Vous êtes sur la page 1sur 2

ORO OXYGEN CORPORATION

website: www.prycegas.com

LUNA STREET, SANTA ROSA, NUEVA ECIJA


INSULATION RESISTANCE AND CONTINUITY TEST REPORT
JULY 6, 2018
INSULATION RESISTANCE TEST ON MOTOR CONTROL AND PANELS INSTALLED ON THE PLANT

CONTINUITY TEST
INSULATION TEST (MEGA OHMS)
(MEGA OHMS)
value must be 0 to 10 MΩ (IDEALLY = 0) value must be greater than 5MΩ
LOCATION CIRCUIT BREAKER WIRE USED L1 TO L2 L2 TO L3 L3 TO L1 L1 TO GRND L2 TO GRND L3 TO GRND
MAIN BREAKER 200 AT 60.00 mm ² 0 0 0 --------- --------- ---------
SUB MAIN 100 AT 32.00 mm ² 0 0.002 0 --------- --------- ---------
AIR COMPRESSOR 60 AT 14 mm ² 0 0 0 606 MΩ 657 MΩ 765 MΩ
LPG PUMP 1 60 AT 14 mm ² 0 0.001 0 133.4 MΩ 138.5 MΩ 138.1 MΩ
LPG PUMP 2 60 AT 14 mm ² 0 0.03 0 150 MΩ 153 MΩ 149 MΩ
GAS COMPRESSOR 60 AT 14 mm ² 0 0 0.01 222 MΩ 225 MΩ 229 MΩ
ALL READINGS DONE WERE HOLD FOR AT LEAST 2 MINUTES DURATION AND AT A TEST VOLTAGE OF 250V.

ORO OXYGEN
Testing Company License No. 65652
CORP.
SANWA
Testing Instrument INSULATION Date 07/06/2018
TESTER MG1000
Test Method Direct Method Time 12am to 2pm

PREPARED BY:
LESTER L. MUSCA
CORP. TSD ELECTRICAL

CHECKED BY; MARIO A. MACATOL


CORP. TSD HEAD

18TH Floor Pryce Center, 1179 Don Chino Roces Avenue cor. Bagtikan Street, Makati City, Philippines Tel. Nos. (02) 8994401
ORO OXYGEN CORPORATION
website: www.prycegas.com

Resistance Ok/Not Ok
TEST LOCATION DATE OF TESTING value in >5
Comment Next due of Testing EARTH TESTING REPORT
ohms
Good Company
1 REFILING HALL 6/23/2018 2.41 Ok Dec. 2018 ORO OXYGEN CORP.
Condition Name:
BFG Good Location:
2 6/23/2018 1.16 Ok Dec. 2018 ALAMINOS LAGUNA
BULK FILLING GANTRY Condition
Good Project: REFILING PLANT
3 STORAGE TANK 1 2.28 Ok Dec. 2018
6/23/2018 Condition
Good
4 STORATE TANK 2 2.3 Ok Dec. 2018
6/23/2018 Condition
Good
5 STORAGE TANK 3 2.22 Ok Dec. 2018
6/23/2018 Condition
Need to add
6 AC GENERATOR 10.5 Not Ok 1 Dec. 2018
6/23/2018 grounding
Good
7 FIREPUMP 3.48 Ok Dec. 2018
6/23/2018 Condition
Good
8 LPG PUMP 1&2 1.54 Ok Dec. 2018
6/23/2018 Condition
Good
9 GAS COMPRESSOR 1.72 Ok Dec. 2018
6/23/2018 Condition
Good
10 MCC 1.83 Ok Dec. 2018
6/23/2018 Condition

Testing Company ORO OXYGEN CORP. License No. 65652


PM2302 GROUND
Testing Instrument Date 6/23/2018
AND EARTH TESTER
Test Method Fall of Potential Time 5pm to 6pm

Conducted by;
LESTER L. MUSCA
Electrical Engineer
CORP TSD - ELEC

Checked by;
MARIO A. MACATOL
CORP TSD HEAD

18TH Floor Pryce Center, 1179 Don Chino Roces Avenue cor. Bagtikan Street, Makati City, Philippines Tel. Nos. (02) 8994401