Vous êtes sur la page 1sur 2

ABB Inc.

Distribution Transformers
PDL 46-301
Athens, GA Jefferson City, MO
Page 1
ISO 9001 Certified

January, 2002
MTR Three Phase
Padmounted
Transformer
45-1500kVA

The ABB MTR is an oil-filled, three-phase, • Low voltages: 208Y/120, 216Y/125, 11. Externally clamped low voltage
commercial padmounted distribution 460Y/265, 480Y/277, 480∆, 240∆ and bushings with threaded copper stud for
transformer specifically designed for 240∆ with 120 volt mid-tap in one full load current below 2100 amps.
servicing such underground distribution phase; (4160Y/2400, 4160∆, 2400∆, Externally clamped integral low voltage
loads as shopping centers, schools, 2400/4160Y/2400 for 500 kVA and bushings for current above 2100 amps.
institutions and industrial plants. It is larger) NEMA spades provided per ANSI hole
available in both live front and dead front requirements.
construction, for radial or loop feed Standard Features: 12. Nameplate.
applications, with or without taps. 1. Four lifting lugs. 13. Fill plug and self-actuating pressure
2. Bolted-on terminal compartment relief device.
ABB MTR meets the following (18⬙ deep) with removable front sill. 14. Drain plug.
industry standards: 3. Hinged, lift-off cabinet doors. 15. Removable neutral ground strap.
4. Interlocked penta-head bolt/padlock 16. Five-legged core/coil assembly.
ANSI C57.12.00
handle operates a cam assembly 17. Handhole cover bolted onto tank top
ANSI C57.12.22
ANSI C57.12.26 which is part of the 3-point door (protected by weathercover).
ANSI C57.12.28 latching mechanism. (A hex-head 18. Panel-type coolers.
bolt is available.) 19. NEMA safety labels.
ANSI C57.12.29
5. For live front construction, externally 20. The paint finish process applies a
ANSI C57.12.70
ANSI C57.12.80 clamped high voltage porcelain durable, corrosion resistant finish to
ANSI C57.12.90 bushings with a single eyebolt, the product. The finish meets or
clamp-type connector (accommo- exceeds all the performance require-
ANSI C57.91
dates #6 AWG solid to 250 MCM ments of ANSI C57.12.28. The multi-
NEMA TR1
WUG 2.13 Rev. 4 stranded conductors). step process includes an epoxy primer
6. For dead front construction, exter- uniformly applied by cationic electro-
nally clamped high voltage bushing deposition and a urethane top coat.
Ratings wells for loadbreak or non-loadbreak
• 45 through 1500 kVA
• 65° C average winding rise inserts. Optional Features
• 60 hertz standard, 50 hertz optional 7. Lightning arrester mounting pads Primary Termination
(live front only). • Externally-clamped bushing wells with
• High voltages: 4160 Grd Y/2400 through
8. Tank ground pads (1 in HV, 1 in LV) loadbreak or non-loadbreak inserts.
34,500 Grd Y/19,920 for Grounded Wye
systems; 2400 through 34,500 for Delta 9. Steel high/low voltage compartment • Integral loadbreak bushings.
systems; various dual high voltages barrier. Secondary Termination
10. Two 1/2⬙ penta-head bolts must be • Externally-clamped bushings with NEMA
• Taps: All voltages are available with or
removed from the flange formed on 6-hole, 8-hole, 10-hole, or 12-hole spades.
without taps
• Insulation classes: 35 kV, 150 kV BIL the steel high/low barrier before the • Spade supports are available. They are
and below HV door can be opened (1/2⬙ hex- provided for 8-hole spades and larger
head bolts available as an option). when the current is 1400 amps or greater.
Primary Switching Live Front, Radial Feed
• LBOR oil switch: one for radial, two for ANSI Fig. 1, 2, and 3 (C57.12.22)
loop feed. Gal. of
• Externally-operated tap changer. KVA A B C D E Wt. Oil
• Externally operated dual voltage switch. 75 54.5 56 44.8 44.8 56 2280 115
• Externally operated delta-wye switch. 112 54.5 56 44.8 44.8 56 2400 115
Overcurrent Protection 150 54.5 56 44.8 44.8 56 2700 125
• Internal primary protective links. 225 54.5 56 49.8 46.8 56 3350 150
• Bayonet-type expulsion fuses. 300 54.5 60 50.8 46.8 56 3650 165
• Drawout, loadbreak current limiting 500 58.5 66 58.8 48.8 56 5200 200
fuses, with or without interlocking 750 66.5 81 60.8 50.8 66 7100 270
transformer switch. 1000 66.5 84 62.8 52.8 66 7900 320
• Secondary oil circuit breaker. 1500 66.5 86 66.8 54.8 66 9700 390
• Internal, partial-range current limiting
fuses. Dead Front, Radial Feed
Overvoltage Protection ANSI Fig. 1, 3, and 4 (C57.12.26)
• Distribution class, metal oxide arresters, Gal. of
3-36 kV. KVA A B C D E Wt. Oil
• Distribution class, valve-type lightning 75 46.5 62 44.8 44.8 62 2350 115
arresters, 3-27 kV. 112 46.5 62 44.8 44.8 62 2450 115
Construction Options 150 46.5 62 44.8 44.8 62 2700 125
• 24⬙ and 30⬙ deep terminal cabinet. 225 46.5 62 49.8 46.8 62 3400 150
• Drain valve and sampling device. 300 46.5 62 50.8 46.8 62 3700 165
• Mounting plate for CT’s or PT’s. 500 54.5 66 58.8 48.8 62 5400 200
• Interphase barriers. 750 58.5 81 60.8 50.8 66 7100 270
• Molded case external secondary 1000 66.5 84 62.8 52.8 66 7900 320
breaker. 1500 66.5 86 66.8 54.8 66 9700 390
• Substation Accessories - Oil gauge,
thermometer, drain valve and sampler, Dead Front, Loop Feed
pressure-vacuum gauge provision. ANSI Fig. 2, 3, and 4 (C57.12.26)
• Weathercover. Gal. of
• Transformers may feature an optional KVA A B C D E Wt. Oil
weathercover over the cabinet which 75 54.5 66 44.8 44.8 66 2400 120
is hinged to allow clearance for 112 54.5 66 44.8 44.8 66 2500 120
replacement of the bayonet-type 150 54.5 66 44.8 44.8 66 2800 130
fuses. 225 54.5 66 49.8 46.8 66 3500 160
• The weathercover can be lifted easily 300 54.5 66 50.8 46.8 66 3800 170
into place and secured with a single 500 54.5 68 58.8 48.8 66 5600 200
supporting arm. 750 66.5 82 60.8 50.8 70 7400 270
• The weathercover requires no 1000 66.5 86 62.8 52.8 70 8200 320
additional holddown hardware. 1500 66.5 88 66.8 54.8 70 10300 390

Design Dimensions
Approximate weights and dimensions: Dimensions are in inches, weights are in pounds.
Dimensions may change to meet the customer spec.
Top View
B
76⬙ 3⬙ MIN.

MAXIMUM PAD
DIMENSIONS
70⬙

42⬙
15.5⬙
MINIMUM CABLE OPENING

5⬙

Side View
C
D
Front View

18⬙
E

ABB Inc.
Distribution Transformers
Athens, GA Jefferson City, MO January, 2002
ISO 9001 Certified