Académique Documents
Professionnel Documents
Culture Documents
Application Note
REPLACE MOTOR T1
IF BURNED, SHAFT
T4
IS JAMMED, OR
DAMAGE IS SEEN
T3
T2
2 RESET
THERMAL
SWITCH
MANUAL RESET
SAFETY
4 TURN OFF AND
LOCK OUT POWER
SWITCH
6 CHECK CENTRIFUGAL SWITCH ON
T1
T4
OFF
T3
T2
NC NC HELD OPEN
Most problems with 1ø motors include a thermal switch that switch is manual, reset the
involve the centrifugal switch, automatically turns the motor thermal switch and turn
thermal switch, or capacitor(s). If OFF when it overheats. Thermal motor ON.
the problem is in the centrifugal switches may have a manual 3. If the motor does not start,
switch, thermal switch, or capac- reset or automatic reset. Caution use a voltmeter to check for
itor, the motor is usually serviced should be taken with any motor voltage at the motor termi-
and repaired. However, if the that has an automatic reset, as nals. The voltage should be
motor is more than 10 years old the motor can automatically within 10 % of the motor’s
and less than 1 HP, the motor is restart at any time. See Figure 1. listed voltage. If the voltage is
usually replaced. If the motor is To troubleshoot a split-phase not correct, troubleshoot the
less than 1/8 HP, it is almost motor, apply the following circuit leading to the motor. If
always replaced. procedure: the voltage is correct, turn
1. Turn power to motor OFF. power to motor OFF so the
Troubleshooting Visually inspect the motor. motor can be tested.
split-phase motors Replace the motor if it is
burned, the shaft is jammed, 4. Turn the handle of the safety
The split-phase motor has a or if there is any sign of switch or combination starter
starting and running winding. damage. OFF. Lock out and tag the
The starting winding is automat- starting mechanism per
ically removed by a centrifugal 2. Check to determine if the company policy.
switch as the motor accelerates. motor is controlled by a ther-
Some split-phase motors also mal switch. If the thermal
OFF
SAFETY
SWITCH
20 k , 5 W
RESISTOR
6
SET YOUR VOLTMETER TO MEASURE
CAPACITANCE. THE CAPACITANCE VALUE 5 REMOVE AND
READ SHOULD BE WITHIN +/- 20% OF THE DISCHARGE CAPACITOR
VALUE ON THE CAPACITOR LABEL
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
In Canada (800) 36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2003 Fluke Corporation. All rights reserved.
Printed in U.S.A. 8/2003 2105247 A-ENG-N Rev A
4 Fluke Corporation Single-phase motors