Vous êtes sur la page 1sur 1

Is the installation connected to a Does client agree to A new consumer unit cannot

satisfactory means of earthing and upgrade earthing to be fitted. Advise client of


is the CSA of the earthing conductor BS7671? dangers. Issue an Electrical
adequate? NO NO Danger Notification form.

YES YES
Are all extraneous parts bonded Does client agree to fit or A new consumer unit cannot
and is the CSA of the main upgrade bonding to BS7671 be fitted. Advise client of
protective bonding conductors standard? NO dangers.
adequate?
NO
YES
Are CPCs present at all of the Can any circuits without a CPC be
lighting points of termination rewired? OR can additional CPCs be A new consumer unit
(lights, switches and sockets for run out to points and switches cannot be fitted. Advise
table lamps)? Carry out a continuity without a CPC? OR can all metal client of dangers.
test between the MET and metal fittings and switches be replaced with NO
light fittings (Class 1), switches and NO all insulated Class 2 fittings? AND can Note 1. If CPCs are not installed all
sockets for lighting to confirm sockets used for lighting be fittings must be Class 2. Plastic light
continuity. Satisfactory? disconnected? Does Client agree to switches must be installed with plastic
the additional works? mounting screws if the back boxes are
YES metal and have metal lugs. The circuit
See Note 1. must be 30mA RCD protected and an
A new consumer unit can be fitted.
insulation resistance test between live
Carry out required inspections and
conductors connected together and any
tests and issue an Electrical
exposed metal parts must be greater
Installation Certificate and notify
than 1MΩ. Premises must be under
for Part P.
effective supervision e.g. owner
occupied see Regulation 412.1.3.
Warning notice to be displayed on
consumer unit.