Engine Controller for Pumps
and Compressors

SW version 2.3.0
1 General information 2
2 Changes in the version 2.3.0 3
3 Changes in the version 2.2.0 7
4 Changes in the version 2.1.0 10
5 Changes in the version 2.0.0 14
6 Related information 15
7 Notes 16

Copyright © 2018 ComAp a.s.


Written by Petr Weinfurt
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: info@comap-control.com, www.comap-control.com New Features List
1 General information
1.1 Version information
In the FW version 2.3.0 there are added several new features as temperature variable preheating. For details
see Changes in the version 2.3.0 on page 3.

1.2 Clarification of notation


Note: This type of paragraph calls readers attention to a notice or related theme.

IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or unproper function of the equipment if not performed correctly and may not be clear at
first sight.

Example: This type of paragraph contains information that is used to illustrate how a specific function
works.

ID-FLX-Lite 2.3.0 New Features List 2


2 Changes in the version 2.3.0
2.1 New features
Manual regulation options in AUT mode.
A new feature of manual regulation by Speed Up/Down LBI or by Analog input in AUT mode has been
implemented. For this purpose there was added following new setpoint:

AUT SpdReq
Setpoint group Regulator Related FW 2.3.0
Range [units] Reg Bias, LBi SpdUp/Dwn, CU AI1-CU AI9, AIO: AI1 - 4 [-]
Force value
Default value Reg Bias NO
Alternative config
Step -
Comm object 13068 Related applications N/A
Config level Standard
Setpoint visibility Always
Description
The setpoint is used for selecting what regulation will be used in AUTO mode in case automatic regulation is
disabled by LBI R Reg Disable. The options are:
Reg Bias – speed request will be set according to setpoint Reg Bias, this function was standard
functionality of R Reg disable LBI in previous FW versions.
LBI SpdUp/Dwn – it is possible to regulate speed manually by LBI Speed Up/Down even in Auto
mode.
CU AI1-CU AI9, AIO: AI1 - 4 – it is possible to regulate speed manually by analog inputs even in Auto
mode

Preheating - temperature variable


A new feature for automatic preheating time adjustment based on temperature has been implemented:

ID-FLX-Lite 2.3.0 New Features List 3


LBO - Preheat
Related FW 2.3.0 Related applications N/A
Comm object N/A
Description
Activation times prior to engine start:
If measured temperature is equal to PreheatTemp1 (°C) or lower, the LBO Preheat activates prior to
the engine start for time equal to value in setpoint PreheatTime1 (s)
If measured temperature is PreheatTemp2 (°C) or higher, the LBO Preheat activates prior to the
engine start for time equal to value in setpoint PreheatTime2 (s)
If the temperature is between the values, the LBO Preheat activates for time calculated by linear
approximation

The LBO Preheat is activated before engine start as same as LBO Prestart or Preglow, the time is
defined by new setpoints (PreheatTime1/2, PreheatTemp1/2) described below.
Activation of Preheat LBO has a variable activation time based on the measured temperature - it can
be activated either before or after Prestart LBO and is deactivated during cranking.

Input for temperature measurement is selected by setpoint – PreheatSensor which is described


bellow
In case of invalid value on selected AIN, the LBO preheat will activate for time given by setpoint
PreheatTime2 = longest preheat time

2.2 New setpoints in version 2.3.0


PreheatTemp1
Setpoint group Engine params Related FW 2.3.0
Range [units] -600 .. PreheatTemp2 [°C]
Force value
Default value 0 °C NO
Alternative config
Step 1 °C
Comm object 15985 Related applications N/A
Config level Standard
Setpoint visibility Always
Description
Defines the temperature, at which the LBO Preheat activate of the longest time prior to engine start. See
description of LBO - Preheat (page 4)

ID-FLX-Lite 2.3.0 New Features List 4


PreheatTime1
Setpoint group Engine params Related FW 2.3.0
Range [units] 0 .. 600 [s]
Force value
Default value 0s NO
Alternative config
Step 1s
Comm object 15987 Related applications N/A
Config level Standard
Setpoint visibility Always
Description
Defines the shortest time of LBO Preheat activation prior to engine start reached when the measured
temperature is PreheatTemp1 or higher. See description of LBO - Preheat (page 4)

PreheatTemp2
Setpoint group Engine params Related FW 2.3.0
Range [units] PreheatTemp1 .. 600 [°C]
Force value
Default value 0 °C NO
Alternative config
Step -
Comm object 15986 Related applications N/A
Config level Standard
Setpoint visibility Always
Description
Defines the temperature, at which the LBO Preheat activates for the shortest time prior to engine start. See
description of LBO - Preheat (page 4)

PreheatTime2
Setpoint group Engine params Related FW 2.3.0
Range [units] 0 .. 600 [s]
Force value
Default value 0s NO
Alternative config
Step -
Comm object 15988 Related applications N/A
Config level Standard
Setpoint visibility Always
Description
Defines the longest time of the LBO Preheat activation prior to engine start reached when the measured
temperature is PreheatTemp2 or lower. See description of LBO - Preheat (page 4)

ID-FLX-Lite 2.3.0 New Features List 5


PreheatSensor
Setpoint group Engine params Related FW 2.3.0
Range [units] OFF/CU: AI1 .. CU: AI9/AIO: AI1 .. AIO: AI4 [-]
Force value
Default value OFF NO
Alternative config
Step -
Comm object 15989 Related applications N/A
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for selection of analog input, which is used for temperature measurement used for
variable preheating time calculation. See description of LBO - Preheat (page 4)

ID-FLX-Lite 2.3.0 New Features List 6


3 Changes in the version 2.2.0
3.1 New features
LBO Glow plugs - new functionality:
Logical binary output Glow plugs is closed prior to every attempt the engine start for time set in setpoint
Preglow time see New setpoints in version 2.2.0 on page 8.

RA15 module fail detect disabeling


A new setpoint allows to enable or disable failure detection of RA15 module which enables or disables
fail detect function of RA15 module. see New setpoints in version 2.2.0 on page 8
Increased number of digits for displaying ECU value Fuel Rate in CU from 5 to 6 digits (9999,9 l/h)
New LBO: ReliefValActiv
Activated when
Controller goes from Running state to Cooling state
Engine is started by Timer1/Timer2
Except case engine is running already
Deactivated when
Expires timer ReliefVal time see New setpoints in version 2.2.0 on page 8
If engine start is requested by BIN either while stopped engine or while running engine in case it was
started by Timer1/2

ID-FLX-Lite 2.3.0 New Features List 7


3.2 Repairs
Potential issue with regulator has been fixed. It was giving incorrect speed requests for limited period of time
after start of engine if setpoints Idle speed and MinSpeedLim had the same value.
Range of setpoint Flow SwitchDelwas changed from 0 .. 180 s to 0 .. 600 s
Potential issue with SD Override function - if Running timer was active (value of setpoint Running timer > 0)
SD Alarm caused stop of engine even if SD Override was activated.

3.3 New setpoints in version 2.2.0


Preglow time
Setpoint group Engine params Related FW 2.3.0
Range [units] 0 .. 600 [s]
Force value
Default value 0 NO
Alternative config
Step 1s
Comm object 11836 Related applications N/A
Config level Standard
Setpoint visibility Always
Description
This setpoint is used for setting of timer for deactivation of Logical binary output Glow plugs.

RA-FailDetect
Setpoint group Basic settings Related FW 2.3.0
Range [units] ENABLED / DISABLED
Force value
Default value ENABLED NO
Alternative config
Step N/A
Comm object 14599 Related applications N/A
Config level N/A
Setpoint visibility Always
Description
This setpoint is used to enable or disable fail detect function of RA15 module which enables or disables
alarm announcement in case RA15 is configured but not communicating.

ID-FLX-Lite 2.3.0 New Features List 8


ReliefVal time
Setpoint group Engine params Related FW 2.3.0
Range [units] 0 .. 3600 [s]
Force value
Default value 30 NO
Alternative config
Step 1s
Comm object 10612 Related applications N/A
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to set duration of time for which LBO ReliefValActiv will be activated.

ID-FLX-Lite 2.3.0 New Features List 9


4 Changes in the version 2.1.0
4.1 New parameter BIN1 delay
In parameter group Engine protect was created new setpoint BIN1 delay. The parameter is used for delay of
set protection:
All the time – the delay is calculated from input activation
Engine Running only – the delay starts to calculate after Eng prot del expiration
Range: 0 - 300 sec.
Default value: 1 sec.

4.2 Support of Final Tier 4


There was implemented support of Final Tier 4 (FT4) standard. Complete functionality is available only with
configured ECU what support FT4. It requires min.:
ECU List v6.3.0
LiteEdit v5.2.0
FT4 support includes:
New screen Aftertreatment
The screen is visible only if configured ECU supports and transmits some FT4 messages. Actived
FT4 icon is indicated by alarm Aftertreatment. When there appear some new icon, controller
automatically switch to Aftertreatment screen.

Meaning of icons:
Icon Meaning Description

Diesel Particulate Filter Active Regeneration Inhibited


Steady light - SPN 3703 = 01b
Due to Inhibit Switch

Steady light - SPN 3697 = 001b


Diesel Particulate Filter Lamp Command
Flash 1 Hz - SPN 3697 = 100b

Diagnostic Trouble Code:


Soot level in the DPF indicates need for filter cleaning
SPN = 3719, FMI = 15

ID-FLX-Lite 2.3.0 New Features List 10


Soot level is "moderately high" and engine performance Diagnostic Trouble Code:
is reduced by ECU SPN = 3719, FMI = 16

Soot level is „extremely hight“ engine performance is


Diagnostic Trouble Code:
reduced by ECU and ECU will perform a shutdown for
SPN = 3719, FMI = 00
engine protection

Exhaust System High Temperature Lamp Command Steady light - SPN 3698 = 001b

Red Stop Lamp Steady light - SPN 623 = 01b

Flash Red Stop Lamp Flash 1 Hz - SPN 3039 = 00b

Amber Warning Lamp Steady light - SPN 624 = 01b

Flash 1 Hz - SPN 3040 = 00b


Flash Amber Warning Lamp
Flash 2 Hz - SPN 3039 = 01b

Steady light - SPN 5245 = 001b


Fluid Tank Low Level Indicator (DEF Level Low)
Flash 1 Hz - SPN 5245 = 100b

DEF tank has 0% measureable volume and machine Diagnostic Trouble Code:
performance is reduced SPN = 1761, FMI = 18

DEF system has lost its prime and machine performance Diagnostic Trouble Code:
is reduced. SPN = 1761, FMI = 01

Malfunction Indicator Lamp (indicates that the active


Steady light - SPN 1213 = 01b
trouble code is emission-related)

Flash Malfunction Indicator Lamp (indicates that the Flash 1 Hz - SPN 3038 = 00b
active trouble code is emission-related) Flash 2 Hz - SPN 3038 = 01b

New screen with FT4 analog values


Created new separate screen with all FT4 analog values:
DPF1 Soot Load
DPF1 Ash Load
DEF Level
The screen is visible only if configured ECU supports and transmits some FT4 messages.
Main screen includes FT4 values
Controller main screen can display DPF1 Soot Level and DEF Level. Two analog values what are
displayed on main screen can be set by parameter Main Screen (group Basic settings).

Parameter value: 1st value 2nd value


TIMERS Run hrs Timer
AIN6,7 AIN-6 AIN-7
ATT DPF1 Soot Level DEF Level

ID-FLX-Lite 2.3.0 New Features List 11


New LBI Regen Inhibit, Regen Force, Lockout1 and Lockout2
Created four new LBI:
Regen Inhibit – used for setting ECU value DPF Regeneration Inhibit Switch if parameter Regen
Inhibit = BIN.
Regen Force – used for setting ECU value DPF Regeneration Force Switch if parameter Regen
Force = BIN.
Lockout1 – used for setting proprietary John Deere message DPF Lockout
Lockout2 – used for setting proprietary John Deere message DPF Lockout.
New setpoint group ATT Settings
Created new setpoint group ATT Settings what includes two parameters:
Regen Inhibit – set ECU value Aftertreatment Regeneration Inhibit Switch (SPN 3695). There can
be set:
OFF – automatic filter regeneration is enabled - SPN 3695 = 00b
ON – automatic filter regeneration is inhibited - SPN 3695 = 01b
BIN – value is set by LBI Regen Inhibit
Transmitted value is set by actual level of parameter ON/OFF or by level of LBI.
 Regen Force – set ECU value Aftertreatment Regeneration Force Switch (SPN 3696). There can
be set:
OFF – automatic filter regeneration is enabled
ON – automatic filter regeneration is inhibited
BIN – value is set by LBI Regen Force
Transmitted value is activated for 5 sec. by rising edge of parameter change OFF to ON or LBI.
Support of proprietary John Deere CAN message
Created proprietary John Deere CAN message DPF Lockout – PGN 61184, transmitted value:
ON = F2 31 FF FF CF FF FF FF
OFF = F2 31 FF FF DF FF FF FF
Value is OFF if there isn’t configured LBI ATT Lockout1 neither ATT Lockout2 or all configured LBI
ATT Lockout are active.
Value is ON if min. one of configured LBI ATT Lockout is inactive.
New LBO for all FT4 icons
Created new LBO what reflect all FT4 icons: DPF Inhibit, DPF Lamp, DPF Hest Lamp, DEF Level,
Malfunction, Red Lamp Icon, Wrn Lamp Icon.

4.3 Repairs
Detection of stopped engine with active LBI Sprinkler
The engine with activated LBI Sprinkler correctly detects stopped engine.
Change value name of parameter Main Screen
The value SHOW AIN of parameter Main Screen (group Basic settings) was renamed to AIN6,7.

ID-FLX-Lite 2.3.0 New Features List 12


LBI FaultResButton confirms ECU alarms
Logical binary input FaulResButton confirms ECU alarms too.
LBI Access Lock locks Start/Stop buttons
Logical binary input Access Lock locks controller and remote display (IL-NT RD) buttons Start and Stop.
Window protection of AIN4 – AIN7
Repaired Window protection of AIN4 – AIN7. It works as complete 4-level protection with setpoints: Low
Wrn, Low Sd, Low Del, High Wrn, High Sd, High Del.

ID-FLX-Lite 2.3.0 New Features List 13


5 Changes in the version 2.0.0
5.1 New parameter BIN1 delay
Protection Wrn+Cd
There was created new protection type of analog inputs Wrn+Cd: 2-level protection with adjustable
limits for warning and cooldown. It replaces previous Cooldown protection.

ID-FLX-Lite 2.3.0 New Features List 14


6 Related information
6.1 Available files
Firmware (*.mhx)
For ID-FLX-Lite
ID-FLX-Lite-2.3.0.mhx

Table 6.1 Available firmware

Archives (*.ail)
For ID-FLX-Lite
ID-FLX-Lite-2.3.0.ail

Table 6.2 Available archives

6.2 Overview of all available hardware


ID-FLX-Lite
Binary Inputs 7
Binary Outputs 7
Analog Inputs 9 (3x 2400 Ω, 2x 0 - 40 V, 4x 0 -10 V)
Analog Outputs -
Communications CAN

Table 6.3 Available hardware

6.3 Available related documentation


Documents Description
ID-FLX-Lite-1.9 Reference guide.pdf Reference guide of ID-FLX-Lite 1.9
LiteEdit 5.1.0 Global Guide.pdf Global Guide of PC tool LiteEdit
InteliMonitor-3.0-Reference Guide.pdf Reference guide of PC tool InteliMonitor-3.0
Inteli Communication Guide.pdf Communication guide for the Inteli controllers

Table 6.4 Available documentation

ID-FLX-Lite 2.3.0 New Features List 15