Engineering Specification -
Setting Out and Construction
GEN ES901 A
P:\Dubai\ONG\DUO Sub Div\Library\Standards\Standard
ES\2018_ES_Final\9_Civil\ES901_Rev A_Setting Out and Construction Tolerances.docx
Mott MacDonald
Tolerances
ES901 Rev A
December 2017
This document is issued for the party which commissioned it and for specific purposes connected with the above-
captioned project only. It should not be relied upon by any other party or used for any other purpose.
We accept no responsibility for the consequences of this document being relied upon by any other party, or being
used for any other purpose, or containing any error or omission which is due to an error or omission in data supplied
to us by other parties.
This document contains confidential information and proprietary intellectual property. It should not be shown to other
parties without consent from us and from the party which commissioned it.
This r epo rt h as b een pre par ed s olely fo r us e by the par ty which co mmissio ned i t (t he ‘Clien t’) in conn ectio n with t he c aptio ned pr oject. I t sho uld not b e us ed f or a ny o the r pu rpos e. No pe rson oth er t han the Clie nt o r a ny pa rty w ho h as ex pres sly ag ree d te rms of r elianc e with us (t he ‘Re cipien t(s)’ ) m ay r ely on the cont ent, i nfo rma tion or a ny views exp resse d in t he rep ort. W e acc ept no d uty o f ca re, resp onsibility or lia bility to any oth er recipie nt of this docu men t. T his r epo rt is c onfid ential and cont ains p rop riet ary in tellect ual p rop erty .
Contents
1 Introduction 1
1.1 Scope 1
1.2 Exclusions 1
1.3 Abbreviations and Definitions 1
1.4 Other References 2
1 Introduction
1.1 Scope
This Specification covers the minimum technical requirements for the Setting out and
Construction Tolerances for Civil and Structural building works as described below.
● Setting out
● Levels, Position and verticality of Structural steel works
● Levels, Position and verticality of in-situ concrete works
● Lift walls
● Block work
● Door and Window openings
● Welded tanks for Oil storage
Different or additional requirements if specified in project specifications shall prevail over this
specification.
1.2 Exclusions
The following structures are excluded from the scope of this document.
● Marine
● Piles
● Precast concrete
● Timber structure
● Manufactured Components
● Cladding
Requirement of accuracy of any other special structures shall be finalised in accordance with
relevant codes, regulations of local regulatory authorities
BS - British Standard
RC - Reinforced Concrete
Table 1: References
Sl. Code ID Description
1 BS 5606 Guide to Accuracy in Building
2 BS 5964 Building Setting out and Measurement
3 BS ISO 1803 Building Construction Tolerances Expressions of Dimensional Accuracy
Principles and Terminology
4 BS 6954 Tolerances for Building
5 BS 7308 Method for Presentation of Dimensional Accuracy Data in Building
Constructions
6 BS 7307-1 Building Tolerances. Measurement of buildings & Building products
Methods and instruments
7 SP 145 Setting out Procedures CIRIA
8 API 650 Welded Tanks for Oil Storage
In case of conflict between the requirements of this specification and the documents listed, the
requirements which are more stringent shall govern.
The Contractor is responsible for the accuracy of all setting out and construction tolerances.
These shall not be greater than those specified in this section.
a. Where a concrete ring wall is provided under the shell, the top of the ring wall shall be level
within ±3 mm (1/8 in.) in any 9 m (30 ft) of the circumference and within ±6 mm (1/4 in.) in
the total circumference measured from the average elevation.
b. Where a concrete ring wall is not provided, the foundation under the shell shall be level
within ±3 mm (1/8 in.) in any 3 m (10 ft) of the circumference and within ±13 mm (1/2 in.)
in the total circumference measured from the average elevation.
c. Where a concrete slab foundation is provided, the first 0.3 m (1 ft) of the foundation (or
width of the annular ring), measured from the outside of the tank radially towards the centre,
shall comply with the concrete ring wall requirement. The remainder of the foundation shall
be within ±13 mm (1/2 in.) of the design shape.
The maximum out-of-plumbness of the top of the shell relative to the bottom of the shell shall not
exceed 1/200 of the total tank height. The out-of-plumbness in one shell course shall not exceed
the permissible variations for flatness and waviness as specified in ASTM A 6M/A 6, ASTM A
20M/A 20, or ASTM A 480M/A 480, whichever is applicable.
The maximum out-of-plumbness of roof columns, guide poles, or other vertical internal
components shall not exceed 1/200 of the total height. The 1/200 criteria shall also apply to fixed
roof columns.
For tank structure having internal floating roof, maximum out-of-plumbness shall be as per clause
No 7.5.2 of API 650
For tolerance on radius of tanks, clause No 7.5.3 of API 650 shall be applicable.