

More than 200mm

372 More than 50mm More than 50mm


More than 200mm

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: VE

LGE Internal Use Only


Ceiling Suspended
ARNU18GVJA2
ARNU24GVJA2

(unit : mm)
Model W H D

Only for training and service purposes


ARNU18GVJA2 950 650 220
ARNU24GVJA2

(unit : mm)

Copyright ©2010 LG Electronics. Inc. All right reserved.


Number Name Descripition
1 Liquid pipe ø6.35 Flare connection
2 Gas pipe ø12.7 Flare connection
3 Suction gille
4 Discharge grille
5 Suspension bracket
6 Right side drain hose hole

- 93-
7 Left side drain hose hole
8 Wiring connection Slit hole
9 Piping connection Slit hole
10 Right side drain pipe connection Slit hole
11 Left side drain pipe connection Slit hole
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

More than 700 m


※Required space(unit:mm)

More than 700mm More than 300mm

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea CHASSIS CODE: VJ

LGE Internal Use Only


Dimensions
Floor Standing Type

1. Function......................................................................................95
2. Operation Details........................................................................96
3. Dimensions.................................................................................99

Copyright ©2010 LG Electronics. Inc. All right reserved. - 94-


Only for training and service purposes
LGE Internal Use Only
Function

1. Function
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C(76°F).

• A standard drain-head height of up to 700mm(27-9/16inch)


High head height Drain pump
is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 95-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature


Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))

Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

Selecting Selecting Selecting


INDOOR FAN Low Low
fan speed fan speed fan speed

COMPRESSOR ON OFF ON OFF ON

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2010 LG Electronics. Inc. All right reserved. - 96-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C(104°F)


Heat-Exchanger
temperature T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C(37 °F)
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - WhileAthe indoor Heat-Exchanger temperature is higher than 40 °C(104 °F), fan operates
at low speed, when it becomes lower than 40 °C(104 °F) fan stops.
- For eluminating
B latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To beCoperated "Low" except initial Hotstart operation

High Static Low Static Convertible


Chassis BH BG BR B1 B2 CE CF VE VJ
Hotstart On T On 19°C(66°F)19°C(66°F)19°C(66°F)19°C(66°F)
19°C(66°F)
19°C(66°F)
19°C(66°F) 26°C(78°F) 26°C(78°F)
Hotstart Off T Off 22°C(72°F)22°C(72°F)22°C(72°F)22°C(72°F)
22°C(72°F)
22°C(72°F)
22°C(72°F) 27°C(80°F) 27°C(80°F)
Low temperatureT LT 25°C(76°F)25°C(76°F)25°C(76°F)25°C(76°F)
25°C(76°F)
25°C(76°F)
25°C(76°F) 28°C(82°F) 28°C(82°F)
Setting Temperature T ST 27°C(80°F)27°C(80°F)27°C(80°F)27°C(80°F)
27°C(80°F)
27°C(80°F)
27°C(80°F) 30°C(86°F) 30°C(86°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 97-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F).

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2010 LG Electronics. Inc. All right reserved. - 98-


Only for training and service purposes
LGE Internal Use Only
1067(42) Floor Standing
ARNU073CEA2 ARNU073CEU2
1 ARNU093CEA2 ARNU093CEU2
ARNU123CEA2 ARNU123CEU2
1067(42) 203(7-15/16)
ARNU153CEA2 ARNU153CEU2

Only for training and service purposes


[Unit : mm(inch)]
Model W H D
ARNU073CEA2
3. Dimensions

1067 635 203

) 52( 536
ARNU093CEA2
ARNU123CEA2 (42) (25) (7-15/16)

Copyright ©2010 LG Electronics. Inc. All right reserved.


ARNU153CEA2
ARNU073CEU2
978 639 190

) 4/ 3- 2( 07

) 61/ 51( 94
148.3
ARNU093CEU2
148.3 (38-1/2) (31-1/4) (7-7/16)
<With Case> 2 (5-13/16)
ARNU123CEU2
(5-13/16)
ARNU153CEU2

[Unit : mm(inch)]

- 99-
Number Name Descripition
1 Air discharge grill
978(38-1/2) 190(7-7/16) 2 Air suction grill
794(31-5/16) 13(1/2) 161(6-5/16) 14(1/2)
Note
1. Unit should be installed in compliance with the installation manual
in the product box.

) 4/ 3( 4. 02
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

) 4/ 1- 13( 936
) 4/ 1(
82. 6
<Without Case>

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: CE
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Dimensions
Floor Standing
ARNU183CFA2 ARNU183CFU2

302
Dimensions

) 61/ 51- 7(
203(7-15/16)
ARNU243CFA2 ARNU243CFU2
1345(52-15/16) 1

Only for training and service purposes


[Unit : mm(inch)]

) 52( 536
Model W H D
ARNU183CFA2 1345 635 203
ARNU243CFA2 (52-15/16) (25) (7-15/16)

Copyright ©2010 LG Electronics. Inc. All right reserved.


) 4/ 3- 2( 07

) 61/ 51- 1( 5. 94
ARNU183CFU2 1256 639 190
148.3 1048.4(41-1/4) 148.3 ARNU243CFU2 (49-7/16) (31-1/4) (7-7/16)
(5-13/16) (5-13/16)

<With Case> 2
(unit : mm)
Number Name Descripition
1 Air discharge grill

- 100-
2 Air suction grill

1256(49-7/16 Note
1098(43-1/4) 109.8(4-5/16) 190(7-7/16)
1072(42-3/16) 30(1-3/16) 161(6-5/16) 14(1/2) 1. Unit should be installed in compliance with the installation manual

) 61/ 3- 1( 4. 12
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

) 61/ 3- 3( 4. 18

) 4/ 1- 13( 936
541
) 61/ 11- 5(

07
) 4/ 3- 2(
<Without Case>

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: CF
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Vertical Air Handling Unit

1. Funtions....................................................................................102
2. Operation Details......................................................................103
3. Dimensions...............................................................................107

Copyright ©2010 LG Electronics. Inc. All right reserved. - 101-


Only for training and service purposes
LGE Internal Use Only
Funtions

1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low speed.

• Although the air-conditioner is turned off by a power failure, it is restarted auto-


Auto Restart
matically previous operation mode after power supply.

• Both the indoor and outdoor fan stops during defrosting.


Deice (defrost) control (Heating)
• Hot start after defrost ends.
• If the electric heater has been installed, indoor fan continuous
will be.
• The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25°C(76°F)

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 102-


Only for training and service purposes
LGE Internal Use Only
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature


Thermo. ON
(SET TEMPERATURE
+0.5°C(33°F))

Thermo. OFF
(SET TEMPERATURE More than More than
-0.5°C(33°F))
3 minutes 3 minutes

Selecting Selecting Selecting


INDOOR FAN Low Low
fan speed fan speed fan speed

COMPRESSOR ON OFF ON OFF ON

Copyright ©2010 LG Electronics. Inc. All right reserved. - 103-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40C(104F)


Heat-Exchanger
temperature
T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3C(37F)
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - WhileAthe indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- For eluminating
B latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To beCoperated "Low" except initial Hotstart operation

Vertical Air Handling Unit


Chassis NJ NK
Hotstart On T On 19°C(66°F) 19°C(66°F)
Hotstart Off T Off 22°C(72°F) 22°C(72°F)
Low temperatureT LT 25°C(76°F) 25°C(76°F)
Setting Temperature T ST 27°C(80°F) 27°C(80°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 104-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 22℃(71.6℉).

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

High Static Low Static Convertible


Chassis BH BG BR B1 B2 CE CF VE VJ
Hotstart On T On 19°C(66°F)19°C(66°F)19°C(66°F)19°C(66°F)
19°C(66°F)
19°C(66°F)
19°C(66°F) 26°C(78°F) 26°C(78°F)
Hotstart Off T Off 22°C(72°F)22°C(72°F)22°C(72°F)22°C(72°F)
22°C(72°F)
22°C(72°F)
22°C(72°F) 27°C(80°F) 27°C(80°F)
Low temperatureT LT 25°C(76°F)25°C(76°F)25°C(76°F)25°C(76°F)
25°C(76°F)
25°C(76°F)
25°C(76°F) 28°C(82°F) 28°C(82°F)
Setting Temperature T ST 27°C(80°F)27°C(80°F)27°C(80°F)27°C(80°F)
27°C(80°F)
27°C(80°F)
27°C(80°F) 30°C(86°F) 30°C(86°F)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 105-


Only for training and service purposes
LGE Internal Use Only
Operation Details

n Heater Operation
• The unit will operate according to the setting temperature and the indoor unit Heat-Exchanger temperature.

• Heater operation diagram is shown as following.

Setting temperature (A)

A-1℃ (34℉)

A-2℃ (36℉)

Heater ON Heater OFF Heater ON

Indoor unit
Heat-Exchanger
temperature 45℃ (113℉)
42℃ (108℉)

30℃ (86℉)
28℃ (82℉)

Heater 2 ON OFF ON
Heater 1 ON OFF ON

Copyright ©2010 LG Electronics. Inc. All right reserved. - 106-


Only for training and service purposes
LGE Internal Use Only
Vertical Air Handling Unit
ARNU183NJA2
ARNU243NJA2
ARNU303NJA2
ARNU363NJA2

Only for training and service purposes


4

41(1-5/8) 40
3. Dimensions

2 3
543(21-3/8)

Copyright ©2010 LG Electronics. Inc. All right reserved.


40(1-9/16) 46(1-13/16)

) 31( 133
) 01( 452

) 81( 754
) 71( 234
308(12-1/8) 117.5(4-5/8) 40(1-9/16) [Unit : mm(inch)]

- 107-
65
(2-9/16) 364(14-5/16)
1236(48-5/8) Number Name Descripition
Unit size(18k):ø6.35(1/4)
6 1 Liquid pipe connection Unit size(24k,30k):ø9.52(3/8)
5 1 2 Gas pipe connection
Unit size(18k):ø12.7(1/2)
Unit size(24k,30k):ø15.88(5/8)
3 Drain pipe connection
4 Power supply connection
5 Air discharge
6 Air suction

Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: NJ
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Dimensions
Vertical Air Handling Unit
Dimensions

ARNU423NKA2
ARNU483NKA2
ARNU543NKA2
4

Only for training and service purposes


41 40
(1-5/8) (1-9/16) 40
2 (1-9/16) 3

Copyright ©2010 LG Electronics. Inc. All right reserved.


40 49 5
(1-9/16) (1-15/16)

) 02(

034
805
) 61/ 51- 61(

25
) 61/ 1- 2(

) 52(
) 42(

536
016
39 118
(1-9/16) (4-5/8)

- 108-
65 362
6

55
) 61/ 3- 2(
1400 (2-9/16) (14-1/4)
(55-1/8)
308 1418 [Unit : mm(inch)]
(12-1/8) (55-13/16)
540 Number Name Descripition
(21-1/4) 1
1 Liquid pipe connection Unit size(28k,36k,42k):ø9.52(3/8)
2 Gas pipe connection Unit size(28k,36k,42k):ø15.88(5/8)
3 Drain pipe connection
4 Power supply connection
5 Air discharge
6 Air suction
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: NK
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com

LGE Internal Use Only


Part 3
Trouble shooting guide

Copyright ©2010 LG Electronics. Inc. All right reserved. - 109-


Only for training and service purposes
LGE Internal Use Only
Trouble shooting guide

Self-diagnosis function...................................................................111

Copyright ©2010 LG Electronics. Inc. All right reserved. - 110-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function

Self-diagnosis function
Self-Diagnosis Function
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
011 ’ 051 : No.105 error of master unit

Display Title Cause of Error


01-Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
02- Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
Transmission error : wired remote controller
03- Failing to receive wired remote controller signal in indoor unit PCB
↔indoor unit
Indoor unit relatederror

04-Drain pump Malfunction of drain pump


05-Transmission error : outdoor unit ↔ indoor unit Failing to receive outdoor unit signal in indoor unit PCB

06-Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short

07-Different operation mode Operation mode between indoor unit and outdoor unit is different

In case when the serial number marked onEEPROM of Indoor unit is 0 or


09-Serial No.
FFFFFF

Disconnecting the fan motor connector/Failure of indoor fan motor lock


10-Poor fan motor operation
Air temperature sensor of indoor unit is open or short

Copyright ©2010 LG Electronics. Inc. All right reserved. - 111-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

01 Indoor unit air sensor error


1. Indoor unit PCB wrong connection
Indoor unit sensor is
02 Indoor unit pipe inlet sensor error 2. Indoor unit PCB failure
open/short
3. Sensor problem (main reason)
06 Indoor unit pipe outlet sensor error

n Error diagnosis and countermeasure flow chart

Is sensor properly No
Connect properly to PCB
connected to PCB?

Yes

Is the resistance value No


Change the sensor
of sensor normal?*

Yes

Change the PCB

** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) ‘ Normal
Air temp sensor: 10°C(50°F) = 20.7kΩ : 25°C(76°F)= 10kΩ : 50°C(122°F)= 3.4kΩ
Pipe temp sensor: 10°C(50°F) = 10kΩ : 25°C(76°F)= 5kΩ : 50°C(122°F)= 1.8kΩ

CN_PIPE/OUT: Pipe outlet temp sensor

CN_PIPE/IN: Pipe inlet temp sensor


CN_ROOM: Indoor air temp sensor

<Fresh Air Intake Unit>

Measure the resistance of outlet pipe temp sensor.

<Standard Indoor Unit>

Copyright ©2010 LG Electronics. Inc. All right reserved. - 112-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

1. Remote controller fault


The remote controller
03 No transmission between cabled did not receive the sig- 2. Indoor unit PCB fault
remote controller & indoor unit nal from indoor unit 3. Connector fault, Wrong connection
during specific time 4. transmission cable problem

n Error diagnosis and countermeasure flow chart

Does the error happens No Replace cabled remote


again if the remote
controller
controller is replaced?*

Yes

Does the error occurred No


when the cable of remote Check connection &
controller is replaced? transmission cable **

Yes

Replace indoor unit PCB ***

* If there is no remote controller to replace : Use another unitʼs remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
‘ make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unitʼs address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing

CN-REMO : Remote controller connection

The PCB can differ from model to model.


Check from the right source.

Checking transmission cable connection status

Copyright ©2010 LG Electronics. Inc. All right reserved. - 113-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

Float switch is open due to 1. Drain pump/float switch fault


rising of condensate water 2. Improper drain pipe location, clog-
04 Drain pump error level because of drain ging of drain pipe
pump fault or drain pipe
3. Indoor unit PCB fault
clogging

Error diagnosis and countermeasure flow chart

Is the drain pan filled Is Float switch short


No No
half with condensate On measuring its Replace float switch
water? (half level of resistance?
float switch)*
Yes
Yes

Replace Indoor PCB or


reconnect the connector

In indoor unit PCB


Is drain pump working? No Does the terminal voltage No
(Sound/drain noise/ Replace indoor unit PCB
for drain pump has
contact etc.) 208/230V output?**
Yes Yes

Replace Drain Pump

Drain pump blocked by


foreign particles?

Yes

Remove it & clean the pump

* If the float goes up higher than a half of float


switch then the circuit is open & the unit is
stopped automatically.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 114-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function

float

A:Point to check rotating ***Indoor PCB drain pump connector


(Check input of 208/230V)
(Marked as CN-DPUMP)

Float switch connector

Float switch Housing (CN-FLOAT)

[***] Standard of drain pipe head height / slope

MAX 450

700mm(27-9/16inch)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 115-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

1. Auto addressing is not done


2. transmission cable is not connected
3. Short circuit of transmission cable
No signal transmission 4. Indoor unit transmission circuit fault
05 Indoor & Outdoor unit between indoor & outdoor 5. Outdoor unit transmission circuit fault
transmission error units. 6. Not enough distance between power and trans-
mission cable?

n Error diagnosis and countermeasure flow chart


Replace the PCB of indoor unit
No Is total number of indoor No displayed error
Does all the IDUs show
units connected displayed
same error code CH05? Re-connect after check the
after auto addressing?
transmission cable of indoor
Yes unit displayed error**
END
Replace outdoor PCB after
No Check the main power No checking
Is outdoor PCB LED
supply at the ODU
blinking?
terminal block? Replace TRANS after checking

Yes
Yes

No Check the insulation of inverter


Is main circuit breaker off? / constant compressor and replace
if required
Yes
Check the capacity of main circuit
breaker and replace if required
Improper connection of power supply cable
If all ok,
Turn on main circuit breaker
Main power supply problem

Check if the
transmission cable is
properly connected No
Re connect transmission cable
to indoor / outdoor
terminal block?*
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking

* (Note1) Transmission from IDU is normal if voltage * If the DC voltage between transmission terminal A, B
fluctuation(-9V ~ +9V) exists when checking DC voltage of indoor unit is fluctuate within (-9V~+9V) then
of communication terminal between IDU and ODU transmission from outdoor unit is normal

Copyright ©2010 LG Electronics. Inc. All right reserved. - 116-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

Indoor unit outlet pipe Indoor unit outlet pipe Refer to CH02
06 temperature sensor temperature sensor open
error or short

Error
Error Type Error Point Main Reasons
No.

The Indoor units started 1. Indoor units are in different mode


07 All Indoor units are not later are operated in dif- 2. PCB fault
running in same mode ferent mode from earlier 3. cabled remote controller fault
one. j Checking ch07 method
IDU doesnʼt operate as Operation mode is
flickering at IDU wired remote controller and IDU
display window.

n Error diagnosis and countermeasure flow chart

Does error code


Is operation mode of No No
disappear
outdoor & Indoor units Replace Indoor PCB***
after set operation
same?
mode same?**

Yes Yes

END

Adjust outdoor main PCB


dip switch setting *

* Check mode selection setting of wired remote controller.


** Outdoor main PCB dip switch no.5 (Cooling) or no.6 (heating) is in On, different mode operation error
may occur because the operation mode is fixed by dip switch setting.

© Dip switch Setting ©

ON ON

1234567 1234567
1234567 891011121314

ON ON

1234567 1234567
1234567 891011121314

*** Dissolution method CH07 with remote controller


1) Error removal method : Turn off remote controller by pressing the On/Off button on the cabled remote controller.
The error code will be removed automatically after few seconds.
With cableless remote controller: Turn off indoor unit, and then turn on by changing the operation
mode. The error will disappear.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 117-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function
**** After replacing the indoor unit PCB, make sure to be done to do Auto addressing and input the address of central control
***** If ODU Dry Contact function is set , different mode operation error may be occurred because the operation mode is fixed.

Error
Error Type Error Point Main Reasons
No.

1. Error developed in transmission between the


09 Indoor unit EEPROM micro- processor and the EEPROM on the sur-
error face of the PCB.
2. ERROR due to the EEPROM damage

n Error diagnosis and countermeasure flow chart

- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control

Copyright ©2010 LG Electronics. Inc. All right reserved. - 118-


Only for training and service purposes
LGE Internal Use Only
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault

n Error diagnosis and countermeasure flow chart

Is connector No
connection proper? Connect properly

Yes

Is fan motor No
Replace indoor unit fan motor
normal?*

Yes

Replace indoor unit PCB **

* It is normal when check hall sensor of indoor fan motor as shown below

Each termainl with the tester


Tester Normal resistance( ±10%)
+- TH chassis TD chassis
1 4
5 4 hundreds k Ω hundreds kk Ω
6 4
7 4 hundreds k Ω hundreds k Ω
1 4 5 6 7

<Checking connection state of fan motor connector>

** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the
address of central control
(Notice: The connection of motor connector to PCB should be done under no power
supplying to PCB)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 119-


Only for training and service purposes
LGE Internal Use Only
P/NO : MFL50459505 NOVEMBER, 2010