Check the injection timing referring to the Fill grease to the rotating part periodically Check the damper for silicone oil
specified timing written on the caution with a grease gun. leak, rubber cracking and any
plate attached on the rocker cover. other defect. Conduct the operational test of protective equipment referring to the check list.
Replace the engine coolant. Add anti-rust coolant as required. Check the smooth rotation of
Replace the fuel filter and check the The control of coolant prevents the engine interior from corrosion. compressor wheel by turning it
main fuel system. ※Use genuine "GLASSY" coolant. by fingers.
Type 4 Cylinder head removal (Top overhaul) Fuel injection nozzle replacement Generator body cleaning
[Every
4years]
(Top O/H) Keep the generator in a clean condition to extend the generator life.
Also, a failure such as a short circuit can be easily found in the clean condition.
Type 5 Engine major overhaul Radiator Generator inside (optional) check and cleaning
[Every The accumulation of dust and sludge is
sometimes seen in a generator installed for
8years] many years. Periodical air blow and cleaning
improve the prevention of troubles such as fire.
(Major O/H) (The specifics will be discussed based on the
condition and environment.)
Major overhaul the engine at the site or bringing back to the Blow off dust and clogging by blowing air in the reverse direction of Battery replacement
factory. Replace main parts. the radiator air flow. A severe clogging will result in not only Replace the battery.
performance degradation but also the cause of failure. (The replacement interval is decided
by the inspection result.)
※Above maintenance items and intervals will be changed according to location and operational environment.
※Please consider the maintenance schedule as a recommendation. Consult with your dealer or the contact point below for the specifics considering the installing condition and operational environment.