Vous êtes sur la page 1sur 12

PSEUDODYNAMIC TESTING OF MASONRY INFILLED REINFORCED

CONCRETE FRAME
By S. G. Buonopane,1 Associate Member, ASCE, and R. N. White,2 Fellow, ASCE

ABSTRACT: Seismic evaluation of a two-story, two-bay reinforced concrete frame infilled with masonry was
performed by pseudodynamic testing of a half-scale specimen. The second-story infill included window openings.
The specimen was subjected to four tests of increasing magnitude based on the Taft ground motion. Explicit
numerical integration with a small time step, soft-coupled load system, and an iterative actuator control algorithm
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

limited the displacement errors normally associated with pseudodynamic testing of stiff structures. The final
sequence of tests produced diagonal cracking in the upper story, but primarily bed joint shear cracking in the
lower story. Relations between the type of observed cracking and story drift-story shear response are explored.
Compressive strut mechanisms are defined from the experimental values of moments and axial forces in the
frame and infill panel strains. Estimates of story stiffness from several simple strut models were found to bound
the experimentally measured values for both the first- and second-story walls prior to significant damage. Fric-
tion-based analytical estimates of panel shear strength were found to underestimate the measured strength and
to be sensitive to the assumed coefficient of friction. Available methods for estimating shear strength that neglect
infill-frame interaction were found to largely underestimate measured shear strength.

INTRODUCTION of the specimen caused by damage and degradation in the


Reinforced concrete frames infilled with unreinforced ma- masonry and concrete through direct measurement of story
sonry form the structural system of many buildings, designed restoring forces.
without the benefit of up-to-date seismic design procedures The masonry infill itself may fail in a variety of modes,
and hence vulnerable to damage during seismic events. These most often involving some combination of bed joint sliding,
reinforced concrete frames are often gravity load designed corner crushing, and diagonal cracking. The exact mode of
(GLD) only, and common design practice considers the infill failure depends upon material properties, such as compressive
a nonstructural component. Historically, such structures have strength, shear strength and coefficient of friction; geometric
been plagued with poor performance during seismic events. constraints, such as frame-wall interface gaps or window open-
Clearly the ‘‘nonstructural’’ masonry infill can drastically alter ings; and other characteristics, such as workmanship. Mehrabi
seismic behavior of the infilled frames. Complex interaction et al. (1996) discusses many of the possible failure modes in
between frame and infill makes lateral strength and seismic more detail. Depending on the failure mode of the masonry,
behavior difficult to quantify, resulting in reliance on experi- large local forces may be applied at differing locations to the
mental research and, more recently, on advanced computer bounding frame, imposing extreme demand on nonductile
GLD frames. Previous studies of GLD frame behavior appear
modeling. After nearly four decades of experimental research
in Pessiki et al. (1990), El-Attar et al. (1997), and Beres et al.
on the performance of infilled frames, certain areas still need
(1996).
further investigation, as detailed in resolutions from a technical
Among the earliest infilled frame experiments were those
workshop (Abrams 1994). Among the research needs identi-
performed by Wood (1958) and Benjamin and Williams (1958)
fied were (1) behavior of infills with openings; (2) effects of
on full-scale, single-bay frames infilled with brick and clay
infill on weak, nonductile (i.e., GLD) frames; and (3) extrap-
block. Holmes (1961) first proposed the concept of an equiv-
olation of existing knowledge to multibay, multistory frames.
alent compressive strut based on a series of small and full-
The research program summarized in this paper addressed
scale steel frames infilled with both concrete and masonry.
these three specific needs through the pseudodynamic (PSD)
Extensive experimentation during the 1960s on small-scale
testing of a two-story, two-bay specimen built at half-scale frames infilled with mortar by Stafford-Smith (1966, 1967)
(Fig. 1). The specimen consisted of a GLD reinforced concrete established the equivalent compressive strut as a practical
frame infilled with unreinforced concrete masonry units method for prediction of the lateral strength and stiffness of
(CMUs), with window openings in the second-story walls. The infilled frame structures. The relations developed by Stafford-
masonry infill was built of 102 ⫻ 102 ⫻ 203 mm two-cell Smith still form the basis for current, recommended analy-
CMU, laid with face shell mortaring and no shear connectors ses of infilled frames [e.g. Drysdale et al. (1994) and the re-
between the infill and frame. The infill was unreinforced and port FEMA-273]. Unreinforced masonry contains weak shear
ungrouted, except surrounding the window openings (Fig. 1). planes along the bed joints, which may initiate degradation
PSD testing provides detailed data on the behavior of the prior to diagonal crushing failures, as noted by Mainstone
frame and infill under seismic loading, including realistic sim- (1971) and later studied in more detail by Dhanasekar and
ulation of story forces in multi-degree-of-freedom (MDOF) Page (1986) through finite-element models and companion ex-
structures with no assumptions necessary for seismic load dis- periments.
tribution. PSD testing accurately captures nonlinear stiffness The most recent generation of experimental research has
1
Sr. Engr., Simpson Gumpertz & Heger, Inc., 297 Broadway, Arling- been well documented in Angel et al. (1994), which tabulates
ton, MA 02474. 11 programs current at the time. These projects include various
2
James A. Friend Family Prof. of Engrg., School of Civ. and Envir. combinations of concrete or steel frames and brick, block, or
Engrg., Cornell Univ., Ithaca, NY 14853. clay tile infill tested at full and reduced scales under mono-
Note. Associate Editor: Julio A. Ramirez. Discussion open until No- tonic, cyclic, and PSD loading. Angel et al. (1994) tested full-
vember 1, 1999. To extend the closing date one month, a written request scale, single-bay, single-story reinforced concrete frames in-
must be filed with the ASCE Manager of Journals. The manuscript for
this paper was submitted for review and possible publication on May 21,
filled with brick and block under cyclic loading. Mehrabi et
1998. This paper is part of the Journal of Structural Engineering, Vol. al. (1996) tested a group of half-scale, single-bay, single-story
125, No. 6, June, 1999. 䉷ASCE, ISSN 0733-9445/99/0006-0578–0589/ specimens infilled with both hollow and solid block, and the
$8.00 ⫹ $.50 per page. Paper No. 18447. concrete frames included specimens with modern seismic de-
578 / JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999

J. Struct. Eng., 1999, 125(6): 578-589


TABLE 1. Average Material Properties of Concrete and
Masonry

Compressive Secant
Specimen Number of strengtha modulusb
Material type specimens (MPa) (MPa)
(1) (2) (3) (4) (5)
Concrete, 4 ⫻ 8 in. 8 30.6 21,900
28 day cylinder
Concrete, 4 ⫻ 8 in. 13 40.0 25,900
15 month cylinder
Masonry single block 12 16.1 8,410
Masonry 3 course 15 10.1 7,550
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

prism
Mortar, 2 ⫻ 4 in. 14 13.9 12,700
type S cylinder
a
Masonry compressive strengths over net area.
b
Secant modulus to 45% of compressive strength.

ically where possible, and the frequencies from the free vibra-
FIG. 1. Elevation of Half-Scale Infill Specimen for PSD Testing tion tests were cross-checked by eigenvalue analysis using the
measured stiffness matrix and an estimated mass matrix. De-
tailed results of all preliminary testing appear in Buonopane
tailing and with nonductile (GLD) detailing. Another substan- (1997).
tial experimental and analytical research program is reported
in Zarnic and Tomazevic (1984, 1985), where cyclic tests were PSEUDODYNAMIC TEST METHOD
performed on one-half and one-third scale reinforced concrete
frames infilled with brick and block. Both unreinforced and Pseudodynamic testing combines features of quasi-static
reinforced infills were tested, as well as panels with window testing, shake table testing, and numerical time history analysis
and door openings. Results have been used to propose some in order to realistically simulate the nonlinear behavior of
innovative nonlinear strut models, including multiple strut structures that exhibit varying stiffness, here caused by dam-
schemes for panels with openings. Tests of unreinforced infill age incurred during the excitation. Whereas numerical simu-
at one-fourth scale in steel frames by Mosalam (1996, 1997) lations rely on hysteretic rules to trace the changing stiffness
include quasi-static and PSD tests on multistory, multibay based on evolving system parameters, such as displacements
specimens and infills with window and door openings. or interstory drifts, PSD testing accounts for the nonlinear ef-
fects through experimentally measured restoring forces. The
measured restoring forces replace the product of the stiffness
SPECIMEN INSTRUMENTATION AND PROPERTIES
matrix and displacement vector in the equation of motion. The
Displacement transducers (DCDTs) mounted on an external remainder of the PSD algorithm follows from established nu-
reference frame measured the story displacements at the center merical integration techniques.
of the interior beam-column joints and displacement at the The PSD test method was first proposed and used by Jap-
center of the base beam. Eighty strain gauges on the reinforc- anese researchers in 1975, and its mathematical formulation
ing steel provided strain values for calculation of moments and and development have been reviewed in Takanashi and Na-
axial forces in the frame members. Three strain gauge delta kashima (1987) and Mahin et al. (1989). Recent advances in
rosettes were applied on each of the first-story masonry panels PSD-specific numerical techniques (Shing et al. 1996) and in
to measure principal strains and directions. Twenty DCDTs actuator control schemes (Seible et al. 1996) have resulted in
measured total length changes across main and off diagonals wider use of PSD testing for stiff, multi-story specimens.
of the masonry, and across window openings. Eight additional A review of PSD literature reveals certain unique advan-
DCDTs positioned near the panel corners measured interface tages and disadvantages compared with quasi-static or shake
gap openings between frame and infill. Story displacements table testing. Considering first the advantages:
were applied at each story level using a 245 kN capacity, ⫾75
mm stroke hydraulic actuator. The actuators were connected 1. For MDOF systems, no assumptions on the distribution
to the beam stubs through compression-only, ball-and-cup con- of seismic forces among the DOFs need be made.
nections, thereby minimizing rotational restraint and allowing 2. Effects of damage on behavior are physically modeled
realistic reinforcing at the points of load application (Fig. 1). with no numerical assumptions regarding degradation
An extensive materials testing program was conducted dur- necessary.
ing construction and PSD testing of the specimen, including 3. Controlled testing speed allows for data acquisition from
mix design development of the frame concrete and various extensive instrumentation with modest electronics and
masonry tests (Buonopane 1997). Important material proper- careful recording of important information such as crack
ties of the as-built concrete and masonry appear in Table 1. trajectories.
Each CMU has a measured gross area of 17,800 mm2, net area 4. Full-scale and large specimens may be tested with equip-
of 9400 mm2, and mortared thickness of 34.4 mm. All rein- ment requirements not much different than necessary for
forcing steel is indicated in Fig. 1, and main longitudinal steel quasi-static testing.
has a nominal yield stress of 275 MPa. 5. Specimen mass need not be accurately reproduced in the
Free vibration and static flexibility tests were performed on lab as it is modeled numerically.
the concrete frame before the infill was built and repeated 6. Unique substructure tests are possible, where part of the
again after construction of the infill. The free vibration tests prototype is built and tested in the lab, while the re-
were used to estimate modal frequencies and natural damping mainder is modeled numerically within the time integra-
ratios. Results of these preliminary tests were verified analyt- tion loop.
JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999 / 579

J. Struct. Eng., 1999, 125(6): 578-589


As for disadvantages: stiffness of the structure is much less than that of the load
system, Q converges to the identity matrix. Seible et al. (1996)
1. Error propagation characteristics of numerical integration propose an iterative actuator control scheme:
require excellent hydraulic control of actuators and tight
tolerances on experimental error in displacement and d a(k⫹1) = d a(k) ⫹ ␰Q(d s ⫺ dˆ (k)
s
) (4)
force feedback. s
2. Nonlinear behavior sensitive to strain rate cannot be re- where d̂ is the measured structure displacement vector at
(k)

produced without real-time PSD testing. iteration step k, and ␰ is a reduction factor to prevent over-
3. Controlled testing speed and small integration time steps shooting of the target. The iteration is halted when the differ-
for numerical accuracy may require excessive testing ence d s ⫺ d̂ s(k) falls below a tolerance level.
times. Seible et al. (1996) demonstrate that intentional soft cou-
4. Test response is often specific to a particular input mo- pling may be used to overcome several experimental problems
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

tion. typically associated with PSD testing of stiff structures. The


iteration scheme of (4), with an ideal Q, has equal convergence
Of course, many of these advantages and disadvantages also rates in all modes, thereby avoiding one of the long-standing
apply to one or more of the other testing methods. pitfalls of PSD testing—spurious higher-mode response. Even
under laboratory conditions, an approximate Q has shown to
Pseudodynamic Algorithm be extremely effective in reducing the spurious higher-mode
response that plagues so many PSD tests. In addition, the re-
The lumped mass matrix for PSD testing of this two-story duction in displacement from the actuator to the structure al-
structure is lows movement of the structure in increments below the res-

M= 冋5080
0
0
3330 册 kg (1)
olution limit of the actuator. Such fine displacement control
can be especially useful during preliminary testing when ex-
tremely low-level excitations are used to verify the PSD al-
Using this mass matrix, the expected modal frequencies during gorithm and software without damaging the specimen.
low-level PSD testing are 13 Hz and 28 Hz. As the specimen The success of this control algorithm depends largely upon
is damaged, the modal frequencies will approach those of the the use of a well-determined matrix Q. Previously, Q has been
bare frame, 3 Hz and 9 Hz. The modal damping ratios were assembled mathematically based on independently measured
specified as 2% and 5% to account for only natural damping, stiffnesses of the specimen and flexible load chain elements.
as PSD testing includes the effects of frictional and hysteretic In the present test setup, soft coupling occurred as a result of
damping through the measured force feedback. Rayleigh several flexible loading system components and also was de-
damping is an acceptable assumption since the system has only pendent upon the direction of loading; therefore, Q was de-
two DOFs with roughly equal magnitude damping. The damp- termined by direct measurement, accounting for flexibility dis-
ing matrix was assumed constant throughout the PSD testing tributed anywhere in the loading system, symmetric or not.
sequence. Control of the actuator displacements and measurement of
An explicit Newmark algorithm (␤ = 0, ␥ = 0.5) was used both actuator and structure displacements allow assembly of
to integrate the equation of motion, with a small time step to Q based on (3). Conveniently, such measurements may be re-
ensure stability and accuracy. The application of explicit in- corded during a typical stiffness test. For this specimen, Q
tegration is limited by the stability criterion was measured before each PSD test. Typically, the plots of
actuator displacements versus structure displacements showed
␻n(⌬t) < 2 (2) both nonlinearity and asymmetry, but a reasonable linear es-
with ␻n the largest circular frequency of the structure. The time timate gave acceptable performance in the PSD tests. Before
step of the input record was approximately 0.0035 s, resulting the Taft 0.10g test
in a criterion of 0.62. Studies of error propagation in PSD tests
by Shing and Mahin (1990) for various integration methods
suggest that, for this structure and time step, explicit integra-
Q= 冋 4.69
⫺1.57
⫺1.24
2.52 册 (5)

tion has comparable error propagation characteristics to other while for the Taft 0.80g test

冋 册
more complicated integration techniques.
1.73 ⫺0.30
Q= (6)
Soft Coupled Load System and Actuator Control ⫺0.53 1.31
A soft coupled load system uses flexible elements in the showing the expected convergence of Q to the identity matrix.
load chain connecting the actuator to the specimen, resulting Severe stiffness degradation occurred during the Taft 0.80g
in actuator displacements that are significantly greater than the test; nevertheless, the single estimated Q of (6) provided sat-
corresponding specimen displacements, and it requires a spe- isfactory actuator control throughout that test.
cific actuator control scheme. This method, introduced at the
University of California at San Diego (Seible 1996), is briefly PSD Displacement Errors
reviewed here.
In PSD testing the structure must be moved to a target dis- As pseudodynamic testing combines experimental and nu-
placement vector dictated by the numerical integration before merical processes, error from both sources may affect results.
restoring forces can be measured, but target specimen dis- Experimental errors enter the numerical process through force
placements from the numerical integration cannot be used di- and displacement feedback and may rapidly build up and over-
rectly as actuator command displacements. The actuator com- whelm the numerical process. Errors in displacement control
mand displacement vector, d a, is related to the target structural may be classified as overshooting or undershooting. Over-
displacement vector, d s, by shooting the target displacement may cause irreversible dam-
d a = Qd s (3)
age to the specimen which then affects the remainder of the
test. Undershooting may require excessive iterations to reach
where Q, the displacement amplification matrix, is a measure the target displacements, resulting in testing times beyond
of relative stiffnesses of structure and load system. When the practical limits and in load reversals near the target displace-
580 / JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999

J. Struct. Eng., 1999, 125(6): 578-589


ment which may cause unrealistic cyclic damage to the spec-
imen.
Frequency spectra of displacement errors have been used as
a performance benchmark in PSD error studies wherein con-
sistent actuator overshooting causes a peak at the fundamental
frequency; undershooting, at the highest natural frequency. Re-
peated undershooting, even of small magnitude, consistently
adds energy to the system near the highest modal frequency
and leads to the spurious higher mode response (Shing and
Mahin 1987; Shing et al. 1996). However, a recent study by
Thewalt (1994), using error data from actual PSD testing,
shows that frequency spectra of displacement errors cannot
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

accurately distinguish between under- and overshooting. Ex- FIG. 2. Taft Response Spectrum (Scaled to PGA of 1.0g)
amination of the experimental error data from these PSD tests
(Buonopane 1997) supports this conclusion. Undershoot errors ground motion for this series of PSD tests. The Taft response
consistently occurred more frequently and with greater mag- spectrum in Fig. 2 (scaled to a peak ground acceleration of
nitude, yet the error frequency spectra showed varied distri- 1.0g) shows that the trend of the spectrum rises between the
butions including nearly uniform and peaks near high or low fundamental period of the undamaged specimen (0.076 s) and
modal frequencies. No direct relationship between peaks in the the bare frame (0.302 s). Thus, damage to the infilled frame
error frequency spectra and the occurrence or magnitude of will increase the seismic demand on the structure. Since the
under- or overshooting errors was observed. specimen is half scale, the time scale of the input motion is
compressed by a factor of 公0.5; all times cited refer to this
Displacement Control Tolerances compressed time scale.
The actuator control algorithm of (4) prevents time integra- Verification with Low-Level Excitation
tion from proceeding unless a certain predefined tolerance
A low-level excitation with the Taft ground acceleration
level is met. With a tight tolerance band, experimental dis-
scaled to a peak ground acceleration (PGA) of 0.10g was used
placement errors entering the numerical integration must be
to verify the accuracy and stability of the PSD algorithm. Story
small. Even for actuator control which consistently under-
drift–story shear plots showed that the structure remained es-
shoots to protect the specimen from unintended damage, a
sentially undamaged, with hysteresis similar in magnitude to
tight tolerance apparently can limit excessive energy addition
that observed during preliminary static testing. No visible
and maintain cumulative error within acceptable bounds.
cracking was observed. Numerical simulation with a bilinear
Table 2 lists the tolerances used in the final sequence of
stiffness model and no degradation was used to verify the re-
PSD testing. The measured displacement is considered ac-
sults of the Taft 0.10g test. Measured and bilinear displacement
ceptable if it is within the specified tolerance above or below
time histories for both stories for 4 s of strong motion exci-
the target displacement. Tolerance expressed as a percentage
tation show good correspondence between the measured and
of maximum measured displacement allows for comparison
bilinear cases, with most local extremes reproduced very
across the tests of different excitation levels and to tests by
closely (Fig. 3). Hysteretic behavior and the frequency spectra
other researchers. For instance, results reported by Seible et
also showed good agreement. The primary conclusion from
al. (1996) show percentages of about 0.5% to 1.0% for tests
the bilinear modeling is that experimental errors in displace-
on a five-story masonry structure. In the Taft 0.35g test the
ment and force feedback, present in the low-level test but not
tolerance was extremely low relative to peak displacement,
in the bilinear model, have been controlled and reduced to the
and at several time steps the control algorithm failed to con-
point which they do not significantly affect the performance
verge within the iteration limit. In these unconverged steps,
of the PSD test.
the maximum error carried forward in the numerical integra-
tion was about 1.4% of peak displacement, a level sufficiently Final Pseudodynamic Tests
low to not adversely affect the remainder of the test. This
testing program, using tight actuator tolerances with a soft The final pseudodynamic testing sequence subjected the
coupled load system and actuator control scheme, suggests specimen to a series of three additional Taft excitations of PGA
PSD error propagation can be confined within acceptable 0.35g, 0.55g, and 0.80g. The Taft 0.35g excitation tested the
bounds by practical means. behavior of the PSD control algorithm with nonlinear stiffness
caused primarily by separation between infill and frame. Sev-
eral of the DCDTs positioned to measure relative movement
RESULTS OF PSEUDODYNAMIC TESTING of frame and infill exhibited gap-opening behavior.
The Taft-Lincoln School S69E record of the event at Kern The final tests at 0.55g and 0.80g produced significant dam-
County, California, on July 20, 1952, was selected as the age and degradation of the infill and frame, comparable to that
which might occur during major seismic events, such as a
TABLE 2. Actuator Control Tolerances and Displacement Er-
maximum considered earthquake. The ‘‘NEHRP recom-
rors mended provisions’’ (1997) map spectral acceleration contours
for a seismic event with 2% probability of occurrence in 50
Tolerance as years (2,500 year return) for 0.2 and 1.0 s period structures.
Test Tolerance Maximum percentage Maximum Spectral accelerations in the Los Angeles area generally range
PGA semibandwidth displacement of maximum error from 1.50g to 2.50g; in the San Francisco area, from 1.50g to
(g) (⫻10⫺3 mm) (mm) displacement (⫻10⫺3 mm) 2.00g. The peak contour surrounding Charleston, South Car-
(1) (2) (3) (4) (5)
olina, is 1.50g; the New Madrid area, 3.00g. From the re-
0.10 1.850 0.213 0.87 1.850 sponse spectrum (Fig. 2), the spectral acceleration at a period
0.35 1.850 2.121 0.09 29.21 of 0.2 s (about midway between the undamaged infilled frame
0.55 9.40 5.090 0.18 9.40
0.80 19.05 11.834 0.16 19.05
and bare frame periods) for a Taft 0.55g excitation is 1.9g,
and for a Taft 0.80g excitation is 2.8g. Thus the final two PSD
JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999 / 581

J. Struct. Eng., 1999, 125(6): 578-589


Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

FIG. 3. Measured and Bilinear Displacement Time Histories for Taft 0.10g Excitation

the second story developed major diagonal cracks from win-


dow corners to panel corners in both directions. The majority
of this cracking occurred relatively early in the record, yet the
second story carried story shears as large as 53 kN even after
cracking. After forming, the diagonal crack pattern stabilized
and did not produce excessive drift or strength degradation.
The Taft 0.55g test also exhibits nonlinearity caused by open-
ing and closing of gaps between frame and infill. Gap instru-
mentation on the west walls measured clearly visible openings
as large as 1.0 mm at one location and other gaps over 0.2
mm. Cubic backbone curves, fit to the story drift–story shear
relations, showed that the small displacement story stiffnesses
FIG. 4. Normalized Deflected Shapes at Peak First-Story Dis- of the specimen were significantly less than those of the un-
placements damaged specimen and approached those of the bare frame.
The first-story small displacement stiffness was 20.5 kN/mm;
tests are reasonable representations of the spectral accelera- the second story, 5.1 kN/mm. Once the structure had displaced
tions currently believed to be expected in major seismic events sufficiently to close the gaps and produce contact between the
in vulnerable areas of the United States. frame and infill, the stiffness increased sharply in response to
Fig. 4 summarizes the story drift behavior of the infilled the strut action induced in the infill.
frame for increasing levels of excitation, showing normalized In the final test of Taft 0.80g, minor additional cracking
displaced shapes of the structure at the times of peak first- occurred in the second story, which carried still greater story
story displacement. During the first three tests, the interstory shears as large as 89 kN. The first story, however, exhibited
drifts are about equal in each story, but the window openings severe cracking, and a detailed history of the crack formation
in the upper walls make them less stiff. Therefore, relative to appears in Buonopane (1997). The first, and largest, peak of
story stiffness, the first three excitations impose greater drift the ground acceleration occurs at 2.63 s, yet it caused no major
demand on the second story. In the final 0.80g test, the demand damage to the specimen, with only minor extension of existing
on the lower story exceeded its capacity and a rapid loss of cracks in both the first and second stories. Major bed joint
stiffness allowed for the soft first-story response. shear cracking occurred at 3.31 and 5.45 s and is reflected in
Fig. 7 by drops in first-story shear as the bed joint fractured
Infill Cracking and Hysteretic Behavior
and slipped. Once the slip was limited by the bounding frame,
The final crack patterns resulting from the Taft 0.55g and the story shear increased beyond the initial bed joint cracking
0.80g tests are shown in Fig. 5, and the story drift–story shear load. Other minor occurrences of cracking did not produce
relations are given in Figs. 6 and 7. During the Taft 0.55g test, such noticeable effects in the shear-drift plot, but contributed
582 / JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999

J. Struct. Eng., 1999, 125(6): 578-589


Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

FIG. 5. Final Crack Patterns

to the gradual accumulation of damage, causing significant


seismic demand during later portions of the ground record. For FIG. 6. Taft 0.55g Story Drift–Story Shear Relations
instance, an excitation peak of about 70% of the PGA (at 9.44
s) resulted in a drift of 7 mm, only slightly less than the max- shear force on the column from interaction of the frame and
imum for the entire record, and a story shear of about 111 kN, infill. Such a shear force would be caused by the formation of
also near the maximum. a compressive strut originating near the loaded corner of the
The hysteretic energy was calculated from the area enclosed panel and sufficiently inclined to pass below the window open-
by each cycle in the story shear–drift plot, and may be con- ing. Fig. 10 suggests a possible strut mechanism that produces
sidered as a measure of damage to the specimen. Fig. 8 shows column moments consistent with those measured. Note that
the cumulative hysteretic energy dissipation for each story the maximum moment will occur in the upper half of the col-
from the Taft 0.55g test. Table 3 lists the total hysteretic energy umn and may be significantly greater than that measured at
levels and percentages in each story for each test. During the midheight. The interaction force will have some varied distri-
Taft 0.55g test, the second story suffered significant diagonal bution, rather than the assumed uniform distribution, so other
cracking, yet showed no appreciable change in relative story possible moment diagrams exist. Measurements of column
hysteretic energy dissipation from the previous lower level moments at many locations or direct measurement of inter-
tests. The large increase in relative hysteretic energy dissipa- action bearing pressures would be needed to define more ac-
tion in the first story during the Taft 0.80g test correlates with curately the nature of the interaction forces. The off-diagonal
the masonry damage characterized by extensive bed joint strut mechanism shown in Fig. 10 is similar to secondary struts
cracking. proposed by Mainstone (1971) and Mander et al. (1993) to
model infill walls in which severe main diagonal compressive
Interaction of Infill and Frame
strut damage had occurred near the center of the panel. Here
Moments and axial forces in the frame columns were com- the window opening causes formation of the struts along the
puted from the strains recorded by pairs of strain gauges off-diagonals in the undamaged panel.
mounted on the reinforcing steel. Fig. 9 shows moment and The formation of the effective strut is also supported by the
axial force diagrams for the Taft 0.55g test at the time of presence of relatively uniform axial tension in the second-story
maximum base shear (6.52 s). Moments and axial forces are loaded side (east) column, caused by the vertical component
given as percentages of pure moment capacity (8810 kN-mm) of force from the effective strut. In the first-story column, the
or compression capacity (730 kN). Story forces and displace- axial force is substantially increased by the addition of tension
ments are indicated in the figure. from strut action in the first-story panel. Because of separation
In the second story, the column on the loaded side (east) of the infill and frame, the column at the unloaded side (west)
exhibited large moments and a reversal of sign at the mid- carries comparatively little compression, as such compression
height location. The relatively large slope of the moment dia- is more efficiently transferred diagonally through strut action
gram over the upper half of the column suggests a substantial in the wall. Thus the overturning moment caused by the lateral
JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999 / 583

J. Struct. Eng., 1999, 125(6): 578-589


TABLE 3. Total Story Hysteretic Energies

Total hysteretic
PGA energy First-story Second-story
(g) (N-m) percentage percentage
(1) (2) (3) (4)
0.10 6.67 63 37
0.35 399 65 35
0.55 1593 66 34
0.80 7129 81 19
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

FIG. 7. Taft 0.80g Story Drift–Story Shear Relations

FIG. 9. Frame Forces for Taft 0.55g Test at Time of Maximum


Base Shear (6.52 s)

FIG. 8. Cumulative Hysteretic Energy for Taft 0.55g Test

FIG. 10. Possible Second-Story Strut Mechanism


loads is counteracted by a moment-couple formed from axial
tension in the loaded side column and compression in the ma-
sonry infill. tion. Triangular portions of the wall adjacent to the window
Column moments and axial forces in the loaded side of the openings remained almost entirely free of bed joint cracking
second story remained qualitatively similar throughout all four (Fig. 5); thus compressive struts could develop at these loca-
tests, increasing in magnitude with increasing excitation. Thus, tions with little or no relative horizontal sliding of masonry
even significant diagonal cracking, which occurred during the courses. The maintained presence of strut action and lack of
Taft 0.55g test, did not prevent load transfer through strut ac- sliding failures help to explain the stable diagonal crack pat-
584 / JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999

J. Struct. Eng., 1999, 125(6): 578-589


tern, as well as the minimal loss of shear and drift capacity of the top of the column will tend to increase the local shear. The
the second story. shear capacity of the column, neglecting any reduction caused
Fig. 11 shows force diagrams for the Taft 0.80g test at the by axial tension, may be estimated at 33 kN according to ACI
time of peak first-story displacement (10.76 s). After substan- 318-95.
tial separation of infill and frame, the first-story column on the
unloaded side (east) shows a moment diagram similar to that Infill Panel Strains
of a bare frame. That is, the moments are primarily a function
of the first-story displacement, with minimal effect from in- Strain gauge rosettes placed at the center of each lower-story
teraction with the infill. In the Taft 0.80g test, shear cracking masonry panel revealed the presence of large principal com-
occurred at the top of the center column because of the ex- pressive strains (Table 4), along with tensile strains of consid-
tremely large moment gradient. Substantial bed joint sliding erably less magnitude, supporting the idealization of the panel
in the upper courses of the masonry, and even spalling of some as a compressive strut. The inclination of the compressive
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

blocks directly adjacent to the column, allowed a significant strain field consistently fell between 40⬚ and 45⬚ below hori-
shear to develop over a relatively short portion of the column. zontal, compared with the main diagonal angle of about 37⬚.
The top moment is 1160 kN-mm (132%) and the midheight The compressive strains generally increased with increasing
moment, 730 kN-mm (83%). Estimating the magnitude of PGA. However, for the Taft 0.80g test at 4.66 s (peak base
shear as the change in moment over half the column height shear) the east panel had a negligible increase in strain over
(630 mm) gives a shear of 30 kN. The actual shear will prob- the Taft 0.55g test, while the west panel had a significant in-
ably be larger than this value as lateral interaction force near crease. This difference between the east and west panels may
be due to the state of cracking at 4.66 s. At this time the east
wall had major bed joint failures near the top and bottom of
the panel, whereas the west wall had only one such failure
near the bottom. The ability of the east panel to develop a
significant corner-to-corner force was severely reduced by hor-
izontal slip along the cracked bed joints, caused by the hori-
zontal component of the strut force itself. The strut resistance
lost in the east panel may have been compensated by higher
strain in the less damaged west panel.
For the Taft 0.80g test at 10.76 s (peak first-story displace-
ment), severe damage had occurred in both first-story masonry
panels, including several full-width bed joint cracks as well as
numerous diagonal and stepped cracks. The increase in first-
story drift seen in the story drift–story shear plot may be as-
sociated with the failure of the infill to mobilize an effective
compressive strut mechanism because of the extensive damage
and many prominent horizontal slip planes.

Effective Strut Models


The experimental data reviewed in the previous sections
have suggested that strut mechanisms might serve as accept-
able idealizations for certain features of the observed infill be-
havior. For unreinforced masonry, compressive strut models
have the potential to model the initial stiffness and low-level
behavior of the infill before significant bed joint cracking.
Hendry (1990) relates the effective strut width, w, to the con-
tact lengths by
1
w= 兹␣ 2h ⫹ ␣ 2L (7)
2
where the vertical contact length, ␣ h, is (Drysdale et al. 1994)

␣h =

2冑 4 4Ec Ic h
E m t sin 2␪
(8)

FIG. 11. Frame Forces for Taft 0.80g Test at Time of Maximum A similar expression gives the horizontal contact length, ␣ L.
First-Story Displacement (10.76 s) Based on an assumed strut width, the axial strut stiffness is

TABLE 4. Infill Panel Principal Compressive Strains and Angles


East wall principal West wall principal
PGA Time Base shear compressive strain East wall compressive compressive strain West wall compressive
(g) (s) (kN) (microstrain) strain inclination (microstrain) strain inclination
(1) (2) (3) (4) (5) (6) (7)
0.10 2.65 9.5 18 40⬚ 15 43⬚
0.35 4.63 44.0 106 44⬚ 72 41⬚
0.55 6.52 93.8 213 42⬚ 187 40⬚
0.80 4.66 122.7 215 45⬚ 370 41⬚
0.80 10.76 71.5 107 41⬚ 104 28⬚

JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999 / 585

J. Struct. Eng., 1999, 125(6): 578-589


ks = (wtE m)/d. The contact lengths for a first-story panel of this
specimen are ␣ h = 542 mm and ␣ L = 1605 mm, based on material
properties from Table 1, dimensions from Fig. 1, and transformed
moments of inertia of the beam and column of 97 ⫻ 106 mm4
and 27 ⫻ 106 mm4, respectively. By (7) the strut width would be
847 mm (40% of the panel diagonal length); the axial stiffness
would be 104.5 kN/mm. Incorporating two such struts into a
beam-element frame model results in a first-story lateral stiffness
of 149 kN/mm. The measured lateral stiffness of the first story,
assuming shear building behavior, was 85.1 kN/mm; therefore this
strut idealization results in a stiffness of 175% of the measured
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

value.
Paulay and Priestley (1992) recommend a conservatively high
strut width of one-fourth of the panel diagonal length, resulting
in a 527 mm wide strut and a story lateral stiffness of 108 kN/
mm (127% of measured). FEMA-273 recommends a strut width
of

冉 冊
⫺0.4
⫺0.4 ␲h
w = 0.175rinf (␭ 1 hcol) = 0.175d (9)
2␣ h

which gives a strut width of 220 mm (10% of the panel di-


agonal) and a lateral story stiffness of 51.8 kN/mm (61% of
measured). The strut width provided by (7) largely overesti-
mates the measured stiffness, while a strut width of one-fourth
the diagonal length provides perhaps a reasonable and conser-
vative overestimate of the measured stiffness. The FEMA-273
method, however, largely underestimates the measured stiff-
ness. An underestimate of strut stiffness may be unconserva- FIG. 12. Assumed Strut Configurations and Forces
tive when the frame-strut model is more flexible resulting in
a lower seismic demand, and when less of the total load is strut configuration and applying horizontal equilibrium. Fig. 12
distributed to the infill strut resulting in an underestimate of shows possible strut configurations for first- and second-story
the force demand on the infill. However, a more flexible infills. All struts are assumed to carry equal loads. For the Taft
frame-strut model may result in larger story drifts, and there- 0.35g test at the time of peak base shear (4.63 s), the total
fore greater deformation demand on the infill, consistent with base shear was 44.0 kN; a first-story horizontal strut compo-
the FEMA-273 classification of infill panels as a deformation- nent RH = 22.0 kN per strut. For the corresponding axial strut
controlled component. Note also that for strut widths that are force, Rs = 27.4 kN, the average axial stress may be approx-
proportional to diagonal length, the axial strut stiffness be- imated as 1.51 MPa, over a strut width of 527 mm and mor-
comes independent of diagonal length. tared thickness of 34.4 mm. Dividing the stress by the masonry
The second-story stiffness may be estimated by dividing modulus of 7550 MPa results in an average axial strain of 200
each infilled bay into two half panels, resulting in ␣ h = 563 microstrain, which causes a total change in length of 0.35 mm
mm and ␣ L = 1318 mm. The equivalent strut width is 717 mm along the main diagonal. Measured main diagonal shortenings
(50% of diagonal) by (7), and the axial stiffness is 131.1 kN/ were 0.36 mm (east panel) and 0.18 mm (west panel), sug-
mm. Incorporating four struts into a frame model gives a sec- gesting that, through diagonal strut action, the panels carry
ond-story lateral stiffness of 101 kN/mm, 240% of the mea- unequal forces and that the west panel (opposite the point of
sured stiffness of 42.0 kN/mm. A strut width of one-fourth the load application) carries significantly less force than the east
length of the half-panel diagonal results in a strut width of 355 panel. Similar results were observed for second-story struts.
mm and a lateral story stiffness of 64 kN/mm (152% of mea-
sured). Both of these methods overestimate lateral stiffness. Infill Shear Behavior
The FEMA-273 equation results in a strut width of 150 mm For unreinforced masonry walls, sliding shear failures of
(11% of diagonal) and a lateral story stiffness of 36 kN/mm bed joints may significantly alter the nature of interaction be-
(86% of measured), again underestimating the stiffness. tween frame and infill, reducing the effectiveness of main di-
The stiffness reduction caused by window openings can also agonal struts and producing large local forces on frame mem-
be estimated by applying a reduction factor to the full-panel bers. Shear strength in masonry is typically modeled with the
stiffness, based on the relative area of window opening to infill Mohr-Coulomb relation
panel. Both experiments and numerical studies have shown a
wide range of stiffness reduction factors, dependent upon both ␶ = ␶ 0 ⫹ ␮␴ (10)
overall size and location of the opening. Finite-element studies In lieu of actual material test data, Paulay and Priestley (1992)
by Mosalam (1996) determined stiffness reduction factors for cite an average value for cohesive strength, ␶ 0, of 3% of the
square, centrally placed window openings covering various masonry compressive strength, f m⬘ , and a typical range for the
percentages of total panel area. With a window area of 8% of coefficient of friction, ␮, of 0.3 to 1.2. Paulay and Priestley
panel area in this specimen, the reduction factor is about 0.85. (1992) argue that almost all of the clamping force across po-
Since the full-panel geometry of the second-story panel is tential sliding planes is provided by the vertical component of
identical to that of the first, the second-story stiffness would the strut force. Interface gaps between the frame and infill will
be estimated as 85% of 149 kN/mm, or 127 kN/mm (175% exist because of initial construction and lengthening of the
of measured), also a large overestimate. tension column, thus preventing transfer of gravity loads from
Strut forces can be directly estimated from experimentally higher stories through the masonry panels. The average shear
measured frame forces by assuming a reasonable geometric stress to cause sliding is
586 / JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999

J. Struct. Eng., 1999, 125(6): 578-589


Vb 0.03 f ⬘m
fv = = (11)
Lt 1 ⫺ ␮ tan ␪
A coefficient of friction of 0.89 has been measured experi-
mentally by Mehrabi et al. (1994) using identical CMU to
those of this specimen and comparable mortar. For this spec-
imen, (11) gives a first-story lateral strength of 105 kN. As-
suming nearly all of the story shear is carried by the masonry
infill before significant bed joint sliding, the average shear
stress would be 0.905 MPa. The PSD experiments showed
significant bed joint cracking at lower story shears. The Taft
0.55g test caused the first bed joint crack at a story shear of
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

about 90 kN (average shear stress of 0.774 MPa). Far more


extensive damage occurred during the Taft 0.80g test, where
many bed joints cracked with story shears in the range of 65
to 110 kN (average shear stresses of 0.559 to 0.945 MPa). The
first-story shear strength was about 120 kN or 1.031 MPa,
114% of the strength calculated by (11).
Other methods available for determining the shear strength
of unreinforced masonry, such as FEMA-273, ‘‘NEHRP rec-
ommended provisions’’ (1997), and ACI 530-95, do not ac-
count for additional lateral strength caused by the interaction FIG. 13. Dependence of Masonry Shear Strength on Coeffi-
of the frame and infill, but rather consider only the cohesive cient of Friction
bond of the bed joints. FEMA-273 allows an average shear
strength of 0.190 MPa (27 psi) for running bond masonry in
good condition when no in-place shear tests are available. For An explicit PSD testing algorithm proved successful in con-
ungrouted, running bond masonry, both ACI 530-95 and junction with a soft coupled load system with an iterative ac-
NEHRP limit shear stress to 0.260 MPa (37 psi) based on a tuator control algorithm. The displacement control matrix nec-
parabolic stress distribution, corresponding to a limiting av- essary for the actuator control scheme was measured directly
erage stress of 0.173 MPa (25 psi). These shear strengths are and found to provide excellent control even with substantial
much less than the measured value of 1.031 MPa, showing stiffness degradation of the specimen. No spurious higher
that the diagonal compression induced by frame-infill inter- mode response, often associated with PSD testing of stiff
action can produce a significant increase in friction-based structures, was observed. Displacement errors analysis verified
shear strength. ACI 530-95 and NEHRP allow an increase in that error frequency spectra are not, in fact, reliable measures
shear strength caused by gravity load compression. This in- of performance. Further study of PSD testing errors will be
crease is not appropriate for infill frames since nearly all grav- needed to determine meaningful performance indicators, and
ity load will be carried through the frame. should be based on increasingly available data from actual
Friction-based formulations for lateral strength of unrein- PSD tests.
forced masonry infill can show extreme sensitivity to the as- The PSD tests revealed that the ability of the structure to
sumed coefficient of friction. Fig. 13 shows this dependence resist lateral loads without excessive drift by mobilizing and
of lateral shear strength determined by (11) for this specimen maintaining effective compressive strut action was closely re-
over a typical range of values of the coefficient of friction. lated to the type of cracking. The stepped crack pattern that
Previous research has shown that such sensitive dependence formed in the second story stabilized and did not allow large
on the coefficient of friction exists even in more advanced drifts. In contrast, the first-story infill deteriorated with long
analytical models for lateral strength of infilled frames. As- bed joint cracks, causing a soft story response. The sliding
suming a lower bound for the coefficient of friction, or ne- failures of the masonry have the potential to cause brittle fail-
glecting the contribution of friction altogether, can be a con- ures, such as column shear cracking, especially in GLD con-
servative assumption that may be acceptable for analysis or crete frames.
design. In fact, Paulay and Priestley (1992) recommend ne- The difference in crack patterns and associated hysteretic
glecting the shear-friction contribution to lateral strength, with behavior between the two stories suggests different strut mech-
frame capacity based strictly on assumed locations of plastic anisms may be needed to capture each type of behavior. The
hinging caused by infill interaction. However, for more accu- first-story infill behavior can be characterized by a main di-
rate assessment of existing structures better estimation of ␮ agonal strut at low force levels. For higher force levels, bed
and more advanced analytical models would be desirable. Un- joint sliding reduces the effectiveness of main diagonal struts
fortunately, published material test data for coefficients of fric- and allows large drifts to occur. Strut mechanisms that form
tion are scarce, and those that are available show large vari- in the lower story panels are affected in configuration and
ation and strong dependence upon type of block and mortar capacity by the numerous shear failure planes that develop as
(Hendry 1990). Even with the experimentally measured value the infill is damaged. In the second story, the window openings
of ␮ available here, predicted and measured shear strengths forced compressive struts to form inclined at steep angles to
differed by 14%. pass below the openings. The large inclination of the strut
provides enough normal force on the bed joints to prevent
CONCLUSIONS widespread cracking. The bed joint cracking that does occur
is almost entirely above or below the window openings where
This PSD experimental program was intended to provide normal forces are low. Thus it could be conjectured that win-
new behavioral information on multistory, GLD reinforced dow openings in unreinforced masonry infills lead to a more
concrete frames with openings in some of the unreinforced desirable cracking pattern than the extensive bed joint cracking
infill panels. The results of the experiment were used to assess that occurs in full-panel infills.
the ability of some simple analytical strut and shear models to Existing estimates for average shear strength that account
predict basic stiffness and strength properties of the specimen. for only cohesive bond were found to severely underestimate
JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999 / 587

J. Struct. Eng., 1999, 125(6): 578-589


the shear strength, or even initial cracking stress, of this spec- ence Foundation and the state of New York, is gratefully acknowledged.
imen. An analytical approximation for lateral shear strength The first writer acknowledges additional financial assistance provided as
a part of an ACI-WR Grace Fellowship. The experimental work for this
that includes the effects of friction and infill-frame interaction research was conducted in the George Winter Laboratory for Structural
was found to underestimate the experimental shear strength, Engineering at Cornell University with the assistance of laboratory man-
when using a measured value for the coefficient of friction. ager Timothy K. Bond. Prof. Khalid Mosalam of the University of Cal-
Further, such formulations are extremely sensitive to the se- ifornia at Berkeley also made available the benefit of his research and
lected value of coefficient of friction, and no good guidelines experience in pseudodynamic testing.
exist for determination of the coefficient of friction without
extensive material tests. For unreinforced masonry infill, APPENDIX I. REFERENCES
where lateral shear strength plays a determining role in overall Abrams, D. P., ed. (1994). ‘‘Proceedings from the NCEER Workshop on
behavior, research should be focused on better understanding Seismic Response of Masonry Infills.’’ Tech. Rep. NCEER-94-0004,
of the shear-friction behavior. Nat. Ctr. for Earthquake Engrg. Res., State University of New York at
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

Several currently available simple strut models were found Buffalo.


to bound widely the measured initial stiffnesses for both the Angel, R., Abrams, D., Shapiro, D., Uzarski, J., and Webster, M. (1994).
‘‘Behavior of reinforced concrete frames with masonry infills.’’ Struct.
first story and the second story, with window openings. Strut Res. Ser. No. 589, UILU-ENG-94-2005, Dept. of Civ. Engrg., Univer-
models for panels with openings should recognize the geo- sity of Illinois, Urbana-Champaign, Ill.
metric constraints and boundary conditions imposed by the Benjamin, J. R., and Williams, H. A. (1958). ‘‘The behavior of one-story
openings. In order to extend strut models beyond the low-level brick shear walls.’’ J. Struct. Div., ASCE, 84(4), 1–30, paper 1723.
range, certain nonlinear properties must be incorporated, in- Beres, A., Pessiki, S. P., White, R. N., and Gergely, P. (1996). ‘‘Impli-
cluding nonlinear shear behavior. Further, the progression of cations of experiments on the seismic behavior of gravity load designed
RC beam-to-column connections.’’ Earthquake Spectra, 12(2), 185–
cracking may impose changing boundary conditions, requiring 198.
adapted strut configurations in the nonlinear range. ‘‘Building code requirements for masonry structures.’’ (1995). ACI Stan-
dard 530-95, American Concrete Institute, Farmington Hills, Mich.
Recommendations for Analysis and Design ‘‘Building code requirements for structural concrete.’’ (1995). ACI Stan-
dard 318-95, American Concrete Institute, Farmington Hills, Mich.
Based on the results of this experiment and review of some Buonopane, S. G. (1997). ‘‘Seismic evaluation of a masonry infilled re-
simple analytical techniques proposed by others, several rec- inforced concrete frame by pseudodynamic testing,’’ MS thesis, School
of Civ. and Envir. Engrg., Cornell University, Ithaca, N.Y.
ommendations are offered for analysis and design of unrein- Dhanasekar, M., and Page, A. W. (1986). ‘‘The influence of brick masonry
forced masonry, infilled frames. infill properties on the behaviour of infilled frames.’’ Proc., Instn. Civ.
A range of strut widths from one-sixth to one-fourth of the Engrs., 81(2), 593–605.
panel diagonal length will probably bound the true stiffness, Drysdale, R. G., Hamid, A. A., and Baker, L. R. (1994). Masonry struc-
although the widths predicted by (7) and (9) should be con- tures: Behavior and design. Prentice-Hall, Englewood Cliffs, N.J.
sidered for comparison. Since the lateral stiffness of a typical El-Attar, A-G., White, R. N., and Gergely, P. (1997). ‘‘Behavior of gravity
load design reinforced concrete buildings subjected to earthquakes.’’
infilled frame structure will be dominated by the contribution ACI Struct. J., 94(2), 133–145.
of the diagonal struts, seismic demand may be highly depen- Hendry, A. W. (1990). Structural masonry. MacMillan Education, Ltd.,
dent on the assumed strut width. An underestimate of strut London.
width may result in less force being transferred to the masonry, Holmes, M. (1961). ‘‘Steel frames with brickwork and concrete infilling.’’
affecting the prediction of cracking or crushing. Proc., Instn. Civ. Engrs., 19, 473–478.
For panels with openings, a multiple strut configuration Mahin, S., Shing, P. B., Thewalt, C. R., and Hanson, R. D. (1989). ‘‘Pseu-
dodynamic test method—Current status and future directions.’’ J.
should be used which recognizes the boundary conditions im- Struct. Engrg., ASCE, 115(8), 2113–2128.
posed by the openings. Again, strut widths of between one- Mainstone, R. J. (1971). ‘‘On the stiffnesses and strengths of infilled
sixth and one-fourth of the strut diagonal lengths will likely frames.’’ Proc., Instn. Civ. Engrs. Suppl., 57–89.
bound the true stiffness. Mander, J. B., Nair, B., Wojtkowski, K., and Ma, J. (1993). ‘‘An experi-
Infill shear strengths based on cohesive bond alone (e.g. mental study on the seismic performance of brick-infilled steel frames
FEMA-273, ACI 530, NEHRP) are extremely conservative, as with and without retrofit.’’ Tech. Rep. NCEER-93-0001, Nat. Ctr. for
Earthquake Engrg. Res., State University of New York at Buffalo.
they do not account for the shear-friction contribution pro- Mehrabi, A. B., Shing, P. B., Schuller, M. P., and Noland, J. L. (1994).
duced by the compressive strut action. Potential shear-friction ‘‘Performance of masonry infilled R/C frames under in-plane lateral
contributions from gravity load should not be used to increase loads.’’ Res. Series No. CU/SR-94/6. Dept. of Civ., Envir., and Arch.
the shear strength as gravity load will be carried by the bound- Engrg., University of Colorado, Boulder.
ing frame. Mehrabi, A. B., Shing, P. B., Schuller, M. P., and Noland, J. L. (1996).
Infill shear-friction models that account for strut action [e.g. ‘‘Experimental evaluation of masonry-infilled RC frames.’’ J. Struct.
Engrg., ASCE, 122(3), 228–237.
(11)] should be used only with a lower-bound coefficient of Mosalam, K. M. (1996). ‘‘Experimental and computational strategies for
friction. A value of 0.30 is currently accepted as appropriate. the seismic behavior evaluation of frames with infill walls,’’ PhD the-
Measured coefficients of friction from masonry unit testing sis, School of Civ. and Envir. Engrg., Cornell University, Ithaca, N.Y.
should be used only with extreme caution and a close exam- Mosalam, K. M., White, R. N., and Gergely, P. (1997). ‘‘Static response
ination of the sensitivity of shear strength to the coefficient of of infilled frames using quasi-static experimentation.’’ J. Struct. Engrg.,
friction. ASCE, 123(11), 1462–1469.
‘‘NEHRP guidelines for the seismic rehabilitation of buildings.’’ (1997).
The localized forces applied to the bounding frame by the FEMA-273, Building Seismic Safety Council, Washington, D.C.
deteriorating masonry should be accounted for by estimating ‘‘NEHRP recommended provisions for seismic regulations for new build-
locations of plastic hinging in the frame members and calcu- ings and other structures.’’ (1997). Building Seismic Safety Council,
lating the lateral force associated with such a frame failure Washington, D.C.
mode. For conservative design, the lateral strength of the Paulay, T., and Priestley, M. J. N. (1992). Seismic design of reinforced
frame with assumed hinge locations should be greater than the concrete and masonry buildings. Wiley, New York.
Pessiki, S. P., Conley, C. H., Gergely, P., and White, R. N. (1990). ‘‘Seis-
shear strength of the infill, including interaction effects. mic behavior of lightly-reinforced concrete column and beam-column
joint details.’’ Tech. Rep. NCEER-90-0014, Nat. Ctr. for Earthquake
ACKNOWLEDGMENTS Engrg. Res., State University of New York at Buffalo.
Seible, F., Hegemier, G. A., and Igarashi, A. (1996). ‘‘Simulated seismic
The financial support of the National Center for Earthquake Engi- laboratory load testing of full-scale buildings.’’ Earthquake Spectra,
neering Research (NCEER), with primary funding from the National Sci- 12(1), 57–86.

588 / JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999

J. Struct. Eng., 1999, 125(6): 578-589


Shing, P. B., and Mahin, S. (1987). ‘‘Cumulative experimental errors in ds = target structural displacement vector;
pseudodynamic tests.’’ Earthquake Engrg. Struct. Dyn., 15, 409–424. d̂ s = measured structural displacement vector;
Shing, P. B., and Mahin, S. (1990). ‘‘Experimental error effects in pseu- Ec = elastic modulus of concrete;
dodynamic testing.’’ J. Engrg. Mech., ASCE, 116(4), 805–821. Em = elastic modulus of masonry;
Shing, P. B., Nakashima, M., and Bursi, O. S. (1996). ‘‘Application of
pseudodynamic test method to structural research.’’ Earthquake Spec-
f ⬘m = masonry prism compressive strength;
tra, 12(1), 29–56. f␯ = masonry shear strength
Stafford Smith, B. (1966). ‘‘Behavior of square infilled frames.’’ J. Struct. h = height of infill panel;
Div., ASCE, 92(1), 381–403. Ic = moment of inertia of column;
Stafford Smith, B. (1967). ‘‘Methods for predicting the lateral stiffness ks = axial stiffness of diagonal strut;
and strength of multi-storey infilled frames.’’ Build. Sci., 2, 247–257. L = length of infill panel;
Takanashi, K., and Nakashima, M. (1987). ‘‘Japanese activities on on- M = mass matrix;
line testing.’’ J. Engrg. Mech., ASCE, 113(7), 1014–1032. Q = displacement amplification matrix;
Thewalt, C. R. (1994). ‘‘Performance parameters for pseudodynamic
Downloaded from ascelibrary.org by Indian Institute of Technology Roorkee on 07/23/18. Copyright ASCE. For personal use only; all rights reserved.

RH = horizontal component of strut force;


tests.’’ J. Struct. Engrg., ASCE, 120(9), 2768–2781. RS = strut force;
Wood, R. H. (1958). ‘‘The stability of tall buildings.’’ Proc., Instn. Civ.
Engrs., 11, 69–102.
RV = vertical component of strut force;
Zarnic, R., and Tomazevic, M. (1984). ‘‘Study of the behaviour of ma- t = mortared thickness of masonry;
sonry infilled reinforced concrete frames subjected to seismic load- Vb = lateral shear strength of a panel;
ing—Part one.’’ Rep., Institute for Testing and Research in Materials w = width of diagonal strut;
and Structures, Ljubljana, Yugoslavia. ␣h = vertical contact length;
Zarnic, R., and Tomazevic, M. (1985). ‘‘Study of the behaviour of ma- ␣L = horizontal contact length;
sonry infilled reinforced concrete frames subjected to seismic load- ␤ = Newmark-beta integration parameter;
ing—Part two.’’ Rep., Institute for Testing and Research in Materials ␥ = Newmark-beta integration parameter;
and Structures, Ljubljana, Yugoslavia. ⌬t = time step;
␪ = strut inclination;
APPENDIX II. NOTATION ␮ = coefficient of friction;
␰ = actuator command displacement reduction factor;
The following symbols are used in this paper: ␴ = bed joint normal stress;
␶ = bed joint shear stress;
d = length of diagonal strut; ␶0 = bed joint cohesive stress; and
d a = actuator command displacement vector; ␻n = circular frequency of highest mode.

JOURNAL OF STRUCTURAL ENGINEERING / JUNE 1999 / 589

J. Struct. Eng., 1999, 125(6): 578-589

Vous aimerez peut-être aussi