Vous êtes sur la page 1sur 11

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO.

9, SEPTEMBER 2009 2065

A Recursive Park Transformation to Improve the


Performance of Synchronous Reference Frame
Controllers in Shunt Active Power Filters
Alberto Pigazo, Member, IEEE, Vı́ctor M. Moreno, Member, IEEE, and Emilio J. Estébanez

Abstract—Load harmonic currents and load unbalances reduce


power quality (PQ) supplied by electrical networks. Shunt active
power filters (SAPFs) are a well-known solution that can be em-
ployed to enhance electrical PQ by injecting a compensation cur-
rent at the point of common coupling (PCC) of the SAPF, the
load, and the electrical grid. Hence, SAPF controllers must de-
termine the instantaneous values of the compensation reference
current, including nondesirable components of the load current. A
family of SAPF controllers, which evaluates the compensation ref-
erence current using synchronous rotating frames (SRFs), employs
a structure based on Park transformations: direct transform, low-
pass filtering (LPF), and inverse transform. The cutoff frequency
and the filter order of the LPF stage must be designed properly in
order to obtain an accurate reference current and a fast dynamic
response of these SAPF controllers. This paper proposes a recur-
sive implementation of the direct Park transformation that avoids Fig. 1. (a) Evaluation of the compensation reference current based on SRF
the filtering stage and allows accurate SRF controllers to be de- methods. (b) General structure of the SRF methods.
signed. Moreover, the proposed implementation is not dependent
on PCC conditions. The proposed implementation is evaluated us-
ing a three-phase, three-wire SAPF and compared with LPF-based e.g., the power quality method [5]–[7], or the Fryze-Buchholz-
controllers by simulation and experiment.
Depenbrock (FBD) method [8], [9]; the direct evaluation of the
Index Terms—Park transformation, power filters, recursive load active current, such as synchronous rotating frame (SRF)
Park transformation. decomposition-based methods [10]–[12]; or the evaluation of
the load current harmonic components for selective compen-
I. INTRODUCTION sation, e.g., discrete Fourier transform [13], [14] or Kalman
filtering [15], [16]. This paper focuses on single-SRF-based
HUNT active power filtering is a well-known technique
S employed to compensate load harmonic currents, load un-
balance, or load reactive power at the point of common coupling
methods for harmonic currents compensation, where the com-
pensation reference current i∗α β (k) can be evaluated by sub-
(PCC) of the shunt active power filter (SAPF), the electrical grid, tracting the target source current îα β (k) from the load current
and the distorting load [1], [2]. A digital SAPF controller must iα β (k) [Fig. 1(a)]. If selective harmonic compensation is re-
carry on three functionalities during each sampling interval: quired, more SRFs should be employed in order to establish
evaluate the instantaneous values of the compensation reference the harmonic components of the source target current. The ba-
current, evaluate the current consumption which is maintained sic structure of SRF methods, depicted in Fig. 1(b), consists of
by the SAPF dc-bus voltage, and ensure that the injected com- direct (DQ) and inverse (DQ−1 ) Park transformations, which
pensation current at the PCC matches the previously evaluated allow the evaluation of a specific harmonic component of the
values [3]. The performance of the SAPF depends on each of input signal iα β (k) and a low-pass filtering stage LPF.
these three functionalities, with the instantaneous evaluation of The software phase-locked loop (SPLL) generates sin ωk and
the compensation reference current being a key point. cos ωk functions, where ω = 2π/N and N ∈ R+ is the number
The reference current can be evaluated using different ap- of samples that should be considered at the fundamental grid
proaches [2], [4], but the most commonly used are the fol- frequency, synchronized with the fundamental component of the
lowing: the calculation of the load active and reactive power, grid voltage. These signals can be applied to iα β (k) through the
direct Park transformation (DQ) in order to obtain a frequency-
shifting effect of the harmonic components of the load current.
Manuscript received February 9, 2007; revised June 13, 2007. Current version The DQ transformation output signals depend on the load cur-
published August 21, 2009. This work was supported in part by the Spanish
Ministry of Science and Innovation under Grant ENE2007-63979/ALT. Recom- rent spectrum (harmonic frequency and sequence) and the per-
mended for publication by Associate Editor R. Teodorescu. formance of the SPLL. The harmonic component matching the
The authors are with the Department of Electronics and Computers, Uni- SRF pulsation (ω) is shifted to a dc component, while other
versity of Cantabria, Santander 39004, Spain (e-mail: pigazoa@unican.es;
morenov@unican.es; estebanezej@unican.es). frequency components of the input signal are shifted to higher
Digital Object Identifier 10.1109/TPEL.2009.2025335 frequencies, i.e., fifth and seventh harmonics to 6ω. Hence, the
0885-8993/$26.00 © 2009 IEEE

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
2066 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 9, SEPTEMBER 2009

input signal components with frequency ω can be obtained af- The DQ–LPF–DQ−1 transformation can be analyzed in the
ter an LPF stage is applied to the DQ transformation outputs. frequency domain [17]–[20] to obtain
Finally, the DQ−1 transformation allows the target source cur-
rent in αβ coordinates to be obtained. As a consequence, the x̂α (z) = G1 (z)xα (z) − G2 (z)xβ (z) (5)
LPF stage must be designed carefully (cutoff frequency and fil- x̂β (z) = G2 (z)xα (z) + G1 (z)xβ (z) (6)
ter order) in order to avoid erroneous compensation reference
signals during the SAPF operation. In particular, the load current where
spectrum must be considered during the design process. 1    
This paper presents a recursive implementation of the DQ G1 (z) = HLPF ej ω z + HLPF e−j ω z (7)
2
transform DQr , which avoids the LPF stage in SRF-based struc- j    
tures. This implementation allows an accurate evaluation of spe- G2 (z) = HLPF ej ω z − HLPF e−j ω z . (8)
2
cific harmonic components independent of PCC conditions. The
mathematical analysis, simulation, and experimental results ob- B. Proposed DQr –DQ−1 Structure
tained on a three-phase, three-wire SAPF are given.
The direct Park transformation and the LPF stage can be
implemented by applying a recursive algorithm. The average
II. SRF-BASED CONTROLLERS IN THE FREQUENCY DOMAIN
values of the DQ transform outputs at instants k and k − 1 can be
This section analyzes the frequency response of the structure obtained by considering Nr ∈ Z + samples at the fundamental
shown in Fig. 1(b) and proposes a first approach to the recursive grid frequency
implementation of the Park transformation DQr . As will be    
shown in this section, this approach is sensitive to frequency x̂d 1 k

= Φn (9)
variations, and a modified DQr will be proposed. x̂q k Nr xβ n
n =k −N r +1
  k −1
  
A. DQ–LP F –DQ−1 Structure x̂d 1 xα
= Φn . (10)
The Park transformation allows the load current signals to be x̂q k −1 Nr xβ n
n =k −N r
represented using a rotating complex frame. The Park transfor-
mation is described as As a consequence, the recursive Clarke transformation can be
    obtained
xd xα      
= Φk (1) x̂d x̂d 1 ∆ (xα , Nr )
xq k xβ k = + Φ (11)
x̂q k x̂q k −1 Nr k ∆ (xβ , Nr ) k
where
  where
cos(ωk) sin(ωk)
Φk =
− sin(ωk) cos(ωk)
(2) ∆ (xα , Nr , k) = xα (k) − xα (k − Nr ) (12)
∆ (xβ , Nr , k) = xβ (k) − xβ (k − Nr ). (13)
with xα (k) and xβ (k) being the load current components in a
stationary complex frame (i.e., the outputs of a Clarke transfor- As in the previous case, the αβ coordinates of the fundamental
mation), xd (k) and xq (k) the outputs of the Park transforma- component of the load current can be obtained by applying (4).
tion, and Φk the transformation matrix obtained by means of It must be considered that, depending on the sampling frequency
the SPLL. The harmonic components of the load current can be and the fundamental grid frequency ω, the number of samples
filtered out from xd (k) and xq (k) by applying an LPF filtering employed for the recursive implementation Nr can be different
stage from N , which is evaluated by the SPLL: the pulsation of sin and
m cos functions (2π/N ) is changed by the SPLL to maintain the
ni z i
HLPF (z) = i=0 m i
(3) synchronization with the grid voltage. The next section discusses
i=0 di z the effect of N = Nr on this implementation.
where m is the filter order, and ni and di are constant coefficients The Appendix analyzes the recursive Park transformation in
corresponding to the numerator and denominator, respectively. the frequency domain to obtain
Butterworth filters are commonly employed in the filtering stage x̂α (z) = G1,r (z)xα (z) − G2,r (z)xβ (z) (14)
due to their plain gain up to the cutoff frequency.
Finally, the αβ coordinates of the fundamental component of x̂β (z) = G2,r (z)xα (z) + G1,r (z)xβ (z) (15)
the load current at ω can be obtained by applying the inverse
with
Park transformation 
    z N r − 1 (z − cos ω)
x̂α −1 x̂d G1,r (z) = (16)
x̂β k
= Φk
x̂q k
(4) Nr (z N r +1 − 2 cos ωz N r + z N r −1 )
 N 
z r − 1 sin ω
where x̂d (k) and x̂q (k) are the filtered outputs of the DQ G2,r (z) = . (17)
transformation. Nr (z N r +1 − 2 cos ωz N r + z N r −1 )

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
PIGAZO et al.: RECURSIVE PARK TRANSFORMATION TO IMPROVE THE PERFORMANCE 2067

depending on the load current spectrum, which can vary with


the PCC voltage distortion, the LPF must be designed properly,
reaching a compromise between the bandpass width of G1 (z)
and the response time under dynamical load conditions. The pro-
posed method, as will be shown in the following sections, has
a constant response time, and its frequency response [G1,r (z)]
allows undesirable harmonic components of the load current to
be compensated by introducing zeros at their frequencies.
Fig. 2(b) shows the frequency response obtained for G2 (z)
and G2,r (z). Again, the LPF with fc = 5 Hz, despite being the
slowest one, obtains the narrowest bandpass at the pulsation of
the SRF. The dynamic response can be improved by increas-
ing the cutoff frequency, but, then, the bandpass frequencies
around ω increase, and hence, the impact of harmonics different
from the fundamental component increases. The effect of these
load current harmonics can be minimized by means of the pro-
posed recursive Park transformation, which introduces multiple
notches in the frequency response at their frequencies.
Fig. 2. Frequency responses of (a) G 1 and G 1 , r and (b) G 2 and G 2 , r .
According to (14)–(17), the proposed recursive implementa-
N = N r = 128. tion is sensitive to frequency variations of the fundamental grid
component. Rewriting (16) in a zero-pole form
N r −1
C. Frequency-Domain Analysis of the SRF Structures 1 z − cos ω z − ej (2π /N r )i
G1,r (z) = × × i=0 j ω . (21)
Fig. 2 compares the frequency responses of DQ–LPF–DQ−1 Nr z (z − e ) (z − e−j ω )
and DQr –DQ−1 transformations through the analysis of the
In the case Nr = N , ω = 2π/N = 2π/Nr , and the two ze-
obtained transfer functions G1 (z) and G1,r (z) [Fig. 2(a)] and
ros in the numerator, at ω, are canceled due to the poles in
G2 (z) and G2,r (z) [Fig. 2(b)]. The analyzed LPF-based imple-
the denominator. When Nr = N , such zero-pole compensa-
mentations consist of second-order Butterworth filters with 5,
tion cannot be done, and as a consequence, a resonance around
30, and 50 Hz cutoff frequencies
ω would appear in the frequency response. Moreover, due to
987 the effect of noncompensated zeros at 2π/Nr , a notch should
H5 Hz (s) = (18)
s2
+ 44.43s + 987 be present in the frequency response at 2π/Nr . An equivalent
35530.6 analysis can be carried out in the case of G2,r . This effect is
H30 Hz (s) = 2 (19) analyzed in Fig. 3 by plotting G1,r at different sampling fre-
s + 266.6s + 35530.6
quencies (fs = 6.4 kHz and fs = 1 kHz) and grid frequencies
98696.0
H50 Hz (s) = 2 . (20) (49–51 Hz). From Fig. 3(a) and (c), the frequency response of
s + 444.3s + 98696.0 the proposed method is little dependent on the sampling fre-
quency because of the gain at very low frequencies (−67.13 dB
As can be seen in Fig. 2(a), G1 (z) and G1,r (z) reach a maxi-
at fs = 6.4 kHz and −51.71 dB at fs = 1 kHz). Hence, the
mum of −6 dB gain, which is due to the fact that both xα and xβ
proposed recursive implementation can be considered an inter-
components contribute to the averaged outputs x̂α and x̂β . The
esting alternative in SAPF controllers operating at low switching
LPF-based method with a 5 Hz cutoff frequency, presents the
frequencies to reduce the switching losses. Due to the effect of
narrowest bandpass at the fundamental grid frequency, but, as
grid frequency variations, the zero of G1,r cannot compensate
will be shown in the following sections, its response time under
for the transfer function poles at the SRF pulsation ω, and as
load transients is the worst. Due to the requirement of a narrow
a consequence, gain peaks appear around the SRF frequency.
bandpass in order to compensate the load current harmonics
This phenomenon is shown in more detail in Fig. 3(b) and (d).
properly, slow response times can be considered as a drawback
As can be seen, the magnitude of the gain peaks depends on the
when the current harmonics of time-varying nonlinear loads are
deviation of Nr from N .
compensated. The frequency response of G1 with fc = 50 Hz
is the worst due to the fact that the attenuation for the third and
D. Modified Recursive Park Transformation
fifth harmonics is low, reaching −9.74 and −19.25 dB gains,
respectively. Moreover, the plain gain response below 50 Hz In order to avoid the effect of grid frequency variations on
does not allow low-frequency load variations to be filtered out. the proposed recursive transformation, two alternatives can be
The LPF-based method with fc = 30 Hz can be an alternative employed: 1) the sampling frequency of the overall controller
for filtering out the fifth harmonic (its effect is reduced to 5% can be changed to match N = Nr or b) the frequency drift
of its initial value), but the third harmonic remains high (−17 effect can be compensated by software. The first solution implies
dB), and it cannot be employed in four-wire configurations with a dynamic redesign process of other elements of the SAPF
high load current consumption at 150 Hz. As a consequence, controller in order to maintain their performance. This is the

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
2068 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 9, SEPTEMBER 2009

Fig. 4. Simulation model.

In order to obtain the αβ coordinates of the fundamental


component of the load current, the inverse Park transformation
must be modified
   
x̂α x̂d
= Θ−1 k . (26)
x̂β k x̂q k
Fig. 3. Frequency response of G 1 , r (z) for different fundamental grid and
sampling frequencies. (a) fs = 6.4 kHz. (b) Detail around ω at fs = 6.4 kHz.
(c) fs = 1 kHz. (d) Detail around ω at fs = 1 kHz. III. SIMULATION RESULTS
The SRF-based controller depicted in Fig. 1(a) has been
case of PI dc-bus voltage controllers where the proportional implemented in MATLAB/Simulink in order to establish its
and integral constants should be changed to ensure the SAPF performance when DQ–LPF–DQ−1 , DQr –DQ−1 , and modified
stability and compensation capability [21]. As a consequence, DQr –DQ−1 transformations are employed. The implementa-
the second alternative has been selected. tions based on LPFs apply second-order Butterworth low-pass
Grid frequency variations are tracked by means of the SPLL, filters with cutoff frequencies fc = 5 Hz and fc = 50 Hz. The
which changes the elements of the transformation matrix Φ. As controller sampling frequency is fs = 6.4 kHz. The simulation
a consequence, and according to (21), resonances and notches in results have been obtained considering that the controller under
Fig. 3 are due to ∆ operators in (12) and (13). In order to place test is applied to an ideal SAPF, without the dc-bus voltage and
properly the zeros in (21), the averaging windows corresponding injection current controllers, and hence, the injection current
to ∆ operators must be dynamically resized for each sampling matches the compensation reference current (Fig. 4). Moreover,
interval. Anyway, it must be considered that only an integer it is assumed that only harmonic compensation is required (no
number of samples N  can be applied to ∆ operators, while N reactive power compensation). The employed test load is a three-
can be noninteger, and, as a consequence, small frequency drifts phase, three-wire full-wave diode rectifier with a capacitive dc
can continue reducing the method performance. Their effect side that is fed by a distorted PCC voltage according to IEEE
can be compensated by applying a new transformation matrix, Std. 519 [22] (3% fifth and 3% seventh harmonics). The load
which can be interpreted as a transformation of αβ components dc-side characteristics can be changed during the tests in order
to a second rotating frame whose pulsation corresponds to N  . to evaluate the dynamic response and the performance of each
In this way, the poles in (21) at ω are shifted to the frequency method. The analyzed SRF implementations have been tested
of the previously displaced zeros and zero-pole compensation under slow frequency variations of the grid voltage (different
success again. Hence, the modified Park transformation can be Nr and N ) and without frequency variations (Nr equals N ) in
defined as
      order to establish their performance.
x̂d x̂d 1 ∆ (xα , N  )
= +  Θk (22)
x̂q k x̂q k −1 N ∆ (xβ , N  ) k A. Nr Equals N
where   The grid frequency is maintained at 50 Hz (N = Nr = 128)
 1 during the test, and the performance of each method is evaluated
N = round (23)
fPLL Ts in abc and dq components. The spectra of the applied source
with Ts being the sampling period, fPLL the measurement of voltage and the load current signals in phase A are shown in
the grid frequency obtained by means of the SPLL, and Fig. 5(a), where the total harmonic distortion (THD) of the load
  current is 57.4%, with high fifth and seventh harmonics.
cos (ω k) sin (ω k)
Θk = Φk (24) Once the SAPF begins the compensation of the load current
− sin (ω k) cos (ω k)
  harmonics, the source current consumption at the fundamen-
1 tal grid component must be maintained under the simulation
ω = 2π − fPLL . (25)
N  Ts model depicted in Fig. 4. The obtained results demonstrate that

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
PIGAZO et al.: RECURSIVE PARK TRANSFORMATION TO IMPROVE THE PERFORMANCE 2069

Fig. 5. Compensation results in stationary state. (a) Grid voltage and load
current (V b a se = 20 Vrm s , Ib a se = 3.16A in phase A). (b) Deviation from the
fundamental component of the source current. (c) Amplitude of the harmonic Fig. 7. SRF-based SAPF controllers with a frequency variation. (a) PCC
components of the source current. voltage v s and load current iL in phase A. (b) Recursive and modified recursive
DQ. (c) LPF-based implementations. V b a se = 20 Vrm s , Ib a se = 3.16 A.

sive implementations are equivalent (Tr = 37.66 ms), while


the fc = 50 Hz LPF-based method is the fastest one, with
Tr = 26.87 ms, and the SRF controller with an fc = 5 Hz LPF
is the slowest one (Tr = 153.2 ms). Moreover, due to the effect
of the LPF, both xd and xq have ripple: 9.90% and 19.13%,
respectively, for fc = 50 Hz, and a low 0.1% and 0.2%, respec-
tively, for fc = 5 Hz. As a consequence, both stationary and
dynamic responses have a high dependence on the employed
LPF characteristics in such SRF-based controllers.

B. Different Nr and N
Section II-C shows that grid frequency variations reduce the
performance of the proposed recursive implementation. Hence,
the SRF implementations have been analyzed under slow grid
frequency variations (Nr = 128 depends on the assumed grid
and sampling frequencies, while N is determined by the SPLL).
Per-unit grid voltage and load current during a frequency vari-
Fig. 6. Response to a load transient. (a) d and (b) q components of each ation are shown in Fig. 7(a). The frequency varies from 50 Hz
SRF-based controller. at 0.4 s to 49 Hz at 0.6 s. Due to the effect discussed in
Section II-C, the recursive implementation fails when compen-
the deviation of the source current from the load current at sating the load current, and as a result, the source current in-
the fundamental grid frequency is maintained within a maxi- creases with time [Fig. 7(b)]. The modified recursive implemen-
mum 0.2% [Fig. 5(b)] due to the employed ideal SAPF model. tation operates properly and maintains the source current THD
The measured source current harmonics are shown in Fig. 5(c), below 0.3%. The response of the LPF-based implementations is
and as can be seen, the SRF method based on the LPF with shown in Fig. 7(c), and as in Section III-A, the performance de-
fc = 50 Hz shows the worst performance due to the frequency pends on the LPF stage characteristics obtaining a source THD
response of this method. In this case, the fifth and seventh load equal to 8.6% in the case of fc = 50 Hz and 0.3% for fc = 5 Hz.
current harmonics are attenuated only up to 3.5% and 1.7%. As a consequence, the proposed modified recursive implemen-
In order to test the performance of the SRF controllers, the tation can be considered as an alternative to LPF-based imple-
load current consumption changes at 0.04 s, reaching a new mentations in electrical grids with frequency variations.
steady state after 22.97 ms. During the load transient, the PCC Fig. 8 shows the dq components of each evaluated SRF
voltage maintains its harmonic distortion levels. The inner dq method. Considering LPF-based implementations, the obtained
components of each SRF controller are shown in Fig. 6(a) results in this case and Nr = N are similar. In the case of the
and (b). The measured response times applying the recur- recursive implementations, Fig. 8(a) and (b) shows that the dq

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
2070 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 9, SEPTEMBER 2009

R = 1.3 Ω) operate as current links. A power generator (HP-


6834-B) is employed to generate the harmonic distortion levels
according to IEEE Std. 519 [22] (3% fifth and 3% seventh har-
monics), and feeds a full-wave diode rectifier with a capacitive
dc side (C = 2200 µF, R1 = 32 Ω, and R2 = 64 Ω). A switch
sw is employed to generate load transients. The SAPF controller
is executed in a control card DS-1104 from DSpace.
A. SAPF Controller Implementations
The SAPF controllers previously analyzed by simulation have
been experimentally implemented in order to compare their per-
formances. The general structure of the developed controller is
shown in Fig. 10. As can be seen, the evaluated methods share
the same general structure: an SPLL, the dc-bus controller, the
injection current controller, and a pulsewidth modulator (PWM).
The measured grid voltages are normalized in order to obtain
vα β signals, which will be applied to the SPLL for synchroniza-
tion purposes. Normalization is required in order to avoid the
impact of the grid voltage amplitude on the inner PI controller
Fig. 8. SRF-based SAPF controllers with a frequency variation. (a) d and gains. The SPLL input signals are transformed to a certain ro-
(b) q components of each SRF-based controller. (c) SPLL frequency measure- tating frame whose frequency ωPLL and phase are adjusted by
ment. (d) Dynamical resize of ∆ operators (N  ).
applying a PI controller (tset = 20 ms and ξ = 0.707) to the q
component of the normalized input voltage signals [23], [24].
As a result, the grid voltage frequency fPLL , only required by
the modified DQr –DQ−1 method, and the rotation matrix Φ are
obtained. In the case of voltage unbalance, the SPLL structure
should be modified in order to track the positive sequence of the
grid voltage.
A PI controller allows the SAPF dc-bus voltage Vdc to be

maintained almost constant at Vdc during the SAPF operation,
ensuring a proper dynamical response under load variations

(Vdc = 210 V, Kp = 0.024, and Ki = 0.011) [21]. In order to
minimize the effect of transients on the integral part of the PI
controller, i.e., during the SAPF startup, an antiwindup block
has been included. The current consumption, which maintains
the dc-bus voltage, is evaluated by multiplying the PI controller
output and the sin and cos signals generated by the SPLL.
Fig. 9. Laboratory setup. The current controller must ensure that the injection current
Iαc β matches the compensation reference current. In this case,
components of the DQr method diverge, and, as a consequence,
and due to the frequency spectrum of the nonlinear load to
the results shown in Fig. 7(b) are obtained. In the case of the
be compensated, one proportional (Kp = 16.5) and three res-
modified DQr method, the obtained dq components are pure
onant blocks, with resonance frequencies at the fundamental
sinusoids whose frequency is ω /2π. This is due to the transfor-
component and the fifth and seventh harmonics (K1 = 103 ,
mation to a second rotating frame. The SPLL measures the grid
K5 = 2 × 103 , and K7 = 5 × 103 ), have been selected as cur-
frequency [Fig. 8(c)], and the window length (N  ) is dynami-
rent controllers. It must be considered that if the frequency
cally resized [Fig. 8(d)]. The oscillation in Fig. 8(a) and (b) is
spectrum of the nonlinear load current contains more harmonic
due to the remaining small frequency drift, which is compen-
orders, the number of applied resonant blocks should be in-
sated by means of the modified transformation matrix (24). As
creased in order to introduce new resonances at such harmonic
a consequence, the amplitude and frequency of these sinusoidal
frequencies. The inclusion of new resonant blocks, if required,
signals depend not only on the characteristics of the load current
could deteriorate the controller stability, and hence, the res-
but also on the value of N  .
onant block gains should be redesigned. Moreover, it must be
considered that grid frequency variations can deteriorate the per-
IV. EXPERIMENTAL RESULTS
formance of such current controllers based on resonant blocks.
The analyzed SRF-based controllers have been tested using Detailed information about the implementation of current con-
a laboratory setup depicted in Fig. 9. A modified VLT-5004 trollers based on resonant blocks can be found in [25]–[29]. The
drive from Danfoss is employed as power stage of the three- structure of the implemented current controller is depicted in
phase, three-wire SAPF, and three inductors (L = 3 mH and Fig. 10.

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
PIGAZO et al.: RECURSIVE PARK TRANSFORMATION TO IMPROVE THE PERFORMANCE 2071

Fig. 10. Block diagram of the experimentally tested SAPF controllers.

Fig. 11. Structure of the evaluated methods. (a) DQ–LPF–DQ−1 .


(b) DQr –DQ−1 . (c) Modified DQr –DQ−1 .

Fig. 12. Compensation results in stationary state. (a) Grid voltage and load
The current controller output signals must be applied to the current (V b a se = 20 Vrm s , Ib a se = 2.21A) in phase A. (b) Deviation from the
modified VLT-5004 drive by means of the DSP timers, which is fundamental component of the source current. (c) Amplitude of the harmonic
done by evaluating the duty cycle of each inverter leg through a components of the source current.
sinusoidal PWM [30]. The switching frequency of the SAPF is
4 kHz (Nr = 80).
analyzed SRF controllers. As can be seen in Fig. 12(b), there
The inner structure of the evaluated methods is shown in
is a deviation from the load current consumption at the grid
Fig. 11, which depicts the structure of a conventional DQ–LPF–
frequency. This is due to the fact that a portion of the load
DQ−1 based method. The tested LPFs, according to (3), have
active power is supplied at the fifth and seventh harmonics. Once
been implemented as discrete second-order Butterworth filters
the SAPF is operated properly, these harmonic currents must
with 5 and 50 Hz cutoff frequencies. The structure of the im-
disappear from the source current spectrum. As a consequence,
plemented recursive Park transformation is shown in Fig. 11(b).
and in order to avoid the active power mismatch, the SAPF
Both ∆ operators are implemented as constant-length circular
must increase the amplitude of the fundamental component of
buffers, and x̂dq are obtained by means of two discrete integra-
the source current. The lowest deviation is measured for the
tors. The implementation of the modified DQr –DQ−1 method
fc = 50 Hz LPF-based controller (4.1%), and as will be shown
requires the measurement of the grid frequency fPLL in order
in Fig. 12(c), this is due to an erroneous harmonic compensation
to establish the window length N  of ∆ operators. As a con-
that requires a lower active power to be supplied through the
sequence, two circular buffers with variable lengths have been
SAPF. It must be considered that the obtained experimental
employed. The maximum and minimum lengths are bounded by
results differ from the simulation ones [Fig. 5(b)] due to the fact
the grid frequency limits. The obtained values are transformed to
that in the first case, only the electrical grid supplies power to
a rotating frame where small frequency drifts are compensated
the PCC, but in the second case, and considering the SAPF as
by applying Θ.
an ideal controllable current source, the power balance at the
PCC can also be changed by the SAPF.
B. Nr Equals N
The measured source current is shown in Fig. 12(c). As can
Fig. 12 shows the experimental results obtained during the be seen, all the analyzed methods compensate the fifth and
compensation process of the nonlinear load by means of the seventh harmonics of the load current. The method involving the

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
2072 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 9, SEPTEMBER 2009

Fig. 13. Response to a load transient. (a) d and (b) q components of each Fig. 14. Measured currents at the PCC at 50 Hz in phase A. (a) Load current.
SRF-based controller. (b) Compensation current. (c) Source current.

fc = 50 Hz LPF exhibits the lowest performance, with 1.28%


and 6.74% for these harmonics, respectively.
A load transient has been applied by means of switch sw
at t = 0.046 s. The evolution of dq components for the SRF
implementations under test is shown in Fig. 13(a) and (b). As
can be seen, the fastest response time corresponds to the LPF-
based SRF method with fc = 50 Hz (45 ms), while the slowest
implementation is the LPF-based one with fc = 5 Hz (170 ms).
Both recursive implementations have equivalent response times
(61 ms). The response time of the recursive implementations
depends on the PCC voltage and current signal characteristics,
while the response times of LPF-based methods also depend on
the LPF stage characteristics.
The instantaneous values of the PCC currents in the case
Nr = N (the grid frequency is 50 Hz) during the compensation
process of the nonlinear load current are shown in Fig. 14.
The initial load current has a THD equal to 70.3%. Once the
SAPF has reached the stationary state, and applying the LPF- Fig. 15. Operation with N r = N . (a) dq components of the DQr controller
based methods with fc = 50 Hz and fc = 5 Hz, the source with fP L L = 49 Hz. (b) Fundamental component of the source current in phase
current THD is reduced to 8.4% and 4.3%, respectively. The A. (c) Fifth harmonic of the source current in phase A. (d) Seventh harmonic
of the source current in phase A. The test frequencies are 49, 49.5, 50, 50.5,
difference between the reached THDs is due to characteristics and 51 Hz.
of the applied LPF in each case. The DQr -based controller and
its modified version also reach low THDs, i.e., 4.2% and 4.3%,
respectively. laboratory setup trips out and the SAPF is stopped. Hence, the
operation of the SAPF prototype at frequencies in the range
49–51 Hz has been tested with LPF-based controllers and the
C. Different Nr and N proposed modified recursive implementation.
The SAPF controllers have been tested by applying grid volt- Fig. 15(b) shows the measured fundamental component of
age frequencies in the range 49–51 Hz with 0.5 Hz variations. the source current with compensation at the test frequencies
Moreover, the resonance frequencies of the current controllers (49, 49.5, 50, 50.5, and 51 Hz). As can be seen, increasing
have been changed during the tests in order to avoid their ef- the test frequency reduces the load current consumption, and
fect on the comparison. Fig. 15(a) shows the dq components as a consequence, the fundamental component of the source
evaluated by the DQr method. As can be seen, due to Nr = N , current. This effect is due to the fact that higher grid frequencies
the recursive implementation fails during the evaluation of the reduce the discharge transient of C, while lower grid frequencies
actual dq components of the load current. As a consequence, make this transient longer, which requires higher peak currents
after the SAPF initialization, the overcurrent protection of the recharge this filtering capacitor. The current consumption of the

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
PIGAZO et al.: RECURSIVE PARK TRANSFORMATION TO IMPROVE THE PERFORMANCE 2073

Fig. 16. Operation with N r = N at fP L L = 51 Hz. (a) d and (b) q compo- Fig. 17. Measured currents at the PCC at 51 Hz in phase A. (a) Load current.
nents of the LPF and the modified DQr -based methods. (b) Compensation current. (c) Source current.

in previous cases, the best THDs are reached by employing an


LPF-based controller with fc = 50 Hz is the lowest one in all LPF stage with a low cutoff frequency, and equivalent results
tests, which is due to errors in the harmonic compensation. can be obtained by applying the proposed method. It must be
The relative amplitudes of the measured fifth and seventh har- considered that, in the case of transients at the PCC, and as was
monics of the source current after the compensation are shown shown in Fig. 13, a low cutoff frequency results in a slower
in Fig. 15(c) and (d), respectively. As can be seen, the LPF-based response time.
implementation with the lowest cutoff frequency and the pro-
posed modified recursive implementation obtain similar results,
V. CONCLUSION
while the fc = 50 Hz LPF-based controller cannot compensate
the load current harmonics properly. This paper has proposed a recursive implementation of the
The dq components evaluated by means of the tested SAPF Park transformation that allows the improvement of SRF-based
controllers are shown in Fig. 16. The programmable power gen- controllers in SAPFs. Two recursive implementations, nontoler-
erator fed the nonlinear load at 51 Hz in order to obtain this ant and tolerant to grid frequency variations, have been proposed
figure. The LPF-based methods obtain equivalent results as in and compared to LPF-based implementations. A mathematical
the case of Nr = N . Small notches in dq components are due to analysis, simulation tests, and experimental results obtained on a
the operation of the antiwindup protection associated with the laboratory prototype of SAPF were given. The obtained results
dc-bus voltage controller (Fig. 10). The modified DQr method demonstrate that the performance of LPF-based implementa-
generates a proper reference current for compensation purposes tions depends on the PCC conditions and the filtering stage
due to a second transformation to a rotating frame. From Fig. 16, characteristics: controllers with low cutoff frequencies can be
the period of the measured dq components is 3.55 s, which cor- designed to obtain a good stationary state behavior, but their
responds to ω /2π = 0.28 Hz, the frequency of the second ro- response times to transients are high, while controllers with
tating frame. The controller adjusted the length of ∆ operators high cutoff frequencies have fast response times and low perfor-
from 80 to 78 samples. In the case of the DQr method, the over- mance in stationary state. The proposed recursive implementa-
current protection of the laboratory setup was tripped out while tion can be applied without considering the PCC conditions, and
charging the dc-bus capacitor, and hence, the SAPF controller it avoids the design stage associated with LPF-based methods.
stopped the laboratory prototype. Moreover, the obtained compensation results in stationary state
The measured currents at the PCC, when the frequency of the and the measured response times to transients make the pro-
programmable power source is 51 Hz and the stationary state posed method suitable for the development of improved SAPF
is reached, are shown in Fig. 17. As was previously discussed, controllers.
the results associated with the DQr -based controller are not de-
picted. The waveform of the source currents are quite similar in APPENDIX
all the tested methods, but the fc = 50 Hz LPF-based controller
exhibits a higher ripple. The measured THDs reveal this effect. FREQUENCY-DOMAIN ANALYSIS OF DQr –DQ−1
CONTROLLERS
The initial load current THD is 72.1%, and applying the labora-
tory prototype of SAPF, it is reduced to 10.1%, 5.7%, and 5.3% The proposed DQr –DQ−1 based controller can be ana-
by means of the LPF and modified DQr -based controllers. As lyzed in the frequency domain by applying Euler’s formula

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
2074 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 9, SEPTEMBER 2009

to (11) [5] S.-J. Lee, H. Kim, S.-K. Sul, and F. Blaabjerg, “A novel control algo-
   −k
 −k
 rithm for static series compensators by use of PQR instantaneous power
a + a  −j ka − −k
1 k k
x̂d a theory,” IEEE Trans. Power Electron., vol. 19, no. 3, pp. 814–827, May
=
x̂q k 2Nr j ak − a−k a +a 2004.
[6] P. Salmerón and R. S. Herrera, “Distorted and unbalanced systems com-
    pensation within instantaneous reactive power framework,” IEEE Trans.
∆(xα ) x̂d
× + (27) Power Del., vol. 21, no. 3, pp. 1655–1662, Jul. 2006.
∆(xβ ) k x̂q k −1 [7] R. S. Herrera and P. Salmerón, “Instantaneous reactive power theory: A
comparative evaluation of different formulations,” IEEE Trans. Power
where a = ej ω = ej (2π /N ) . Considering the property Del., vol. 22, no. 1, pp. 595–604, Jan. 2007.

  [8] O. F. Kashani and M. Braun, “Stability analysis of a compensated load
Z ck f (k) = F c−1 z (28) on a grid to obtain unity power factor,” in Proc. 2005 Eur. Conf. Power
Electron. Appl., Sep. 2005, pp. 1–8.
it can be transformed into [9] V. M. Moreno and A. Pigazo, “Modified FBD method in active power
 N      filters to minimize the line current harmonics,” IEEE Trans. Power Del.,
z r − aN r xα a−1 z − jxβ a−1 z vol. 22, no. 1, pp. 735–736, Jan. 2007.
x̂d (z) =
2Nr (z N r − z N r −1 ) [10] J. M. M. Ortega, M. P. Esteve, M. B. Payan, A. G. Exposito, and L.
G. Franquelo, “Reference current computation methods for active power
 N 
z r − a−N r [xα (az) + jxβ (az)] filters: Accuracy assessment in the frequency domain,” IEEE Trans.
+ (29) Power Electron., vol. 20, no. 2, pp. 446–456, Mar. 2005.
2Nr (z N r − z N r −1 ) [11] I. Etxeberria-Otadui, A. L. Heredia, H. Gaztañaga, S. Bacha, and M.
 N      R. Revero, “A single synchronous frame hybrid multifrequency controller
z r − aN r xβ a−1 z + jxα a−1 z for power active filters,” IEEE Trans. Ind. Electron., vol. 53, no. 5,
x̂q (z) = pp. 1640–1648, Oct. 2006.
2Nr (z N r − z N r −1 ) [12] M. I. M. Montero, E. R. Cadaval, and F. B. González, “Comparison of
 N  control strategies for shunt active power filters in three-phase four-wire
z r − a−N r [xβ (az) − jxα (az)] systems,” IEEE Trans. Power Electron., vol. 22, no. 1, pp. 229–236, Jan.
+ . (30)
2Nr (z N r − z N r −1 ) 2007.
[13] M. El-Habrouk and M. K. Darwish, “Design and implementation of a
The inverse DQ transform in (4), by employing Euler’s formula, modified Fourier analysis harmonic current computation technique for
can be represented as power active filters using DSPs,” Proc. Inst. Electr. Eng. Electr. Power
      Appl., vol. 148, no. 1, pp. 21–28, Jan. 2001.
x̂α 1 ak + a−k  j ak − a−k x̂d [14] S. Mariethoz and A. C. Rufer, “Open loop and closed loop spectral fre-
= quency active filtering,” IEEE Trans. Power Electron., vol. 17, no. 4,
x̂β k 2 −j ak − a−k ak + a−k x̂q k pp. 564–573, Jul. 2002.
(31) [15] J. Barros and E. Pérez, “An adaptive method for determining the reference
and by applying (28), it can be transformed into compensating current in single-phase shunt active power filters,” IEEE
Trans. Power Del., vol. 18, no. 4, pp. 1578–1580, Oct. 2003.
1   −1     [16] V. M. Moreno, A. Pigazo, and R. I. Diego, “Reference current estimation
x̂α (z) = x̂d a z + x̂d (az) + j x̂q a−1 z − j x̂q (az) under distorted line voltage for control of shunt active power filters,” IEEE
2 Trans. Power Electron., vol. 19, no. 4, pp. 988–994, Jul. 2004.
(32) [17] D. N. Zmood, D. G. Holmes, and G. H. Bode, “Frequency-domain analysis
of three-phase linear current regulators,” IEEE Trans. Ind. Appl., vol. 37,
1      
x̂β (z) = x̂q a−1 z + x̂q (az) − j x̂d a−1 z + j x̂d (az) . no. 2, pp. 601–610, Mar./Apr. 2001.
[18] M. J. Newman, D. N. Zmood, and D. G. Holmes, “Stationary frame
2
harmonic reference generation for active filter systems,” IEEE Trans.
(33) Ind. Appl., vol. 38, no. 6, pp. 1591–1599, Nov./Dec. 2002.
[19] P. Mattavelli, “A closed-loop selective harmonic compensation for active
Overall transfer functions for the proposed method can be filters,” IEEE Trans. Ind. Appl., vol. 37, no. 1, pp. 81–89, Jan./Feb.
obtained by applying (29) and (30) to (32) and (33) 2001.
 N  [20] J. Allmeling, “A control structure for fast harmonics compensation in
z r − 1 [(z − cos ω) xα (z) − sin ωxβ (z)] active filters,” IEEE Trans. Power Electron., vol. 19, no. 2, pp. 508–514,
x̂α (z) = (34) Mar. 2004.
Nr (z N r +1 − 2 cos ωz N r + z N r −1 ) [21] J.-C. Wu and H.-L. Jou, “Simplified control method for the single-phase
 N  active power filter,” Proc. Inst. Electr. Eng. Electr. Power Appl., vol. 143,
z r − 1 [(z − cos ω) xβ (z) + sin ωxα (z)] no. 3, pp. 219–224, May 1996.
x̂β (z) = . (35)
Nr (z N r +1 − 2 cos ωz N r + z N r −1 ) [22] IEEE Recommended Practices and Requirements for Harmonic Control
in Electrical Power Systems, IEEE Standard 519-1992, Apr. 12, 1993.
[23] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, “Overview
of control and grid synchronization for distributed power generation sys-
tems,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1398–1409, Oct.
REFERENCES 2006.
[24] L. G. B. Rolim, D. R. da Costa, Jr., and M. Aredes, “Analysis and software
[1] H. Akagi, “Trends in active power line conditioners,” IEEE Trans. Power implementation of a robust synchronizing PLL circuit based on the PQ
Electron., vol. 13, no. 2, pp. 263–268, Mar. 1994. theory,” IEEE Trans. Ind. Electron., vol. 53, no. 6, pp. 1919–1926, Dec.
[2] T. C. Green and J. H. Marks, “Control techniques for active power filters,” 2006.
Proc. Inst. Electr. Eng. Electr. Power Appl., vol. 152, no. 2, pp. 369–381, [25] X. Yuan, W. Merk, H. Stemmler, and J. Allmeling, “Stationary-frame
Mar. 2005. generalized integrators for current control of active power filters with zero
[3] M. Sedighy, S. B. Dewan, and F. P. Dawson, “A robust digital current steady-state error for current harmonics of concern under unbalanced and
control method for active power filters,” IEEE Trans. Ind. Appl., vol. 35, distorted operating conditions,” IEEE Trans. Ind. Appl., vol. 38, no. 2,
no. 4, pp. 979–986, Jul./Aug. 2000. pp. 523–532, Mar./Apr. 2002.
[4] L. Asiminoaei, F. Blaabjerg, and S. Hansen, “Evaluation of harmonic [26] R. I. Bojoi, G. Griva, V. Bostan, M. Guerriero, F. Farina, and F. Pro-
detection methods for active power filter applications,” in Proc. IEEE fumo, “Current control strategy for power conditioners using sinusoidal
20th Annu. Appl. Power Electron. Conf. Expo., Mar. 6–10, 2005, pp. 635– signal integrators in synchronous reference frame,” IEEE Trans. Power
641. Electron., vol. 20, no. 6, pp. 1402–1412, Nov. 2005.

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.
PIGAZO et al.: RECURSIVE PARK TRANSFORMATION TO IMPROVE THE PERFORMANCE 2075

[27] L. Asiminoaei, C. Lascu, F. Blaabjerg, and I. Boldea, “New current control Vı́ctor M. Moreno (A’01–M’01) received the M.Sc.
structure for shunt active power filters,” Proc. IEEE 41st IAS Annu. Meet., and Ph.D. degrees in physics (electronics) from the
Oct. 2006, pp. 183–190. University of Cantabria, Santander, Spain, in 1980
[28] P. Lezana, C. A. Silva, J. Rodrı́guez, and M. A. Pérez, “Zero-steady- and 1994, respectively.
state-error input-current controller for regenerative multilevel converters He is currently an Associate Professor in the De-
based on single-phase cells,” IEEE Trans. Ind. Electron., vol. 54, no. 2, partment of Electronics and Computers, University
pp. 733–740, Apr. 2007. of Cantabria, and teaches electronics, power electron-
[29] D. Sera, T. Kerekes, M. Lungeanu, P. Nakhost, R. Teodorescu, G. K. ics, and signal processing techniques at the School of
Andersen, and M. Liserre, “Low-cost digital implementation of Nautical Studies. His main research interests include
proportional-resonant current controllers for PV inverter applications us- electrical power quality, electromagnetic compatibil-
ing delta operator,” in Proc. 32nd Annu. Conf. IEEE Ind. Electron. Soc., ity (EMC), digital signal processing, and digital con-
Nov. 2005, pp. 2517–2522. trol of power converters.
[30] D. G. Holmes and T. A. Lipo, Pulse Width Modulation for Power Con- Dr. Moreno has been a member of the IEEE Power Electronics Society
verters. Principles and Practice. Piscataway, NJ: IEEE Press, 2003. (PELS) since 2001, and contributes as an author and reviewer for IEEE journals
and conferences. His Ph.D. thesis, entitled “Distributed Measurement and Anal-
ysis System for Power Quality in Electrical Grids Applying Kalman Filtering”
received the Viesgo Award in 1994.

Alberto Pigazo (M’05) received the M.Sc. and


Ph.D. degrees in physics (electronics) in 1997 and
2004, respectively, from the University of Cantabria,
Santander, Spain.
Emilio J. Estébanez received the M.Sc. degree in
He has been an Assistant Professor in the Depart-
telecommunications engineering (radiocommunica-
ment of Electronics and Computers, University of
tions) from the University of Cantabria, Santander,
Cantabria, since 2000, teaching courses in electron-
ics, power electronics, and digital signal processing. Spain, in 2007.
He is currently a Researcher on the Project
He has been a Visiting Researcher and Professor at
ENE2007-63979/ALT “Islanding Detection Algo-
the Polytechnic of Bari, Bari, Italy. His main research
rithms for Low-Voltage Grid-Connected Inverters
interests include electrical power quality and digital
signal processing techniques applied to the control of power converters. in Photovoltaic Distributed Generation Systems Ac-
cording to the EU Standards (IDAPhoS).” His main
Dr. Pigazo is a member of the Industrial Electronics Society (IES) Technical
research interests include electrical power quality and
Committee on Renewable Energy Systems (TCRES). He is also an Associate
digital signal processing techniques applied to the
Editor of the IEEE INDUSTRIAL ELECTRONICS MAGAZINE (IEM) and contributes
as author and reviewer for IEEE journals and conferences. control of power converters.

Authorized licensed use limited to: Shri Shankaracharya Col of Eng and Tech. Downloaded on August 14,2010 at 06:02:18 UTC from IEEE Xplore. Restrictions apply.

Vous aimerez peut-être aussi