Wind span 550 m


Weight span 800 m

400 519 400 519 400 519

928 911 730 717 696 684

0 0 287 280 287 280


2,448 2,448 1,915 1,915 1,827 1,827

0 0 772 772 2,640


1,870 1,870 1,870 1,870 1,870 1,870

2,448 2,448 1,915 1,915 1,827 1,827

0 0 772 772 2,640


1,870 1,870 1,870 1,870 1,870 1,870

2,448 2,448 1,915 1,915 1,827 1,827

0 0 772 772
1,870 1,870 1,870 1,870 1,870 1,870
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any two phase conductors broken)

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type AA ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


210 170421 PNG Table Load_AA 00-05

Wind span 550 m


Weight span 800 m

1,670 1,833 400 519 200 200

144 144 144 144 72 72

720 720 0 0 720 720


360 360 360 360 180 180

0 0 1,800 1,800 1,800 1,800


1,870 1,870 5,363 5,363 935 935

360 360 360 360 180 180

0 0 0 0 1,800 1,800
1,870 1,870 1,870 1,870 935 935

360 360 360 360 180 180

0 0 0 0 1,800 1,800
1,870 1,870 1,870 1,870 935 935
DW x 1.1

DW x

DW x
Case 4 Case 4 Case 4
Stringing Condition Stringing Condition Self Support Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type AA ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


220 170421 PNG Table Load_BB 00-15

Wind span 600 m


Weight span 1,000 m
Uplift span -300 m

-150 -150 -150 -150 -150 -150


499 649 499 649 499 649

1,491 1,471 1,274 1,260 1,197 1,184

288 288 549 542 549 542


3,861 3,861 3,280 3,280 1,327 2,654

720 720 1,405 1,405 6,600


2,420 2,420 2,420 2,420 1,210 2,420
-726 -726 -726 -726 -363 -726
3,861 3,861 3,280 3,280 2,654 1,327

720 720 1,405 1,405 6,600


2,420 2,420 2,420 2,420 2,420 1,210
-726 -726 -726 -726 -726 -363
3,861 3,861 3,280 3,280 2,654 2,654
6,600

720 720 1,405 1,405


2,420 2,420 2,420 2,420 2,420 2,420
-726 -726 -726 -726 -726 -726
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any two phase conductors broken)

Note
All Loads are in kgf Negative figures shows Uplift force RAMU Transmission System Reinforcement Project
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type BB ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


220 170421 PNG Table Load_BB 00-15

Wind span 600 m


Weight span 1,000 m
Uplift span -300 m

1,806 2,010 499 649 250 250

431 431 431 431 215 215

1,800 1,800 0 0 1,800 1,800


1,077 1,077 1,077 1,077 538 538

0 0 4,500 4,500 4,500 4,500


2,420 2,420 6,113 6,113 1,210 2,420

1,077 1,077 1,077 1,077 538 538

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 2,420

1,077 1,077 1,077 1,077 538 538

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 2,420

DW x 1.1
DW x 1.1
DW x 1.1

Case 4 Case 4 Case 4


Stringing Condition Stringing Condition Self Support Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible
All longitudinal loads are in the same direction
RAMU Transmission System Reinforcement Project
Overload factors are included Loading Diagram for Tower Type BB ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


230 170421 PNG Table Load_CC 00-30

Wind span 700 m


Weight span 1,000 m
Uplift span -300 m

-150 -150 -150 -150 -150 -150


499 649 499 649 499 649

2,353 2,330 2,100 2,084 1,959 1,943

288 288 593 585 593 585


6,031 6,031 5,356 5,356 2,073 4,146

720 720 1,519 1,519 6,600


2,420 2,420 2,420 2,420 1,210 2,420
-726 -726 -726 -726 -363 -726
6,031 6,031 5,356 5,356 4,146 2,073

720 720 1,519 1,519 6,600


2,420 2,420 2,420 2,420 2,420 1,210
-726 -726 -726 -726 -726 -363
6,031 6,031 5,356 5,356 4,146 4,146

720 720 1,519 1,519


2,420 2,420 2,420 2,420 2,420 2,420
-726 -726 -726 -726 -726 -726
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any two phase conductors broken)

Note
All Loads are in kgf Negative figures shows Uplift force
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type CC ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


230 170421 PNG Table Load_CC 00-30

Wind span 700 m


Weight span 1,000 m
Uplift span -300 m

1,806 2,010 499 649 250 250

854 854 854 854 427 427

1,800 1,800 0 0 1,800 1,800


2,135 2,135 2,135 2,135 1,068 1,068

0 0 4,500 4,500 4,500 4,500


2,420 2,420 6,113 6,113 1,210 1,210

2,135 2,135 2,135 2,135 1,068 1,068

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 1,210

2,135 2,135 2,135 2,135 1,068 1,068

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 1,210

DW x 1.1
DW x 1.1
DW x 1.1

Case 4 Case 4 Case 4


Stringing Condition Stringing Condition Self Support Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type CC ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


240 170421 PNG Table Load_DD 00-90

Wind span 700 m


Weight span 1,000 m
Uplift span -300 m

-150 -150 -150 -150 -150 -150


499 649 499 649 499 649

4,935 4,912 4,682 4,666 4,326 4,310

288 288 593 585 593 585


12,486 12,486 11,811 11,811 4,292 8,584

720 720 1,519 1,519 6,600


2,420 2,420 2,420 2,420 1,210 2,420
-726 -726 -726 -726 -363 -726
12,486 12,486 11,811 11,811 8,584 4,292

720 720 1,519 1,519 6,600


2,420 2,420 2,420 2,420 2,420 1,210
-726 -726 -726 -726 -726 -363
12,486 12,486 11,811 11,811 8,584 8,584

720 720 1,519 1,519


2,420 2,420 2,420 2,420 2,420 2,420
-726 -726 -726 -726 -726 -726
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any two phase conductors broken)

Note
All Loads are in kgf Negative figures shows Uplift force
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type DD ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


240 170421 PNG Table Load_DD 00-90

Wind span 700 m


Weight span 1,000 m
Uplift span -300 m

1,806 2,010 499 649 250 250

2,333 2,333 2,333 2,333 1,167 1,167

1,800 1,800 0 0 1,800 1,800


5,834 5,834 5,834 5,834 2,917 2,917

0 0 4,500 4,500 4,500 4,500


2,420 2,420 6,113 6,113 1,210 1,210

5,834 5,834 5,834 5,834 2,917 2,917

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 1,210

5,834 5,834 5,834 5,834 2,917 2,917

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 1,210

DW x

DW x
DW x

Case 4 Case 4 Case 4


Stringing Condition Stringing Condition Self Support Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible
All longitudinal loads are in the same direction
RAMU Transmission System Reinforcement Project
Overload factors are included Loading Diagram for Tower Type DD ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


250 170421 PNG Table Load_DDE Dead End Rev 170331

Wind span 400 m


Weight span 400 m

200 260 200 260 200 260


130 130 130
960 1,018 880
2,453 1,480 2,366 1,339 1,255 1,247

2,880 2,400 2,880 3,054 2,552 3,050 2,640 2,200 2,640


6,236 3,836 5,997 3,445 2,200 2,637
550 550 550

7,200 7,200 7,657 7,657 0 6,600


1,650 1,100 1,650 1,100 550 1,100
2,400 2,552 0
6,236 3,836 5,997 3,445 4,837 0
550 550 275

7,200 7,200 7,657 7,657 6,600 0


1,650 1,100 1,650 1,100 1,100 550
2,400 2,552 2,200
6,236 3,836 5,997 3,445 4,837 2,637
550 550 550

7,200 7,200 7,657 7,657 6,600 6,600


1,650 1,100 1,650 1,100 1,100 1,100

DW x 1.1
DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any two phase conductors broken)

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type DD-E Deadend ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


250 170421 PNG Table Load_DDE Dead End Rev 170331

Wind span 400 m


Weight span 400 m

1,397 1,479 200 260


740 130
600 600
573 573 573 573

1,800 1,500 1,800 1,800 1,500 1,800


1,500 0 2,933 1,433
550 550

0 0 4,500 4,500
550 0 4,313 4,313
1,500
1,500 0 1,433 1,433
550 550

0 0 0 0
550 0 550 0
1,500
1,500 0 1,433 1,433
550 550

0 0 0 0
550 0 550 0

DW x
DW x

Case 4 Case 4
Stringing Condition Stringing Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type DD-E Deadend ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


110 170421 PNG Table Load_SA 00-05

Wind span 550 m


Weight span 800 m

400 400 200

928 730 348

0 287 2,640
2,448 1,915 913

0 772 2,640
1,870 1,870 935

2,448 2,448 1,915 1,915 1,827 1,827

0 0 772 772
1,870 1,870 1,870 1,870 1,870 1,870
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any one phase conductor or arrester wire broken)

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SA ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


110 170421 PNG Table Load_SA 00-05

Wind span 550 m


Weight span 800 m

1,670 400 200

144 144 72

720 0 720
360 360 180

0 1,800 1,800
1,870 5,363 935

360 360 360 360 180 180

0 0 0 0 1,800 1,800
1,870 1,870 1,870 1,870 935 935
DW x 1.1

DW x 1.1

DW x 1.1
Case 4 Case 4 Case 4
Stringing Condition Stringing Condition Self Support Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SA ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


120 170421 PNG Table Load_SB 00-15

Wind span 600 m


Weight span 1,000 m
Uplift span -300 m

-150 -150 -75


499 499 250

1,491 1,274 599

288 549 2,640


3,861 3,280 1,327

720 1,405 6,600


2,420 2,420 1,210
-726 -726 -363
3,861 3,861 3,280 3,280 2,654 2,654

720 720 1,405 1,405


2,420 2,420 2,420 2,420 2,420 2,420
-726 -726 -726 -726 -726 -726
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any one phase conductor or arrester wire broken)

Note
All Loads are in kgf Negative figures shows Uplift force RAMU Transmission System Reinforcement Project
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SB ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


120 170421 PNG Table Load_SB 00-15

Wind span 600 m


Weight span 1,000 m
Uplift span -300 m

1,806 499 250

431 431 215

1,800 0 1,800
1,077 1,077 538

0 4,500 4,500
2,420 6,113 1,210

1,077 1,077 1,077 1,077 538 538

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 2,420

DW x 1.1
DW x 1.1
DW x 1.1

Case 4 Case 4 Case 4


Stringing Condition Stringing Condition Self Support Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible
All longitudinal loads are in the same direction
RAMU Transmission System Reinforcement Project
Overload factors are included Loading Diagram for Tower Type SB ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


130 170421 PNG Table Load_SC 00-30

Wind span 700 m


Weight span 1,000 m
Uplift span -300 m

-150 -150 -75


499 499 250

2,353 2,100 1,959

288 593 2,640


6,031 5,356 4,146

720 1,519 6,600


2,420 2,420 2,420
-726 -726 -726
6,031 6,031 5,356 5,356 4,146 4,146

720 720 1,519 1,519


2,420 2,420 2,420 2,420 2,420 2,420
-726 -726 -726 -726 -726 -726
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any one phase conductor or arrester wire broken)

Note
All Loads are in kgf Negative figures shows Uplift force
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SC ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


130 170421 PNG Table Load_SC 00-30

Wind span 700 m


Weight span 1,000 m
Uplift span -300 m

1,806 499 250

854 854 427

1,800 0 1,800
2,135 2,135 1,068

0 4,500 4,500
2,420 6,113 1,210

2,135 2,135 2,135 2,135 1,068 1,068

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 1,210

DW x 1.1
DW x 1.1
DW x 1.1

Case 4 Case 4 Case 4


Stringing Condition Stringing Condition Self Support Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SC ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


140 170421 PNG Table Load_SD 00-90

Wind span 700 m


Weight span 1,000 m
Uplift span -300 m

-150 -150 -75


499 499 250

4,935 4,682 2,163

288 593 2,640


12,486 11,811 4,292

720 1,519 6,600


2,420 2,420 1,210
-726 -726 -726
12,486 12,486 11,811 11,811 8,584 8,584

720 720 1,519 1,519


2,420 2,420 2,420 2,420 2,420 2,420
-726 -726 -726 -726 -726 -726
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any one phase or arrester wire to line side broken)

Note
All Loads are in kgf Negative figures shows Uplift force
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SD ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


140 170421 PNG Table Load_SD 00-90

Wind span 700 m


Weight span 1,000 m
Uplift span -300 m

1,806 499 250

2,333 2,333 1,167

1,800 0 1,800
5,834 5,834 2,917

0 4,500 4,500
2,420 6,113 1,210

5,834 5,834 5,834 5,834 2,917 2,917

0 0 0 0 4,500 4,500
2,420 2,420 2,420 2,420 1,210 1,210
DW x 1.1

DW x 1.1
DW x 1.1

Case 4 Case 4 Case 4


Stringing Condition Stringing Condition Self Support Condition
Arrester wire Top Conductor

Note
All Loads are in kgf
All Transverse loads are reversible
All longitudinal loads are in the same direction
RAMU Transmission System Reinforcement Project
Overload factors are included Loading Diagram for Tower Type SD ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


150 170421 PNG Table Load_SDE Dead End

Wind span 400 m


Weight span 400 m

389 389 260

2,440 2,356 1,503

2,880 3,050 2,640


6,236 5,997 3,519

7,200 7,657 6,600


1,650 550 1,650 550 1,100 550
2,400 2,552 2,200
3,836 3,445 0

7,200 7,657 0
1,100 1,100 0
2,552
6,236 5,997 4,837

7,200 7,657 6,600


1,650 1,650 1,650
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any one phase or arrester wire to line side broken)

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SD-E1 Deadend ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


160 170421 PNG Table Load_SDE2cct Dead End

Wind span 400 m


Weight span 400 m

389 389 389

2,440 2,356 2,127

2,880 3,050 2,640


6,236 5,997 4,837
7,200 7,657 0
7,200 7,657 6,600
1,650 1,650 1,650
2,400 3,836 2,552 3,445 2,200 0

550 1,100 550 1,100 550 0


6,236 5,997 2,637

7,200 7,657 0
1,650 1,650 550
6,236 5,997 4,837
7,200 7,657 6,600
7,200 7,657 6,600
1,650 1,650 1,650
2,400 3,836 2,552 3,445 2,200 2,637

550 1,100 550 1,100 550 1,100


6,236 5,997 4,837

7,200 7,657 6,600


1,650 1,650 1,650
DW x 1.1

DW x 1.1

DW x 1.1
Case 1 Case 2 Case 3
Transverse Wind Oblique Wind Broken Wire
(any two phase conductors broken)

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SD-E2 Deadend ( 1/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


150 170421 PNG Table Load_SDE Dead End

Wind span 400 m


Weight span 400 m

1,479 260

1,173 1,173

1,800 1,800
1,500 2,933

0 4,500
550 550 4,313 550
1,500 1,500
0 1,433

0 4,500
0 4,313

1,500 2,933

0 4,500
550 4,313

DW x
DW x

Case 4 Case 4
Stringing Condition Stringing Condition
Arrester wire Conductor

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SD-E1 Deadend ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project


160 170421 PNG Table Load_SDE2cct Dead End

Wind span 400 m


Weight span 400 m

1,479 260

1,173 1,173

1,800 1,800

1,500 2,933
0 4,500
0 4,500
550 4,313
3,836 1,500 1,433

550 550 1,100


1,500 2,933

0 4,500
550 4,313
1,500 2,933
0 4,500
0 4,500
550 4,313
3,836 1,500 1,433

550 550 1,100


1,500 2,933

0 4,500
550 4,313

DW x
DW x

Case 4 Case 4
Stringing Condition Stringing Condition
Arrester wire Conductor

Note
All Loads are in kgf
All Transverse loads are reversible RAMU Transmission System Reinforcement Project
All longitudinal loads are in the same direction
Overload factors are included Loading Diagram for Tower Type SD-E2 Deadend ( 2/2 )
DW : Dead weight of tower
All figures are for bidding purposed only

PNG Power Limited Ramu Transmission System Reinforcement Project

Vous aimerez peut-être aussi