ASSEMBLY AND INSTALLATION INSTRUCTIONS

700 Lumens
WARNING: When using this lighting device, safety precautions should be followed at all times.

READ THE INSTRUCTIONS BELOW CAREFULLY AND FOLLOW THEM FOR YOUR OWN SAFETY!

1. This device is designed for indoor use. Do not use outdoors.


2. Prior to installation, battery connector must be open to prevent high voltage from being present on out put leads
(red & yellow).
3. This device is designed for use with 17W–110W single pin or bipin fluorescent lamps, from 2’ through 8’. Please
use energy-saving circline, U-shaped, or 4-pin rapid start long compact fluorescent lamps.
4. Please ensure the electricity connections conforms to the National Electrical Code and local regulations if applicable.
5. To avoid electric shock, please disconnect normal and emergency power supplies, and battery connector of the
emergency ballast before servicing.
6. This device is designed for factory or field installation in either the ballast channel, or on top of the indoor fixture,
except air handling heated air outlets, wet or hazardous location fixtures. Do not install this device near gas or
electric heaters.
7. AC power source of 120 VAC or 277 VAC is required.
8. The battery is sealed, non-maintenance, and is not replaceable in the field. Please contact manufacturer for
information on service. Do not attempt to service the battery please.
9. Do not use accessory equipment that is not recommended by manufacturer. Failure to do so may cause unsafe
conditions. Servicing should only be performed by qualified service personnel.
10. Do not use the product for other purpose that the product is NOT designed for.

PLEASE SAVE THESE INSTRUCTIONS


INSTALLATION INSTRUCTIONS DIAGRAM
DIAGRAM121
NOTE: All the branch circuit wiring has to be ready as well as an unswitched source of power before the fixture is installed.
Confirm the same branch circuit would be used for both the emergency ballast and the AC ballast.
CAUTION: Battery connector has to be opened for preventing high voltage on output leads (red and yellow).
Wait until the installation process has been completed and AC is supplying power to the emergency
ballast, and then join the battery connector.

Emergency Ballast
1. AC power has to be off before installation. Battery Pack Channel Cover
2. Choose the right wiring diagram to connect the ballast to the AC ballast and lamp.
Test Switch Charging Indicator Light
3. Please ensure the electricity connections conform to the National Electrical Code and local regulations.
4. Follow diagrams 1 and 2 to install the battery pack on the top of the fixture or in the
ballast channel. DIAGRAM 2
Emergency Ballast
5. To install the test switch, it would go through the side of a strip fixture or the ballast channel cover of a troffer.
Follow diagrams 1 and 2 to drill a 1/2” hole and install the test switch. In order to remove AC power from both
the emergency ballast and the AC ballast, the test switch has to be connected properly (see diagram 4).
6. Match violet and brown leads to connect the charging indicator light to the battery pack (see diagram 5).
Charging Indicator Light
The charging indicator will be on after the fixture is installed properly.
Test Switch
7. Please search for a readily visible location to apply the CAUTION label which reads, “This unit has more
than one power supply connection point. To reduce the risk of electric shock, disonnect
both the branch circuit-breakers or fuses, and emergency power supply before servicing.”
8. Do not join the inverter connector until the fixture is completely installed and supply
AC power to the emergency ballast.
9. The battery needs to be charged for one hour in order to have short-term testing on the
emergency function. Before having a long-term emergency function testing, the battery in the emergency ballast
has to be charged for 24 hours. DIAGRAM 3

DIAGRAM 4

SINGLE POLE
UNSWITCHED FIXTURE SWITCHED FIXTURE

EMERGENCY EMERGENCY
BALLAST BALLAST

EMERGENCY EMERGENCY
BALLAST BALLAST
DIAGRAM 5
TROFFER-STYLE FIXTURE OPTIONAL STRIP-STYLE FIXTURE

Emergency Ballast

Fixture Fixture Fixture


Ballast Channel Cover

Leads to Charging Indicator Light


Indicator Indicator
Light Light
Violet (+) Violet (+)
7/8” Punch

Brown (-) Brown (-) AC ON


7/8” Bushing Inserted into
Ballast Channel Cover TEST

Plastic Tubing
(please cut to necessary length)

1/2” White Bushing to Hold


Charging Indicator Light
Step 1 Step 2

Charging Indicator Light


Fixture Lens

Operation
• The charging indicator light would be on to indicate the battery is being charged when AC power is applied.
• This emergency ballast would function and operate one or two lamps at least 90 minutes when the AC power is failed.

Maintenance
Note: Services should only performed by qualified personnel. The emergency ballast should be checked periodically to
confirm proper functioning and the following schedule is recommended:
1. To inspect the charging indicator every month and confirm that is illuminated.
2. Push the test switch for 30 seconds to ensure the emergency ballast is functioning. Recommended to perform this
testing every 30 days.
3. Perform a long-term test (90-minute battery discharge) at least once every year. One or two lamps should operate for
no less than 90 minutes.
WIRING DIAGRAMS FOR 1- and 2-LAMP EMERGENCY OPERATION
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
For 1-Lamp Emergency Operation For 2-Lamp Emergency Operation

A. INSTANT START AC BALLAST A. TWO-LAMP INSTANT START AC BALLAST


AC EMERGENCY AC EMERGENCY
BALLAST BALLAST BALLAST BALLAST

B. RAPID START AC BALLAST B. THREE-LAMP INSTANT START AC BALLAST


AC EMERGENCY AC EMERGENCY
BALLAST BALLAST BALLAST BALLAST

C. TWO-LAMP INSTANT START BALLAST


LINE
BLACK
WHI TE
BLUE BLUE
BLUE/WHITE
ORANGE
BLAC K
277V TO UNSWITCHED AC
USE PROPER TAP
C. FOUR-LAMP INSTANT START AC BALLAST
120V
YELLOW/GREEN WHI TE CAP UNUSED LEAD
AC COM
YELLOW EMERGENCY RED AC
BALLAST BLUE
BALLAST EMERGENCY
RED WHITE
VI OL ET (+)
BR OWN( -)
BALLAST BALLAST
RED

INVERTER
LAMP 1 CONNECTOR

LAMP 2 (EMERGENCY)

D. TWO-LAMP RAPID START BALLAST D. TWO-LAMP RAPID START AC BALLAST


BLACK BLUE BLUE ORANGE
277V TO UNSWITCHED AC
LINE WHITE BLUE BLUE/W HITE BLACK USE PROPER TAP
120V
YELLOW/GREEN CAP UNUSED LEAD
AC EMERGENCY
WHITE COM AC
YELLOW
RED EMERGENCY
YELLOW
BALLAST RED BALLAST BALLAST BALLAST
YELLOW WHITE
VIOLET (+)
RED BROWN( -)
RED

INVERTER
LAMP 1 CONNECTOR

LAMP 2 (EMERGENCY)

E. THREE-LAMP RAPID START AC BALLAST


E. THREE-LAMP INSTANT START BALLAST AC
BLACK BLUE BLUE ORANGE
277V TO UNSWITCHED AC EMERGENCY
BLUE/WHITE BLAC K
LINE WHITE
YELLOW/GREEN
120V USE PROPER TAP BALLAST BALLAST
WHI TE CAP UNUSED LEAD
AC COM
BLUE YELLOW EMERGENCY RED
BLUE
BALLAST RED BALLAST WHITE
VIOLET (+)
BROWN( -)
RED

INVERTER
LAMP 1 CONNECTOR
LAMP 2

LAMP 3 (EMERGENCY)

F. FOUR-LAMP RAPID START AC BALLAST


F. THREE-LAMP RAPID START BALLAST BLUE
BLACK BLUE ORANGE TO UNSWITCHED AC
277V AC
LINE WHITE BLUE BLUE/WHITE BLACK
120V
USE PROPER TAP EMERGENCY
BLUE/WHITE
AC YELLOW/GREEN WHITE
COM
CAP UNUSED LEAD BALLAST BALLAST
BLUE/WHITE YELLOW EMERGENCY RED
RED
BALLAST YELLOW
BALLAST WHI TE
YELLOW VI OL ET (+)
RED BROW N(-)
RED

INVERTER
LAMP 1 CONNECTOR
LAMP 2

LAMP 3 (EMERGENCY)

G. FOUR-LAMP INSTANT START BALLAST Emergency-Only Operation


BLUE BLUE ORANGE
BLACK
277 V TO UNSWITCHED AC
BLUE/WHITE BLACK

A. ONE-LAMP WITHOUT AC BALLAST


LINE WHITE
120 V USE PROPER TAP
YELLOW/GREEN WHITE CAP UNUSED LEAD
YELLOW
AC BLUE YELLOW EMERGENCY RED
COM

RED
YELLOW BALLAST RED VI OL ET (+) BALLAST WHITE
BROWN( -)
RED

INVERTER
EMERGENCY
LAM P 1 CONNECTOR BALLAST
LAM P 2

LAM P 3

LAM P 4 (EMERGENCY)

H. FOUR-LAMP RAPID START BALLAST B. TWO-LAMP WITHOUT AC BALLAST


BLACK RED BLUE OR ANGE
277 V TO UNSWITCHED AC
LINE WHITE RED BLUE/WHITE BLA CK
120 V USE PROPER TAP
AC
YELLOW/GREEN WHITE
CO M CAP UNUSED LEAD EMERGENCY
YELLOW
BLUE/W HITE YELLOW EMERGENCY RED BALLAST
BLUE/W HITE
YELLOW BALLAST BLUE BALLAST WHITE
BROWN VI OLET (+ )
BROWN BLUE BR OWN(-)
RED

INVERTER
LAM P 1 CONNECTOR
LAM P 2

LAM P 3

LAM P 4 (EMERGENCY)

NOTE: Use the proper tap cap to unswitched AC lead.