Vous êtes sur la page 1sur 73

POWERTRONIX

Mizar-Alcor

Service Manual

DT 0424

Document : DT0424 PTX English


Revision Date Checked Approved
00 14-03-2008 18-03-2008 21-03-2008
Ghezzi R. Gorlani A.
01 19-05-2008 19-05-2008 20-05-2008
Pirola G. Gorlani A.

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01


Index
1. GENERAL ITEMS ......................................................................................................4
1.1 INTRODUCTION...................................................................................................4
1.1.1 General Fault Identification Procedure .........................................................4
1.2 TOOLS..................................................................................................................5
1.2.1 Portable PC with software ............................................................................5
1.2.2 Oscilloscope .................................................................................................5
1.2.3 Digital multimeter( DSM)...............................................................................5
1.2.4 Discharging resistor ......................................................................................5
2 UPS COMPONENTS RECOGNIZING .......................................................................6
2.1 UPS CLOSED .......................................................................................................6
2.2 INNER VIEW WITH SAFETY COVER REMOVED ...............................................7
2.3 REAR UPS DESCRIPTION ..................................................................................8
2.4 MIZAR ELECTRONIC PARTS LAYOUT...............................................................9
2.5 ALCOR ELECTRONIC PARTS LAYOUT ...........................................................10
2.6 MIZAR BOARDS................................................................................................11
2.7 ALCOR BOARDS...............................................................................................11
2.8 BOARDS LAYOUT..............................................................................................12
2.8.1 CS0152 MIZAR Power Interface Board Component Layout.......................12
2.8.2 CS0151 ALCOR Power Interface Board Component Layout......................13
2.8.3 CS0150 MIZAR ALCOR Control Logic Board.............................................14
2.8.4 CS0153 MIZAR ALCOR Power Supply Board............................................15
2.8.5 CS0098 MIZAR ALCOR Relay & Communication Board ...........................16
2.8.6 MIZAR ALCOR SNMP Communication Board ...........................................16
2.8.7 CS0161 MIZAR ALCOR Terminal Blocks Board ........................................17
3 TROUBLESHOOTING .............................................................................................18
3.1 FUSE CHECK LIST ............................................................................................18
3.2 POWER FUSE ....................................................................................................19
3.2.1 Mizar...........................................................................................................19
3.2.2 Alcor ...........................................................................................................20
3.3 CHECK ALL PFC & INVERTER OUT IGBTS. ....................................................21
3.3.1 Mizar...........................................................................................................21
3.3.2 Alcor ...........................................................................................................22
3.4 CS0153 MIZAR ALCOR POWER SUPPLY BOARD .........................................23
3.4.1 Check Auxiliary Power Supply Control Board.............................................24
3.5 CS0150 CONTROL LOGIC BOARD...................................................................25
3.5.1 LED Status .................................................................................................26
3.5.2 Check Control Board ..................................................................................27
3.5.3 Check Power Supply Voltage .....................................................................27
3.6 CS0152 POWER INTERFACE MIZAR BOARD ................................................28
3.7 CS0151 POWER INTERFACE ALCOR BOARD ................................................30
4 PC BASED CHECKS AND SETTINGS ....................................................................32
5 ELECTRICAL DIAGRAM..........................................................................................40
5.1 PCB electrical diagram index ..............................................................................40
5.1.1 DE1111 UPS general diagram Mizar..........................................................41
5.1.2 DE1112 UPS general diagram Alcor ..........................................................43
Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 2 of 73


5.1.3 DE0098 Relay & Communication Board.....................................................46
5.1.4 DE0138 Temperature sensor PCB .............................................................47
5.1.5 DE0143 Battery Fuse PCB (Battery 7.2-9Ah) / DE0157 Battery Fuse PCB
(Battery 4.5-5.2Ah) ...................................................................................................47
5.1.6 DE0150 Control Logic.................................................................................48
5.1.7 DE0151 Inverter Driver & Feedback Alcor..................................................59
5.1.8 DE0152 Inverter Driver & Feedback Mizar .................................................65
5.1.9 DE0153 Power Supply Board .....................................................................69
5.1.10 DE0154 H-F Filter Mizar .............................................................................70
5.1.11 DE0155 LCD Mimic Display .......................................................................71
5.1.12 DE0161 H-F Filter Alcor..............................................................................72
5.1.13 DE1235 Battery String ................................................................................73

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 3 of 73


WARNING !
The following documentation requires the knowledge and the support of Mizar-Alcor
USER MANUAL .

1. GENERAL ITEMS
1.1 INTRODUCTION
The UPS contains complex electronic control circuits which require a firm understanding
in order to carry out comprehensive fault diagnosis and repair of the equipment.
The aim of the information contained in this chapter is to provide sufficient guidance to
the trained service engineer, to enable successful fault location to printed circuit board
level. When a faulty circuit board or component has been identified, it should be replaced
or returned to the nearest service centre to repair.
The troubleshooting information include the following items :

• Component location and identification


• Diagnostic information
• Troubleshooting procedures
• Test procedures

Note: when following the procedures cross referencing is inevitable, therefore


it is recommended that this chapter is read in its’ entirety, before commencing
work on the equipment.

There is no practical way detecting an impending UPS malfunction, as most problems do


not emerge as a gradual performance degradation. Generally the UPS will either work
correctly or shut down with or without a warning indication.
In the event of a UPS malfunction troubleshooting should be carried out methodically
along the following guide lines.

1.1.1 General Fault Identification Procedure

When first summoned to the UPS fault the immediate action should be to observe and
record the LED indication displayed on the unit operator panel.

a) Determine the UPS power status.


b) Note the control switch configuration, and also the warning horn sequence if it is
operating.

WARNING: during the troubleshooting it will be necessary to power up the


unit whit the side or top covers removed. In this situation exposure
to potentially lethal voltage is possible even whit the input utility
supply switched off.
Take great care at all switch to minimize the risk of contact whit live
voltage, especially when working around the battery or DC bus

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 4 of 73


c) Power down the unit, and ensure that the DC Bus Safety discharge check is
carried out.
d) Gain access to the internal components follow the procedure for removing the UPS
covers.
e) Check the status of the UPS fuses refer to the check list on table 1,2,3
f) Apply power and analyse LCD indications
g) Refer troubleshooting chart to identify possible fault
h) Check PFC converter power components. Pag.20 for component location
i) Check inverter power components. Pag.20 for component location

1.2 TOOLS
Special mechanical tools aren’t required to service the UPS, a normal electricians tool kit
will be adequate. Are necessary insulating gloves and glasses for safety. However to
carry out the check procedures in this chapter the following test equipment will be
required.

1.2.1 Portable PC with software

POWERTRONIX UPS Maintenance UCT


See the chapter 4

is absolutely necessary for a skilled service engineer because every set point or UPS
logic status or regulation constant can be set or checked only via PC and
POWERTRONIX software

1.2.2 Oscilloscope

A dual trace oscilloscope, which has the ability to sum the two channel, allowing
differential voltage measurements to be made.
For the measure points that it is needed to check it is mandatory to have the
oscilloscope insulated from the supply whit a transformer or battery fed scope.
A storage facility is useful, but not essential.

1.2.3 Digital multimeter( DSM)

A standard digital multimeter is necessary to take essential measurements ; a reference


type could be the FLUKE 70 series multimeter or equivalent.

1.2.4 Discharging resistor

To discharge electrolytic capacitors bank in a short time it’s necessary use a discharging
resistor , ref. value 10K / 50W nom. Before using discharging resistor verify that
battery circuit breaker is open !

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 5 of 73


2 UPS COMPONENTS RECOGNIZING
To do servicing it’s necessary to recognize UPS parts , so , before troubleshooting ,
some pictures of UPS and parts will be shown in the following pages . To check pictures
it’s necessary to follow the UPS general schematic diagram (DE1111 for Mizar and
DE1112 for Alcor) attached at the end of this document .

2.1 UPS CLOSED


E:P:O: Command

UPS Control Panel

UPS Side Cover panel

UPS Front Cover

BATTERY Front Cover

Fig.1

*** WARNING !! Before removing safety covers after power disconnection , it’s
necessary to wait for 10 minutes to have discharged inner capacitors . In any case be
careful and never touch circuits or components before a voltage check

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 6 of 73


2.2 INNER VIEW WITH SAFETY COVER REMOVED

UPS Power Section

UPS Battery Location

BATTERY Connections

BATTERY String

Fig.2

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 7 of 73


2.3 REAR UPS DESCRIPTION

Output
Air window

RS232 & Status


Remote Control
Slot location

SNMP-Net Com
Slot location

Rotary Switch
Breaker

Terminal Blocks
Power
Connection

Fig.3

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 8 of 73


2.4 MIZAR ELECTRONIC PARTS LAYOUT

LEFT SIDE
Fig.4
CS0150
NEUTRAL BAR
Connection HEATSINK

FAN

DC Busbar

Power Impedence

RIGHT SIDE
Fig. 5
CS0153

DC
Busbar

Power Impedence

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 9 of 73


2.5 ALCOR ELECTRONIC PARTS LAYOUT
LEFT SIDE
Fig. 6
NEUTRAL BAR
CONNECTION HEATSINK CS0153

Fuse

DC Busbar

Power Impedence

RIGHT SIDE
Fig. 7
CS0150

Fuse

DC Busbar
Power Impendence

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 10 of 73


2.6 MIZAR BOARDS

This paragraph describes the PCB 's fitted in the UPS,

Subassembly code Description Diagram Circuit code

0sde 0150 Control Logic 7-30KVA DE0150 CS0150


0sde 0152 Inverter Drivers&Feedback Mizar DE0152 CS0152
0sde 0153 Aux. Converter DE0153 CS0153
0sde 0155 LCD Mimic Display "4*20" DE0155 CS0155
0sde 0143 Fuse Holder x 7-9 Ah DE0143 CS0143
0sde 0157 Fuse Holder x 7-9 Ah DE0157 CS0157
0sde 0154 H-F Filter DE0154 CS0161
0sde 0162 Temperature Sensor SMT DE0138 CS0138
0sde 0098 Relay Board DE0098 CS0098

2.7 ALCOR BOARDS

This paragraph describes the PCB 's fitted in the UPS,

Subassembly code Description Diagram Circuit code

0sde 0150 Control Logic 7-30KVA DE0150 CS0150


0sde 0151 Inverter Drivers&Feedback Mizar DE0151 CS0151
0sde 0153 Aux. Converter DE0153 CS0153
0sde 0155 LCD Mimic Display "4*20" DE0155 CS0155
0sde 0143 Fuse Holder x 7-9 Ah DE0143 CS0143
0sde 0157 Fuse Holder x 7-9 Ah DE0157 CS0157
0sde 0161 H-F Filter DE0161 CS0161
0sde 0162 Temperature Sensor SMT DE0138 CS0138
0sde 0098 Relay Board DE0098 CS0098
0sde 0114 Fan Board DE0114 CS0114

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 11 of 73


2.8 BOARDS LAYOUT

2.8.1 CS0152 MIZAR Power Interface Board Component Layout


Refer to Electrical Diagram :DE0152

Fig. 8

Positive Positive
INVERTER
DC Battery Fuse DC Capacitor Fuse
Relay
Static Switch

IGBT IGBT
Input Output
Section Section

Negative RESERVE
Negative Relay
Input DC Capacitor DC Battery Fuse
Precharge Fuse Static Switch
Relay

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 12 of 73


2.8.2 CS0151 ALCOR Power Interface Board Component Layout
Refer to Electrical Diagram :DE0151

Fig. 9

IGBT
OUTPUT INVERTER
SECTION Static Switch
Thyristor

Input IGBT RESERVE


Precharge INPUT Static Switch
Thyristor SECTION Thyristor

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 13 of 73


2.8.3 CS0150 MIZAR ALCOR Control Logic Board
Refer to Electrical Diagram :DE0150

Fig. 10

SNMP Relay Board


Connector Connectors

Fiber Optic
Connector
Parallel
Communicatio

LCD Mimic
Display Board Interface
Connectors Board
Connectors

LED BAR
UPS STATUS

LED BAR
Processor
STATUS

Battery
Keep Timer

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 14 of 73


2.8.4 CS0153 MIZAR ALCOR Power Supply Board
Refer to Electrical Diagram :DE0153

Fig. 11

Power Interface
Supply Board
status Connector

Input Mains
Connector

Input Reserve
Connector

DC Bus
Connector

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 15 of 73


2.8.5 CS0098 MIZAR ALCOR Relay & Communication Board
Refer to Electrical Diagram :DE0098

Fig. 12

Free voltage contacts


Ups status

E.P.O.
Terminal
Connection

DB9
RS232
Communication
Connector

Control
Logic
Connector

2.8.6 MIZAR ALCOR SNMP Communication Board

Fig. 13

NET RJ45 + Config Switch


status led
CONNECTOR

Serial Comport Control


Logic
Connection
Status Led
Error Link

Aux
Input/Output
Drycontact

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 16 of 73


2.8.7 CS0161 MIZAR ALCOR Terminal Blocks Board
Refer to Electrical Diagram :DE0161

Fig. 14

MAINS-INPUT RESERVE-INPUT BATTERY OUTPUT


FUSES FUSES FUSES FUSES

MAINS-INPUT RESERVE-INPUT BATTERY OUTPUT


Terminal Terminal Terminal Terminal
Blocks Blocks Blocks Blocks

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 17 of 73


3 TROUBLESHOOTING

To identify a fault cause please refer to the following items.


Fig.15 MIZAR ALCOR TERMINAL BLOCKS BOARD

3.1 FUSE CHECK LIST


Prior to any fault diagnosis , a check of all UPS fuses is recommended.
Fault fuse can give an indication of a defective power device or component .

TAB.1
Fuse Value Value Protection of Location
MIZAR ALCOR

EMC/RF FILTERS BOARD (CS0161)


32A 50A
F1-F2-F3 Mains Input Front high left corner
10X38mm 14x51mm
(DE0154 MIZAR) (DE0161 ALCOR)
EMC/RF FILTERS BOARD (CS0161)
32A 50A
F4-F5-F6 Reserve Input Front high Centre left corner
10X38mm 14x51mm
(DE0154 MIZAR) (DE0161 ALCOR)
EMC/RF FILTERS BOARD (CS0161)
32A 50A
F7-F8 External Battery Front high centre right corner
10X38mm 14x51mm
(DE0154 MIZAR) (DE0161 ALCOR)
EMC/RF FILTERS BOARD (CS0161)
32A 50A
F9-F10-F11 Output UPS Front high right corner
10X38mm 14x51mm
(DE0154 MIZAR) (DE0161 ALCOR)

SCH.1

HOLE 5.5mm
HOLE 5.5mm metal Plated
metal Plated
PW6 PW7 PW8 PW9 PW10 PW11 PW12 PW13 PW14 PW15 PW16 PW17
PW1 PW2 PW3 PW4 PW5 L1-R L2-R L3-R N-R + BATTERY - BATTERY COMM. L1-O L2-O L3-O N-O GROUND
GROUND L1-I L2-I L3-I N-I

F4 F5 F6 F7 F8 F9 F10 F11
F1 F2 F3

C1
1µF
275Vac
C10 X2
1µF 0.47µF 0.47µF 0.47µF 1µF 0.47µF 0.47µF 0.47µF 0.47µF 0.47µF
1µF 0.47µF 0.47µF 0.47µF C6 275Vac C7 275Vac C8 275Vac C9 275Vac 275Vac C11 275Vac C12 275Vac C13 275Vac C14 275Vac C15 275Vac
C2 275Vac C3 275Vac C4 275Vac C5 275Vac X2 X2 X2 X2 X2 X2 X2 X2 X2 X2
X2 X2 X2 X2

PW33 PW34 PW35 PW36 PW37 PW38 PW39 PW40


PW30 PW31 PW32

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 18 of 73


3.2 POWER FUSE
F1-F2: Positive and Negative DC BUS.
F3-F4: Positive and Negative BATTERY

3.2.1 Mizar

Refer to Electrical Diagram :DE0152


Refer to Fig.8 MIZAR Interface Board Component Layout

TAB.2
Fuse Value Protection of Location

32A Power Interface BOARD (DE0152)


F1-F2 Battery Input
10x38mm MIZAR
32A Power Interface BOARD (DE0152)
F3-F4 DC BUS
10x38mm MIZAR

SCH.2

FS10
+ BATTERY 1 F2 3
2 4
32A 10x38

FS14 1 F3 3
+ DC 2 4
32A 10x38

INPUT INVERTER OUTPUT INVERTER


R182 P+5
Q1 16_+DC-BUS Q4
13
12

12
13

SK60GB128 100K 0.25W SK60GB128 E4-T


2

C38 C37 R95 R96 R180 R188 C40 C41


E1-T 27 28 G1-T 2.2µF PHB 2.2µF PHB 2.2µF PHB 2.2µF PHB G4-T 28 27
FS6 24 850V 850V R183 150K 0.25W 850V 850V 24 FS20
L1 23 150K 0.25W 150K 0.25W 150K 0.25W 23 L1
From Input

1 100K 0.25W 1
1

G1-B P+5 G4-B


Inductor

2 Q2 Q5 2
13
12

12
13

E1-B E4-B
SK60GB128 R99 SK60GB128
1

6.8K R184 D41


6
5

5
6

E2-T 27 28 G2-T G5-T 28 27 E5-T


FS5 24 CN3 100K 0.25W 24 FS21
L2 23 AUX_CONV +DC 4 To Aux. 1N4148 23 L2
1 3 1
12

2
G2-B
Q3 2
Conve rte r D42
REF
Q6
G5-B
2
13
12

12
13

E2-B CS0153 E5-B


SK60GB128 AUX_CONV -DC 1 SK60GB128
R185
6
5

5
6

E3-T 27 28 G3-T 1N4148 G6-T 28 27 E6-T


FS4 24 DC BUS 100K 0.25W 24 FS22
2

L3 23 R100 23 L3
1 G3-B 6.8K G6-B 1
2 E3-B R186 + E6-B 2
C62
To Inverter
2

C39 R97 R98 R181 100K 0.25W 10µF 16V C43


6
5

5
6

2.2µF PHB 2.2µF PHB Inductor


850V 850V
150K 0.25W 150K 0.25W 150K 0.25W R187
1

16_-DC-BUS 100K 0.25W

1 F4 3
FS15 2 4
-DC 32A 10x38

1 F1 3
FS11 2 4
- BATTERY 32A 10x38

Note the location of fuse are different in Mizar compare to Alcor:

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 19 of 73


3.2.2 Alcor

Refer to Fig.6/7 ALCOR LEFT/RIGHT SIDE electronic parts LAYOUT

TAB.3
Fuse Value Protection of Location

Positive Battery Input Right side Heatsink (DE0152)


F1-F3 100A 690V
Positive DC BUS ALCOR
Negative Battery Input Left side Heatsink (DE0152)
F2-F4 100A 690V
Negative DC BUS ALCOR

If you find one or more fuses blown, you have to check firstly
ALL the POWER semiconductors on the UPS

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 20 of 73


3.3 CHECK ALL PFC & INVERTER OUT IGBTS.
well locked . If IGBT is damaged , remember that probably the driver circuitry could be
damaged , so the following parts on interface board.

3.3.1 Mizar

CS 0152 have to be tested.


The following diagram detail regards only the driver circuitry for PFC L1 , only to indicate
the part of circuit .
Obviously also PFC L2&L3 and INVERTER L1&L2&L3 driver has to be tested.

SCH.3

DRV_L1-TOP_ING
INVERTER_IN PHASE L1
TP1
P+15
8

ISO1
2 + 6 R1 33
G1-T
D1 Totem R7 33
R4 3 7

P6KE18CAC250
1.8K 2 1 -

1
HCPL3120 Z1

1
1N4148 Z4
5

100µF 35V

D4 C1 15V
2 1 + TP4
R10 3
270 T1 UF4007 C4
2

6 1µF 2 E1-T
2
100µF 35V

4 2 1 D10 1N4148
C7 R13
1 +
UF4007 1K
5 D7
22

VAC4721X004
100µF 35V

C10 D13 R16


+
HF supply 1 1K
1N4148
2 1

HF supply 2 C13 E1-B


1µF
100µF 35V

P6KE18CAC250
1

Z7
+
P+15 15V TP7
DRV_L1-BOTT_ING C16
Z10
1
8

R19 D16 ISO4


2

1.8K 2 1 2 + 6 R22 33
G1-B
Totem 33
1N4148 3 7 R25
- TP10
HCPL3120
R28
5

270

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 21 of 73


3.3.2 Alcor

CS 0151 have to be tested.


The following diagram detail regards only the driver circuitry for PFC L1 , only to indicate
the part of circuit .
Obviously also PFC L2&L3 and INVERTER L1&L2&L3 driver has to be tested.

SCH.4

DRV_L1-TOP_ING
INVERTER_IN PHASE L1
TP1
P+15

8
ISO1
2 + 6 R1 10
G1-T
D1 Totem R7 10
R4 3 7

P6KE18CAC250
1.8K 2 1 -

1
HCPL3120 Z1

1
1N4148 Z4
5

100µF 35V 100µF 35V


D4 C1 15V
2 1 + TP4
R10 3
270 UF4007 C4

2
1 1µF E1-T
2

1
4 2 1 D10 1N4148
C7 R13
6 +
UF4007 1K
5 D7

T1 22
100µF 35V

VAC4721X004 C10 D13 R16


+
HF supply 1 1K
1N4148
2 1

HF supply 2 C13 E1-B


1µF
100µF 35V

P6KE18CAC250
1

Z7
P+15 DRV_L1-BOTT_ING +
15V TP7
C16
Z10
1
8

R19 D16 ISO4


2

1.8K 2 1 2 + 6 R22 10
G1-B
Totem 10
1N4148 3 7 R25
- TP10
HCPL3120
R28
5

270

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 22 of 73


3.4 CS0153 MIZAR ALCOR POWER SUPPLY BOARD LED D23
Fig. 15

F3-F4-F5

F6-F7-F8

F1-F2

This board receives power from three different redundant sources :


800Vdc Voltage coming from DC bus ,
400V ac Voltage coming from Reserve ac input
400V ac Voltage coming from Mains ac input

These voltages, rectified are applied to a flyback dc/dc insulated converter that gives
regulated dc voltages on the output to all the boards of the UPS
Each line coming in are protected with fuse on the board.

Name Description Value Note


F1-F2 Positive and Negative DC input 1A 5x20 Fig.15

F3-F4-F5 Input Mains AC L1-L2-L3 input 1A 5x20 Fig.15

F4-F5-F6 Reserve Input AC L1-L2-L3 input 1A 5x20 Fig.15

Output dc voltages status is monitored by a green Led D23 that have to be light while the
Power Supply is running

Name Description ON OFF


D23 Power Supply status P+15 Volt Output Present P+15 Volt Output not
Present

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 23 of 73


3.4.1 Check Auxiliary Power Supply Control Board

• 1-Check Input Fuse


From F1-F8
• 2-Check Input Voltage
2a-DC source Coming from DC BUS
(check between F1&F2 DC BUS Voltage ->800Vdc)
2b-AC source Coming from AC Reserve Line
(check between F3&F4 - F4&F5 - F5&F3-> 400Vac)
2c-AC source Coming from AC Mains Line
(check between F6&F7 – F7&F8 – F8&F9-> 400Vac)
• 3-Check Output Voltage
3a-DC Output 7.5Volt dc
(check between TP7&TP9 DC Voltage ->7.5Vdc)
3b--DC Output 15Volt dc
(check between TP7&TP4 DC Voltage ->15Vdc)
3c--DC Output Isolated 15Volt dc
(check between TP14&TP12 DC Voltage ->15Vdc)

-------------------------------------------------------------------------------------------------------------------
Safe-Life Battery remote UPS’s location function

During battery discharging , the battery voltage is monitored by the control board ; when
the battery voltage reaches the minimum value the inverter is stopped ;
After few minutes (If SLB function is enabled) the control board sends an off command to
the dc/dc converter that switches off itself , avoiding the deep discharge of the UPS
battery .

The dc/dc converter turns automatically on when mains or reserve ac voltages come
back present .

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 24 of 73


3.5 CS0150 CONTROL LOGIC BOARD
Refer to Electrical Diagram :DE0150

Fig. 16
SW2-Button
Up-load SW1-Button
software micro Not Used

LED BAR
UPS STATUS

LED BAR
Processor
STATUS

LED DL3-Green LED DL1-Green LED DL2-Yellow


Power Supply Power Supply +5 Power Supply +12
+12 Volt Volt Volt
Enabled Enabled Enabled

DL1= Green ON when Power supply 5Volt Volt is present


DL2= Yellow ON when Power supply 12Volt Volt is present
DL3= Green ON when Power supply 12 Volt is inside the right parameters

SW1=Push Button
SW2=Push Button
Upload STL Software Enable Function

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 25 of 73


Every control function of UPS depends by this board ,
Neither jumpers nor trimmers are employed for setting all UPS quantities on this board .
To change parameters it’s necessary to access to this board through the RS232 interface
communication board (CS0098) with a PC and follow the procedures described in
chapter 4.
No settings are needed , except when a new control board , not set in factory , has to be
placed in substitution of a faulty one.
Here is described meaning and localization of the LED present on the board

3.5.1 LED Status


On the control Logic you will find two LED BAR showing the status of the main block of
the ups.(Ref. to Fig.16 for localization)
Here you will find the meaning of each one.

The first BAR of LED L1-L6 shows the status of the Main blocks of the UPS.
The second BAR of LED M1-M4 show the status of the Microprocessor inside the control.

Name Colour Description ON OFF BLINKING

L1 Green Mains Line Status MAINS is OK Mains is not OK PFC-overload

L2 Green Battery Status Battery VOLT-OK Battery VOLT -NOK Battery-Prealarm

L3 Green Inverter Status RUNNING NOT RUNNING INV-overload

L4 Green Reserve Line Status Res. Line is OK Res. Line is not OK Phase-Rot. ERR

L5 Green PFC Status Battery-Charged PFC-NOT RUNN. Battery-In Charge

L6 Red Static Switch Status Load on Reserve Load on Inverter Load not Feed

L7 Yellow Normal Mode Synchro-OK Sync-Not Present X

L8 Green Parallel Status Master Slave X

Name Colour Description ON OFF BLINKING

M1 Yellow Micro Status_0 M1=ON M1 & M2 Alternative


M4= OFF Serial data communication
Normal Operation active

M2 Yellow Micro Status_1 M1 & M2 Alternative


Serial data communication
active

M3 Yellow Micro Status_2 M1 & M2 &M3 together


Memory Writing on course

M4 Red Micro Status_3 Waiting for Boot M1=ON Waiting for APPL.Software
Loader Software M4= OFF from EXT Serial Input
from EXT Serial Normal Operation
Input

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 26 of 73


3.5.2 Check Control Board

If at least one of the source input are available (reserve/Mains/Battery)is possible to


check the control Logic board

3.5.3 Check Power Supply Voltage

With references to electrical drawing DE 0150 check the following voltage-on the board

Name Description Test Point Value


P+15 Input Power Supply from CS0152 TP55-TP52 17.5Vdc
(15-20Vdc)

P+7.5 Input Power Supply from CS0152 TP61-TP58 7.5Vdc


(7.5-10Vdc)

P+12 Internal stabilized Power Supply TP55-TP53 12Vdc


(11.75-12.25Vdc)

P+5 Internal stabilized Power Supply TP61-TP59 5Vdc


(4.75-5.25Vdc)

P+3.3 Internal stabilized Power Supply TP61-TP63 3.3Vdc


(3.1-3.5Vdc)

P+1.5 Internal stabilized Power Supply TP61-TP64 1.5Vdc


(1.4-1.6Vdc)

N-7 Internal Power Supply TP61-TP67 -7Vdc


(-6/-10Vdc)

P+12Delay Internal Power Supply Delay TP61-TP54 12Vdc

After this control is possible to understand the status of the rest of the UPS connecting
the control board through the RS232 interface communication board with a PC and
follow the procedures described in chapter 4.

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 27 of 73


3.6 CS0152 POWER INTERFACE MIZAR BOARD
On this board are present all the electrical circuit used to adapt the level to the real used
from control, and all the actuators circuit used to drive the power parts present on UPS :

Here are described all the main component present on board:

Description Figure Ref.


17 Drawing

IGBT –L1 Input PFC 1 DE0152-Pag.2


IGBT –L2 Input PFC 2 DE0152-Pag.2
IGBT –L3 Input PFC 3 DE0152-Pag.2
IGBT –L1 Output INV 4 DE0152-Pag.2
IGBT –L2 Output INV 5 DE0152-Pag.2
IGBT –L3 Output INV 6 DE0152-Pag.2
Pre-charge Input section RELE 7 DE0152-Pag.2
SS-Switch Inverter Relay 8 DE0152-Pag.3
SS-Switch Reserve Relay 9 DE0152-Pag.3
Positive Battery Fuse Protection 10 DE0152-Pag.2
Positive DC Capacitors Fuse 11 DE0152-Pag.2
Negative DC Capacitors Fuse 12 DE0152-Pag.2
Negative Battery Fuse Protection 13 DE0152-Pag.2
Snubber Capacitors 14 DE0152-Pag.2
J4 50-pin Flat Cable Connector to Control Logic CS 0150 15 DE0152-Pag.4
J5 40-pin Flat Cable Connector to Control Logic CS 0150 16 DE0152-Pag.4
J7 20-pin Flat Cable Connector to Auxiliary Power Supply CS 0153 17 DE0152-Pag.4
CN9 2-Pin Molex Connector to Thermal Sensor “°C External Battery Box” 18 DE0152-Pag.4
CN7 2-Pin Molex Connector to Thermal Sensor “°C Internal Battery Box” 19 DE0152-Pag.4
CN6 2-Pin Molex Connector to Thermal Sensor “°C Heatsink” 20 DE0152-Pag.4
CN5 2-Pin Molex Connector “Not used” 21 DE0152-Pag.4
CN1 2-Pin Molex Connector to Over Temperature Protection 85°C 22 DE0152-Pag.4
CN10 2-Pin Molex Connector to “AUX Contact MANUAL BYPASS” 23 DE0152-Pag.2
CN11 2-Pin Molex Connector “Not used” 24 DE0152-Pag.2
CN2 5-Pin Molex Connector “Mains line to CS 0153” 25 DE0152-Pag.2
CN3 4-Pin Molex Connector “Feedback DC-BUS Voltage” 26 DE0152-Pag.2
CN4 5-Pin Molex Connector “Reserve line to CS 0153” 27 DE0152-Pag.3
F42 1A 250V Fuse protection for Fan 28 DE0152-Pag.2

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 28 of 73


MIZAR Interface Board Component Layout
Refer to Electrical Diagram :DE0152

Fig.17

18 19 20 21 22
10 11

28

15 16 1 4

8
23
24 2 14 5

17
3 6

7 12 13 9

25 26
27

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 29 of 73


3.7 CS0151 POWER INTERFACE ALCOR BOARD

On this board are present all the electrical circuit used to adapt the level to the real used
from control, and all the actuators circuit used to drive the power parts present on UPS :

Here are described all the main component present on board:

Description Figure Ref.


18 Drawing

IGBT – Input PFC 1 DE0151-Pag.1


IGBT – Output INV 2 DE0151-Pag.1
Pre-charge Input section SCR 3 DE0151-Pag.2
SS-Switch Inverter SCR 4 DE0151-Pag.2
SS-Switch Reserve SCR 5 DE0151-Pag.2
J1 50-pin Flat Cable Connector to Control Logic CS 0150 6 DE0151-Pag.6
J4 40-pin Flat Cable Connector to Control Logic CS 0150 7 DE0151-Pag.6
J2 14-pin Flat Cable Connector to Control Logic CS 0150 8 DE0151-Pag.6
J3 20-pin Flat Cable Connector to Auxiliary Power Supply CS 0153 9 DE0151-Pag.6
CN11 2-Pin Molex Connector to Thermal Sensor “°C External Battery Box” 10 DE0151-Pag.6
CN9 2-Pin Molex Connector to Thermal Sensor “°C Internal Battery Box” 11 DE0151-Pag.6
CN8 2-Pin Molex Connector “Not used” 12 DE0151-Pag.6
CN7 2-Pin Molex Connector “Not used” 13 DE0151-Pag.6
CN6 2-Pin Molex Connector “Not used” 14 DE0151-Pag.6
CN5 2-Pin Molex Connector “Not used” 15 DE0151-Pag.4
CN4 2-Pin Molex Connector to “AUX Contact MANUAL BYPASS” 16 DE0151-Pag.4
CN1 4-Pin Molex Connector “Feedback DC-BUS Voltage” 17 DE0151-Pag.2
CN12 2-Pin Molex Connector “Second Speed Fan to CS 0114” 18 DE0151-Pag.4
CN2 5-Pin Molex Connector “Mains line to CS 0153” 19 DE0151-Pag.2
CN3 5-Pin Molex Connector “Reserve line to CS 0153” 20 DE0151-Pag.4

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 30 of 73


ALCOR Interface Board Component Layout
Refer to Electrical Diagram :DE0151

Fig.18

10 11 12 13 14

15 16

2 17
8
6
7
4

18

9
3 1
5
19

20

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 31 of 73


4 PC BASED CHECKS AND SETTINGS
As the UPS is equipped with LCD panel, most of basic operations can be done by the
user without using additional tools. Although, for the convenience and time save while
executing more complicated operations, the UPS logic control can be accessed also by
PC with dedicated POWERTRONIX UPS Maintenance UCT program.
This program is also the only way to modify some UPS parameters which are not
accessible through LCD panel.
Necessary things: PC with program installed, serial communication cable DB9-DB9 and
RS232 / Relay board CS0098 (standard on-board).

Below there is a short description of the program and its possibilities.

Few seconds after start, the program will be ready to use. The initial screen is similar to
the following picture:

As there is no standard way of using the program, the informations below contain just the
description of major functions. The user decides, which of them wants to use.
In most of cases it will be necessary to start the transmission between UPS and
computer. To do this, the user must define the serial port number and transmission

speed (usually 2400 bps),

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 32 of 73


and click on OK button. After this, program sends control data string to the UPS,
expecting correct response.
This process will be initiated automatically before any try of interaction between PC and
UPS, or can be involved manually by the user (menu Options > Communication mode).
Program remembers parameters (port number, speed, etc.) of last successful
transmission and uses them later as default settings.

Below there is description of main program functions.


Attention: all further explanations refers to the Alcor/Mizar and R&D user access level.
Depending on the program version (R&D, service, user) some functions may be hidden
or disabled.

1. UPS identification button

Opens window containing UPS identification informations (model name, serial


number, firmware version, test date and service contact details). User can read all
the informations from the UPS or the backup file, modify them (except firmware
version) and write back to the UPS.

1
press

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 33 of 73


2. UPS configuration button

Opens window containing three tabs as described below:

• Main configuration tab

2
press

This tab contains essential UPS parameters: parallel mode and batteries
settings, output parameters (frequency, number of phases), and others.

• Nominal values tab

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 34 of 73


"Nominal values" tab gives an access to some nominal UPS numeric
settings: output power and voltage, number of phases, battery parameters,
power factor and input/output frequencies.

• UPS Real Time Clock tab

This tab lets to control and change UPS internal clock and calendar
settings. The "Update from system" button serves for copying actual
computer time and date to the form.

With any tab, the user can read the informations from the UPS or from the file,
modify them and write back to the UPS.
The program operates (read / write operations) on the parameters which are
present on visible tab only.

3. UPS status and meters button

This button opens the window containing four different tabs, as described below.
All of them (except of the last one called "UDBS Obj.history") use the Idle read
mode to present actual UPS state and meters.
It means that the content of the "UPS status and meters" window is valid only when
the "Idle read" control is activated (green colour).

Otherwise, all the values in the window are not updated and becomes grey to
indicate inactive state.
Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 35 of 73


• Main screen tab

3
press

This tab presents the mimic screen with the simplified diagram of the UPS
and 5 sections with values of measures. When the Idle read mode is active,
all the tab content is refreshed every second.

• UDBS object 2 to 9 tab

This tab gives an access to several informations available in UDBS


protocol. The user can choose from 1 to 6 different parameters from the
lists and watch them simultaneously. When the Idle read mode is active, all
the tab content is refreshed every second.
Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 36 of 73


• UDBS object 10 tab

With this tab user can observe several important internal UPS signals. It
can be useful in the case of UPS malfunction, servicing or maintenance.
As for the previous tabs, also this tab content is refreshed every second if
the Idle read mode is activated.

• UDBS object history tab

Using this tab user can download event log content from the UPS. Updated
log can be also saved to the file (button "Save to file" or File > Save UPS

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 37 of 73


history menu option). Unlikely to previous tabs, this one does not use Idle
read mode.

4. Commands and update button


This button opens the window containing two tabs, as described below.
• UPS commands tab

4
press

This tab contains several UPS commands, which can be useful while UPS
service or maintenance. To send the command to the UPS, the user should
choose the command and click "Execute command".
• Software updates tab

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 38 of 73


"Software updates" tab allows changing the UPS firmware and/or LCD
panel language file, depending on the selected radio button. After clicking
on the "Open file" button, the user chooses the right update file, and the
program controls its content. If the file content is correct, the "Send update
to UPS" button will be enabled and ready to use.

5. Power/voltage button

This button opens the window with three tabs, containing important internal
numeric values of the UPS. Normally all the values are set correctly in the factory

5
press

and there is no need to modify them.

6. UPS setup button

This button opens "UPS setup" window, which contains some of the power/voltage
UPS values, used while performing unit setup process in the factory.

Except of the functions described above, the program allows creating the UPS backup
file (File > Save UPS backup option), saving Program Event Log, UPS History Log,
changing the interface language, supervising the transmission, etc.

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 39 of 73


5 ELECTRICAL DIAGRAM
5.1 PCB electrical diagram index
- DE1111 UPS general diagram Mizar
- DE1112 UPS general diagram Alcor
- DE0098 Relay & Communication Board
- DE0138 Temperature sensor PCB
- DE0143 Battery Fuse PCB gap18mm
- DE0150 Control Logic
- DE0151 Inverter Driver & Feedback Alcor
- DE0152 Inverter Driver & Feedback Mizar
- DE0153 Power Supply Board
- DE0154 H-F Filter Mizar
- DE0155 LCD Mimic Display
- DE0157 Battery Fuse PCB gap22mm
- DE0161 H-F Filter Alcor
- DE1235 Battery String

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 40 of 73


Page. 41 of 73
L1-BYPASS 39 20 19 38
L2-BYPASS 39 22 21 38
L3-BYPASS 39 24 23 38
36 35 40
0SDE0154/B 41
EMC FILTER
NEU TR AL B AR C M 1294
RESERVE

45 8 7 7
L1 M8 PW6 To DC filter page 2 | NEUTRAL BAR
46 10 9 8
L2 M7 PW7
47 12 11 9 22 30
L3 M6 PW8
I1 C7
N M8 PW9 Rotary Switch
57
INPUT SECTION
PW29 NEUTRAL BAR
10µF / 400-450V
18
18 18 C8
CM1293

0SDE0154/A I1
EMC FILTER Rotary Switch C4 C5 C6

Powertronix spa reserves the right to modify this document without notice
40 - p1, 41 - p2

10µF / 400-450V 10µF / 400-450V 10µF / 400-450V 10µF / 400-450V


UPS INPUT

51 2 1 3 18
L1 M4 PW2 L1 L2 L3 C9
52 4 3 4

R&D – TECHNICAL SPECIFICATION DT0424-E01


L2 M1 PW3
53 6 5 5 19 DSM191 20 DSM191 21 DSM191 29 28 27 10µF / 400-450V
L3 M2 PW4
N M3 PW5 PW16
15
FS38

FS39

FS40

FS48

FS50

FS34
FS38

FS36
CN10[1..2]
FS8

FS2

FS3

FS4
FS49

FS35
FS39

FS40
FS9

FS7

FS1

FS6

FS5
PW58 PW1 FS45
FS37
16
FS32 I1 0SDE0154/D
UPS_GND FS47 Rotary Switch EMC FILTER

UPS OUTPUT
0SDE0154/C 11 13 14 48
EXT BATTERY

EMC FILTER GND UPS FS29 PW13 M12 L1


12 15 16 49
FS30 PW14 M13 L2
13 17 18 50
COM M11 PW12 FS31 PW15 M14 L3
0SDE0152
UPS general diagram Mizar

M9 PW10 CN9[1..2] PW5, PW9, PW12 PW16 M15 N


CN5[1..2]
Power Board and Feedback CN6[1..2] CM1293
M11 PW11
1 0SDE162 PW17 PW59
2 Module Temp
CN7[1..2]
1 0SDE162
37 - B ATTERY 2 Internal Battery Temp
FS11 CN8[1..2]
UPS_GND
R2 R1
44 43 36 35 33 + B ATTERY 1 0SDE162
55 54 FS10 2 External Battery Temp
PRCH Resitor 50W PRCH Resitor 50W
15 - p1, 16 - p2 ST1
31

39

37

25
CN1[1..2]

J5[1..40]
85°C

J7[1..20]

J4[1..50]
I1 I1 I1 I1 15

FS16

FS28

FS22
FS43
FS44

FS20

FS25

FS21

FS24

FS27

FS23

FS26

FS42

FS51

FS41
CN4
CN2
CN3
Rotary Switch Rotary Switch Rotary Switch Rotary Switch C°
(Batt 2-) (Prech Neg) (Prech Pos) (Batt 1+) 16
32

40

38

26
18 19 20
56 34 DSM191 23 DSM191 24 DSM191 25 CN10
I1 1 1 NEUTRAL FAN
Rotary Switch 2 2 AUX FAN
L4 L5 L6 3 3 PHASE FAN
33 34 4 4
C3 C2 C1
20µF / 400-450V 20µF / 400-450V 20µF / 400-450V 17 MATLOK VT1
I1 I1 0CEVTM2204P16W
Rotary Switch Rotary Switch
(Batt 1-) (Batt 2+) 18 18
27 28 29 30
0SDE0098
INVERTER OUT SECTION

J5[1..40]

J4[1..50]
J2[1..20] J2[1..20] RELAY BOARD
1 2 3 4 5 6 7 8 9 10
58 17 31 26
P7 P8 P9 P10 P11 P12
1
2

1
2

1
2

1
2

1
2

1
2
SNMP
P1 P2 P3 P4 P5 P6 J3[1..26] J3[1..26]
0SDE0150
1
2

1
2

1
2

1
2

1
2

1
2
CONTROL LOGIC&SIGNALLING
5.1.1 DE1111

NEUT R AL B AR CM 1294
0SDE0155
J1[1..26] J1[1..26] LCD BOARD

+
-

-
-
Battery Bank_1

Battery Bank_2

Battery Bank_3

Battery Bank_4

Battery Bank_5

Battery Bank_6
10x7Ah

10x7Ah

10x7Ah

10x7Ah

10x7Ah

10x7Ah
CN3
CN2 0SDE0153
CN4 AUX CONVERTER
J7[1..20]
3°Floor 2°Floor 1°Floor
Page. 42 of 73
CM1173
COMMON_NEUTRAL BAR
CM1180
+ CE3 + CE1
4400µF 4400µF
450V 450V 31 15
1
30
CM1181 L1 - RES L2 - RES L3 - RES N - RES
17 FS40 FS39 FS38 FS37
+DC NEUTRAL N - RES
FS14 FS16 FS45
C9 L1
10µF 400-450V FS36
27
0SDE0152\A 0SDE0152\B 0SDE0152\C

Powertronix spa reserves the right to modify this document without notice
PRECHARGE PFC AND 18
C8 L2
S.SWITCH
SECTION INVERTER 10µF 400-450V FS35 SECTION
+ BAT

R&D – TECHNICAL SPECIFICATION DT0424-E01


FS10 F2 F3 SECTION 28
2 4 2 4
1 3 1 3 9
N - IN N 18 6
FS43 FS44 32A 10x38 32A 10x38 C7 L3
10µF 400-450V FS34
8
29 5
Q1 Q4

13
12

12
13
7
L1 - IN L1 L1 L1 L1 L4 L1 4 L1-OUT
FS7 R63 FS1 FS6 27 28 28 27 FS20 FS25 FS29
24 24
H1 23 23 H4 H8
56R 10W DSM191 1 1 DSM191 K5
2 Q2 2 Q5

13
12

12
13
L2 - IN L2 L2 L2 L2 L5 L2 L2-OUT

6
5

5
6
FS8 FS2 FS5 27 28 28 27 FS21 FS24 FS30

2
1
R64
24 24
H2 23 23 H5 H9
56R 10W DSM191 1 1 DSM191
2 Q3 2 Q6

13
12

12
13
L3 - IN L3 L3 L3 L3 L6 L3 9 L3-OUT

6
5

5
6
FS9 R65 FS3 FS4 27 28 28 27 FS22 FS23 6 FS31
24 24
H3 23 23 H6 H10
56R 10W DSM191 1 1 DSM191 8
2 2 5
9 L3-OUT

6
5

5
6
C4 L1 6 C3 L1 7 FS47
10µF 400-450V FS48 20µF 400-450V FS28 4
735-3A-C-T SONG CHUAN

Q1..Q3: SK60GB128 Q4..Q6: SK60GB128


19 8 23
5 - BAT F1 F4
FS11 1 3 1 3 K4
18 2 4 2 4 18
C5 L2 7 C2 L2
10µF 400-450V FS49 4 32A 10x38 32A 10x38 20µF 400-450V FS27

1
2
20 24
K4, K5:
18 18 735-3A-C-T SONG CHUAN
C6 L3 C1 L3
10µF 400-450V FS50 K1 20µF 400-450V FS26
2
1
21 25
-DC N
FS15 FS32
26
CM1180
2
16
+ CE4 + CE2
4400µF 4400µF
450V 450V
CM1181
22
COMMON_NEUTRAL BAR
CM1173
Page. 43 of 73
I1
Rotary Switch
10 L1-BYPASS 19 20 13
11 L2-BYPASS 21 22 14
12 L3-BYPASS 23 24 15
35 36 36
0SDE0161/B 35 N EU TR A L B A R C M 1294
EMC FILTER
To DC filter page 2 NEUTRAL BAR
RESERVE

29 8 7 4
L1 M8 PW6
30 10 9 5 NEUTRAL FAN
L2 M7 PW7
31 12 11 6 PHASE FAN
L3 M6 PW8
43 45 44 41 AUX FAN 12
N M5 PW9
37 VT1
PW29 NEUTRAL BAR
C7 0CEVTM2204P16W
INPUT SECTION
CM1293

Powertronix spa reserves the right to modify this document without notice
0SDE0161/A I1 10µF 400-450V
EMC FILTER Rotary Switch 39 39 40 39
C8

FS5

FS4

FS2

FS1
26 2 1 1
UPS INPUT

R&D – TECHNICAL SPECIFICATION DT0424-E01


L1 M1 PW2 C4 C5 C6
27 4 3 2 10µF 400-450V 10µF 400-450V 10µF 400-450V 10µF 400-450V 10
L2 M2 PW3 FS7
35 - p1, 36 - p2

39
28 6 5 3 L1 L2 L3 C9 9
L3 M3 PW4 FS6
0SDE0114
N M4 PW5 PW16 FS3 FAN BOARD
DSM192 DSM192 DSM192 10µF 400-450V
46 47 48 51 50 49

9 - p1, 10 - p2
PW58 PW1 NC
PW5

PW4

PW7

PW8

PW9

FS11

FS12

FS10

FS13

FS14

FS15
PW23

PW22

PW21

FS1

PW25

FS2

PW26

FS3

PW27
CN4[1..2]

FS9
PW6

UPS_GND
11
0SDE0161/C
EXT BATTERY

EMC FILTER GND UPS


CN12[1..2] I1 0SDE0161/D
Rotary Switch EMC FILTER
UPS general diagram Alcor

UPS OUTPUT
COM M11 PW12 7 13 14 32
PW14 PW13 M12 L1
+ M9 PW10 8 15 16 33
PW15 PW14 M13 L2
- M10 PW11 0SDE0151
PW16
9 17 18 34
PW15 M14 L3
Power Board and Feedback
PW5, PW9, PW12 PW16 M15 N
C M1293
20 - BATTERY CN5[1..2] NC
PW12 PW17 PW59
CN7[1..2] NC
R2 R1
21 22 18 17 16 + BATTERY CN8[1..2] NC
PW1
PRCH Resitor 50W PRCH Resitor 50W
CN9[1..2]
31

39

37

I1 I1 I1 1 0SDE0162

IGBT Q2 PIN5

IGBT Q2 PIN4

IGBT Q2 PIN3
2 Cabinet Temp. UPS_GND
Rotary Switch Rotary Switch Rotary Switch

25
(Batt 2-) (Prech Neg) (Batt 1+) (Prech Pos) CN11[1..2]

J2[1..14]
J3[1..20]

J4[1..40]

J1[1..50]
I1
1 0SDE0162
32

40

38

PW18

PW19

PW20
Rotary Switch

CN3

CN2

CN1
2 External Battery Temp.

FS4

FS5

FS6
13 - p1, 14 - p2
23 19 CN6[1..2]

26
13
25 24 ST1

4 - p1, 5 - p3, 6 - p5

1 - p1, 2 - p3, 3 - p5
14

7 - p1, 8 - p4
L4 52 L5 53 L6 54 C°
85°C
DSM192 DSM192 DSM192
27 28 29 30
I1 I1 33 34 38 0SDE0155

J5[1..40]

J4[1..50]

J6[1..14]
Rotary Switch Rotary Switch C1 C2 C3 J1[1..26] J1[1..26]
LCD BOARD
(Batt 1-) (Batt 2+) I1 40µF 400-450V 40µF 400-450V 40µF 400-450V
1 2 3 4 5 6 7 8 9 10 Rotary Switch
42 39 39 0SDE0098
1
2

1
2

1
2

1
2

1
2

1
2
P7 P8 P9 P10 P11 P12 J2[1..20] J2[1..20]
RELAY BOARD
0SDE0150
P1 P2 P3 P4 P5 P6 INVERTER OUT SECTION CONTROL LOGIC & SIGNALLING
1
2

1
2

1
2

1
2

1
2

1
2
SNMP
5.1.2 DE1112

J3[1..26] J3[1..26]
+

+
-

-
CN3

I553981

I553993

I553973

I553985

I553977

I553989
CN2

10x7Ah

10x7Ah

10x7Ah

10x7Ah

10x7Ah

10x7Ah
0SDE0153
N EU T R A L B A R C M 1294 AUX CONVERTER
CN4
J7[1..20]
3°Floor 2°Floor 1°Floor
Page. 44 of 73
09_A-MAINS_L1

11_A-MAINS_L3
10_A-MAINS_L2

+DC_VOLT
R64
150k / 0.25W
Inverter IN Inverter OUT
+DC_VOLT
DC_Cor_L1
R65
150k / 0.25W
DC_Cor_L2
FS1
DC_Cor_L3
Q1

G6-T
G1-T

G2-T

G5-T
E1-T

E2-T

E5-T

E6-T
C98 C100 C99 SEMiX201GD128Ds Q1_POS R66
AC INPUT 150k / 0.25W Q2_POS 3 = L1
FS2 3 = L1 R67 4 = L2
+

CAPACITORS

INDUCTORS L4, L5, L6


100uF 100uF 100 uF 4 = L2 16_+DC-BUS 5 = L3
C4, C5, C6 5 = L3

12
13

13
12
8
9

9
8
6.8k
FS3 R62 R63 R61
22k / 0.25W 22k / 0.25W 22k / 0.25W
16 16
G3-T G4-T
3 17 4 17 3
A-MAINS_POS E3-T E4-T
4 TO AU X 3 4
5 C ON VER TER 2 5
A-MAINS_NEG
C S0153 1

Powertronix spa reserves the right to modify this document without notice
14 14
G3-B G4-B
C39 C40 C41 15 CN1 15
SCR_L1-IN
SCR_L2-IN
SCR_L3-IN

E3-B E4-B
DC BUS

R&D – TECHNICAL SPECIFICATION DT0424-E01


S1 0.1µF 0.1µF 0.1µF R68

20

19

11
10

10
11

19

20
SCR SKUT85

7
6

6
7
16_-DC-BUS
P+5
INDUCTORS L1, L2, L3
7

1
2
3

G1-B
E1-B

E2-B
G2-B
6.8k
PRCH-G1_POS

G5-B
E5-B

G6-B
E6-B
L1 L1 L1 P+5 Q1_NEG R71 Q2_NEG
PRCH-G1_NEG
4 1 4 5 150k / 0.25W
PW4 PW7 PW25
SCR_L1-OUT
10 H1 Q2
1
2
3
12 ACS754 SEMiX201GD128Ds
PRCH-G2_POS
INPUT

L2 L2 L2 R211 R70
5 2 PRCH-G2_NEG 4 5 150k / 0.25W
28_PFC_TEMP 27_INVERTER_TEMP
PW5 PW8 PW26 - DC_VOLT
SCR_L2-OUT
13 H2 10 R212 10

1
2
3
14 ACS754 R210 R213
PRCH-G3_POS
L3 L3 L3 5k R69 5k
6 3 PRCH-G3_NEG 4 5 150k / 0.25W
PW6 PW9 PW27
SCR_L3-OUT H3
ACS754
11

- DC_VOLT
R78
A-BATT_POS +DC_VOLT
H4

LEM DI BATTERIA
C43 10 / 5W
0.1µF MABA01 C103
1 47nF
R79 PW1 R72 P+5 P+5
2 A-BATT_NEG
+ BATTERY 100k
C44 10 / 5W 3
0.1µF MABA01 C104 R76
PW12 4 4.7nF R74 DC_Cor_L1
R81 - BATTERY C105 100k
5 47nF R75 D67 10k
17_A-BATTERY
150k 1N4148
C45 10 / 5W 6 R73
0.1µF MABA01 10 / 0.25W R77
HAIS 50-P 100k R80
DC_Cor_L2
10k
R87 R88 R89 R82
P+15 100k
06_V-MAINS_L1
+ D68
27k / 0.25W 27k / 0.25W 27k / 0.25W 1N4148 R83
HF supply 1 TO PAGE 1
R85 C46 DC_Cor_L3
100 Q3 P+15 R84 10µF 16V

2
R91 R92 R93 IRFD110 1 100k 10k
DRIVERS SUPPLY
07_V-MAINS_L2 U1 3 R90 3
27k / 0.25W 27k / 0.25W 27k / 0.25W 13 16 2.2 / 5W
C48 + 15 VC VREF 2 C47 6 R86

4
10µF VCC +V R94 1000pF 2 100k
R96 R97 R98 9 47 5 T7
1 COMP 1
08_V-MAINS_L3 -V
VAC4097X055
12 14 C50
27k / 0.25W 27k / 0.25W 27k / 0.25W GND OUTB 100µF/35V + 4 -DC_VOLT
5 R95
6 CT 1k
7 RT
DISC 11
CN2 R99 47 OUTA
3 4
SY NC OSC HF supply 2 TO PAGE 1
8 10 R100
TO AU X CSS SD
C49 R101 47

2
C ON VER TER 5.6k 1
C S0153 SG3525
1nF + C51
3
INPUT MAINS 10µF Q4
IRFD110

4
Page. 45 of 73
UPS OUTPUT
PW14 PW15 PW16
L1-OUT L2-OUT L3-OUT
03_A-INV_L1

04_A-INV_L2

05_A-INV_L3

00_V-INV_L1

01_V-INV_L2

02_V-INV_L3

R156 R147 R148 R149 TO FAN


12_V-OUT_L1 VOUT_L1_FAN SUPPLY
R132 R133 R134 R129 R130 R131 C73 10 / 5W 27k / 0.25W 27k / 0.25W 27k / 0.25W CIRCUIT
10 / 0.25W 10 / 0.25W 10 / 0.25W 27k / 0.25W 27k / 0.25W 27k / 0.25W 0.1µF MABA01
R155 R141 R142 R143
14_V-OUT_L3
A-INV_POS
R135 R136 R137 C69 10 / 5W 27k / 0.25W 27k / 0.25W 27k / 0.25W
27k / 0.25W 27k / 0.25W 27k / 0.25W 0.1µF MABA01
C64 C65 C66
0.1µF 0.1µF 0.1µF R151 R144 R145 R146
A-INV_NEG 13_V-OUT_L2
R138 R139 R140 C67 10 / 5W 27k / 0.25W 27k / 0.25W 27k / 0.25W
27k / 0.25W 27k / 0.25W 27k / 0.25W 0.1µF MABA01

Powertronix spa reserves the right to modify this document without notice
11
3
2
1

H5
FROM INDUCTORS

ACS754
G-POS_3
PW20 4 5 3 6

21_A-OUT_L1

23_A-OUT_L3
22_A-OUT_L2
L3

R&D – TECHNICAL SPECIFICATION DT0424-E01


G-NEG_3
14
K-NEG_3 K-POS_3
3
2
1

H6 13
ACS754
G-POS_2
PW19 4 5 2 5
L2
G-NEG_2
12
K-NEG_2 K-POS_2
3
2
1

H7 10
ACS754
G-POS_1
PW18 4 5 1 4
L1
G-NEG_1
R152 R153 R154
K-NEG_1 K-POS_1 10 / 0.25W 10 / 0.25W 10 / 0.25W

7
S2
SCR SKUT85
A-OUT_NEG
FS4 FS5 FS6 C70 C71 C72
L1 L2 L3 0.1µF 0.1µF 0.1µF
A-OUT_POS

1
2
3
C1 C2 C3
TO AC CAPACITORS 4 5
H8

1
2
3
ACS754
4 5
H9

1
2
3
ACS754
TO AC CAPACITORS C74 R157 4 5
C7 C8 C9 H10
0.1µF MABA01 10 / 5W ACS754
FS15 FS14 FS13
C75 R158
TO AU X 0.1µF MABA01 10 / 5W
C ON VER TER
C S0153
C76 R159
CN3 P+15
INPUT RESERVE
0.1µF MABA01 10 / 5W
N.O.
K8
R209

7
47 / 1W CN12
INPUT RESERVE

G-POS_6 TO FAN
PW21 4 1
L1-RES BOARD
G-NEG_6
10 Max_Speed
K-NEG_6 K-POS_6
12

1
G-POS_5
PW22 5 2 D69
L2-RES 1N4007
G-NEG_5
13
K-NEG_5 K-POS_5
14

2
G-POS_4
PW23 6 3
FAST-SPEED
L3-RES
G-NEG_4
K-NEG_4 K-POS_4

11
S3
R160 R161 R162 R163 SCR SKUT85
270k / 0.25W 27k / 0.25W 27k / 0.25W 27k / 0.25W
TP33
CN4
TO
AUX_BY -PASS_ON
ROTARY
R164 R165 R166 R167 SWITCH
270k / 0.25W 27k / 0.25W 27k / 0.25W 27k / 0.25W BY -PASS ON
TO NEUTRAL BAR
FS9 FS11 FS12 FS10
R168 R169 R170 R171 TP34
270k / 0.25W 27k / 0.25W 27k / 0.25W 27k / 0.25W
CN5
SPARE_2
SPARE_2

SIG_SYNCRO

18_V-RES_L1

19_V-RES_L2

20_V-RES_L3
P+15

Page. 46 of 73
R16
2.2K EPO
IC3 4N35 CN1
5 1
2
4 2 JP1

6
1
0.1nF C8 R17
470K R15
50V 1K
Z4
TP1 C9
P+15 D10 12V
1µF
TRANSFORMER FLAT 2+2
1 T1 7 1N4148
R1 100 Z1 9 Turns 5 Turns
D1
Coil Coil
47V 2 8 SER-12V
3 5
1N4148 Q1 R2 100 1 Turn 10 Turns
Coil Coil

Powertronix spa reserves the right to modify this document without notice
4 6 C1 Z2 TP2
+ C2 2N2222 D3 R3
10µF 1.2K 1µF 12V
1N4148

R&D – TECHNICAL SPECIFICATION DT0424-E01


D4 D2
C4 R4 1N4148 C3 Z3
1µF 22 1N4148 C5
TP3 1µF 1µF 12V
CN2
SER+12V
TP4
1 IC1 4N35 R6 CN3
2 1 5 2.7K 1
3 6
4
Relay & Communication Board

EPOA R5 1K 2 4 2
5 EPOB 7
6 3

6
7 8
8 R7 4
9 C6 9
10 470K 5
11 P+15
50V 0.1nF
12
13 DB9-FEMALE
14
15 P+15
16
17
18
19 R8 TP5
20 10K
CON20 IC2 4N35
5 1
4 2 R9 1K
D5

6
P+15 P+15 P+15 P+15 1N4148
LOAD ON INVERTER C7 1nF
LOW A/C FAILURE AUTOMATIC BY -PASS ON R10
BATTERY 470K 50V
R11 D6 K1 R12 D7 K2 R13 D8 K3 R14 D9 K4
100 4007 100 4007 100 4007 100 4007
2 2 2 2
1 1 1 1
3 3 3 3
4 4 4 4
5 5 5 5
12V-12A 12V-12A 12V-12A 12V-12A
1
2
3
4
5.1.3 DE0098

5
6
7
8
9
10
11
12
M1
5.1.4 DE0138 Temperature sensor PCB

U1
RESISTOR TABLE
R4 R1 LM334M
R1 R4
1 8
4.7 ohm 18 ohm 10µA\°K ALCOR\MIZAR 0SDE0162
2 7

3 6

4 5
C1
1uF 25V
2
1

J1

5.1.5 DE0143 Battery Fuse PCB (Battery 7.2-9Ah) / DE0157 Battery Fuse PCB
(Battery 4.5-5.2Ah)

FS1 FS2
FASTON-F FASTON-F

FS3 FS4
FASTON-F FASTON-F

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 47 of 73


From Cyclone

Page. 48 of 73
P+3.3 P+5
DEBUG_LED4
DEBUG_LED3
DEBUG_LED2
DEBUG_LED1
UPS-LD8
UPS-LD7
UPS-LD6
UPS-LD5
UPS-LD4
UPS-LD3
UPS-LD2
UPS-LD1

UPS-STATUS LED DEBUG/STATUS LED


2

2
L1 L2 L3 L4 L5 L6 L7 L8 M1 M2 M3 M4
Green Green Green Green Green Red Y ellow Green Y ellow Y ellow Y ellow Red
1

1
1
2
3
4

1
2
3
4

1
2
3
4

RP1 RP2 RP3


470 470 470
4
3
2
1

4
3
2
1

4
3
2
1
RP4 RP5 RP6
8
7
6
5

8
7
6
5

8
7
6
5

470 470 470


9

U15A
5
6
7
8

5
6
7
8

5
6
7
8
1 16
ULN2003A
U15B
8

2 15

Powertronix spa reserves the right to modify this document without notice
U15C ULN2003A

R&D – TECHNICAL SPECIFICATION DT0424-E01


3 14
U15D
ULN2003A
4 13
U15E
ULN2003A
5 12
U15F
ULN2003A
6 11
U15G
ULN2003A
7 10
ULN2003A

9
U16A
1 16
ULN2003A
Control Logic

U16B

8
2 15
ULN2003A
U16C
3 14
ULN2003A U16D
4 13
U16E
ULN2003A
5 12
ON OFF BLINK
ULN2003A
LD1 = MAINS STATUS OK NOK X
5.1.6 DE0150

LD2 = BATTERY STATUS BATTERY OK BATT. DISCHARGE BATT. PREALARM


LD3 = INVERTER STATUS RUN OFF INV.OVERLOAD
LD4 = RES.LINE STATUS OK NOK PHASE ROTATION
LD5 = BATTERY CHARGER BATT. FULL B.CH OFF FLOAT CHARGE
LD6 = STATIC-SW STATUS LOAD ON RES LOAD ON INV LOAD NOT FEED
LD7 = PARALLEL STATUS MASTER \ SLAVE \ RX-. ALL \
NORMAL MODE SYNCRO OK SYNCRO NOK X
LD8 = TEST TEST MODE X PC COMM.
Page. 49 of 73
INVERTER_ON
Synchro-Front

ENA _DC/DC
SPARE_ULN

MAINS_NOK
BYPASS_ON
85TMP_ALL

EPO_LOCAL
BY-PASS_ON
SPARE_1

BATT_LOW
CL_RESET

FAST-FAN

P+3.3 P+3.3 P+3.3


To From
EPO-REM
SPARE_2

PIO_0

Cyclone Cyclone
1
2
3
4

1
2
3
4

1
2
3
4
RP7 RP8 RP9
10K 470 470
TP1
14

U17A
8
7
6
5

8
7
6
5

8
7
6
5
R1
OVER-85TMP_ALL 1 2
1M
C1
TP2
1µF
14 7

9
TP3 U19A
U17B
1 16
R2 REM_MAINS_NOK
CONTACT_SPARE_1 3 4
ULN2003A
1M
C2
TP4

8
1µF
14 7

TP5 U19B

Powertronix spa reserves the right to modify this document without notice
U17C
2 15
R3 REM_BY PASS_ON
5 6
AUX_BY-PASS_ON
ULN2003A

R&D – TECHNICAL SPECIFICATION DT0424-E01


100K
C3
TP6
1µF
14 7

TP7 U19C
U17D
3 14
R4 REM_INVERTER_ON
CONTACT_SPARE_2 9 8
ULN2003A
100K
C4
1µF TP8
14 7

TP9
VL1-Reserv e Line U17E U19D
R5 100K
Sy ncro 11 10 4 13
REM_BATT_LOW
C5 ULN2003A
P+3.3
1nF
7

TP10
C6
U19E
14

U17F 0.1µF
R6 1M 5 12
ENABLE _DC/DC
CN_EPO-REM 13 12
ULN2003A
R166
P+3.3 C7 R7 1K
TP11
7
1µF 1M
U19F
1
2
3
4

P+3.3
RP10 6 11
FAST-SPEED
10K C8 ULN2003A
R159

14
U18A 0.1µF 1K
8
7
6
5

R8 1M TP12
1 2
CN-EPO_LOCAL
U19G
C9
7 10
1µF

7
ULN2003A

14

1
U18B
R9 DZ3
3 4
24V

2
100K WIRED-AND EPO SIGNALS

7
C10 RELAYS COMMAND TO BOTH COMMUNICATION CARDS
SW1
RESET-CL 0.1µF

14
U18C
R10
5 6
100K

7
C11
SW2
PBswitch 0.1µF

3
Page. 50 of 73
000-SCLK_0
000-INBT_-CS_0

000-SDATA_0

000-INBT_-CS_1
000-B_MPX-0
000-C_MPX-0
000-D_MPX-0

000-B_MPX-1
000-C_MPX-1
000-D_MPX-1
000-A_MPX-0

000-A_MPX-1

000-SDATA_1

000-SCLK_1
TP13

TP14

TP15

TP16

TP17

TP18

TP19

TP20

P+5 P+5 U10 CD4504B P+3.3


U8 16 1
9 10 2 VDD VCC 13
ANALOG-00 I0 A Aout Sel
8 11 4 3
ANALOG-01 I1 B Bout Ain P+5 U12
7 14 6 5
Corrispondenza Misure ANALOG-02 I2 C Cout Bin
6 13 10 7 1 6
ANALOG-03 I3 D Dout Cin Vdd -cs
Analog-00 = V-Inv erter_L1 5 12 9
ANALOG-04 I4 Eout Din
TP21

Analog-01 = V-Inv erter_L2 4 15 15 11 C12 R11


ANALOG-05 I5 INBT Fout Ein
Analog-02 = V-Inv erter_L3 3 8 14 2 5
ANALOG-06 I6 VSS Fin GND sdata
Analog-03 = V-Inv erter_L1 2 1µF
ANALOG-07 I7 470
Analog-04 = V-Inv erter_L2 23
ANALOG-08 I8
Analog-05 = A-Inv erter_L3 22 1 3 4
ANALOG-09 I9 OUT Vin sclk
Analog-06 = V-Mains_L1 21
ANALOG-10 I10
Analog-07 = V-Mains_L2 20 24 121S101
ANALOG-11 I11 VCC
Analog-08 = V-Mains_L3 19 C13 C14 C15 R12
ANALOG-12 I12
Analog-09 = A-Mains_L1 18 12
ANALOG-13 I13 GND 2,2K
Analog-10 = A-Mains_L2 17 0,1µF 0,1µF 0,1µF
ANALOG-14 I14
Analog-11 = A-Mains_L3 16
Analog-12 = V-Out_L1 I15
Analog-13 = V-Out_L2
Analog-14 = V-Out_L3 HCF4067BM
Analog-15 = N.U.
TP22

TP23

TP24

TP25

TP26

TP27

TP28

Analog-16 = V-DC bus


Analog-17 = A-DC Battery
Analog 18 = V-Reserv e_L1
Analog-19 = V-Reserv e_L2
Analog-20 = V-Reserv e_L3
Analog-21 = A-Out_L1
TP29

TP30

TP31

TP32

TP33

TP34

TP35

TP36

Analog-22 = A-Out_L2
Analog-23 = A-Out_L3

Powertronix spa reserves the right to modify this document without notice
Analog-24 = Temp.°C-Heatsink
Analog-25 = Temp.°C-Internal Battery P+5 P+5 U11 CD4504B P+3.3
Analog-26 = Temp.°C-External Battery U9 16 1
Analog-27 = Temp.°C-Inv erter IGBT 9 10 2 VDD VCC 13
ANALOG-16 I0 A Aout Sel
Analog-28 = Temp.°C- PFC IGBT 8 11 4 3
ANALOG-17 I1 B Bout Ain P+5 U13

R&D – TECHNICAL SPECIFICATION DT0424-E01


Analog-29 = N.U. 7 14 6 5
ANALOG-18 I2 C Cout Bin
Analog-30 = N.U. 6 13 10 7 1 6
ANALOG-19 I3 D Dout Cin Vdd -cs
Analog-31 = N.U. 5 12 9
ANALOG-20 I4 Eout Din

TP37
4 15 15 11 C16 R13
ANALOG-21 I5 INBT Fout Ein
3 8 14 2 5
ANALOG-22 I6 VSS Fin GND sdata
2 1µF
ANALOG-23 I7 470
23
ANALOG-24 I8
22 1 3 4
ANALOG-25 I9 OUT Vin sclk
21
ANALOG-26 I10
20 24 121S101
ANALOG-27 I11 VCC
19 C17 C18 C19 R14
ANALOG-28 I12
18 12
17 I13 GND 0,1µF 0,1µF 0,1µF 2,2K
16 I14
I15
HCF4067BM
TP38

TP39

TP40

TP41

TP49

V-INVERTER
R15
00_V-INV_L1 ANALOG-00 V-MAINS V-OUTPUT V-RESERVE DC-BUS
3.3K
2

R19 R20
82K 470 D2 P+5
C20
10nF 1N4148 R16 R17 R18

1
1

06_V-MAINS_L1 ANALOG-06 12_V-OUT_L1 ANALOG-12 18_V-RES_L1 ANALOG-18


D1
P+5 P+5 1K R21 R22 1K R23 R24 1K R25 R26 V BOOST FBK
MONTATA AL MONTATA AL MONTATA AL 1N4148

4
82K 1K 82K 1K 82K 1K U14A
+ C134 C21 R167 POSTO DI D3 C22 R168 POSTO DI D4 C23 R169 POSTO DI D5 R27 22K 3

2
16_+DC-BUS +
100µF (10V) 10nF 1K 1N4148 10nF 1K 1N4148 10nF 1K 1N4148 1
16_-DC-BUS 2 ANALOG-16
-
LM324 R28 10K
P+5 REF_2.5V P+5 P+5 REF_2.5V P+5 P+5 REF_2.5V P+5 R29 22K
0.1µF

11
R32 C26 R30 C24 C25
10K
01_V-INV_L2 ANALOG-01 0.1µF
3.3K
2

R36 R37 R33 R34 R35 0.1µF


82K 470 D6 R31 10K
07_V-MAINS_L2 ANALOG-07 13_V-OUT_L2 ANALOG-13 19_V-RES_L2 ANALOG-19
C27
10nF 1N4148 1K R38 R39 1K R40 R41 1K R42 R43
82K 1K MONTATA AL 82K 1K MONTATA AL 82K 1K MONTATA AL
1

C28 R170 POSTO DI D7 C29 R171 POSTO DI D8 C30 R172 POSTO DI D9


P+5 P+5 10nF 1K 1N4148 10nF 1K 10nF 1K
1N4148 1N4148
+ C135
100µF (10V) P+5 REF_2.5V P+5 P+5 REF_2.5V P+5 P+5 REF_2.5V P+5
R44 R45 R46 R47 R48
02_V-INV_L3 ANALOG-02 08_V-MAINS_L3 ANALOG-08 14_V-OUT_L3 ANALOG-14 20_V-RES_L3 ANALOG-20 17_A-BATTERY ANALOG-17
3.3K 1K 1K 1K 1K
2

2
R49 R50 R51 R52 R53 R54 R55 R56
82K 470 D10 82K 1K MONTATA AL 82K 1K MONTATA AL 82K 1K MONTATA AL D14
C31
1N4148
C32 R173 POSTO DI C33 R174 POSTO DI C34 R175 POSTO DI C35
1N4148
10nF 10nF 1K 10nF 1K 10nF 1K 10nF
D11 1N4148 D12 1N4148 D13 1N4148
1

1
P+5 P+5 P+5 REF_2.5V P+5 P+5 REF_2.5V P+5 P+5 REF_2.5V P+5 P+5
+ C136
100µF (10V)
R57 R58 R59 R60 R61
03_A-INV_L1 ANALOG-03 09_A-MAINS_L1 ANALOG-09 21_A-OUT_L1 ANALOG-21 24_MODULE_TEMP ANALOG-24 25_INT-BATT_TEMP ANALOG-25
1K 1K 1K

2
1K Temperature 1K Temperature P+5

2
D15 D16 D17 R62 HTSK-MODULE R63 D18 Battery
C36 C37 C38 1K C39 D19 1K C40
10nF 1N4148 10nF 1N4148 10nF 1N4148 1N4148 CABINET R64
1µF 1N4148 1µF NOT MOUNTED

1
1
P+5 P+5 P+5 P+5
P+5
REF_2.5V
R66 R67 R68 R70 R65
10_A-MAINS_L2 26_EXT-BATT_TEMP ANALOG-26 0 ohm
04_A-INV_L2 ANALOG-04 ANALOG-10 22_A-OUT_L2 ANALOG-22

2
1K 1K 1K

2
D20 1K Temperature
D21 D22 R72 D24 EXT-BATTERY
C41 C42 1N4148 C43 R164 1K C45
10nF 1N4148 10nF 10nF 1N4148 1N4148

1
27_INVERTER_TEMP ANALOG-27
1µF

1
P+5 1K R69 C145 D23
P+5 P+5 10M 10nF 1N4148 Temperature P+5
IGBT Inv erter
30kVA
R73 R74 R75 P+5 f rom NTC
05_A-INV_L3 ANALOG-05 11_A-MAINS_L3 ANALOG-11 23_A-OUT_L3 ANALOG-23
1K 1K 1K

2
R165
D25 D26 D27 ANALOG-28
28_PFC_TEMP
C46 C47 C48
10nF 1N4148 10nF 1N4148 10nF 1N4148 1K R71 C146
10M D29 Temperature

1
10nF 1N4148 IGBT PFC
P+5 P+5 P+5 30kVA
P+5 f rom NTC
Input inverter (PFC) Output inverter
IGBT commands IGBT commands
P+3.3
From From P+3.3
Cyclone Cyclone

4
3
2
1
P+12_DELAY P+12_DELAY P+12_DELAY P+12_DELAY P+12_DELAY P+12_DELAY

4
3
2
1
RP13
RP14
470 C51 C52 C53 C54 C55 C56
470

L3-TOP_INV
L2-TOP_INV
L1-TOP_INV

L3-BOTT_ING
L3-TOP_ING
L2-BOTT_ING
L2-TOP_ING
L1-BOTT_ING
L1-TOP_ING
5
6
7
8
L3-BOTT_INV
L2-BOTT_INV
L1-BOTT_INV
TP75 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF

5
6
7
8
TP81

1
1
U22B U25B
R80 R81
4 T otem
5 4 T otem
5
DRV_L1-TOP_ING P+12_DELAY DRV_L1-TOP_INV
P+12_DELAY TP76
ICL7667 100 ICL7667 TP82 100

6
6

8
8
R82 R83
2 T otem
7 2 T otem
7
DRV_L1-BOTT_ING DRV_L1-BOTT_INV
TP77 U22A 100 U25A 100
ICL7667 TP83 ICL7667

1
1

3
3

U23B U26B
R84 R85
4 T otem
5 4 T otem
5
DRV_L2-TOP_ING P+12_DELAY DRV_L2-TOP_INV
P+12_DELAY TP78
ICL7667 100 ICL7667 TP84 100

6
6

U26A

8
8

R86 R87
2 T otem
7 2 T otem
7
DRV_L2-BOTT_ING DRV_L2-BOTT_INV
TP79 U23A 100 ICL7667 100
ICL7667 TP85

1
1

3
3

U24B U27B
R88 R89
4 T otem
5 4 T otem
5
DRV_L3-TOP_ING P+12_DELAY DRV_L3-TOP_INV
P+12_DELAY TP80
ICL7667 100 ICL7667 TP86 100

6
6

U27A

8
8

R90 R91
2 T otem
7 2 T otem
7
DRV_L3-BOTT_ING DRV_L3-BOTT_INV
U24A 100 ICL7667 100
ICL7667

3
3

R&D – TECHNICAL SPECIFICATION DT0424-E01


P+3.3

Powertronix spa reserves the right to modify this document without notice
4
3
2
1
RP12

470

5
6
7
8

Page. 51 of 73
Page. 52 of 73
P+3.3
From From Precharge SCR
Cyclone Cyclone
P+3.3 Static Switch Commands P+12_DELAY P+12_DELAY
(20/30 kVA)

Precharge-MAINS
C60 C61
SCR Commands

4
3
2
1
P+12_DELAY P+12_DELAY
RP17 0.1µF 0.1µF
(20/30 kVA) C57 C58

Powertronix spa reserves the right to modify this document without notice
SS-RELE_RES

SCR_L3
SCR_L2
SCR_L1
SS-RELE_INV

4
3
2
1

470
SS-INV_HF1
SS-INV_HF0
SS-BY_HF1
SS-BY_HF0

RP15 0.1µF 0.1µF


TP96

5
6
7
8

R&D – TECHNICAL SPECIFICATION DT0424-E01


470

1
TP87
5
6
7
8

R93
4 T otem
5
1

P+12_DELAY DRV_SCR_L1
U31B P+12_DELAY TP97 100
R92
4 5 ICL7667
T otem DRV_SS-INV_HF0

6
8
U28B TP88 100
R95
6

ICL7667 2 7
T otem DRV_SCR_L2
8

R94 100
2 7 U31A
T otem DRV_SS-INV_HF1
TP98 ICL7667
U28A 100

3
1
ICL7667
3

R97
TP89 4 5
T otem DRV_SCR_L3
1

U33B 100
R96
4 5 ICL7667
T otem DRV_SS-BY _HF0

8
U29B P+12_DELAY 100
ICL7667
TP90
8

6
R98
2 T otem
7 DRV_SS-BY _HF1
U29A 100
ICL7667

3
Precharge
Relay
Static Switch Command
Relay (7/15 kVA)
Commands
(7/15 kVA)

9
U38E

9
5 12 U38G
DRV_SS-RELE_INV
7 10
DRV_Precharge-MAINS

9
ULN2003A U38F

8
6 11 R158 ULN2003A
DRV_SS-RELE_RES 1K

8
ULN2003A

8
R156 R157
1K 1K
P+12_DELAY

6
2 T otem
7
U33A
ICL7667

3
Male header
JTAG
P+3.3 connections:

Page. 53 of 73
pin# jtag P+3.3
1 TCK
RP19 2 GND P+3.3
4 5
3 6
3 TDO

5
6
7
8
2 7 P+3.3 P+3.3 4 Vcc
1 8 5 TMS RP20
6 Vccio 10K
10K 7 (NC)

4
3
2
1
8 (NC)

5
6
7
8
CN_PRG1
RP21 9 TDI
1
U2 10 GND 2 nSTATUS
1K
3 CONF_DONE

programming
Byte-Blaster
1 44
A5 A4 A5 A6 4
2 43

4
3
2
1
A4 A3 A6 A7 5 nCONFIG
R104 3 42

EPCS1
A3 A2 A7 A8 6 nCE
4
A2 A1 7
5K6 5 41 CN_PRG2
A1 A0 OEn RAM_OEn 8
40 TCK P+3.3
UBn RAM_UBn 1 9
6 39
RAM_CEn CEn LBn RAM_LBn 2 10
TDO

Byte-Blaster FPGA
7 38 3 10p-2.54 C63
D0 DQ0 DQ15 D15 4
8 37
D1 DQ1 DQ14 D14 TMS 5
9 36 1µF

programming
D2 DQ2 DQ13 D13 6
10 128Kx16bit 35
D3 DQ3 DQ12 D12 P+3.3 7
TSOP2-44pin 8
11 34
VCC GND TDI 9
12 33
GND VCC 10

8
C64 C65 U5
13 32 10p-2.54 1

VCC

VCC

VCC
D4 DQ4 DQ11 D11 nCSO NCS
1µF 14 31 1µF 5
D5 DQ5 DQ10 D10 ASDO ASDI
15 30
D6 DQ6 DQ9 D9
16 29 6 2

GND
D7 DQ7 DQ8 D8 DCLK DCLK DATA DATA0
17 28
RAM_WEn WEn NC A19
EPCS1
18 27

4
A17 A16 A8 A9
19 26
A16 A15 A9 A10
20 25 FPGA Programming Connector
A15 A14 A10 A11

Powertronix spa reserves the right to modify this document without notice
21 24
A14 A13 A11 A12
22
A13 A12 23
NC A18
Hardware Boot Memory Programming Connector
BS616LV2010

R&D – TECHNICAL SPECIFICATION DT0424-E01


U3 BS616LV8010 C66 33pF
1 44 CLK_IN
A5 A4 A5 A6
2 43
A4 A3 A6 A7
3 42
A3 A2 A7 A8
4 XT1
A2 A1
5 41 16.128.000 Hz
A1 A0 OEn RAM_OEn
40 R105
UBn RAM_UBn
6 39
RAM_CEn CEn LBn RAM_LBn
1M
7 38
D0 DQ0 DQ15 D15
8 37
D1 DQ1 DQ14 D14
P+3.3 9 36
D2 DQ2 DQ13 D13
10 512Kx16bit 35
D3 DQ3 DQ12 D12 P+3.3 CLK_OUT
TSOP2-44pin
11 34 C67 33pF R107 220
12 VCC GND 33
GND VCC P+3.3
13 32
D4 DQ4 DQ11 D11
14 31
D5 DQ5 DQ10 D10
15 30 CPU Clock Crystal
D6 DQ6 DQ9 D9
16 29
D7 DQ7 DQ8 D8
17 C68
RAM_WEn WEn 28
A8 A9
18 27 0.1µF
A19 A18 A9 A10

4
3
2
1
19 26
A18 A17 A10 A11
20 25 RP22
A17 A16 A11 A12
21 24
A16 A15 A12 A13
22 23 10K
A15 A14 A13 A14

5
6
7
8

TP42
Output Test Frequency:
Y2 U7 512Hz when Oscillator is

8
32.768kHz at 32.768KHz
1 7

VCC
OSCI FT/OUT
These two RAM are never mounted together. PCB footprints must be overlapping.
2 6
OSCO SCL TMR_SCL

VSS
3 5
VBAT SDA TMR_SDA
M41T00

4
BT1
3V Lithium
P+3.3 50maH
5
6
7
8

System Calendar Clock


RP23
10K
4
3
2
1

U4 AM29LV400-TSOP48
1 48
A16 A15 A16 A17
2 47
A15 A14 nBY TE FLASH_BY TEn
3
A14 A13
4 46
A13 A12 VSS
5
A12 A11
6 45
A11 A10 DQ15/A-1 D15
7 44
A10 A9 DQ7 D7
8 43
A9 A8 DQ14 D14
9 42
A20 NC DQ6 D6
10 512Kx8bit 41
A21 NC DQ13 D13
256kx16bit 40
DQ5 D5
11 39
FLASH_WEn nWE DQ12 D12
12 38
nRESET DQ4 D4 P+3.3
R108 1K 13 37
14 NC VCC C69
15 NC 36
NY /nBY DQ11 D11
16 35 1µF
A19 NC DQ3 D3
34
DQ10 D10
17 33
A18 A17 DQ2 D2
18 32
A8 A7 DQ9 D9
19 31
A7 A6 DQ1 D1
20 30
A6 A5 DQ8 D8
21 29
A5 A4 DQ0 D0
22
A4 A3
23 28
A3 A2 nOE FLASH_OEn
24
A2 A1 27
VSS
26
nCE FLASH_CEn
25
A0 A1
Flash memory
Page. 54 of 73
LCD_RW
LCD_RS

LCD_D7
LCD_D6
LCD_D5
LCD_D4
LCD_D3
LCD_D2
LCD_D1
LCD_D0
LCD_E

P+3.3
From
to Cyclone Cyclone P+12
LCD_LIGHT_ON

6
U45A
BOTT1
BOTT2
BOTT3
BOTT4
5
6
7
8

P+3.3 RP28
RP24 2 T otem
7 1 8
2 7
10K C70 3 6
U35A ICL7667 4 5
0.1µF
14
4
3
2
1

1
40106 U45B
RP25 470
CN-LCD_D0
1 8 1 2 4 5
CN-T1 T otem CN-LCD_D1
2 7
CN-T2 CN-LCD_D2

Powertronix spa reserves the right to modify this document without notice
3 6 RP29
CN-T3 CN-LCD_D3
4 5 C71 ICL7667 1 8
CN-T4 CN-LCD_D4
2 7
7

8
CN-LCD_D5
0.1µF P+12 3 6

R&D – TECHNICAL SPECIFICATION DT0424-E01


10K CN-LCD_D6
4 5
CN-LCD_D7

6
BOTTONS FROM LCD BOARD U46A
U35B
2 7 470
14

T otem
40106
ICL7667
3 4

3
CN-LCD_E

1
C74 U46B
CN-LCD_RW
7

CN-LCD_RS
0.1µF 4 T otem
5
CN-LCD_LIGHT_ON
U35C ICL7667
P+12
14

8
40106

6
U47A
5 6
2 T otem
7
C77 ICL7667
7

0.1µF

1
U35D U47B
14

4 5 RP30
40106 T otem
1 8
9 8 2 7
ICL7667 3 6
P+12 4 5

8
6
U48A
7

C78 470
2 T otem
7
0.1µF
ICL7667

1
U48B
4 T otem
5

9
U38A P+12 ICL7667

8
6
1 16 TP43 U44A
LD1 CN-LD1
2 T otem
7

9
ULN2003A U38B
ICL7667

8
2 15 TP44
CN-LD2

1
U44B

3
LD2
ULN2003A 4 T otem
5

9
U38C

8
3 14 CN-BUZZER P+12 ICL7667
BUZZER TP45

8
6
U49A
ULN2003A
2 7

8
T otem
TP93 ICL7667

3
TP

1
U49B

1
DZ4 4 T otem
5
24V
ICL7667

8
U38E, U38F, U38G
spostati a pag.5
to Cyclone from Cyclone
P+3.3
USER SERIAL INTERFACE
P+3.3 P+12
R142
1K

PAR-OPT_SER_RX
SER_TX

SER_RX
SNMP_SER_TX

SNMP_SER_RX
PAR-OPT_SER_TX
TP47

TP46
6
C128 U50A C79

14
U39A 0.1µF 0.1µF R143
R109 10K 2 T otem
7
CNSER_TX
1 2
CN-SER_RX
ICL7667 100

3
C80 R138 40106

7
10K
1nF

P+3.3

UPS PARALLEL SERIAL INTERFACE R137


TP74

1K

1
U50B
8 TRX1
P+5 4 5 1
T otem
2
P+5 3
ICL7667 4

8
HFBR-1528

Gnd

8
RX1 R139

TP72
C137 U35F
4 nc 0.1µF 10K 5

14
3 Vc c 40106
IC 2 Gn d R140
1 Vo 13 12

Gnd

HFBR-2528
1K R144 R145

5
0.25 W

7
560 560

SNMP SERIAL INTERFACE

P+5
P+5 ISO_P+15
ISO_P+15

R113
R111 R112
R141 R114 1K
270 2.7K

TP51
14
2.2K 2.2K ISO1 U39C
TP50

4N35
9

1 5 5 6 U38D ISO2
4N35
2 4 4 13 1 5
CN-SNMP_SER_TX
R115 10K Q1 3 40106

7
1 2 4
CN-SNMP_SER_RX

6
2 C82 ULN2003A

1
8

C83 R116
6

D28 1nF
1nF 560K C84 R117

R&D – TECHNICAL SPECIFICATION DT0424-E01


1N4148

2
1nF 560K
ISO_N-15

Powertronix spa reserves the right to modify this document without notice
ISO_N-15

U35E

14
14
14
14
14

40106 U39B U39E U39D U39F

11 10 3 4 11 10 9 8 13 12

40106 40106 40106 40106

7
7
7
7
7

Page. 55 of 73
Page. 56 of 73
P+1.5 P+1.5 P+1.5 P+1.5 P+1.5 P+1.5 P+1.5 P+1.5 P+3.3 P+3.3 P+3.3 P+3.3 P+3.3 P+3.3 P+3.3 P+3.3 P+3.3 P+3.3 P+3.3 P+3.3
C85 C86 C87 C88 C89 C90 C91 C92
C93 C94 C95 C96 C97 C98 C99 C100 C101 C102 C103 C104
0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF
0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF 0.1µF
154

110
191
211
229

189
209
231

130
157
172

112
27

72
90

22
51

70
92
9

28 149
VCCA_PLL1
VCCA_PLL2

VCCIO1
VCCIO1
VCCIO1

VCCIO2
VCCIO2
VCCIO2

VCCIO3
VCCIO3
VCCIO3

VCCIO4
VCCIO4
VCCIO4
VCCINT
VCCINT
VCCINT
VCCINT
VCCINT
VCCINT

CLK_IN CLK0 TDO TDO


29 147
CLK1 TCK TCK
153 155
CLK2 TDI TDI
152 148
CLK3 TMS TMS
50 35
11 DPCLK0 MSEL1 34
228 DPCLK1 MSEL0 239
DPCLK2 DEV_OE P+3.3
193 240
DPCLK3 DEV_CLRN P+3.3
170 3
131 DPCLK4 CLKUSR 1
108 DPCLK5 INIT_DONE 24
DPCLK6 NCSO nCSO
73 37
DPCLK7 ASDO ASDO
38 32
39 PLL1_OUT0P NCEO 33
PLL1_OUT0N NCE nCE
144 25
PLL2_OUT1P DATA0 DATA0
143 36

Powertronix spa reserves the right to modify this document without notice
PLL2_OUT1N DCLK DCLK
26
NCONFIG nCONFIG
146
NSTATUS nSTATUS
145
CONF_DONE CONF_DONE

R&D – TECHNICAL SPECIFICATION DT0424-E01


2 121
LCD_E IO_V0B1_0 IO_V2B3_0 L1-TOP_INV
4 122 TP56
LCD_RW IO_V0B1_1 IO_V2B3_1 L1-BOTT_INV
5 123
LCD_RS VREF0B1 IO_V2B3_2 L2-TOP_INV R160
6 124
LD1 IO_V0B1_2 IO_V2B3_3 L2-BOTT_INV
7 125
LD2 IO_V0B1_3 IO_V2B3_4 L3-TOP_INV 222-TP_DBG1
8 126
BUZZER IO_V0B1_4 IO_V2B3_5 L3-BOTT_INV
12 127 1K
BOTT4 IO_V0B1_5 VREF2B3 L1-TOP_ING
13 128
BOTT3 IO_V0B1_6 IO_V2B3_6 L1-BOTT_ING
14 132 TP94
BOTT2 IO_V0B1_7 IO_V2B3_7 L2-TOP_ING
15 133
BOTT1 IO_V0B1_8 IO_V2B3_8 L2-BOTT_ING R161
16 134
PAR-OPT_SER_RX IO_V0B1_9 IO_V2B3_9 L3-TOP_ING
17 135
PAR-OPT_SER_TX IO_V0B1_10 IO_V2B3_10 L3-BOTT_ING 223-TP_DBG2
18 136
UPS-LD1 IO_V0B1_11 IO_V2B3_11 D14
19 137 1K
UPS-LD2 IO_V0B1_12 IO_V2B3_12 D15
20 138 TP95
UPS-LD3 IO_V0B1_13 IO_V2B3_13 Precharge-MAINS
21 139
UPS-LD4 IO_V0B1_14 IO_V2B3_14 LCD_LIGHT_ON R162
23 140
CLK_OUT VREF1B1 IO_V2B3_15 SCR_L1
41 141
UPS-LD5 IO_V2B1_0 IO_V2B3_16 SCR_L2 224-TP_DBG3
42 156
UPS-LD6 IO_V2B1_1 VREF1B3
43 158 1K
UPS-LD7 IO_V2B1_2 IO_V0B3_0 SCR_L3
44 159
UPS-LD8 IO_V2B1_3 IO_V0B3_1
45 160 TP100
DEBUG_LED1 IO_V2B1_4 IO_V0B3_2
46 161
DEBUG_LED2 IO_V2B1_5 IO_V0B3_3
47 162
DEBUG_LED3 IO_V2B1_6 IO_V0B3_4 SS-INV_HF0
48 163
DEBUG_LED4 IO_V2B1_7 IO_V0B3_5 SS-INV_HF1 R163
49 164
PIO_0 IO_V2B1_8 IO_V0B3_6 SS-BY _HF0
53 165
CL_RESET IO_V2B1_9 IO_V0B3_7 SS-BY _HF1 225-TP_DBG4
54 166
A1 IO_V2B1_10 IO_V0B3_8 SS-RELE_INV
55 167 1K
A2 VREF2B1 IO_V0B3_9 SS-RELE_RES
56 168
A3 IO_V2B1_11 IO_V0B3_10 000-SCLK_1
57 169
A4 IO_V2B1_12 IO_V0B3_11 000-SDATA_1
58 173
A5 IO_V2B1_13 IO_V0B3_12 000-INBT_-CS_1
59 174
A6 IO_V2B1_14 IO_V0B3_13 000-SCLK_0
60 175
A7 IO_V2B1_15 IO_V0B3_14 000-SDATA_0
61 176
A8 IO_V2B4_0 VREF0B3 000-INBT_-CS_0
62 177
A9 63 IO_V2B4_1 IO_V0B3_15 178 000-D_MPX-1
A10 IO_V2B4_2 IO_V0B3_16 000-C_MPX-1
64 179
A11 IO_V2B4_3 IO_V0B3_17 000-B_MPX-1
65 180
A12 IO_V2B4_4 IO_V0B3_18 000-A_MPX-1
66 181
A13 IO_V2B4_5 IO_V0B2_0 000-D_MPX-0
67 182
A14 IO_V2B4_6 IO_V0B2_1 000-C_MPX-0
68 183
A15 IO_V2B4_7 IO_V0B2_2 000-B_MPX-0
74 184
A16 VREF2B4 IO_V0B2_3 000-A_MPX-0
75 185
A17 IO_V2B4_8 IO_V0B2_4 SPARE_2
76 186
A18 IO_V2B4_9 IO_V0B2_5 BY-PASS_ON
77 187
A19 IO_V2B4_10 IO_V0B2_6 SPARE_1 P+1.5
78 188
A20 IO_V2B4_11 IO_V0B2_7 85TMP_ALL
79 194
A21 IO_V2B4_12 VREF0B2 Sy nchro-Front
80 195
81 IO_V2B4_13 IO_V0B2_8 196
IO_V2B4_14 IO_V0B2_9 RUN
82 197
P+1.5 D0 IO_V2B4_15 IO_V0B2_10 HQ4
83 198 C141
D1 IO_V2B4_16 IO_V0B2_11
84 199
D2 IO_V2B4_17 IO_V0B2_12 P+1.5
85 200 0.1µF
D3 IO_V2B4_18 IO_V1B2_0
86 201
D4 IO_V1B4_0 IO_V1B2_1 ENA _DC/DC
C139 87 202
D5 IO_V1B4_1 IO_V1B2_2 FAST-FAN
0.1µF 88 203
D6 IO_V1B4_2 IO_V1B2_3 SPARE_ULN
93 204
D7 VREF1B4 IO_V1B2_4
94 205
D8 IO_V1B4_3 IO_V1B2_5
95 206 C142
D9 IO_V1B4_4 IO_V1B2_6 EPO_LOCAL
96 207
IO_V1B4_5 IO_V1B2_7 EPO-REM
97 208 0.1µF
IO_V1B4_6 VREF1B2 MAINS_NOK
98 213
D10 IO_V1B4_7 IO_V1B2_8 BYPASS_ON
99 214
D11 IO_V1B4_8 IO_V1B2_9 INVERTER_ON
100 215
P+1.5 D12 IO_V1B4_9 IO_V1B2_10 BATT_LOW
101 216
D13 IO_V1B4_10 IO_V2B2_0 SER_RX P+1.5
102 217
IO_V0B4_0 IO_V2B2_1 SER_TX
C140 103 218
IO_V0B4_1 IO_V2B2_2 SNMP_SER_RX
0.1µF 104 219
P+1.5 FLASH_OEn IO_V0B4_2 IO_V2B2_3 SNMP_SER_TX
105 220
FLASH_CEn 106 IO_V0B4_3 IO_V2B2_4 221
FLASH_WEn 107 IO_V0B4_4 U1 IO_V2B2_5 222
C144 VREF0B4 IO_V2B2_6 222-TP_DBG1
0.1µF 113 ALTERA EP1C6 QFP 240 223
FLASH_BY TEn IO_V0B4_5 IO_V2B2_7 223-TP_DBG2
114 224 C143
RAM_CEn IO_V0B4_6 IO_V2B2_8 224-TP_DBG3
115 225
RAM_OEn IO_V0B4_7 STD IO_V2B2_9 225-TP_DBG4
116 226 LCD_D0 0.1µF
RAM_LBn IO_V0B4_8 IO_V2B2_10
117 IC 227 LCD_D1
RAM_UBn IO_V0B4_9 VREF2B2
118 233 LCD_D2
RAM_WEn IO_V0B4_10 IO_V2B2_11
119 234 LCD_D3
TMR_SCL IO_V0B4_11 IO_V2B2_12

150 GNDG_PLL1
GNDG_PLL2
120 EP1CC6Q240C7 235

151 GNDA_PLL1
GNDA_PLL2
TMR_SDA IO_V0B4_12 IO_V2B2_13 LCD_D4
236 LCD_D5
IO_V2B2_14 237
IO_V2B2_15 LCD_D6
238

GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
IO_V2B2_16 LCD_D7

109
111
129
142
171
190
192
210
212
230
232
10
40
52
69
71
89
91

30

31
Page. 57 of 73
D2PAK D39
TP52

2 1
N-7

TP57
P+15 U40 7812 TP53
1 3 P+15 R122 R125 1n4148
IN OUT P+12 U14C

11

14
REF

+ C105 C107 + C106 C108 U18D


LM324
1.2K 1K 9 - R120 R150
TP55

10µF 35V 0.1µF 0.1µF R124 8 9 8


10µF 35V 1K 10 RUN
2

+
10K 10M
0=pow-OK C110 1=RUN to EPLD
R123 R118

7
1µF
TP58

TP59

C119
D2PAK 1K 1K

Powertronix spa reserves the right to modify this document without notice
2

1
0.1µF
P+7.5 U41 7805 D38 DZ5
1 N-7
1 3 1n4148 3.9V P+12
IN OUT P+5
D37

R&D – TECHNICAL SPECIFICATION DT0424-E01


REF

+ C111 C113 + C112 C114 1n4148

2
TP61
10µF 35V 0.1µF 10µF 35V 0.1µF P+7.5

2
2
TP62

TP63

SOT223

TP54
U42
P+5 LM2937IMP3.3
1 3
P+3.3
Q2 BDX54
+ C115 C117 + C116 C118 3 2
Sorveglianza PSP OK P+12 P+12_DELAY
10µF 35V 0.1µF 10µF 35V 0.1µF
(+15V e +7.5V) + C109 R119
2

10µF35V 560
R121

1
R146
P+5
560 470

1
DPAK
TP64

TP65

TP60
D34

2
U43 1n4148
NCP1117DT15 U16F
P+5 DL3

2
3 2 6 11 Green
REF

IN OUT P+1.5
+ C120 C122 + C121 C123

1
10µF 35V 0.1µF 10µF 35V 0.1µF ULN2003A
1

U14D

11
U14B

11
LM324
LM324 13 -
6 - 14
7 12 +
5 +
P+5 P+12

4
4

TP68

TP69

TP70

TP71
P+5 P+15
R134 R135

7
U18E U18F
1K 2.2K

TP67
R131 R132 R133 11 10 13 12
680 1K 1K
U16G

2
C126 D31 UF4007

14

14
7 10 1 2 DL1 DL2
HQ4 N-7

2
D32 C127 DZ8
distribuiti GREEN Y ELLOW
1µF
UF4007
+
10µF35V sulla scheda
ULN2003A 6.2V
scrivere

1
simbolo di
massa
POWER SOURCE TEST LED
Connettore LCD Connettore SERIALE RELE CONTATTI Connettore SNMP-BOX
P+7.5 J3
J1 J2
1 ISO_N-15
26 1 RX 2 ISO_P+15
25 Clear 2 TX CN-SER_RX 3 CN-SNMP_SER_RX
24 Home CN-T1 3 CNSER_TX 4 CN-SNMP_SER_TX
23 UP-Next CN-T2 4 EPOA 5
22 DOWN-Back CN-T3 5 EPOB CN_EPO-REM 6
21 BUZZER CN-T4 6 7
20 CN-BUZZER 7 8
19 8 9
18 LD2 9 10
17 LD1 CN-LD2 10 11

to SNMP BOX
16 CN-LD1 11 P+15 12
LCD LIGHT ON
15 EPO CN-LCD_LIGHT_ON 12 13
14 RS CN-EPO_LOCAL 13 14
13 R/W CN-LCD_RS 14 MAINS FAILURE 15
12 EN CN-LCD_RW 15 REM_MAINS_NOK 16
MANUAL BY PASS ACTIVE
11 DB0 CN-LCD_E 16 REM_BY PASS_ON 17
INVERTER ON
10 DB1 CN-LCD_D0 17 REM_INVERTER_ON 18
BATTERY LOW
9 DB2 CN-LCD_D1 18 REM_BATT_LOW 19
8 DB3 CN-LCD_D2 19 20
7 DB4 CN-LCD_D3 20 21
6 DB5 CN-LCD_D4 22
5 DB6 CN-LCD_D5 23
CON20
4 DB7 CN-LCD_D6 24
3 CN-LCD_D7 25
2 26
1
CON26
CON26

J6 J5 J4
P+5 1 ISO_N-15 1 1
P+5 2 ISO_N-15 2 2
DRV_SS-INV_HF0 3 ISO_P+15 3 06_V-MAINS_L1 3
DRV_SS-INV_HF1 4 ISO_P+15 4 07_V-MAINS_L2 4
DRV_SS-BY _HF0 5 5 08_V-MAINS_L3 5
DRV_SS-BY _HF1 6 6 6
DRV_SCR_L1 7 DRV_L1-TOP_INV 7 18_V-RES_L1 7
DRV_SCR_L2 8 DRV_L1-BOTT_INV 8 19_V-RES_L2 8
DRV_SCR_L3 9 DRV_L2-TOP_INV 9 20_V-RES_L3 9
10 DRV_L2-BOTT_INV 10 10
27_INVERTER_TEMP 11 DRV_L3-TOP_INV 11 00_V-INV_L1 11
12 DRV_L3-BOTT_INV 12 01_V-INV_L2 12
28_PFC_TEMP 13 DRV_L1-TOP_ING 13 02_V-INV_L3 13
14 DRV_L1-BOTT_ING 14 14
DRV_L2-TOP_ING 15 12_V-OUT_L1 15
CON14 DRV_L2-BOTT_ING 13_V-OUT_L2
16 16
DRV_L3-TOP_ING 17 14_V-OUT_L3 17
DRV_L3-BOTT_ING 18 18
19 P+5 19
20 09_A-MAINS_L1 20
C129
DRV_Precharge-MAINS 21 10_A-MAINS_L2 21
1µF
DRV_SS-RELE_INV 22 11_A-MAINS_L3 22
DRV_SS-RELE_RES 23 23
24 P+5 24
25 03_A-INV_L1 25
Sy ncro C130
26 04_A-INV_L2 26
1µF
FAST-SPEED 27 05_A-INV_L3 27
ENABLE _DC/DC 28 28
OVER-85TMP_ALL 29 P+5 29
CONTACT_SPARE_1 30 21_A-OUT_L1 30
C131
AUX_BY -PASS_ON 31 22_A-OUT_L2 31
1µF
CONTACT_SPARE_2 32 23_A-OUT_L3 32
P+15 33 33
P+15 34 34
P+7.5 35 16_+DC-BUS 35
P+7.5 36 36
P+5 37 16_-DC-BUS 37
P+5 38 38
39 P+5 39
40 17_A-BATTERY 40
C132
1µF 41
CON40
42
24_MODULE_TEMP 43
44
25_INT-BATT_TEMP 45
46
26_EXT-BATT_TEMP 47
48
49
50
CON50

Connettore DRIVER POWER Connettore DRIVER POWER Connettore ANALOG POWER

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 58 of 73


Page. 59 of 73
DRV_L1-TOP_ING DRV_L2-TOP_ING INVERTER_IN PHASE L2 DRV_L3-TOP_ING
INVERTER_IN PHASE L1 INVERTER_IN PHASE L3
TP1 TP2 TP3
P+15 P+15 P+15
8

8
ISO1 ISO2 ISO3
2 + 6 R1 10 2 + 6 R2 10 2 + 6 R3 10
G1-T G2-T G3-T
Totem Totem Totem
R4 D1 3 7 R7 10 R5 D2 3 7 R8 10 R6 D3 3 7 R9 10
P6KE18CAC250

P6KE18CAC250

P6KE18CAC250
1.8K 2 1 - 1.8K 2 1 - 1.8K 2 1 -
1

1
HCPL3120 Z1 HCPL3120 Z2 HCPL3120 Z3
1

1
1N4148 Z4 1N4148 Z5 1N4148 Z6
5

5
100µF 35V 100µF 35V

100µF 35V 100µF 35V

100µF 35V 100µF 35V


D4 C1 D5 C2 D6 C3
15V 15V 15V
2 1 + TP4 2 1 + TP5 2 1 + TP6
R10 3 R11 3 R12 3
270 UF4007 C4 270 UF4007 C5 270 UF4007 C6
2

2
1 1µF E1-T 1 1µF E2-T 1 1µF E3-T
2 2 2
1

1
4 2 1 D10 1N4148 4 2 1 D11 1N4148 4 2 1 D12 1N4148
C7 R13 C8 R14 C9 R15
6 + 6 + 6 +

Powertronix spa reserves the right to modify this document without notice
UF4007 1K UF4007 1K UF4007 1K
5 D7 5 D8 5 D9
22

22

22
T1 T2 T3
100µF 35V

100µF 35V

100µF 35V

R&D – TECHNICAL SPECIFICATION DT0424-E01


VAC4721X004 C10 D13 R16 VAC4721X004 C11 D14 R17 VAC4721X004 C12 D15 R18
+ + +
HF supply 1 1K HF supply 1 1K HF supply 1 1K
1N4148 1N4148 1N4148
2 1

2 1

2 1
HF supply 2 C13 E1-B HF supply 2 C14 E2-B HF supply 2 C15 E3-B
1µF 1µF 1µF
100µF 35V

100µF 35V

100µF 35V
P6KE18CAC250

P6KE18CAC250

P6KE18CAC250
1

1
Z7 Z8 Z9
P+15 DRV_L1-BOTT_ING +
15V TP7 P+15
+
15V TP8 P+15
+
15V TP9
C16 DRV_L2-BOTT_ING C17 DRV_L3-BOTT_ING C18
Z10 Z11 Z12
1

1
Inverter Driver & Feedback Alcor

8
R19 D16 ISO4 R20 D17 ISO5 R21 D18 ISO6
2

2
1.8K 2 1 2 + 6 R22 10 1.8K 2 1 2 + 6 R23 10 1.8K 2 1 2 + 6 R24 10
G1-B G2-B G3-B
Totem 10 Totem 10 Totem 10
1N4148 3 7 R25 1N4148 3 7 R26 1N4148 3 7 R27
- TP10 - TP11 - TP12
HCPL3120 HCPL3120 HCPL3120
R28 R29 R30 TP13
5

5
270 270 270
DRV_L1-TOP_INV INVERTER_OUT PHASE L1 DRV_L2-TOP_INV INVERTER_OUT PHASE L2 DRV_L3-TOP_INV INVERTER_OUT PHASE L3
TP14 TP15 TP16
P+15 P+15 P+15
8

8
ISO7 ISO8 ISO9
2 + 6 R31 10 2 + 6 R32 10 2 + 6 R33 10
G4-T G5-T G6-T
Totem Totem Totem
R34 D19 3 7 R37 10 R35 D20 3 7 R38 10 R36 D21 3 7 R39 10

P6KE18CAC250

P6KE18CAC250

P6KE18CAC250
1.8K 2 1 - 1.8K 2 1 - 1.8K 2 1 -

1
HCPL3120 1 Z13 HCPL3120 Z14 HCPL3120 Z15

1
1N4148 Z16 1N4148 Z17 1N4148 Z18
5

5
100µF 35V 100µF 35V

100µF 35V 100µF 35V

100µF 35V 100µF 35V


D22 C19 D23 C20 D24 C21
15V 15V 15V
2 1 + TP17 2 1 + TP18 2 1 + TP19
R40 3 R41 3 R42 3
270 UF4007 C22 270 UF4007 C23 270 UF4007 C24

2
1 1µF E4-T 1 1µF E5-T 1 1µF E6-T
2 2 2

1
4 2 1 D28 1N4148 4 2 1 D29 1N4148 4 2 1 D30 1N4148
C25 + R43 C26 + R44 C27 + R45
6 6 6
UF4007 1K UF4007 1K UF4007 1K
5 D25 5 D26 5 D27

22

22

22
T4 T5 T6

100µF 35V

100µF 35V

100µF 35V
VAC4721X004 C28 D31 R46 VAC4721X004 C29 D32 R47 VAC4721X004 C30 D33 R48
+ + +
HF supply 1 1K HF supply 1 1K HF supply 1 1K
1N4148 1N4148 1N4148

2 1

2 1

2 1
HF supply 2 C31 E4-B HF supply 2 C32 E5-B HF supply 2 C33 E6-B
1µF 1µF 1µF

100µF 35V

100µF 35V

100µF 35V
P6KE18CAC250

P6KE18CAC250

P6KE18CAC250
1

1
Z19 Z20 Z21
+ + +
P+15 15V TP20 P+15 15V TP21 P+15 15V TP22
DRV_L1-BOTT_INV C34 DRV_L2-BOTT_INV C35 DRV_L3-BOTT_INV C36
Z22 Z23 Z24

1
8

8
R49 D34 ISO10 R50 D35 ISO11 R51 D36 ISO12

2
1.8K 2 1 2 + 6 R52 10 1.8K 2 1 2 + 6 R53 10 1.8K 2 1 2 + 6 R54 10
G4-B G5-B G6-B
Totem 10 Totem 10 Totem 10
1N4148 3 7 R55 1N4148 3 7 R56 1N4148 3 7 R57
- TP23 - TP24 - TP25
HCPL3120 HCPL3120 HCPL3120
R58 R59 R60

5
270 270 270
5.1.7 DE0151

TP26
Page. 60 of 73
09_A-MAINS_L1

11_A-MAINS_L3
10_A-MAINS_L2

A-MAINS_POS

to AC Input
Capacitors
Inverter IN Inverter OUT
FS3 FS2 FS1 16_+DC-BUS +DC_VOLT
DC_Cor_L1
R66 R65 R64
DC_Cor_L2 DC_Cor_L3 3 = L1 3 = L3

G5-T

E6-T
G6-T
E5-T
4 = L2 4 = L2
G1-T
E1-T

G2-T
E2-T
A-MAINS_NEG

150K 0.25W 150K 0.25W 150K 0.25W Q2_POS


5 = L3 Q1_POS
5 = L1
+ C100
100uF Q1 Q2
PRCH-G1_POS

13
12
2

9
8
PRCH-G1_NEG

SEMiX201GD128Ds R67 SEMiX201GD128Ds


PRCH-G2_POS

R63

12
13
8
9

2
SCR_L1-OUT

SCR_L2-OUT

22K 0.25W
SCR_L1-IN

SCR_L2-IN

R61 6.8K
22K 0.25W CN1 16
16 DC BUS G4-T 17 3
G3-T E4-T
C98 3 17 4 4
+ E3-T
R62 100uF + C99 4 TO AUX 3 5
22K 0.25W 100 uF 5 2
CONVERTER
7

1 14
CS0153 G4-B
PW7 14 15
G3-B E4-B
TO INDUCTOR

4 1 L1 15

Powertronix spa reserves the right to modify this document without notice
PW4 E3-B
10 R68

10
11

19

20
L1-INPUT 12

6
7

R&D – TECHNICAL SPECIFICATION DT0424-E01


20

19

11
10
PW8 6.8K

7
6

1
5 2 L2 P+5

G2-B
PW5

E2-B
Q1_NEG Q2_NEG

E1-B
G1-B
13 C39 C40 C41 P+5 R71 R70 R69

E6-B
G5-B
E5-B

G6-B
L2-INPUT 14
PW9 0.1µF 0.1µF 0.1µF
6 3 L3 150K 0.25W 150K 0.25W 150K 0.25W
PW6
28_PFC_TEMP 27_INVERTER_TEMP
1
2
3

L3-INPUT R211 16_-DC-BUS -DC_VOLT R212


11

S1 R210 10 10 R213
SCR_L3-IN

PRCH-G2_NEG
PRCH-G3_POS
SCR_L3-OUT

SCR SKUT85 4 5 5K 5K
PW25
PRCH-G3_NEG

L1 H1
1
2
3
ACS754
PW26 4 5
L2
H2

1
2
3
ACS754
R72
PW27 4 5 +DC_VOLT
L3
H3
ACS754 100K P+5
R74
PW1 A-BATT_POS 100K
+ BATTERY
H4
1 C103 P+5 R76
+5V R75
47nF DC_Cor_L1
PW12 2 150K
0V A-BATT_NEG
10K

BATTERIA
- BATTERY
3 R77
C43 R78 OUT C104 100K D67

LEM DI
4 4.7nF 1N4148
VREF
C44 R79 0.1µF MABA0110 5W 17_A-BATTERY
5 R80
CE C105 R73 DC_Cor_L2
6 47nF 10 0.25W
0.1µF MABA01 10 5W C45 R81 NC D68 10K
HAIS 50-P 1N4148
R82
0.1µF MABA01 10 5W 100K
CN2
+ C46 R83
TO AUX 10µF 16V DC_Cor_L3
P+15
CONVERTER 10K
CS0153 HF supply 1
TO PAGE 1 R84
HF supply 2 100K
INPUT MAINS R85 posizionare il
R86
R87 R88 R89
100
C47 P+15 più vicino
-DC_VOLT
06_V-MAINS_L1 U1
possibile
R90
27K 0.25W 27K 0.25W 27K 0.25W 13
VC VREF
16 1000pF 100K a R62,R63,R61
15 2 Q3
R91 R92 R93 VCC +V 2.2 5W
C48 + IRFD110

2
07_V-MAINS_L2 10µF 9 1 3
1 COMP T7
-V R95
27K 0.25W 27K 0.25W 27K 0.25W 12 14 3 6
GND OUTB 1K 2
R96 R97 R98 5 R94 47 5

4
R99 6 CT 1
08_V-MAINS_L3 RT
7 TP27 TP28 TP29
DISC R100 47
27K 0.25W 27K 0.25W 27K 0.25W 11 4
47 OUTA
C49 3 4 VAC4097X055
SY NC OSC

2
R101 8 10 Q4 1 +
1nF CSS SD C50
5.6K 3 100µF 35V
SG3525
+ C51 IRFD110
10µF DRIVERS SUPPLY

4
Page. 61 of 73
R102 R103
PRCH-G1_POS SCR_L1-OUT PRCH-G3_POS SCR_L3-OUT
470R 470R
C52 C53
0,1uF 0,1uF
D37 D38
1 2 1 2
R104 100K R105 100K
1N4007 1N4007
R106 R107
ISO13 100K ISO14 100K
DRV_SCR_L1 1 6 DRV_SCR_L3 1 6
C54 C55
2 4 2 4
P+15 MOC3051 P+15 MOC3051
R108 4700pF/2KV R109 4700pF/2KV
100/1W 100/1W
1

1
TP30 D39 C56 TP31 D40 C57

Powertronix spa reserves the right to modify this document without notice
R110 R111
680R 1N4148 ISO15 680R 1N4148 ISO16
1 6 1 6

R&D – TECHNICAL SPECIFICATION DT0424-E01


2

2
R112 4700pF/2KV R113 4700pF/2KV
2 4 2 4
100K 100K
R114 R115
MOC3051 MOC3051
R116 D41 R117 D42
100K 1 2 100K 1 2
100R 100R
1N4007 1N4007
C58 C59
0,1uF 0,1uF
R118 R119
PRCH-G1_NEG SCR_L1-IN PRCH-G3_NEG SCR_L3-IN
470 470
R120
PRCH-G2_POS SCR_L2-OUT
470R
C60
0,1uF
D43
1 2
R121 100K
1N4007
R122
ISO17 100K
DRV_SCR_L2 1 6
C61
2 4
P+15 MOC3051
R123 4700pF/2KV
100/1W
TP32 1
D44 C62
R124
680R 1N4148 ISO18
1 6

2
R125 4700pF/2KV
2 4
100K
MOC3051 R126
R127 D45
100K 1 2
100R
1N4007
C63
0,1uF
R128
PRCH-G2_NEG SCR_L2-IN
470
Page. 62 of 73
00_V-INV_L1

01_V-INV_L2

02_V-INV_L3
03_A-INV_L1

04_A-INV_L2

05_A-INV_L3

A-INV_NEG

UPS OUTPUT
PW14 PW15 PW16
R131 L1-OUT L2-OUT L3-OUT
R129
27K 0.25W 27K 0.25W
R130

12_V-OUT_L1

13_V-OUT_L2

14_V-OUT_L3
27K 0.25W
R132 R133 R134
10 0.25W 10 0.25W 10 0.25W R137
R135
27K 0.25W 27K 0.25W
C64 C65 C66 R136
27K 0.25W
0.1µF 0.1µF 0.1µF
R138 R140 R141 R142 R143
G-POS_2

K-NEG_3
G-NEG_3

G-POS_3

K-POS_3
27K 0.25W
27K 0.25W
A-INV_POS
R139 27K 0.25W 27K 0.25W 27K 0.25W
27K 0.25W
11
3
2
1

H5
ACS754 R144 R145 R146
PW20 4 5 3 6
L3
14 S2 27K 0.25W 27K 0.25W 27K 0.25W
3
2
1

H6 13 SCR SKUT85
Inductor

ACS754
K-NEG_2

Powertronix spa reserves the right to modify this document without notice
PW19 4 5 2 5 R147 R148 R149
From

L2
12
K-POS_2
3
2
1

H7 10 27K 0.25W 27K 0.25W 27K 0.25W


ACS754

R&D – TECHNICAL SPECIFICATION DT0424-E01


PW18 4 5 1 4
L1

21_A-OUT_L1

22_A-OUT_L2

23_A-OUT_L3
A-OUT_NEG
A-OUT_POS
7

K-POS_1
G-NEG_2

G-NEG_1
G-POS_1

K-NEG_1
R152 R153 R154
C67 R151

10 0.25W

10 0.25W

10 0.25W
FS4 FS5 FS6
L1 L2 L3
0.1µF MABA01 10 5W
TO A/C CAPACITORS
C69 R155
C71 C72
0.1µF MABA01 10 5W C70 0.1µF 0.1µF
0.1µF
C73 R156

1
2
3
0.1µF MABA01 10 5W
4 5

1
2
3
H8
ACS754
4 5

1
2
3
C74 R157 H9
ACS754
4 5
0.1µF MABA01 10 5W
H10
ACS754
C75 R158
TO AC-Capacitors
0.1µF MABA01 10 5W P+15
FS13 FS14 FS15
C76 R159 R209
47R 1W
TO AUX
CONVERTER 0.1µF MABA01 10 5W

5
CS0153 K8 CN12
Max_Speed
N.O.
CN3
INPUT RESERVE S3 To Fan

2
1

4
SCR SKUT85 Board

1
D69
K-NEG_6 G-POS_6 K-POS_6 1N4007

2
FAST-SPEED
INPUT Reserve

PW21 4 1
L1-RES
10
G-NEG_6
12
G-POS_5
PW22 5 2
L2-RES
K-POS_5
13
K-NEG_5 G-NEG_5
14
G-POS_4
PW23 6 3
L3-RES

11
R161 R163 R160 K-NEG_4 G-NEG_4 K-POS_4
27K 0.25W R162 270K 0.25W
27K 0.25W 27K 0.25W
TP33
CN4
R165 R167 R164 AUX_BY-PASS_ON
27K 0.25W R166 270K 0.25W
27K 0.25W 27K 0.25W NEUTRAL
BY -PASS ON TO
FS9 FS10 FS11 FS12 TP35 TP36 TP37 TP38
CN5 ROTARY
SWITCH
SPARE_2
R171 R168
R169 R170 270K 0.25W
27K 0.25W 27K 0.25W 27K 0.25W
TP34 SPARE_2

18_V-RES_L1

19_V-RES_L2

20_V-RES_L3

SIG_SYNCRO
Page. 63 of 73
TP39 TP40
R172 R173
D46 15 2W D47 15 2W
G-POS_1 G-POS_4
UF4007 UF4007
T8 TP41 T9 TP42
3 R174 C77 3 R175 C78
R176 470 0.1µF 63v R177 470 0.1µF 63v
K-POS_1 K-POS_4

Powertronix spa reserves the right to modify this document without notice
1 1
10 5W 2 10 5W 2
C79 5 C80 5
6 6

R&D – TECHNICAL SPECIFICATION DT0424-E01


1µF 63v 1µF 63v
K-NEG_1 K-NEG_4
4 R178 4 R179
C83 C81 C84 C82
470 470
VAC4721X004 0.1µF 63v TP43 VAC4721X004 0.1µF 63v TP44
1µF 63v D48 1µF 63v D49
C85 G-NEG_1 C86 G-NEG_4
UF4007 15 2W UF4007 15 2W
1µF 63v R180 1µF 63v R181
TP45 TP46
Q5 R182 TP47 Q7 R183 TP48
BD439 D50 15 2W BD439 D51 15 2W
2 1 1 2 2 1 1 2
G-POS_2 G-POS_5
Q6 UF4007 Q8 UF4007
BD440 P+15 T10 TP51 BD440 P+15 T11 TP52
TP49 5 R184 C87 TP50 3 R185 C88
3

3
R186 470 0.1µF 63v R187 470 0.1µF 63v
K-POS_2 K-POS_5
1 1
4 2
10 5W 10 5W
2 1 1 2 3 2 1 1 2 5
D52 6 D53 6
Q9 Q10 1N4148 Q11 Q12 1N4148
TP55 K-NEG_2 TP56 K-NEG_5
BD439 BD440 2 R188 BD439 BD440 4 R189
C89 C90
3

3
470 470
VAC4721X004 0.1µF 63v TP53 VAC4721X004 0.1µF 63v TP54
D58 D59 D55 D60 D61 D57
1N4148 1N4148 D54 1N4148 1N4148 D56
G-NEG_2 G-NEG_5
1N4148 1N4148
P+15 15 2W P+15 15 2W
UF4007 UF4007
R190 R191 TP58
C91 TP57 C92
+

+
TP59 TP60
100µF 25V R194 100µF 25V R195
R192 D62 15 2W R193 D63 15 2W
4.7 5W 4.7 5W
G-POS_3 G-POS_6
DRV_SS-INV_HF0 DRV_SS-BY _HF0
UF4007 UF4007
T12 T13
P+15 R196 TP61 P+15 R197 TP62
DRV_SS-INV_HF1 5 C93 DRV_SS-BY _HF1 5 C94
R198 470 0.1µF 63v R199 470 0.1µF 63v
K-POS_3 K-POS_6
1 1
10 5W 4 10 5W 4
3 3
6 6
K-NEG_3 K-NEG_6
2 R200 2 R201
470 C95 470 C96
VAC4721X004 0.1µF 63v TP63 VAC4721X004 0.1µF 63v TP64
D64 D65
G-NEG_3 G-NEG_6
15 2W 15 2W
UF4007 UF4007
R202 R203
TP65 TP66
J1

1 P+5
2 J2
3 06_V-MAINS_L1
4 07_V-MAINS_L2 1

TO CONTROL LOGIC
5 08_V-MAINS_L3 2
6 3 DRV_SS-INV_HF0
7 18_V-RES_L1 4 DRV_SS-INV_HF1
8 19_V-RES_L2 5 DRV_SS-BY _HF0
9 20_V-RES_L3 6 DRV_SS-BY _HF1
10 7 DRV_SCR_L1
11 00_V-INV_L1 8 DRV_SCR_L2
12 01_V-INV_L2 9 DRV_SCR_L3
13 02_V-INV_L3 10

CS0150
14 11 27_INVERTER_TEMP
15 12_V-OUT_L1 12
16 13_V-OUT_L2 13 28_PFC_TEMP
17 14_V-OUT_L3 14
18
19 A-MAINS_POS
FLAT 14VIE
TO CONTROL LOGIC

20 09_A-MAINS_L1
21 10_A-MAINS_L2
22 11_A-MAINS_L3
23 A-MAINS_NEG
24 A-INV_POS J3
25 03_A-INV_L1
26 04_A-INV_L2 1 P+15
27 05_A-INV_L3 2
28 A-INV_NEG 3
CS0150

29 A-OUT_POS 4
30 21_A-OUT_L1 5 P+7.5
31 22_A-OUT_L2 6
32 23_A-OUT_L3 7
33 A-OUT_NEG 8
34 9
35 16_+DC-BUS CONVERTER 10
36 11
FROM AUX

37 16_-DC-BUS 12
CS0153
38 13
39 A-BATT_POS 14 ENABLE _DC/DC
40 17_A-BATTERY 15
41 A-BATT_NEG 16 ISO_P+15
42 17
43 24_MODULE_TEMP 18 ISO_N-15
44 19
45 25_INT-BATT_TEMP 20
46
47 26_EXT-BATT_TEMP
FLAT 20VIE
48
49
50

FLAT 50 VIE

J4

1 ISO_N-15
TP67
2 ISO_N-15
3 ISO_P+15
4 ISO_P+15
CN6 OVER-85TMP_ALL
5 OVR TEMP
6 TP68
7 DRV_L1-TOP_INV
8 DRV_L1-BOTT_INV
9 DRV_L2-TOP_INV
CN7 SPARE_1
10 DRV_L2-BOTT_INV
SPARE_1
11 DRV_L3-TOP_INV
12 DRV_L3-BOTT_INV
13 DRV_L1-TOP_ING
P+15
14 DRV_L1-BOTT_ING
R204 1K TP69
15 DRV_L2-TOP_ING
CN8
TO CONTROL LOGIC

16 DRV_L2-BOTT_ING
MODULE TEMP 24_MODULE_TEMP
17 DRV_L3-TOP_ING
18 DRV_L3-BOTT_ING
P+15
19 R205 1K TP70
20 CN9
21 CABINET TEMP
22 25_INT-BATT_TEMP
23
24
CS0150

P+15
25 R207 1K TP72
26 SIG_Sy ncro
CN11
27 FAST-SPEED
EXT BATTERY TEMP 26_EXT-BATT_TEMP
28 ENABLE _DC/DC
29 OVER-85TMP_ALL
30 SPARE_1
P+15 P+7.5 P+5
31 AUX_BY -PASS_ON
32 SPARE_2
33
34
35
36
TO CS0138 TEMPERATURE
37
38
SENSOR
39
40

FLAT 40VIE

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 64 of 73


Page. 65 of 73
DRV_L1-TOP_ING DRV_L2-TOP_ING DRV_L3-TOP_ING
INVERTER_IN PHASE L1 INVERTER_IN PHASE L2 INVERTER_IN PHASE L3
TP1 TP2 TP3
P+15 P+15 P+15
8

8
ISO1 ISO2 ISO3
2 + 6 R1 33 2 + 6 R2 33 2 + 6 R3 33
G1-T G2-T G3-T
Totem Totem Totem
R4 D1 3 7 R7 33 R5 D2 3 7 R8 33 R6 D3 3 7 R9 33
P6KE18CAC250

P6KE18CAC250

P6KE18CAC250
1.8K 2 1 - 1.8K 2 1 - 1.8K 2 1 -
1

1
HCPL3120 Z1 HCPL3120 Z2 HCPL3120 Z3
1

1
1N4148 Z4 1N4148 Z5 1N4148 Z6
5

5
100µF 35V

100µF 35V 100µF 35V

100µF 35V
D4 C1 D5 C2 D6 C3
15V 15V 15V
2 1 + TP4 2 1 + TP5 2 1 + TP6
R10 3 R11 3 R12 3
270 T1 UF4007 C4 270 T2 UF4007 C5 270 T3 UF4007 C6
2

2
6 1µF E1-T 6 1µF E2-T 6 1µF E3-T
2 2 2
100µF 35V

100µF 35V
1

1
4 2 1 D10 1N4148 4 2 1 D11 1N4148 4 2 1 D12 1N4148
C7 R13 C8 R14 C9 R15
1 + 1 + 1 +
UF4007 1K UF4007 1K UF4007 1K
5 D7 5 D8 5 D9
22

22

22
VAC4721X004 VAC4721X004 VAC4721X004
100µF 35V

100µF 35V

100µF 35V
C10 C11 C12

Powertronix spa reserves the right to modify this document without notice
+ D13 R16 + D14 R17 + D15 R18
HF supply 1 1K HF supply 1 1K HF supply 1 1K
1N4148 1N4148 1N4148
1

1
HF supply 2 C13 E1-B HF supply 2 C14 E2-B HF supply 2 C15 E3-B

R&D – TECHNICAL SPECIFICATION DT0424-E01


2

2
1µF 1µF 1µF
100µF 35V

100µF 35V

100µF 35V
P6KE18CAC250

P6KE18CAC250

P6KE18CAC250
1

1
Z7 Z8 Z9
+ + +
P+15 15V TP7 P+15 15V TP8 P+15 15V TP9
DRV_L1-BOTT_ING C16 DRV_L2-BOTT_ING C17 DRV_L3-BOTT_ING C18
Z10 Z11 Z12
1

1
8

8
R19 D16 ISO4 R20 D17 ISO5 R21 D18 ISO6
2

2
1.8K 2 1 2 + 6 R22 33 1.8K 2 1 2 + 6 R23 33 1.8K 2 1 2 + 6 R24 33
G1-B G2-B G3-B
Totem 33 Totem 33 Totem 33
1N4148 3 7 R25 1N4148 3 7 R26 1N4148 3 7 R27
Inverter Driver & Feedback Mizar

- TP10 - TP11 - TP12


HCPL3120 HCPL3120 HCPL3120
R28 R29 R30 TP25
5

5
270 270 270
COM
DRV_L1-TOP_INV INVERTER_OUT PHASE L1 DRV_L2-TOP_INV INVERTER_OUT PHASE L2 DRV_L3-TOP_INV INVERTER_OUT PHASE L3
TP13 TP14 TP15
P+15 P+15 P+15
8

8
ISO7 ISO8 ISO9
2 + 6 R31 33 2 + 6 R32 33 2 + 6 R33 33
G4-T G5-T G6-T
Totem Totem Totem
R34 D19 3 7 R37 33 R35 D20 3 7 R38 33 R36 D21 3 7 R39 33

P6KE18CAC250

P6KE18CAC250

P6KE18CAC250
1.8K 2 1 - 1.8K 2 1 - 1.8K 2 1 -

1
HCPL3120 1 Z13 HCPL3120 Z14 HCPL3120 Z15

1
1N4148 Z16 1N4148 Z17 1N4148 Z18
5

5
100µF 35V

100µF 35V

100µF 35V
D22 C19 D23 C20 D24 C21
15V 15V 15V
2 1 + TP16 2 1 + TP17 2 1 + TP18
R40 3 R41 3 R42 3
270 T4 UF4007 C22 270 T5 UF4007 C23 270 T6 UF4007 C24

2
6 1µF E4-T 6 1µF E5-T 6 1µF E6-T
2 2 2

100µF 35V

100µF 35V

100µF 35V
1

1
4 2 1 D28 1N4148 4 2 1 D29 1N4148 4 2 1 D30 1N4148
C25 + R43 C26 + R44 C27 + R45
1 1 1
UF4007 1K UF4007 1K UF4007 1K
5 D25 5 D26 5 D27

22

22

22
VAC4721X004 VAC4721X004

100µF 35V

100µF 35V

100µF 35V
VAC4721X004 C28 D31 R46 C29 D32 R47 C30 D33 R48
+ + +
HF supply 1 1K HF supply 1 1K HF supply 1 1K
1N4148 1N4148 1N4148
E4-B

1
HF supply 2 C31 HF supply 2 C32 E5-B HF supply 2 C33 E6-B

2
1µF 1µF 1µF

100µF 35V

100µF 35V

100µF 35V
P6KE18CAC250

P6KE18CAC250

P6KE18CAC250
1

1
Z19 Z20 Z21
+ + +
P+15 15V TP19 P+15 15V TP20 P+15 15V TP21
DRV_L1-BOTT_INV C34 DRV_L2-BOTT_INV C35 DRV_L3-BOTT_INV C36
Z22 Z23 Z24

1
8

8
R49 D34 ISO10 R50 D35 ISO11 R51 D36 ISO12

2
1.8K 2 1 2 + 6 R52 33 1.8K 2 1 2 + 6 R53 33 1.8K 2 1 2 + 6 R54 33
G4-B G5-B G6-B
Totem 33 Totem 33 Totem 33
1N4148 3 7 R55 1N4148 3 7 R56 1N4148 3 7 R57
- TP22 - TP23 - TP24
HCPL3120 HCPL3120 HCPL3120
5.1.8 DE0152

R58 R59 R60

5
270 270 270
TP26
COM
Page. 66 of 73
TP38
A-MAINS_NEG
A-MAINS_NEG
CN10
R144 10K 0.25W AUX_BY -PASS_ON AUX_BY -PASS_ON 1
09_A-MAINS_L1 2 BY -PASS ON
09_A-MAINS_L1
R145 10K 0.25W
10_A-MAINS_L2 TO PAGE 4 To Sw itches
10_A-MAINS_L2
R146 10K 0.25W FS10 CN11
REF 11_A-MAINS_L3 + BATTERY 1 F2 3 SPARE_2 1
11_A-MAINS_L3 SPARE_2
2 4 2 Spare_2
32A 10x38
+ C67 R135 TO PAGE 4 TP39
+ C66 R136 100uF 22K 0.25W
100uF 22K 0.25W + C65 R134
22K 0.25W
100uF
FS14 1 F3 3

Powertronix spa reserves the right to modify this document without notice
+ DC 2 4
FS44 32A 10x38
NEUTRAL IN C50 C48 C49
0.1µF 0.1µF 0.1µF
INPUT INVERTER OUTPUT INVERTER

R&D – TECHNICAL SPECIFICATION DT0424-E01


A-MAINS_POS R182 P+5
A-MAINS_POS 16_+DC-BUS
FS43 Q1 Q4
13
12

12
13
NEUTRAL IN SK60GB128 100K 0.25W SK60GB128 E4-T

2
C38 C37 R95 R96 R180 R188 C40 C41
1
2
3

27 28 2.2µF PHB 2.2µF PHB 2.2µF PHB 2.2µF PHB 28 27


Input

R63 E1-T G1-T G4-T


UPS

24 850V 850V R183 150K 0.25W 850V 850V 24 FS20


FS7 4 5 FS1 FS6 23 150K 0.25W 150K 0.25W 150K 0.25W 23 L1
L1-INPUT L1 L1 1 100K 0.25W 1
From Input

1
G1-B P+5 G4-B
To Input Inductor

56R 10W 2 Q2 Q5 2

13
12

12
13
H1 E1-B E4-B
Inductor
SK60GB128 R99 SK60GB128

1
6.8K R184 D41

6
5

5
6
ACS754
1
2
3

E2-T 27 28 G2-T G5-T 28 27 E5-T


R64 FS2 24 CN3 100K 0.25W 24 FS21
FS8 4 5 L2 FS5 23 AUX_CONV +DC 4 To Aux. 1N4148 23 L2
L2-INPUT L2 1 3 1

12
56R 10W 2
G2-B
Q3 2
Conve rte r D42
REF
Q6
G5-B
2

13
12

12
13
H2 E2-B CS0153 E5-B
SK60GB128 AUX_CONV -DC 1 SK60GB128
R185

6
5

5
6
ACS754
1
2
3

E3-T 27 28 G3-T 1N4148 G6-T 28 27 E6-T


R65 FS3 24 DC BUS 100K 0.25W 24 FS22

2
FS9 4 5 L3 FS4 23 R100 23 L3
L3-INPUT L3 1 G3-B 6.8K G6-B 1
56R 10W 2 E3-B R186 + E6-B 2
H3 C62
3xDSMxxx To Inverter

2
C39 R97 R98 R181 100K 0.25W 10µF 16V C43

6
5

5
6
ACS754 2.2µF PHB 2.2µF PHB Inductor
735-3A-C-T SONG CHUAN 850V 850V
150K 0.25W 150K 0.25W 150K 0.25W R187
K1

1
9 16_-DC-BUS 100K 0.25W
6
A-BATT_POS
8 H7
5 1 C70
+5V
2 47nF 1 F4 3
BATTERIA

To AC 7 0V A-BATT_NEG TO PAGE 4 FS15 2 4


Capacitors 4 3 -DC 32A 10x38
OUT
LEM DI

C69
4 4.7nF
FS48 VREF TP29 TP30 TP31
17_A-BATTERY
L1 P+15 5
CE C68 R130
6 47nF 10 0.25W
FS49 NC
L2 R191 D37 HAIS 50-P FROM
2
1

47 1W 1N4007
PAGE F42
FS50 1 2 DRV_Precharge-MAINS P+15 3
DRV_Precharge-MAINS VOUT_L1_FAN
L3 1 F1 3
D45 R195 FS11 2 4 1A 250V
2 1 1.5K 0.25W - BATTERY 32A 10x38
Y ellow CN2
INPUT MAINS

AUX_MAINS-L1 5
4 To Aux.
AUX_MAINS-L2 3 R194
Conve rte r

5
2 47R 1W K7
AUX_MAINS-L3 1 CS0153 P+15 R189 R190
N.O. 22R 5W 22R 5W
HF supply 1
C42 TO PAGE 1
HF supply 2

1
R89 R90 R117 D44

2
1

4
06_V-MAINS_L1 R66
06_V-MAINS_L1 1000pF
100 R67 1N4007
27K 0.25W 27K 0.25W 27K 0.25W P+15 FAST-SPEED
1K

2
R91 R92 R118 U1 FS42 C63
07_V-MAINS_L2
To Connector 13 16
R68
07_V-MAINS_L2 Page 4 VC VREF
15 2 Q7
27K 0.25W 27K 0.25W 27K 0.25W C44 + VCC +V 22 5W
IRFD110

2
10µF 9 1 3 PHASE_FAN 4.4 uF 250Vac MAB
R93 R94 R119 1 COMP T7
-V R69 47
08_V-MAINS_L3 12 14 3 6 220Vac Fan
08_V-MAINS_L3 GND OUTB 2
27K 0.25W 27K 0.25W 27K 0.25W 5 5 Supply FS51 C64

4
R71 6 CT 1
7 RT
DISC R72 47
11 4
47 OUTA AUX FAN 3uF 250Vac MAB
C45 3 4 VAC4097X055
R74 8 SY NC OSC 10 +
1nF CSS SD C46 FS41
5.6K

2
SG3525 Q8 1 100µF 35V
+ C47
10µF DRIVERS SUPPLY 3
NEUTRAL_FAN
IRFD110

4
Page. 67 of 73
From Inverter Inductor
FS23 FS24 FS25
L3 L2 L1

To page 4
12_V-OUT_L1
A-OUT_POS
13_V-OUT_L2
A-OUT_NEG
14_V-OUT_L3
21_A-OUT_L1 To page 4

12_V-OUT_L1

13_V-OUT_L2

14_V-OUT_L3
A-INV_POS
22_A-OUT_L2
A-INV_POS

C51 23_A-OUT_L3
H6
ACS754
4

R127

21_A-OUT_L1

22_A-OUT_L2

23_A-OUT_L3
A-OUT_NEG
A-OUT_POS
3 0.1µF 05_A-INV_L3
05_A-INV_L3
2 R126 R125 R124
1 C52 10 0.25W
H5 27K 0.25W 27K 0.25W 27K 0.25W
4

ACS754 R128
3 0.1µF 04_A-INV_L2 To page 4 R131 R132 R133
5

04_A-INV_L2
2
C53

10 0.25W

10 0.25W

10 0.25W
1 10 0.25W
4

R129 R78 R79 R82


3 0.1µF 03_A-INV_L1 27K 0.25W 27K 0.25W 27K 0.25W
5

03_A-INV_L1
2 A-INV_NEG
A-INV_NEG
1 10 0.25W

Powertronix spa reserves the right to modify this document without notice
C56 C55
H4 C54 0.1µF 0.1µF
ACS754 0.1µF R77 R80 R81
5

27K 0.25W 27K 0.25W 27K 0.25W

R&D – TECHNICAL SPECIFICATION DT0424-E01


R137 R88 R87

1
2
3
27K 0.25W 27K 0.25W 27K 0.25W
00_V-INV_L1 9 K4
6 4 5 FS29
To page 4

R138 R86 R85 L1-OUT

1
2
3
27K 0.25W 27K 0.25W 27K 0.25W H8
01_V-INV_L2 8 ACS754
5 4 5 FS30
R139 R84 R83 L2-OUT

1
2
3
27K 0.25W 27K 0.25W 27K 0.25W H9
02_V-INV_L3 7 ACS754
4 4 5 FS31
L3-OUT
H10
735-3A-C-T SONG CHUAN ACS754
TP27 FS32
NEUTRAL
FS26 FS27 FS28
L3 L2 L1 R192 P+15

1
2
D40 47 1W
DRV_SS-RELE_INV 2 1 FS47
NEUTRAL
TO A/C CAPACITORS P+15 1N4007 D46
D47 R197 1 2
2 1 UPS
1.5K 0.25W Green
Red 1.5K 0.25W R196 FS16 Output
D39 NEUTRAL
R193 1 2
DRV_SS-RELE_RES
1N4007

2
1
47 1W K5
VOUT_L1_FAN
735-3A-C-T SONG CHUAN To page 2
4
7
5
8
6
9
R101 R102 R120
AUX_RES-L1 18_V-RES_L1
CN4 18_V-RES_L1
5 27K 0.25W 27K 0.25W 27K 0.25W
To Aux. 4 R103 R104 R121
3 AUX_RES-L2 19_V-RES_L2
Conve rte r 2
19_V-RES_L2
CS0153 1 27K 0.25W 27K 0.25W 27K 0.25W
R105 R106 R122
To page 5
INPUT RESERVE AUX_RES-L3 20_V-RES_L3
20_V-RES_L3
TP28 27K 0.25W 27K 0.25W 27K 0.25W
R107 R108 R123
SIG_SY NCRO
SIG_SY NCRO
270K 0.25W 270K 0.25W 270K 0.25W
FS37 FS45 L3 L3-RES L2 L2-RES L1 L1-RES
NEUTRAL RES NEUTRAL RES FS38 FS34 FS39 FS35 FS40 FS36
RESERVE INPUT
Page. 68 of 73
J4 J5
ISO_N-15 ISO_N-15
1 1 ISO_N-15 TP36
2 2 ISO_N-15
06_V-MAINS_L1 06_V-MAINS_L1 ISO_P+15 ISO_P+15
3 07_V-MAINS_L2 3 ISO_P+15
4 07_V-MAINS_L2 4 ISO_P+15
08_V-MAINS_L3 08_V-MAINS_L3 CN1 2 OVER-85TMP_ALL OVER-85TMP_ALL
5 5 OVR TEMP 1
6 18_V-RES_L1 6 TP37
7 18_V-RES_L1 7 DRV_L1-TOP_INV
19_V-RES_L2 19_V-RES_L2 DRV_L1-BOTT_INV
8 20_V-RES_L3 8

Powertronix spa reserves the right to modify this document without notice
9 20_V-RES_L3 9 DRV_L2-TOP_INV
DRV_L2-BOTT_INV CN5 2 SPARE_1
10 10 SPARE_1
00_V-INV_L1 00_V-INV_L1 DRV_L3-TOP_INV Spare_1 1
11 11

R&D – TECHNICAL SPECIFICATION DT0424-E01


01_V-INV_L2 01_V-INV_L2 DRV_L3-BOTT_INV
12 02_V-INV_L3 12
13 02_V-INV_L3 13 DRV_L1-TOP_ING
DRV_L1-BOTT_ING P+15
14 12_V-OUT_L1 14 R140 1K TP32
15 12_V-OUT_L1 15 DRV_L2-TOP_ING
13_V-OUT_L2 13_V-OUT_L2 DRV_L2-BOTT_ING CN6 2
16 14_V-OUT_L3 16 MODULE TEMP 1 24_MODULE_TEMP
17 14_V-OUT_L3 17 DRV_L3-TOP_ING 24_MODULE_TEMP
18 18 DRV_L3-BOTT_ING
A-MAINS_POS A-MAINS_POS P+15
19 19
TO CONTROL LOGIC

09_A-MAINS_L1 09_A-MAINS_L1 R141 1K TP33


TO CONTROL LOGIC

20 10_A-MAINS_L2 20 DRV_Precharge-MAINS CN7 2


21 10_A-MAINS_L2 21 DRV_Precharge-MAINS
11_A-MAINS_L3 11_A-MAINS_L3 DRV_SS-RELE_INV DRV_SS-RELE_INV INT-BATT_TEMP 1 25_INT-BATT_TEMP 25_INT-BATT_TEMP
22 A-MAINS_NEG 22 DRV_SS-RELE_RES
23 A-MAINS_NEG 23 DRV_SS-RELE_RES
A-INV_POS A-INV_POS P+15
24 03_A-INV_L1 24 R143 1K TP35
25 03_A-INV_L1 25
04_A-INV_L2 04_A-INV_L2 SIG_Sy ncro SIG_Sy ncro CN9 2
26 05_A-INV_L3 26 FAST-SPEED EXT BATTERY TEMP 1 26_EXT-BATT_TEMP
27 05_A-INV_L3 27 FAST-SPEED 26_EXT-BATT_TEMP
A-INV_NEG A-INV_NEG ENABLE _DC/DC ENABLE _DC/DC
28 A-OUT_POS 28 OVER-85TMP_ALL
29 A-OUT_POS 29 OVER-85TMP_ALL
21_A-OUT_L1 21_A-OUT_L1 SPARE_1 SPARE_1
30 22_A-OUT_L2 30 AUX_BY -PASS_ON
31 22_A-OUT_L2 31 AUX_BY -PASS_ON
23_A-OUT_L3 23_A-OUT_L3 SPARE_2 SPARE_2
32 A-OUT_NEG 32 J7
33 A-OUT_NEG 33 P+15
34 16_+DC-BUS 34 1 P+15
35 16_+DC-BUS 35 P+7.5 2
36 16_-DC-BUS 36 3
37 16_-DC-BUS 37 P+5 4
38 A-BATT_POS 38 5 P+7.5
39 A-BATT_POS 39 6
17_A-BATTERY 17_A-BATTERY
40 A-BATT_NEG 40 7
41 A-BATT_NEG 8
42 24_MODULE_TEMP FLAT 40VIE 9
43 24_MODULE_TEMP FROM AUX 10
44 CONV ERTER 11
25_INT-BATT_TEMP 25_INT-BATT_TEMP
45 12
46 26_EXT-BATT_TEMP 13 ENABLE _DC/DC
47 26_EXT-BATT_TEMP 14 ENABLE _DC/DC
48 15
49 16 ISO_P+15
50 17
18 ISO_N-15
FLAT 50 VIE 19
20
FLAT 20VIE
Page. 69 of 73
TP1
R1 +POSITIVE
A

DRIVERS&FEEDBACK
47 2W
R2 33
R3
100K TP2

TO INVERTER
1W C1 Q1
8 TP3 C2 1µF K1119 2
REF 10µF 50V
R4
1

1 3 TP4
+

6 330 C3
R5 PWM

1
220µF 220µF 220µF

BYT11-1000
D1 1µF D3 200W D4 J7
PK-Curr

1
C4 1N4148 1.5K T1 DZ1 2 1 50V 50V 50V
1µF f errite philips R8
80KHz TP9 1
TP5 R6
1 3 TP6 1/13_1/6.5 MUR1540 P+15 2
2

100K 3
1W D2 ° ° 10K 15V C8 C5 + C6 + C7 +

Powertronix spa reserves the right to modify this document without notice
400 / 800 Vdc

R9 4
3 1N4148

2
C9 1nF CURR R10 4700pF 5
2
6.8K T2 6
4 10 2 4 2000V 2 5 C10 P+7,5
RC 7

R&D – TECHNICAL SPECIFICATION DT0424-E01


R11 R12 C12 8
C28 C11 U1 1K TP8 D5 0.1µF
0.47µF 0.47µF PT0 1 UC3844 100K R13 33 MUR1540 9
VE 1W 1µF 10
MABA01 MABA01 TP10 1 6 2 1
Q3 11
C13 R15 K1119 2 C17 C15 TP7 12
R14 33K D6 R16 330 D7 C14 + + 220µF C16 13
ENABLE_DC/DC 14
4.7K 1nF 7 1 2 2 1 1 3 4700pF TP11 220µF 50V 0.1µF
VCC 15

PK-Curr
2000V 7 50V

BYT11-1000
R17 16

1
2 BY T01400 1N4148 D8 8
IN D9 17

1
C18 BYT01400
1K 18
1nF DZ2 1 23 TP12
GND

VFBK 19

1,8
C19 + R46 R20 15V D10

1,8

1,8
R18 33K 2.2K + 4 9 2 1 20

2
1K 330µF VFBK C20 FLAT 20VIE

2
f errite philips
35V 10µF MUR1540 C23 ISO_P+15
5

50V +
B C22
R21 R22 R23 0.1µF TP14
220µF
-NEGATIVE 50V
A TP15
TP13
ISO_N-15
C21 1µF
D11 D12
2 1 1 2
P+15
1

D14 D15 D16 1N4007 1N4007


Power Supply Board

1N4007

1N4007

1N4007

C31 R41
R27 1µF 10K P+7,5 P+15
2

100K 1W R30
1.5K
R31

2
1.5K
R25 R26
F4 1 TP20 D23 100 220
1

1A
1N4007

1N4007

Q6 2 LED green
1N4007

D19 D20 D21

1
3
F5 F3 R33 2N2907 DZ3

2
TP19

1N4148
1A 1A 100K 1W 3 15V

1N4148
2 Q8 ISO3 D17 D18
2

2
5
4
3
2
1

1 2N2222 5 1 DZ4

2
CN2 TP18 R44 1K ISO1 8.2V
1

4 2 5 1 2 1

1
D24 D25 D26 ENABLE_DC/DC VFBK
R S T
1N4007

1N4007
1N4007

DZ6 ISO4 R45 10K R47 470K 4N35 4 2


PT0
INPUT MAINS 1 2 1 5

6
2
R38 C30 R43 4N35 2 1
2

2
2 4 10K D32 C32 1µF

6
24V 1µF 1N4148 C24 1uF DZ5
4N35 10K 18V

6
R37 TP21

1
C29
47K 1µF
1

1N4007
C33 1µF F1 CN3
D27 D28 D29

1N4007

1N4007
4
F7

DC BUS
3
1A D30 D31 1A 5x20 2
F6 F8 1 2 2 1 1

2
1A 1A
1N4007 1N4007 F2 1A 5x20
5.1.9 DE0153

B
5
4
3
2
1
TP17
CN4
R S T
INPUT RESERVE
Page. 70 of 73
BROXING BROXING BROXING BROXING
PW13 PW12 PW10 PW9
FS32 FS33 FS34 NEUTRAL FS21 FS22 FS23 PW11 FS24 FS25 FS26 FS27 FS28 NEUTRAL
FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M NEUTRAL GROUND FASTON-M FASTON-M NEUTRAL FASTON-M FASTON-M FASTON-M
PW14
GROUND
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11
32A 10x38mm 32A 10x38mm 32A 10x38mm 32A 10x38mm 32A 10x38mm 32A 10x38mm 32A 10x38mm 32A 10x38mm 32A 10x38mm 32A 10x38mm 32A 10x38mm
C1
1µF

Powertronix spa reserves the right to modify this document without notice
275Vac
C30 X2
1µF 0.47µF 0.47µF 0.47µF 1µF 0.47µF 0.47µF 0.47µF 1µF 0.47µF 0.47µF 0.47µF 0.47µF 0.47µF

R&D – TECHNICAL SPECIFICATION DT0424-E01


C2 275Vac C3 275Vac C4 275Vac C5 275Vac C6 275Vac C7 275Vac C8 275Vac C9 275Vac 275Vac C10 275Vac C11 275Vac C12 275Vac C13 275Vac C14 275Vac
X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2
FS38 FS37 FS36 FS35 FS20 FS19 FS18 FS17 FS16 FS15 FS14 FS13 FS12 FS11 FS10
FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M
BROXING
PW7 PW8
NEUTRAL GROUND
BROXING BROXING BROXING
H-F Filter Mizar

FS29 FS30 FS31 PW2 FS1 FS2 FS3 PW3 FS4 FS5 FS6 FS7 FS8 FS9 PW5
FASTON-M FASTON-M FASTON-M NEUTRAL FASTON-M FASTON-M FASTON-M NEUTRAL FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M FASTON-M NEUTRAL
82K 2W 82K 2W
PW4
C15 1µF R1 C17 R2 C18 R3 C19 1µF R4 C21 R5 C22 R6 GROUND C29 R8 R9 C26 R10 C27 R11 C28
R7
275Vac 82K 2W 82K 2W 82K 2W 275Vac 82K 2W 82K 2W 82K 2W 1µF 82K 2W 82K 2W 82K 2W 1µF
X2 C16 X2 C20 275Vac C23 C24 C25 275Vac
X2 X2
1µF 1µF 1µF 1µF 1µF 1µF 1µF 1µF 1µF 1µF 1µF
275Vac 275Vac 275Vac 275Vac 275Vac 275Vac 275Vac 275Vac 275Vac 275Vac 275Vac
X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2
BROXING
PW1 M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15
5.1.10 DE0154

PW6
GROUND L1-I L2-I L3-I N-I L1-R L2-R L3-R N-R + BATTERY - BATTERY COMM. L1-O L2-O L3-O N-O GROUND
RETE PRINCIPALE RETE DI RISERVA BATTERIA USCITA UPS
MAINS RESERVE BATTERY LOAD
Page. 71 of 73
EPO
MOLEX-2
P+5 P+5 CN1
TP1
T4 T3 T2 T1 P+5
U2
DOWN-Back UP-Next Home Clear 1 3
R1 R2 7805
330 330 TP2 + C1 C2 + C3 C4
10µF35V 1µF 10µF35V 1µF

2
BZ1
LD1 LD2 BUZZER
green red

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01


P+5
Q1
BACK-LIGHT R16
2N2222 1K
R17 RS R21
10K 1.5K
R19 R20
R/W 1.5K 1.5K
R25
EN 1.5K R18
1.5K
R24 J1
1.5K
26
25
R23 24
R3 DB0 1.5K 23
10R 22
21
20
R22 19
LCD Mimic Display

1.5K 18
17
16
R27 15
DB1 1.5K 14
13
12
1 11
JP1 2 R26 10
3 R29 1.5K 9
1.5K 8
DB2 R31 7
1 DB3 1.5K 6
JP2 2 DB4 R28 5
3 DB5 1.5K 4
DB6 R30 3
DB7 1.5K 2
CONTRAST 1
P+5 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16 C17 CON26
R33
C5 1nF 1nF 1nF 1nF 1nF 1nF 1nF 1nF 1nF 1nF 1nF 1.5K
+
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
R32
1µF35V 1.5K
J2/U3
R35
1.5K
Put a Label with following description:
5.1.11 DE0155

R34
Backlight Diode 1.5K
15=K-16=A -> CLOSE JP1 pin 2-3, JP2 pin 1-2
R37
15=A-16=K -> CLOSE JP1 pin 1-2, JP2 pin 2-3 1.5K
R39
1.5K
R36
1.5K
R4 P+5 R38
1.5K
P1 10K 10k
Page. 72 of 73
FORO 5.5mm FORO 5.5mm
metallizzato metallizzato
PW1 PW2 PW3 PW4 PW5 PW6 PW7 PW8 PW9 PW10 PW11 PW12 PW13 PW14 PW15 PW16 PW17
GROUND L1-I L2-I L3-I N-I L1-R L2-R L3-R N-R + BATTERY - BATTERY COMM. L1-O L2-O L3-O N-O GROUND
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11
50A 14x51mm 50A 14x51mm 50A 14x51mm 50A 14x51mm 50A 14x51mm 50A 14x51mm 50A 14x51mm 50A 14x51mm 50A 14x51mm 50A 14x51mm 50A 14x51mm

Powertronix spa reserves the right to modify this document without notice
C1
1µF
275Vac

R&D – TECHNICAL SPECIFICATION DT0424-E01


C10 X2
1µF 0.47µF 0.47µF 0.47µF 1µF 0.47µF 0.47µF 0.47µF 1µF 0.47µF 0.47µF 0.47µF 0.47µF 0.47µF
C2 275Vac C3 275Vac C4 275Vac C5 275Vac C6 275Vac C7 275Vac C8 275Vac C9 275Vac 275Vac C11 275Vac C12 275Vac C13 275Vac C14 275Vac C15 275Vac
X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2
PW29
NEUTRAL
PW30 PW31 PW32 PW33 PW34 PW35 PW36 PW37 PW38 PW39 PW40
FORO 5.5mm
FORO 5.5mm metallizzato
metallizzato
PW41 PW42
GROUND GROUND
inserto filettato maschio a saldare (broxing)
H-F Filter Alcor

PW43 PW44 PW45 PW46 PW47 PW48 PW49 PW50 PW51 PW52 PW53 PW54 PW55 PW56 PW57
82K 2W 82K 2W
C16 1µF R1 C18 R2 C19 R3 R4 C21 R5 C22 R6 R8 R9 C28 R10 C29 R11 C30
R7
275Vac 82K 2W 82K 2W 82K 2W 82K 2W 82K 2W 82K 2W 82K 2W 82K 2W 82K 2W 1µF
X2 C17 C20 C23 C24 C25 C26 C27 275Vac
1µF 1µF X2
1µF 1µF 1µF 1µF 1µF 1µF 275Vac 275Vac 1µF 1µF 1µF 1µF 1µF
275Vac 275Vac 275Vac 275Vac 275Vac 275Vac X2 X2 275Vac 275Vac 275Vac 275Vac 275Vac
X2 X2 X2 X2 X2 X2 X2 X2 X2 X2 X2
5.1.12 DE0161

PW58 M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15


PW59
GROUND L1-I L2-I L3-I N-I N-R L3-R L2-R L1-R + BATTERY - BATTERY COMM. L1-O L2-O L3-O N-O GROUND
FORO 5.5mm FORO 5.5mm
metallizzato metallizzato
RETE PRINCIPALE RETE DI RISERVA BATTERIA USCITA UPS
MAINS RESERVE BATTERY LOAD
5.1.13 DE1235 Battery String
Battery 7.2 – 9 Ah

From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up
to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah

POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG.

F2 F4

F1 F3

F2 F4

F1 F3
CS0143

CS0143
30A 80V 30A 80V

BATTERIES STRING LEFT


2
1

BATTERIES STRING RIGHT


1
2

30A 80V 30A 80V


CS0143

CS0143
F3 F1

F4 F2

F3 F1

F4 F2
NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS.

From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up From 7Ah up
to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah to 9Ah

Battery 4.5 – 5.2 Ah

NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS.

From 4.5Ah From 4.5Ah From 4.5Ah From 4.5Ah From 4.5Ah
up to 5Ah up to 5Ah up to 5Ah up to 5Ah up to 5Ah

F3 F1
30A 80V

1
2
CS0157
BATTERIES STRING LEFT
F4 F2
From 4.5Ah From 4.5Ah From 4.5Ah From 4.5Ah From 4.5Ah
up to 5Ah up to 5Ah up to 5Ah up to 5Ah up to 5Ah

POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG.

POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG.

From 4.5Ah From 4.5Ah From 4.5Ah From 4.5Ah From 4.5Ah
up to 5Ah up to 5Ah up to 5Ah up to 5Ah up to 5Ah

F3 F1
30A 80V

2
1
CS0157
BATTERIES STRING RIGHT
F4 F2
From 4.5Ah From 4.5Ah From 4.5Ah From 4.5Ah From 4.5Ah
up to 5Ah up to 5Ah up to 5Ah up to 5Ah up to 5Ah

NEG. POS. NEG. POS. NEG. POS. NEG. POS. NEG. POS.

Powertronix spa reserves the right to modify this document without notice

R&D – TECHNICAL SPECIFICATION DT0424-E01 Page. 73 of 73