Académique Documents
Professionnel Documents
Culture Documents
03
4/27/2017
1 Page 1
Project Friday Mosque
Customer
Customer ref.
Our ref. Our Reference
Unit
Supply air flow 4.30 m³/s Exhaust air flow 1.40 m³/s
Ext. static pressure 300 Pa Ext. static pressure 200 Pa
Size 41 Size 41
Voltage 3*400 V, 50 Hz Weight 2258 kg
SFP 1.46 kW/m³/s
V
SUMMARY
Functional sections in v0 Et tw ts dP
direction of airflow (m/s) (%) (°C) (°C) (Pa)
Supply:
Connection wall 5
Bag filter 2.4 146
Empty section 0
Empty section 0
Heat exchanger, REGOTERM 2.4 32.0 -20.0 / -5.6 89
Empty section 0
Air cooler 2.6 23.4 / 16.0 62
Fan 68.6 733
Exhaust:
Connection wall 0
Empty section 0
Empty section 0
Empty section 0
Heat exchanger, REGOTERM 0.8 25.0 / -16.0 32
Fan 77.9 275
Empty section 0
Connection section 1.7 22
Air handling unit EU
Ver 5.03.03
Project Friday Mosque 4/27/2017
Unit Page 2
TECHNICAL SPECIFICATION
(Components listed in direction of air flow)
SUPPLY
1 Connection wall 5 Pa
Damper leakage class T4 (CEN3)
Galvanized steel frame
2 Filter 146 Pa
Galvanized steel frame
Bag filter Synthetic, class F7 (EU7)
Number of filters 4x1/1, 2x1/2
Pressure drop, design 146 Pa
Pressure drop, start 96 Pa
Pressure drop, end 196 Pa
Filter area 16.0 m²
Face velocity 2.4 m/s
3 Empty section 0 Pa
Length 900 mm
4 Empty section 0 Pa
Length 400 mm
6 Empty section 0 Pa
Length 300 mm
Air handling unit EU
Ver 5.03.03
Project Friday Mosque 4/27/2017
Unit Page 3
7 Air cooler 62 Pa
Copper tubes, aluminium fins
Fin pitch 2.0 mm
1 stage
Galvanized steel frame
Capacity variant 2
Capacity 44.0 kW
Face velocity 2.6 m/s
Air temperature 23.4 / 16.0 °C
Relative humidity 55 / 84 %
Refrigerant R 22
Evaporation temperature 6.0 °C
Pressure drop, refrigerant 3.7 kPa
8 Fan
Backward curved blades, V-belt drive
Fan size 1
One motor, Internal, Rubber anti-vibration mounts
Galvanized steel frame
Fan speed 2006 rpm
Efficiency, fan 68.6 %
Efficiency, total 56.3 %
Total pressure rise 733 Pa
to duct with dimension 600 * 600 mm
A straight duct of 340 mm is needed between fan and bend but if the bend direction is the same
as that of fan scroll then no straight duct is needed.
Fan Shaft Power 4.59 kW
Motor:
Start: Direct start
One stator winding
Efficiency 87.0 %
Voltage 400 V
Speed 1450 rpm
Rated power 5.50 kW
Current 11.10 A
Number of poles 4
Belt drive:
For V-belts
Efficiency 94.3 %
Accessories:
Air handling unit EU
Ver 5.03.03
Project Friday Mosque 4/27/2017
Unit Page 4
Door lock (number 1)
EXHAUST
9 Connection wall 0 Pa
Without damper
10 Empty section 0 Pa
Length 900 mm
11 Empty section 0 Pa
Length 900 mm
12 Empty section 0 Pa
Length 200 mm
13 Fan
Backward curved blades, V-belt drive
Fan size 1
One motor, Internal, Rubber anti-vibration mounts
Galvanized steel frame
Fan speed 976 rpm
Efficiency, fan 77.9 %
Efficiency, total 54.5 %
Total pressure rise 275 Pa
Fan Shaft Power 0.51 kW
Motor:
Start: Direct start
One stator winding
Efficiency 78.2 %
Voltage 400 V
Speed 1400 rpm
Rated power 0.75 kW
Current 2.15 A
Number of poles 4
Belt drive:
For V-belts
Efficiency 89.3 %
Air handling unit EU
Ver 5.03.03
Project Friday Mosque 4/27/2017
Unit Page 5
Accessories:
Door lock (number 1)
Air distributor (number 1)
14 Empty section 0 Pa
Length 400 mm
15 Connection section 22 Pa
Damper leakage class T4 (CEN3)
Galvanized steel frame
Grille with galvanized steel frame and plastic
vanes.