Vous êtes sur la page 1sur 14

Engineering Structures 159 (2018) 213–226

Contents lists available at ScienceDirect

Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct

Critical load cases for lattice transmission line structures subjected to T


downbursts: Economic implications for design of transmission lines

Ashraf El Damattya, , Amal Elawadyb
a
Department of Civil and Environmental Engineering, Western University, London, Ontario, Canada
b
Department of Civil and Environmental Engineering, Florida International University, Miami, Florida, USA

A R T I C L E I N F O A B S T R A C T

Keywords: An extensive research program was recently conducted at The University of Western Ontario, Canada to in-
High Intensity Wind vestigate the load profiles that can be used in the analysis and the design of transmission towers subjected to
Transmission line downbursts. This research was motivated by many transmission line failures that have occurred in different
Conductor locations around the globe during downburst events. It was also triggered by the fact that the existing codes of
Downburst
practice and guidelines provide very limited information regarding the critical load profiles associated with
Critical loads
downbursts, which act on the towers and conductors of a transmission line system. One of the challenges in
Structural behaviour
predicting the critical forces acting on the towers and conductors is that they are not only dependent on the
magnitude of the event but also on its size and location relative to the center of the tower. This complexity
results from the localized nature of such events. In the current study, an extensive parametric study is conducted
on a number of transmission line systems to evaluate their critical response to downburst loads. The study
considers the variations in the downburst location, angle of attack, and size to determine the effect of changing
these parameters on the response of the transmission line systems. Based on the results obtained from this
parametric study, three critical load cases are identified. The studied towers are then used to assess the economic
impact of applying those load cases, expressed by the increase in the weight of the tower.

1. Introduction economic losses, the social implications for the affected society due to
such outage are tremendous.
A downburst is defined as a mass of cold and moist air that drops Downbursts have unique characteristics compared to synoptic
suddenly from a thunderstorm cloud base, impinges on the ground winds such as hurricanes and typhoons. One of those characteristics is
surface, and then horizontally diverges from the center of impact [1]. the localized nature of downbursts with respect to space and time. The
Past reports indicated that about 80% of the weather-related trans- wind field associated with downbursts is quite complicated as it varies
mission line failures have been attributed to High Intensity Wind (HIW) from one location to another depending on the distance from the
events in the form of downbursts and tornadoes [2]. In Canada, downburst center. The vertical profile of the downburst wind field also
McCarthy and Melsness [3] reported a series of transmission tower varies depending on the location. This profile can differ from the typical
failures under HIW events that belong to the Manitoba Hydro Company. boundary layer profile, which is currently used in the design codes. For
More recently, two 500 kV guyed towers failed during a severe thun- long span structures such as transmission lines in which towers and
derstorm in August 2006 belonging to Hydro One, Ontario, Canada conductors extend for many kilometers, the localized nature of the
(Hydro One failure report [4]). In the USA, a recent report released by downbursts might result in a non-uniform and unsymmetrical dis-
the Executive Office of the President [5] estimated that more than 600 tribution of the wind loads over the line spans. This results in load cases
power outages occurred due to severe weather. The report stated that that do not usually exist under uniform and symmetrical large-scale
the annual average of financial losses due to the weather-related wind events. Despite the large number of failures reported due to
outages over this period ranged between $18 billion to $33 billion. In downbursts and the unique characteristics of the downburst wind field,
China, Zhang [6] reported the failure of 18 (500 kV) and 57 (110 kV) the design codes do not provide enough information about critical
transmission line structures that occurred in 2005 under severe wind downburst loads, which should be considered in the design of trans-
events such as typhoons, tornadoes, and downbursts. In addition to the mission line structures. The purpose of this research is to fill in this gap.


Corresponding author.
E-mail address: damatty@uwo.ca (A. El Damatty).

https://doi.org/10.1016/j.engstruct.2017.12.043
Received 1 February 2017; Received in revised form 13 November 2017; Accepted 22 December 2017
Available online 08 January 2018
0141-0296/ © 2018 Elsevier Ltd. All rights reserved.
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

A limited of attempts to conduct downburst field measurements are


found in the literature. Wolfson et al. [7] reported the field measure-
ments of the FAA/Lincoln Laboratory Operational Weather Studies
(FLOWS) where different intensities and durations of downbursts were
recorded. Fujita [1] characterized the downburst wind field using the
field measurements of Northern Illinois Meteorological Research
(NIMROD) and the Joint Airport Weather Studies (JAWS). Hjelmfelt [8]
reported a number of individual and line microbursts in Colorado.
Recently, a number of downbursts were recorded, classified, and ana-
lyzed as a part of the Ports and Winds project in Italy [9–11]. Similarly,
Lombardo et al. [12] characterized the downburst wind events recorded
in Texas, USA for the period 2003–2010. Despite of the merit provided
in the mentioned studies regarding the analysis of the downburst flow
field parameters, turbulence characterization, and intensities, available
field measurements do not provide data for the spatial variation of
downburst which is fundamental for long span structures. Numerical
simulations of downbursts have be conducted using one of the fol-
lowing techniques: (a) Ring Vortex Model, (b) Impinging Jet (Impulsive Fig. 1. Downburst characteristic parameters.
Jet) Model, and (c) Cooling Source (Buoyancy-Driven) Model. The lit-
erature related to this subject includes a number of numerical studies and El Damatty [27] studied the behaviour of guyed and self-supported
conducted to characterize the downburst wind field. Zhu and Etkin [13] transmission line systems subjected to downburst loadings, respec-
used the ring vortex model to simulate the vortex ring formed during tively. Both studies were conducted in a quasi-static manner where the
the descent of the downburst. Vermeire et al. [14] used the cooling time variations of the mean component of the downburst field was
source model to examine the initiation of the event inside a cloud. Kim considered. The two studies reported possible loading scenarios of the
and Hangan [15] adopted the impinging jet approach using the Rey- downburst causing peak internal forces in the towers’ members. These
nolds Averaged Navier-Stockes (RANS) equations to simulate the studies showed that the spatial parameters of the downburst control the
downburst wind field. This yielded a time series of the mean radial and intensity of the loads imposed on the transmission line. Fig. 1 illustrates
vertical velocity components of the downbursts. Using the impinging jet the spatial parameters of the downburst that affect the loading acting
model, Aboshosha et al. [16] utilized the Large Eddy Simulations (LES) on a tower and the attached conductors. Those parameters are the
to account for the fluctuating component. In addition, a number of downburst jet diameter (DJ), the radial distance (R), and the angle of
experimental studies explored the downburst flow field using axisym- attack (ϴ). Wang et al. [28] conducted a quasi-static analysis where
metric jet impinging on a flat surface [17–20]. Most of the experimental they utilized an empirical lateral force model to assess the dynamic
studies utilized small geometries for the jet diameter, which limits the response of a high rise transmission tower, with no conductors at-
structural applications especially for long span structures such as tached, to downburst forces. Mara et al. [29] compared the load-de-
transmission lines. In order to simulate a relatively large-scale down- formation curve of a transmission tower when subjected to both
burst that can be used for structural applications, Lin and Savory [21] downburst and normal winds. Their study showed that normal wind
simulated downburst-like profile using a slot jet with a controllable gate capacity curves can be used as an approximate alternative for those
in boundary layer wind tunnel. Recently, the authors conducted a large- capacity curves resulting from downbursts. Elawady and El Damatty
scale experimental simulation of the downburst (diameter considered [30] assessed the longitudinal response of the conductors of transmis-
was 3.2 m) flow at the Wind Engineering, Energy and Environment sion lines to the oblique downburst cases. The oblique downburst
Research Institute (WindEEE RI) in Canada [22].” loading scenarios occur when the downburst acts with an angle of at-
The numerical, experimental and field measurements studies in- tack ϴ, illustrated in Fig. 1, where 0° < ϴ < 90°. In their study, Ela-
dicated that the mean component of the downburst winds varies with wady and El Damatty [30] provided a simple approach to estimate
time. As such, the mean component has been referred to as a “varying- conductor’s longitudinal forces using a number of charts and linear
mean” or “mobile-mean” [9,15,16,22,23]. Accordingly, a temporal interpolation equations. Yang and Zhang [31] analyzed two transmis-
decomposition needs to be applied to separate the mean and fluctuating sion towers under both normal and downburst winds. In their study,
components. In a number of studies, such as Aboshsosha et al. [16], Yang and Zhang [31] considered the wind loads acting on the con-
Elawady et al. [22], the mean component of the wind field was sepa- ductors as a simplified resultant vertical and lateral forces at the in-
rated from the turbulence component assuming that the cut-off fre- sulators’ connections while ignoring the spatial localization of the
quency is higher than the shedding frequency of the ring vortices. This downburst winds.
approach have shown a good agreement with the averaging periods The characterization of the downburst wind field showed that the
suggested by Holmes et al. [23] and Solari et al. [9] for particular frequency of the mean component of the wind field is less than 0.05 Hz
measured events. More discussion about downburst characteristics is [15]. This frequency is much less than the frequency of the towers,
provided in Section 2.1. which is typically higher than 1 Hz [32]. Darwish et al. [33] found that
Few studies focused on assessing the behaviour of transmission the conductors’ frequencies ranged between 0.06 and 0.1 Hz, which
tower systems under downbursts. The first study reported in the lit- indicates a potential sensitivity to dynamic excitations. Darwish et al.
erature was conducted by Savory et al. [24] in which they modelled a [33] utilized the field measurements reported by Holmes et al. [23] and
single self-supported tower with no conductors attached. In their study, extracted the turbulent component, which was assumed to not vary
the vertical profile of the downburst mean radial velocity was evaluated spatially. This was used to assess the dynamic response of the trans-
based on an analytical expression obtained from a wall jet simulation mission line conductors. The study showed that the aerodynamic
conducted used by Vicroy [25]. Savory et al. [24] reported that the self- damping of the conductors tends to attenuate its vibration and, there-
supported tower was more vulnerable to tornadoes than to downbursts. fore, no dynamic response is anticipated for the conductors. This was
Probably this conclusion resulted from the exclusion of the conductors confirmed by Aboshosha and El Damatty [34] who showed that the
in the numerical modelling. Downbursts are significantly larger than transverse and the longitudinal forces transmitted from the conductors
tornadoes and as such they are expected to engulf a larger portions of to the tower increased by only 5% and 6%, respectively, with the
the conductors compared to tornadoes. Shehata et al. [26] and Darwish

214
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

inclusion of the dynamic effect. In Elawady et al. [22], the dynamic 100
response of an aero-elastic model of a multi-spanned lattice transmis- R/DJ=1.1
80 R/DJ=1.1
sion line subjected to downburst loads simulated at the WindEEE dome

Elevation (m)
was assessed. The study showed that for the typical range of downburst 60 R/DJ=1.2
R/DJ=1.2
velocities (50–70 m/s), the dynamic response of the conductors and the
tower was in the order of 15% and 10%, respectively. This observation 40
agrees well with the results reported by Aboshosha and El Damatty R/DJ=1.3
R/DJ=1.3
20
[35], Lin et al. [21], Loredo-Souza and Davenport [36], Darwish et al.
[33], Gani and Legeron [37], Battista et al. [38], and Hamada et al. 0
[39]. Taking into consideration the considerable uncertainty sur- 0 0.2 0.4 0.6 0.8 1 1.2
rounding downburst critical loadings, due to spatial and temporal lo- VRD /VJ
calization, one can assume that the quasi-static response of the line
provides a sufficient representation of the line response. Fig. 2. Radial velocity profile along the height.

The objectives of the current study can be summarized as follows: (i)


study the behaviour of a spectra of transmission line systems subjected 200
to different downburst loading configurations; (ii) identify a number of 180
critical downburst configurations that can be generalized to apply to 160
lattice tangent transmission lines; (iii) propose wind profiles for both

Elevation (m)
140
the towers and the conductors associated with those critical downburst 120
configurations, and (iv) study the economic implications of considering 100
R/DJ=0.0
R/D
the proposed load cases in the design of the towers. J=0.0
80
The current paper starts by describing the methodology used in the R/D J=1.0
R/DJ=1.0
60
study including a description of the numerical model and the applied R/D J=1.1
R/DJ=1.1
40
techniques. This is followed by a description of the transmission line R/DJ=1.2
R/D J=1.2
systems used in the conducted parametric studies. In the results section, 20
R/D J=1.3
R/DJ=1.3
an explanation of the behaviour of the studied transmission line systems 0
-0.4 -0.2 0 0.2 0.4 0.6 0.8
under downburst loads is provided. Based on the behaviour observa-
VVR/VJ
tions, the study proposes a number of critical load cases simulating the
critical effect of downbursts on transmission line structures for possible Fig. 3. Axial velocity profile along the height.
implementation in the codes of design. An economic study is then
conducted to assess the implication of applying those load cases on the assess the capacity of a transmission tower. The study showed that the
increase in the weight of the towers. Finally, the conclusions reached wind direction affects the force-deformation relationship. The study
from the entire study are presented. also showed that the capacity curves of transmission towers subjected
to synoptic winds can be used for the cases of downburst winds.
2. Methodology The variations of the mean radial (VRD) and vertical (VVR) velocities,
both normalized by the downburst jet velocity, along the height are
2.1. Downburst wind field provided in Figs. 2 and 3, respectively. Fig. 2 shows that the absolute
maximum value for the radial velocity component occurs when R/DJ is
The current study utilizes the downburst wind field developed and 1.3. This maximum VRD occurs at an elevation of approximately 50 m,
validated by Kim and Hangan [15]. This Computational Fluid Dynamics which is the typical height for high voltage transmission towers. The
(CFD) simulation provides a time series of the mean wind speed in both figure also shows that the absolute maximum radial velocity is ap-
the radial and vertical directions for a small-scale model. The current proximately equal to 1.15 VJ. This means that for a jet velocity of 50 m/
study uses the scaling-up procedure proposed by Shehata et al. [26] for s, one would expect a maximum radial velocity to be about 57.5 m/s.
the CFD data in order to estimate the spatial and time variations of the For the vertical velocity component, Fig. 3 shows that the maximum
wind velocities associated with full-scale downbursts. value for the vertical velocity occurs at R/DJ = 1.0. Although this dis-
An assumption has been made in the analysis in order to account for tance ratio is close to those ratios corresponding to the maximum radial
the background component of the response by scaling-up the mean velocity, the elevation of the maximum vertical velocity at R/DJ = 1.0
component of the radial velocities, which is provided by the utilized is about 150 m. At the typical height of a transmission tower, the ver-
CFD model, to the gust wind speeds. This means that the resonant tical velocity component is in order of 0.2 VJ, which is less than 20% of
contribution to the total response of the transmission line systems the maximum radial velocity (1.15 VJ). Based on the fact that the wind
subjected to downburst winds is assumed to be small and accordingly is forces are proportional to the square of the velocity, the vertical forces
neglected. This assumption coincides with the findings of the authors’ in the critical downburst range will be significantly less than the radial
previous research [22,30] and many other researchers including, forces, and thus can be ignored.
among others, Choi and Hidayat [40], Lin et al. [21], Loredo-Souza and Fig. 4 shows the time variations for the radial velocity components
Davenport [36]. The magnitudes of the velocity components depend on at DJ = 500 m and R/DJ = 1.3. The figure demonstrates the localized
the jet diameter (DJ), and the jet velocity (VJ). They also vary tempo- nature of the downburst wind field in time. Therefore, an attempt
rally and spatially depending on the distance (R) measured relative to should be made to identify the time instant corresponding to the
the center of the downburst. Shehata et al. [26] showed that for dif- maximum radial velocity. Shehata et al. [26] stated that the time of
ferent DJ values, the maximum radial velocity was found to be constant maximum radial and/or axial velocity depends on both the jet diameter
at the same R/DJ ratio while the time instant of that maximum radial and the jet velocity.
velocity varied with DJ. Therefore, in different structural studies, such
as those conducted by Shehata et al. [26], Shehata and El Damatty [32],
Darwish and El Damatty [27], the distance ratio factor (R/DJ) was used 2.2. Modelling technique and method of analysis
to assess the structural behaviour of transmission line systems under
different downburst configurations. Mara et al. [29] utilized the peak The current study utilizes the numerical models developed by
vertical profile of the radial component of the downburst in order to Shehata et al. [26] and Aboshosha and El Damatty [41] and validated

215
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

1.2

1 Maximum Peak 45

0.8 40
VRD/VJ

35
0.6
30

Height (m)
0.4
25
0.2 Minimum Peak
20

0 15
0 100 200 300 400
Time (sec) 10

Fig. 4. Time history of the radial velocity at a point in space. 5


20
0 10
by Elawady [42] to analyze the performance of the tower and the 30 20 0
10 0 -10 Y (m)
conductors, respectively. The tower members are modelled using two- -10 -20 -20
X (m) -30
nodded three-dimensional frame elements with three rotational and
translation degrees of freedom at each node. The conductor’s behaviour Fig. 5. Transmission Line System (G1).
is estimated using the semi-analytical solution developed by Aboshosha
and El Damatty [41], which accounts for the conductor’s geometric ϴ within the following range:
nonlinear behaviour, the pretension force, the sagging, and the in- – DJ = 500–2000 m with an increment of 250 m.
sulator’s flexibility. Three spans on either side of the tower of interest – R/DJ = 0–2.0 with an increment of 0.1.
are modelled. Shehata et al. [26] has shown that this number of spans is – ϴ = 0–90° with an increment of 15°.
sufficient for an accurate prediction of the forces transmitted from the (i) The absolute peak internal forces are obtained from the entire
conductors to the tower of interest due to downburst loading. A full parametric study, which covers all of the potential downburst
description of the conductor analysis technique is described by configurations. The downburst configurations associated with those
Aboshosha and El Damatty [41]. This technique has proven to be peak forces are then recorded.
computationally efficient compared to typical nonlinear finite element
analysis. The sequence of the analysis to predict the maximum response
2.3. Structural characteristics of analyzed transmission line systems
of a transmission line structure under downbursts is as follows:

This studied transmission line systems consider the variations in: (1)
(a) A specific downburst configuration is selected based on assumed
the structural systems (guyed and self-supported), (2) the tower and
values for DJ, R/DJ, and ϴ (see Fig. 1 for the description of these
cross arm configurations, (3) the conductors span and properties. The
parameters). Here VJ is assumed to be constant and equal to an
three dimensional view of the towers of the six line systems analyzed
arbitrary value of 70 m/s. This value represents the maximum ob-
and reported in this study are shown in Figs. 5–10. The height of each
served downburst velocity as reported by Fujita [1], Holmes and
tower, span of the wires as well as other conductors and ground wires’
Oliver [43], Orwig and Schroeder [44], and CIGRE [45]. The pro-
properties are summarized in Table 1.
posed critical downburst wind profiles are normalized with respect
Of the six towers, three are guyed and the other three are self-
to the jet velocity. Therefore, the proposed critical downburst wind
supported. The three guyed towers, G1, G2, and G3 have different
profiles can serve for any other value of a downburst jet velocity.
shapes. Tower G1 is slender and carries two conductors, while towers G2
More details are provided in Section 3.2.
and G3 are Y and V shapes, respectively, and they both carry three
(b) Based on the scaling procedure described by Shehata et al. [26], the
conductors. The heights of the three towers vary between 43.44 m and
velocity wind field is defined.
46.57 m and the wires’ spans vary between 400 m and 480 m. The self-
(c) The external loads acting on the tower of interest and the six span
supported towers S1 and S2 are similar in shape, and they each carry six
conductors associated with the downburst wind field are calculated
following the procedure described by Shehata et al. [26]. The es-
timated wind forces were recently validated by the authors against
experimental data [42].
(d) The non-linear response of the conductors is estimated using the
semi-analytical solution developed by Aboshosha and El Damatty
[41]. This leads to the evaluation of the reactions RX, RY, and RZ at
the location of the tower of interest, which are reversed to represent
the forces transmitted from the conductors to the tower in the case
of a specific downburst.
(e) The tower is analyzed under the combined effects of the conductor
forces and the joint forces acting directly on the lattice structure.
This leads to the evaluation of the internal forces in all members of
the tower.
(f) Steps (d) to (e) are repeated through the time history of the
downburst while the analysis is conducted in a quasi-static manner
as discussed above.
(g) The maximum internal forces obtained from the entire time history
analysis are then calculated.
(h) The analyses are repeated by varying the parameters DJ, R/DJ, and Fig. 6. Transmission Line System (G2).

216
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

40

30
Height (m)

20

10

20
0 20
-20 0 10
X (m) -20 -10
Y (m)
Fig. 7. Transmission Line System (G3). Fig. 10. Transmission Line System (S3).

conductors. However, a large difference exists between the wire spans


of the two towers (213.6 m for tower S1 and 450 m for tower S2). Tower
50
S3 carries three conductors and has a different cross arm configuration
compared to S1 and S2.
40 It is assumed that the six tower systems considered in the study
cover a wide variety of tower support systems, tower shapes, cross arm
configurations, number of conductors and conductors' spans. They
Height (m)

30 provide an accurate representation for high voltage lattice towers used


in the industry.
20
3. Results and discussion

10 3.1. Tower response

In view of the analysis results, the behaviour of the six transmission


0 line systems is explained with a focus on identifying the critical
5 downburst configurations. As mentioned earlier, the downburst con-
0 5 figurations are defined by the parameters DJ, R/DJ, VJ, and ϴ, respec-
-5 -5 0
X (m) tively, and an arbitrary value for the jet velocity of 70 m/s is selected.
Y (m)
The choice of the jet velocity will affect the magnitude of the internal
Fig. 8. Transmission Line System (S1). forces but will not affect the identification of critical downburst con-
figurations, which is the aim of this study. The results are presented by
50 dividing the tower systems into two categories; Guyed towers and Self-
supported towers. For each category, the behaviour is explained for two
groups of members; members located below the cross arm, and mem-
40 bers located within the cross arm zone.
Height (m)

30 3.1.1. Guyed towers


The following observations are found for the guyed towers G1, G2,
and G3.
20
3.1.1.1. Below the cross arm zone. The peak internal forces in most of
10 the leg members occur at a downburst configuration of ϴ = 90°, R/
DJ = 1.2–1.3, and DJ = 500 m. The peak internal forces in few other
members occur at another downburst configuration where ϴ = 0°, R/
0 DJ = 1.2, and DJ = 500 m. In order to visualize the loading associated
with the configuration of ϴ = 90°, the reader is referred to Fig. 1. For
4
2 ϴ = 90°, the radial velocity profile is parallel to the conductors while
0 5
-2 0 for ϴ = 0°, the radial velocity profile is perpendicular to the
X (m) -4 -5
Y (m) conductors. A guyed tower can be treated as an overhanging beam,
Fig. 9. Transmission Line System (S2).
where the cantilever portion is located above the guys-tower
attachment point. The conductor forces act on the cantilever portion
of the tower. In tower G1, it is clear that the conductor forces tend to

217
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

Table 1
Properties of selected towers.

Tower G1 G2 G3 S1 S2 S3

Type Guyed Guyed Guyed Self-supported Self-supported Self-supported


Span (m) 480 400 460 213.36 450 420
Height (m) 44.39 43.44 46.57 54.65 51.81 47.5
Width of conductor cross arm (m) 13.3 25.0 29.34 8.2 & 14.3 8.2 & 14.3 15.4
No. of conductors 2 3 3 6 6 3
No. of GWs 1 2 2 2 2 2
Single conductor weight (N/m) 28.97 7.98 8.67 28.97 20.14 32.7
Single conductor diameter (m) 0.0406 0.0215 0.0215 0.0345 0.034036 0.0527
No. of conductors 2 (0.48)a 4 (0.48)a 4 (0.48)a 1 1 2 (0.48)a
GW weight (N/m) 3.9 4.027 5.45 10.4 3.823 5.68
GW diameter (m) 0.009 0.0122 0.00953 0.0142 0.00978 0.0097
Insulator length (m) 4.27 4.27 4.27 2.44 2.44 4.9 & 5.9b
Conductor Sag (m) 20 16 14 3.9 19.5 15
Ground wire sag (m) 13.54 11 16 3 14 7.5
Modulus of elasticity/conductor (N/m2) 6.23E+10 6.48E+10 5.18E+10 1.86E+11 6.48E+10 7.03E+10
Modulus of elasticity/GW (N/m2) 1.86E+11 1.05E+11 2.0E+11 6.23E+10 1.05E+11 1.72E+11
Guy diameter (m)c 0.0165 0.0143 0.01905 N/A N/A N/A

a
Horizontal spacing.
b
V shaped insulator.
c
Galvanized steel wires.

reduce the bending moment acting on the members below the cross arm 3.1.2.1. Below the cross arm zone. For the leg members located below
zones, i.e., between the supports. For the case of ϴ = 90°, no radial the cross arms, the critical downburst configurations are found to be R/
velocity profile acts on the conductors which leads to maximum forces DJ = 1.2–1.3, ϴ = 0°, and DJ = 500–750 m. A self-supported tower
developing in the tower zones below the cross arm. This behaviour was behaves like a cantilever. As such, the peak straining actions in the
also described by Shehata and El Damatty [32]. On the other hand, for tower occur when both the tower and the conductors are fully loaded
towers G2 and G3, where one cross arm is used for both the guys and the by downburst wind forces, i.e., at ϴ = 0°. The leg members in Tower S2
conductors, the analyses show that the conductor’s forces have a experience the peak forces at an oblique angle of attack of ϴ = 15°. The
negligible effect on the tower members since a large percentage of properties of the conductors in tower S2 cause a strong longitudinal
the conductor’s forces transfers directly to the ground supports through force to develop in the conductors due to the oblique loading. More
the guys. As such, the conductor’s forces have a minimal effect on the elaboration on this finding is provided in the next section.
internal forces developing in the tower members. However, for those Similar to the response in the case of guyed towers, the diagonal
two towers, the aerodynamics of the tower face, which is perpendicular members experience their peak force at a downburst configuration
to the line direction, are larger than those of the tower face which is corresponding to R/DJ = 1.2–1.3, DJ = 500–1000 m, and ϴ = 0° or 90°
parallel to the line direction. Therefore, most of the shaft members depending on the plane in which each member is located. Similar to the
experience their peak internal forces at an angle of attack of 90°. leg members, a number of diagonals in tower S2 experience their peak
The diagonal members located below the cross arm zone are found internal forces when the downburst configurations are R/DJ = 1.3–1.5,
to experience peak internal forces at downburst configurations of R/ ϴ = 15–30°, and DJ = 500 m.
DJ = 1.2–1.3, DJ = 500 m, and ϴ = 0° or 90°. As stated by Shehata and
El Damatty [32], diagonal members located in a plane perpendicular to 3.1.2.2. Cross arm zone. The chord members of tower S1 and tower S3
the line, are critical under the configuration of ϴ = 0°; while members experience their peak internal forces under a downburst configurations
located in a plane parallel to the line are critical under the configura- of R/DJ = 1.2–1.3, DJ = 500–1000 m and ϴ = 0° or 90°. On the other
tion of ϴ = 90°. hand, oblique load configurations are found to be critical for such
members in tower S2. The analysis of tower S2 shows that the cross arm
members experience peak internal forces at downburst configurations
3.1.1.2. Cross arm zone. For tower G1, the chord members located in
of R/DJ = 1.5–1.6, ϴ = 15–30°, and DJ = 500–750 m.
the cross arm zone are found to experience peak internal forces with a
The presence of the downburst oblique cases indicates a strong
downburst configuration of R/DJ = 1.4–1.7, DJ = 500–1000 m, and
impact of the conductors’ longitudinal forces. The next section provides
ϴ = 15–45°. Such cases of ϴ, which are not equal to either 0° or 90°, are
an explanation of the significance of the conductor’s longitudinal forces
referred to as oblique cases. By referring to Fig. 1, the oblique cases
in the six studied tower systems.
mean that the downburst is closer to one side of the line than the other
side around the tower of interest. This means that the two spans
adjacent to the tower will be subjected to unequal wind loads. This 3.1.3. Conductor forces
leads to a difference in the tension forces developing in the left and An oblique downburst load configuration causes a longitudinal force
right spans resulting in a net longitudinal force acting on the tower to develop in the conductors and the ground wires. Fig. 11 illustrates
cross arms causing an out-of-plane bending moment. the direction of the conductor forces, which develop due to the oblique
Some other members in tower G1 and all the cross arm members in downburst scenarios. This figure shows that the transverse force, RY,
G2 and G3 have shown a critical response under non-oblique load acts in a direction that is perpendicular to the line direction; while the
configurations where ϴ = 0° or 90°, R/DJ = 1.2–1.3 while longitudinal force, RX, acts in a direction parallel to the line direction.
DJ = 500–750 m. The longitudinal force RX develops, simultaneously with RY, only when
the downburst attacks the line at an oblique angle. In the current study,
it is noticed that the oblique downburst configurations are critical for
3.1.2. Self-supported towers two of the towers, G1 and S2. In order to understand why those two
The following observations are made for the self-supported towers towers in particular are more vulnerable to the oblique downburst
S1, S2, and S3. configurations than the others, the magnitudes of the developed

218
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

RX Fig. 11. Conductor reactions under downburst


wind field.

RY
Y

Table 2 as well as a third configuration where ϴ has intermediate values be-


Downburst configurations causing maximum RX. tween 0° and 90° (oblique case). Other parameters associated with those
three configurations will be determined from the discussion carried
Tower Downburst configuration RX/T*
below.
G1 DJ = 960 m, R/DJ = 1.6, ϴ = 30 0.46 For ϴ = 90°, the downburst wind field is parallel to the line and
G2 DJ = 800 m, R/DJ = 1.6, ϴ = 30 0.9 therefore no conductor loads will result from this configuration. Loads
G3 DJ = 920 m, R/DJ = 1.6, ϴ = 30 0.72
will result only from the drag effect of the wind field on the tower
S1 DJ = 426 m, R/DJ = 1.6, ϴ = 30 0.09
S2 DJ = 900 m, R/DJ = 1.6, ϴ = 30 1.25 members. As such, the downburst diameter and distance leading to
S3 DJ = 840 m, R/DJ = 1.6, ϴ = 30 0.47 maximum wind profile on the tower are the critical parameters that
should be considered with this configuration. Investigation of the wind
field reveals that the maximum profile occurs for a distance ratio R/
longitudinal force RX in all the studied conductor cases are evaluated. DJ = 1.3. It also reveals that the smaller the diameter, the larger are the
They are then normalized by the conductors’ pretension force, T, in values of the wind profile. As such, the critical downburst parameters
order to get an indication of their severity. Table 2 shows the down- associated with the configuration ϴ = 90°, are the minimum value of DJ
burst parameters (DJ, R/DJ, and ϴ), which correspond to the maximum which is 500 m together with R/DJ = 1.3.
RX vales developing in the conductors. The analyses show that the For ϴ = 0°, the downburst wind field is perpendicular to the line. As
longitudinal force RX increases with the increase of the conductor’s such, both the tower and the conductors will be subjected to wind
diameter and the line’s span. Therefore, the conductors of towers G2 loads. Similar to the ϴ = 90°, the peak loads acting on the tower will
and G3 develop a higher RX than the conductors of G1. For the self- correspond to a configuration in which DJ = 500 m and R/DJ = 1.3.
supported towers, the table shows that the conductor forces of tower S2 The velocity profile along the conductors and consequently the con-
are significantly higher than those of tower S1 and S3. The span of line ductors’ loads will depend on one extra parameter, which is the ratio
S2 is approximately double that of S1, which results in a significant between the span and the jet diameter, L/DJ. To investigate the effect of
increase in RX. Although the spans of S2 and S3 are approximately equal, this ratio, Fig. 12 shows the radial velocity distribution along the two
the conductors used in line S3 are heavier and have longer insulators spans adjacent to a tower for different L/DJ ratios at ϴ = 0° and R/
compared to S2. These differences result in a reduction in the RX value DJ = 1.3. The larger the area enclosed by those velocity distributions,
that develops in line S3 compared to the longitudinal force in line S2. the higher are the transverse loads acting on the two conductors and
The effect of the conductors’ forces on the tower response is closely consequently the force transmitted to the tower. From the figure, it can
associated with the structural system of the cross arm. For the guyed be detected that the largest enclosed area corresponds to L/DJ = 0.25.
towers, the ratio (RX/T) is found to be 0.72 for G3, 0.9 for G2 and 0.42 The area enclosed by the profile corresponding to L/DJ = 0.5 is slightly
for G1. Only tower G1 is found to experience peak internal forces due to smaller. The reduction in the area for higher values of L/DJ is more
a critical RX developing in the conductors. This can be attributed to the significant. For the critical DJ value of 500 m, L/DJ = 0.25 will corre-
difference in the structural system of the cross arms used in G1, G2, and spond to a span of 125 m. This is quite small for high voltage trans-
G3. Towers G2 and G3 have a much wider cross arm. Therefore, the mission lines where the span typically exceeds 250 m. As such, L/
cross arm forces associated with ϴ = 0° are stronger in towers G2 and DJ = 0.25 is not deemed to be practical. It is therefore recommended to
G3 compared to G1. This effect tends to make the configuration ϴ = 0° consider the distribution corresponding L/DJ = 0.5. This will be the
more critical compared to the oblique case for systems G2 and G3. It can right distribution for a downburst having a jet diameter of 500 m acting
be observed that for G2 and G3, the guys are attached directly to the on a line with a span of 250 m. For larger spans, this distribution will be
cross arm. This tends to attenuate the twist effect resulting from the conservative for the critical downburst diameter of 500 m.
longitudinal force associated with the oblique case. However, the si- The third critical downburst configuration is called the “oblique
tuation is different with tower G1 where the guys are located at a level case” and it happens for intermediate values of ϴ between 0° and 90°.
lower than that of the conductor cross arm. This tends to make the cross This load case will typically affect the cross arm members. At this in-
arm very sensitive to the out-of-plane effect resulting from the long- termediate downburst location, the magnitude and distribution of ve-
itudinal force associated with the oblique case. locities and, consequently loads, along two spans adjacent to the tower
will be unequal. This will lead to a difference in the conductors’ tension
in two adjacent spans. This difference will lead to a net longitudinal
3.2. Proposed downburst load cases
force acting on the cross arm of the towers. As such, the critical oblique
downburst configuration is the one that would lead to maximum values
In view of the results of the parametric studies reported above, load
for this longitudinal force. In the extensive study conducted by Elawady
cases that simulate the critical effect of downburst events on a generic
and El Damatty [30], it was shown that the maximum longitudinal
tangent lattice transmission lines are identified and presented in this
forces occur at a downburst configuration having ϴ = 30° and R/
section.
DJ = 1.6, and L/DJ = 0.5.
The analyses reveal that three load cases will cover the situations
Based on this discussion, the velocity profiles acting along the tower
leading to peak internal forces in all members of a tangent lattice tower.
height and the line spans associated with the three critical
Those will correspond to two configurations with ϴ = 90° and ϴ = 0°

219
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

1.2 Fig. 12. Radial velocity distribution along line spans


at R/DJ = 1.3 and ϴ = 0°.

0.8
VRD/VJ

0.6
L/DJ=0.25
L/D =0.25
J

0.4 L/DJ=0.50
L/DJ=0.5

L/DJ=0.75
L/DJ=0.75
0.2
L/DJ=1.0
L/DJ=1.0

Conductor spans

configurations of the downbursts named herein as critical load cases, same approach described in load case 1. The calculated values for VeqT
are presented below. and VeqC are found to be equal to 1.10 VJ and 1.06 VJ, respectively.
The 3-s gust velocity is usually used as a reference for the downburst
events. Therefore, the studies conducted by Holmes et al. [23] and later
3.2.1. Load case#1: R/DJ = 1.3, ϴ = 90°, DJ = 500 m
by Aboshosha and El Damatty [46] reported a span reduction factor
This configuration represents the maximum velocity profile acting
that can be applied to account for the non-correlation in turbulence
on the tower in the direction perpendicular to the line’s direction. In
along the spans of the line. The relation between the length of the span
this load case, there are no forces acting on the conductors. The max-
and the span reduction factor of the downburst is provided in Fig. 16.
imum velocity profile along the height of the tower is provided in
Fig. 13. Equivalent uniform velocity distribution, VeqT is evaluated to
reproduce the overall effect of the non-uniform profile in order to fa-
3.2.3. Load case#3: R/DJ = 1.6, ϴ = 30°, L/DJ = 0.5
cilitate its application. This is done by first squaring the velocity profile
This configuration represents the maximum oblique velocity profile
to represent forces. VeqT is calculated that as the area enclosed by its
acting on the tower and the conductors. Fig. 17 shows the radial ve-
squared value as well as the first moment of the squared value at the
locity distribution along the tower height for both the transverse and
tower base are equal to or exceed the corresponding value associated
the longitudinal directions associated with this load case. Fig. 18 shows
with the non-uniform profile. The calculated value for VeqT is found to
the radial velocity distribution of the critical oblique downburst con-
be equal to 1.10 VJ.
figuration along the line spans associated with this load case. Similar to
the previous load cases, equivalent uniform velocities of VeqTT, and
3.2.2. Load case#2: R/DJ = 1.3, ϴ = 0°, L/DJ = 0.5 VeqTL, and VeqC are evaluated to replace the nonlinear velocity profiles
This configuration represents the maximum velocity profile acting in the tower’s transverse direction, the tower’s longitudinal direction,
on the tower and the conductors in the direction parallel to the line and the conductor’s transverse direction, respectively. The calculated
direction. The critical velocity profiles along the height of the tower as values for VeqTT, and VeqTL, and VeqC are found to be equal to 0.8 VJ and
well as along the spans adjacent to the tower of interest are given in 0.47 VJ, and 0.65 VJ, respectively. It is important to mention that the
Figs. 14 and 5–15, respectively. Equivalent uniform velocity distribu- value of VeqC can be only used to calculate the transverse reaction RY
tions, VeqT and VeqC, are evaluated to reproduce the overall effect of the under this load configuration. The longitudinal reaction RX depends on
non-uniform profiles in order to facilitate their application using the the conductor’s properties and the downburst velocity and therefore,

50 Fig. 13. Radial velocity distribution along tower


height- ϴ = 90°.
45
40 Velocity distribution along tower height-‫=ڧ‬90°
35
30
Height (m)

25
20 Equivalent velocity distribution-VeqT
15
10
5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
VRD/VJ

220
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

50 Fig. 14. Radial velocity distribution along tower


height ϴ = 0°.
45
Velocity distribution along tower height-‫=ڧ‬0°
40
35
Height (m)

30
25 Equivalent velocity distribution-VeqT
20
15
10
5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
VRD/VJ

requires conducting a nonlinear analysis for the conductors under non- 1.1

Span Reduction Factor


uniform loading. A set of graphs and an interpolation procedure that 1
takes into account the variation in loading and conductors’ properties 0.9
was developed by Elawady and El Damatty [30] to facilitate the eva-
0.8
luation of those forces manually.
0.7
Downburst Wind SRF-
0.6
Holmes et al. (2008)
3.3. Load cases validation 0.5
0.4
Three hypotheses have been made in order to propose the three 0 200 400
critical load cases discussed in the previous section. First, three critical Span Length (m)
load cases are selected out of the entire parametric study, which con-
Fig. 16. Downburst span reduction factor.
sisted of approximately 900 load cases, to represent the critical loading
scenarios anticipated for the tangent transmission towers subjected to
the downbursts. Second, the proposed load cases are then simplified
from nonlinear to linear wind velocity profiles to facilitate their ap- analysis shows that the internal forces developing in most of the tower
plications by practitioners. Third, the dynamic response of the tower members under the proposed simplified load profiles are either greater
and the conductors is assumed to be only background while neglecting than or equal to those resulting from the parametric study. The figure
the resonant response, which varies between 10 and 15% of the total shows that, for some members, the maximum internal force FP is
force [22]. These three hypotheses need to be validated. In this section, greater than the corresponding FC force by a value equal or less than
the forces developing in each member of the studied towers due to the 5%. By adding this error to the 15% increase expected from the re-
extensive parametric study (FP) are compared to those forces devel- sonant response, the proposed load cases can underestimate the values
oping in the members due to the proposed critical load profiles (FC). of the internal forces by a maximum of 20% of some members.
The comparison graphs are shown in Fig. 19. The vertical axes of these It should be noted that the peak forces developing in the members
figures represent the ratio between the envelopes of the forces experi- (FP) are based on the assumption of having an extreme loading scenario
enced by each member under the considered downburst configurations that takes place at a specific downburst diameter, at a specific location
(FP), approximately 900 load cases, to the envelopes of the forces in of the downburst relative to the tower and at a specific time. However,
those members under the three proposed simplified load cases (FC). The

1.2 Fig. 15. Radial velocity distribution over six con-


ductor spans ϴ = 0°.

0.8
VRD/VJ

0.6
VeqC

0.4
Tower of interest
0.2

Conductor spans

221
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

Fig. 17. Radial velocity distribution along tower


Velocity distribution along tower height-‫=ڧ‬30°-Y direction height at R/DJ = 1.5 and L/DJ = 0.5, and ϴ = 30°.
Velocity distribution along tower height-‫=ڧ‬30°-X direction
50
45
40 Equivelent velocity Equivelent velocity
35 distribution-Longitudinal distribution-
Height (m)

30 Transverse (Y)
25
20
15
10
5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
VRD/VJ

the probability that such a combination will simultaneously occur for a assumed in this study. The compression capacity of the tower members
specific tower is low. In addition, transmission line towers often possess is calculated based on the recommendations given in ASCE 10 [47] for
sufficient redundancy and ductility [29], which allows them survive angle cross sections.
beyond the local failure of some members. The above two reasons For a number of selected members, Table 3 identifies the critical
justify accepting the maximum ratio of 20% underestimated by the downburst load cases and the corresponding peak internal forces found
proposed load cases for few members. in each member (FDB). The table also shows the ratio between FDB and
the corresponding member capacity, FCapacity. The table shows that the
3.4. Economic implications ratio FDB/FCapacity randomly varies depending on the studied system
and the member locations. Table 4 shows the failed members, in red
In this section, the economic implications of considering the iden- and solid lines, in each of the studied towers due to the effect of the
tified downburst load cases in the design of the towers is assessed. The downburst loads. Table 5 summarizes the results of the economic study
change in the total weight of the towers resulting from considering where the increase of weight relative to the initial weight of each tower
those load cases is the parameter used to assess the economic im- is provided. The upgrade required for each of the studied towers to
plications. The three downburst load cases are used to evaluate the peak resist the downburst load cases is provided below:
internal forces developing in the tower members for the six considered
systems. Those internal forces are then compared to the members’ ca- 3.4.1. For the guyed towers
pacity. Since the downburst internal forces can switch from tension to Different zones require an upgrade for the three studied guyed
compression depending on the location of the downburst, the member’s towers. For G1 which was originally designed to resist a 32 m/s wind
capacity are assumed to be governed by their compression strengths speed, the analysis shows that the members located in the main body of
since they are usually less than the corresponding tensile strengths. The the tower below and above the cross arm zones do not need any up-
ratio between the internal force and the strength is evaluated for all grade. Out of 48 members in the cross arm zone, 22 members are found
members. When this ratio is found to exceed unity, the cross section of to need an upgrade. The total weight of the tower is increased by 3% in
the member is upgraded such that this ratio is slightly below unity. The order to resist the downburst loads. For tower G2 which was originally
weight of the upgraded towers is evaluated and compared to the initial designed to resist a 36 m/s wind speed, below the cross arm zone, 290
weight in order to assess the economic implication of designing the members are shown to experience internal forces exceeding their
towers to resist downburst loadings. A downburst jet speed of 50 m/s is strength capacities, while with the except of few diagonal members, the

1.2 Fig. 18. Radial velocity distribution over six con-


ductor spans at R/DJ = 1.5 and L/DJ = 0.5, and
ϴ = 30°.
1 ࣄ=30°

0.8
VRD /VJ

0.6

0.4
VeqC

0.2 Tower of interest

Conductor spans

222
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

Tower G 1 Tower G 2 Fig. 19. Load cases validation.


1.2 1.2

1.1 1.1

1 1
FP/FC

FP/FC
0.9 0.9

0.8 0.8

0.7 0.7

Member check Member check


Mean Mean
0.6 0.6
members members

Tower G 3 Tower S 1
1.2 1.2
Member check Member check
Mean Mean
1.1 1.1

1 1
FP/FC

FP/FC

0.9 0.9

0.8 0.8

0.7 0.7

0.6 0.6
members members

Tower S 2 Tower S 3
1.2 1.2
Member check Member check
Mean Mean
1.1 1.1

1 1
FP/FC

FP/FC

0.9 0.9

0.8 0.8

0.7 0.7

0.6 0.6
members members

rest of the cross arm members do not need any upgrade. The resulting 36 m/s wind speed, 156 members located in the tower’s main legs and
increase in the total weight of the upgraded tower is 23% compared to the girder are shown to exceed their strength capacities The upgrade of
the original design. For G3 which was originally designed to resist a those members results in a 14% increase in the total weight of the

223
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

Table 3 4. Conclusion
Results of the economic study.
An extensive parametric study is conducted to identify the critical
Member Type Downburst linear profiles FDB/FCapacity
downburst load cases acting on lattice transmission line systems. Six
Critical Load Case FDB (kN) % different transmission lines are analyzed with respect to several
downburst loads representing different tower systems, spans, heights,
Guyed tower G1
and conductor properties. The study investigates the effect of different
30P Chord* 2 −30 16
351P Chord 1 −98 35 parameters describing the downburst configuration on the internal
430P Guys Cross arm diagonal 2 −53 200 force of the tower members. For each transmission line system, the
437P Guys Cross arm diagonal 3 −42 227 parametric study considers varying the downburst jet diameter (DJ), the
Self-supported tower G2 distance ratio (R/DJ), and the angle of attack (ϴ). The behaviour of the
40P Chord 2 −144 103 studied towers under the considered downburst load configurations is
132P Chord 2 −753 442 explained and the following observations are made:
308P Chord 1 −237 139
−25
• The load configuration of ϴ = 90°, R/D
955P Cross arm chord 1 10
J = 1.3 results in maximum
Self-supported tower G3
longitudinal loads on the transmission towers. This load configura-
539P Chord 2 −220 110
726P Chord 2 −132 76 tion, which does not induce loads on the conductors, is found to be
352P Chord 2 −180 43 critical for guyed towers. This is because the guyed towers act as a
95P Cross arm chord 3 −144 115 hanging beam where the conductor forces reduce the maximum
Self-supported tower S1 bending moment acting on members located between the cross arm
217P Chord 1 −462 71 and the ground support.
434P
528P
Chord
Chord
1
1
−320
−272
62
45
• The load configuration of ϴ = 0°, R/DJ = 1.3 causes the maximum
transverse loads on the line. This load configuration is found to be
799P Cross arm chord 3 −13 9
critical for the self-supported towers where the tower behaves in a
Self-supported tower S2
manner that is similar to a free cantilever.

2P Chord 1 −686 295
41P Chord 3 −632 272
For both tower systems, either ϴ = 0° or 90° is found to be critical
52P Chord 1 −403 60 for diagonal members depending on the plane in which the diagonal
331P Cross arm chord 3 −72 138 members are located. For members located in a plane parallel to the
Self-supported tower S3 line direction, an angle of attack of ϴ = 90° is found to be critical;
85P Chord 1 −584 40
while for members located in a plane that is perpendicular to the
566P Chord 1 −481 31
725P Chord 1 −467 30 line direction, an angle of attack of ϴ = 0° is found to be critical.
928P Cross arm chord 3 −35 149 • In some cases, an oblique load case (at 0° < ϴ < 90°) is found to
be critical for members located in the cross arm zones. This result is
* Chord: vertical member below the cross arm zone. due to the large longitudinal forces transmitted to the towers in the
oblique load cases. Those forces result from the difference in the
tower. The significant increase in the weight required for G2 and G3 tension forces that develop in the conductor spans adjacent to the
compared to G1 is a result of their relative high flexibility. In addition, towers because of the uneven distribution of the external loads be-
the aerodynamics of G2 and G3 is much higher than that of G1 under the tween those spans.
critical load case of ϴ = 90° which is observed for the studied guyed
towers. This triggered higher downburst loads acting on the tower.
• The results of the parametric study are used to propose three critical
load cases, corresponding to ϴ = 0°, ϴ = 90°, and an intermediate
value for ϴ, respectively. An analysis is made to select the critical
downburst parameters for each case, in terms of jet diameter, dis-
3.4.2. For the self-supported towers tance to jet ratio and span to jet diameter ratio. The recommended
Tower S1 is found to sustain the three downburst load cases without velocity profiles along the height of the tower and along the spans of
any need for upgrade. For tower S2, 190 members in various locations the conductors are provided for the three critical load cases. Those
in the tower are shown to exceed their strength capacities. The upgrade profiles are found to have a nonlinear distribution and thus are
of the member’s cross sections results in 16.3% increase in the total simplified to equivalent uniform profiles to facilitate their applica-
weight of the tower. For tower S3, only 10 members, all located in the tion by practitioners. A validation of the simplified load cases is
cross arm zone, are shown to need an upgrade resulting in a 1% in- conducted by evaluating the internal member forces resulting from
crease in the total weight of the tower. Although the transmission tower applying the simplified velocity profiles and comparing them to the
system used in S2 is similar to that one of S1, a significant upgrade is corresponding values obtained from the extensive parametric stu-
estimated for tower S2 to sustain the downburst loads. This is due to the dies. The analyses show that considering the simplified velocity
high longitudinal force developing in the conductors of S2 compared to profiles can provide very close internal forces in the tower members
S1 and S3. In addition, the original design wind speed of S2 (34 m/s) was compared to these forces obtained from the extensive parametric
significantly lower than that of S1 (45 m/s) and S3 (40 m/s). study.
It is important to mention that the effects of the foundation beha-
viour and in particular the nonlinear soil-foundation interactions on the The economic implications of upgrading the resistance of the towers
response of transmission tower line systems have not been taken into of six studied transmission line systems to sustain the proposed down-
consideration in the structural and economic analyses of the current burst load cases are then assessed. A downburst jet velocity of 50 m/s is
study. The foundations are assumed to be rigid. This assumption may assumed. The ratio of increase in the weight of the upgraded towers
not be valid for cases of weak soils especially if the wind event is ac- relative to the initial towers is used to assess the implication of de-
companied by precipitation. In such events, the soil surrounding the signing the towers to resist the downburst loads. For the three guyed
foundation can be saturated resulting in higher vulnerability of the tower systems, the increase in weight is found to be 3%, 23%, and 14%,
transmission system to foundation failure. Further dedicated study is respectively. Meanwhile, for the towers of the three self-supported
needed to investigate the uncertainty arising from the soil-structure systems, this increase is found to be 0%, 16.3%, and 1%, respectively.
interaction for lattice tower structures during downburst events. The significant increase in the tower weight required for S2, 16.3%, is a

224
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

Table 4
Failed members under downburst load case of a jet speed equal to 50 m/s.

Table 5 References
Summary of the economic implications of the downburst.
[1] Fujita TT. The downburst : microburst and macroburst : report of projects NIMROD
Tower No. of failed Location of failed members Weight increase
and JAWS. Satellite and Mesometeorology Research Project, Dept. of the
members (%) Geophysical Sciences, University of Chicago; 1985.
[2] Dempsey D, White H. Winds wreak havoc on lines. Transm Distrib World
G1 22 Cross arms 3 1996;48(6):32–7.
G2 290 Main shaft chords 23 [3] McCarthy PMM. Severe weather elements associated with September 5, 1996 hydro
G3 156 Main tower shaft + cross arm 14 tower failures near Grosse; 1996.
S1 0 N/A 0 [4] Hydro One. Failure of towers 610 and 611, circuit X503E – 500 kV guyed towers
S2 190 All tower zones 16.30 near the township of Waubaushene; 2006.
S3 10 Cross arm 1 [5] Economic benefits of increasing electric grid resilience to weather outages.
Executive Office of the President, The White House; 2013.
[6] Zhang Y. Status quo of wind hazard prevention for transmission lines and coun-
termeasures. East Chin Electr Power 2006;34(3):28–31.
[7] Wolfson FTMM, DiStefano JT. Low-altitude wind shear characteristics in the
result of the high longitudinal force developing in the conductors Memphis, TN area. In: The 14th conference on severe local storms; 1985. p. 322.
compared to that found in S1 and S3. Meanwhile, the significant in- [8] Hjelmfelt MR. Structure and life cycle of microburst outflows observed in Colorado.
crease in the weight of G2, 23%, might be attributed to the low original J Appl Meteorol 1988;27(8):900–27.
[9] Solari G, Burlando M, De Gaetano P, Repetto MP. Characteristics of thunderstorms
wind speed used in the design of this tower. relevant to the wind loading of structures. Wind Struct Int J 2015;20(6):763–91.
[10] De Gaetano P, Repetto MP, Repetto T, Solari G. Separation and classification of
extreme wind events from anemometric records. J Wind Eng Ind Aerodyn
2014;126:132–43.
Acknowledgements [11] Burlando M, Romanić D, Solari G, Hangan H, Zhang S. Field data analysis and
weather scenario of a downburst event in Livorno, Italy, on 1 October 2012. Mon
The authors gratefully acknowledge Hydro One Ontario and the Weather Rev 2017;145(9):3507–27.
[12] Lombardo FT, Smith DA, Schroeder JL, Mehta KC. Thunderstorm characteristics of
Natural Sciences and Engineering Research Council of Canada (NSERC) importance to wind engineering. J Wind Eng Ind Aerodyn 2014;125:121–32.
for their in-kind support, their collaboration in this project, and for the [13] Zhu S, Etkin B. Model of the wind field in a downburst. J Aircr 1985;22(7):595–601.
financial support provided for this research. The authors are grateful for [14] Vermeire BC, Orf LG, Savory E. Improved modelling of downburst outflows for wind
engineering applications using a cooling source approach. J Wind Eng Ind Aerodyn
the valuable feedback received from the members of the ASCE-74 code
2011;99(8):801–14.
committee responsible for updating the transmission lines manual. [15] Kim J, Hangan H. Numerical simulations of impinging jets with application to
downbursts. J Wind Eng Ind Aerodyn 2007;95(4):279–98.

225
A. El Damatty, A. Elawady Engineering Structures 159 (2018) 213–226

[16] Aboshosha H, Bitsuamlak G, El Damatty A. Turbulence characterization of down- under downburst. Wind Struct Int J 2016;22(6):685–701.
bursts using LES. J Wind Eng Ind Aerodyn 2015;136:44–61. [32] Shehata AY, El Damatty AA. Behaviour of guyed transmission line structures under
[17] Donaldson R, Snedeker CD. A study of free jet impingement. Part 1. Mean properties downburst wind loading. Wind Struct Int J 2007;10(3):249–68.
of free and impinging jets. J Fluid Mech 1971;45(2):281–319. [33] Darwish MM, Damatty AAEI, Hangan H. Dynamic characteristics of transmission
[18] Didden N, Ho C-M. Unsteady separation in a boundary layer produced by an im- line conductors and behaviour under turbulent downburst loading. Wind Struct Int
pinging jet. J Fluid Mech 1985;160:235–56. J 2010;13(4):327–46.
[19] Letchford C, Mans C, Chay M. Thunderstorms—their importance in wind en- [34] Aboshosha H, El Damatty A. Engineering method for estimating the reactions of
gineering (a case for the next generation wind tunnel). J Wind Eng Ind Aerodyn transmission line conductors under downburst winds. Eng Struct 2015;99:272–84.
2002;90(12–15):1415–33. [35] Aboshosha H, El Damatty A. Dynamic response of transmission line conductors
[20] Sengupta A, Sarkar PP. Experimental measurement and numerical simulation of an under downburst and synoptic winds. Wind Struct Int J 2015;21(2):241–72.
impinging jet with application to thunderstorm microburst winds. J Wind Eng Ind [36] Loredo-Souza AM, Davenport AG. A novel approach for wind tunnel modelling of
Aerodyn 2008;96(3):345–65. transmission lines. J Wind Eng Ind Aerodyn 2001;89(11–12):1017–29.
[21] Lin WE, Savory E, McIntyre RP, Vandelaar CS, King JPC. The response of an [37] Gani F, Legeron F. Dynamic response of transmission lines guyed towers under wind
overhead electrical power transmission line to two types of wind forcing. J Wind loading. Can J Civ Eng 2010;37(3):450–65.
Eng Ind Aerodyn 2012;100(1):58–69. [38] Battista R, Rodrigues R, Pfeil M. Dynamic behavior and stability of transmission line
[22] Elawady A, Aboshosha H, El Damatty A, Bitsuamlak G, Hangan H, Elatar A. Aero- towers under wind forces. J Wind Eng Ind Aerodyn 2003;91(8):1051–67.
elastic testing of multi-spanned transmission line subjected to downbursts. J Wind [39] Hamada A, King JPC, El Damatty AA, Bitsuamlak G, Hamada M. The response of a
Eng Ind Aerodyn 2017;169:194–216. guyed transmission line system to boundary layer wind. Eng Struct
[23] Holmes JD, Hangan HM, Schroeder JL, Letchford CW, Orwig KD. A forensic study of 2017;139:135–52.
the Lubbock-Reese downdraft of 2002. Wind Struct Int J 2008;11(2):137–52. [40] Choi EC, Hidayat Fa. Dynamic response of structures to thunderstorm winds. Prog
[24] Savory E, Parke GA, Zeinoddini M, Toy N, Disney P. Modelling of tornado and Struct Eng Mater 2002;4(4):408–16.
microburst-induced wind loading and failure of a lattice transmission tower. Eng [41] Aboshosha H, El Damatty A. Effective technique to analyze transmission line con-
Struct 2001;23(4):365–75. ductors under high intensity winds. Wind Struct Int J 2014;18(3):235–52.
[25] Vicroy DAND. Assessment of microburst models for downdraft estimation. J Aircr [42] Elawady A. Development of design loads for transmission line structures subjected
1992;29(6):1043–8. to downbursts using aero-elastic testing and numerical modeling; 2016.
[26] Shehata AY, El Damatty AA, Savory E. Finite element modeling of transmission line [43] H JD, O SE. A model of downburst winds near the ground for transmission line
under downburst wind loading. Finite Elem Anal Des 2005;42(1):71–89. loading. Australia: CSIRO Div. of Building, Construction and Engineering; 1996.
[27] Darwish MM, El Damatty AA. Behavior of self supported transmission line towers [44] Orwig KD, Schroeder JL. Near-surface wind characteristics of extreme thunderstorm
under stationary downburst loading. Wind Struct Int J 2011;14(5):481–98. outflows. J Wind Eng Ind Aerodyn 2007;95(7):565–84.
[28] Wang Y, Lou X, Li W-J, Chen H-N. Wind-induced dynamic response of high-rise [45] Overhead line design guidelines for mitigation of severe wind storm damage, 31.
transmission tower under downburst wind load. J Zhejiang Univ Eng Sci Conseil International des Grands Réseaux Électriques/International Council on
2009;43(8):1520–5. Large Electrical Systems (CIGRÉ); 2009.
[29] Mara TG, Hong HP, Lee CS, Ho TCE. Capacity of a transmission tower under [46] Aboshosha H, El Damatty AA. Span reduction factor of transmission line conductors
downburst wind loading. Wind Struct 2016;22(1):65–87. under downburst winds. J Wind Eng 2014;11(1):13–22.
[30] Elawady A, El Damatty A. Longitudinal force on transmission towers due to non- [47] Design of latticed steel transmission structures, ASCE/SEI 1. American Society of
symmetric downburst conductor loads. Eng Struct 2016;127:206–26. Civil Engineers; 2015.
[31] Yang FL, Zhang HJ. Two case studies on structural analysis of transmission towers

226

Vous aimerez peut-être aussi