Project: ETAP Page: 1

Location: 16.0.0C Date: 30-07-2018


Contract: SN: 4359168
Engineer: Revision: Base
Study Case: LF
Filename: Etude sélectivité Config.: Normal

Line/Cable Input Data

ohms or siemens/1000 m per Conductor (Cable) or per Phase (Line)

Line/Cable Length

ID Library Size Adj. (m) % Tol. #/Phase T ( C) R X Y

2(3x120)mm² Cu 6.6NCUN3 120 16.0 0.0 2 75 0.186940 0.093100


2(3x150 )mm² Cu 6.6NCUN3 150 15.0 0.0 2 75 0.151650 0.090800
2(3x150)mm² Cu 6.6NCUN3 150 12.0 0.0 2 75 0.151650 0.090800
2(3x185)m² Cu 6.6NCUN3 185 90.0 0.0 2 75 0.122083 0.088100
2x3x150mm² Cu 6.6NCUN3 150 100.0 0.0 2 75 0.151650 0.090800
2x(3x185)m² Cu 6.6NCUN3 185 295.0 0.0 2 75 0.122083 0.088100
cable 3.3MCUN3 120 50.0 0.0 2 75 0.186940 0.078000 0.0001109
Cable 1 11NALS3 400 100.0 0.0 5 75 0.097190 0.084900
Cable 2 6.6NCUN3 185 280.0 0.0 3 75 0.122083 0.088100
Cable 3 6.6NALS1 630 100.0 0.0 6 75 0.060982 0.095500
Cable 4 5.0NCUS3 150 100.0 0.0 2 75 0.145400 0.087900
Cable5 6.0NCUS3 185 60.0 0.0 2 75 0.122083 0.079200
Cable6 6.0NCUS3 16 50.0 0.0 1 75 1.402049 0.110000
Cable7 6.0NCUS3 300 25.0 0.0 2 75 0.075730 0.077600
Cable8 6.6NCUN3 300 150.0 0.0 3 75 0.076302 0.084700
Cable9 6.6NCUS3 150 12.0 0.0 1 75 0.151650 0.090800
Cable 12 11NALS3 300 50.0 0.0 4 75 0.123870 0.087400
Cable 13 6.0NCUS3 240 50.0 0.0 3 75 0.094710 0.077333
Cable 14 6.6NCUS3 70 50.0 0.0 1 75 0.327145 0.102000

Line / Cable resistances are listed at the specified temperatures.