HVDC Control
• DC control should:
– Regulate current (or power)
– keep the extinction angle sufficiently large for avoiding commutation
failures
• Standard Control Strategy:
– current-control at the rectifier station
– γ - control at the inverter station
HVDC Control
Vd
OP
γ -control
Current-control
Id
2
Rectifier Current Controller
DIgSILENT
12-pulse Rectifier Current Controller:
I alpha
Imea Ictrl 0
StaImea* ElmIctrl* tap 1 Rec2
2
ElmRec*
0
tap 1 Rec1
F0Hz1 ElmRec*
Phi1 2
ElmPhi__PLL
Ictrl_Rectifier:
Isetp
0
alpha_max
I
- dI o12 yi1 alpha
1 K Limiter
Kp
alpha_min
o13
alpha_max
[1/sT]
Ti
alpha_min
3
Inverter Gamma-Controller
DIgSILENT
12-pulse Inverter Gamma Control:
gamma
alpha
gctrl 0
ElmGctrl* tap 1 Inv2
2
ElmRec*
0
tap 1 Inv1 gamma_min
F0Hz ElmRec*
Phi1 2
ElmPhi__PLL
gctrl_Inverter:
gamma_ref
0
alpha_max
gamma
- yi o12 yi1 gamma(1)
1 K Limiter
Kp
alpha_min
o13
alpha_max
[1/sT]
Ti
alpha_min
4
HVDC Control
Vd
α min γ -control
OP
Current-control
Id
Two-Directional Controller
DIgSILENT
Ctrl_gamma_current:
Isetp
0
alpha_max
1
I - dI
K
o12 cosalpha
cos^-1(alpha)
Kp..
alpha_min
alpha_1
o13
Im
2 alpha_max
[1/sT]_cosalpha
TiI 0
alpha
MIN
alpha_min 1
gamma_ref
alpha2
alpha_max
alpha_no_limit
-
gamma dgamm.. Kdgam..
4 K(.. Limiter_deg
Kp..
alpha_min
Kdgam..
i_dga..
alpha_max
[1/sT]_deg
TiG
alpha_min
5
Two-Directional Controller
DIgSILENT
12-pulse Converter Controller:
gamma
0
alpha
Controller 0
I ElmCtrl*
Imea 1 1 Rec2
StaImea* 2
ElmRec*
tap
0
Tap Changer
vdc ElmTap*
Vmea 1
StaVmea*
0
1 Rec1 gamma_min
Fmeas ElmRec*
Phi1 2
ElmPhi__pll
Tap-Changer
DIgSILENT
tap_TapChanger:
alpha<pi/2
alpha_min
0
tap_order
0
dalpha Kdalpha
-
irec
alpha yi
1 Dband(K)_deg K
da Kalpha
tap_max
delta tap
[1/sT] bias 1
Ttap
Kdv
tap_min
2
vdc - dvdc
K
Kv
v_ref
3
6
Two-Directional Controller
α min OP1
γ -control
Im
current-control
OP2 γ -control
α min
Malfunctioning
7
Commutation Failure
DIgSILENT
3.000
2.000
1.000
0.00
-1.000
-2.000
-3.000
-0.008 -0.004 0.00 0.00 0.01 .. 0.01
Inv 1: Phase Current A/Terminal AC in kA
Inv 1: Phase Current B/Terminal AC in kA
Inv 1: Phase Current C/Terminal AC in kA
Commutation Failure
DIgSILENT
3.000 1.676
2.000
1.535
1.00
1.393
0.00
1.251
-1.000
1.109
-2.000
-3.000 0.97
-0.008 -0.004 0.00 0.00 0.01 .. 0.01 -0.008 -0.004 0.00 0.00 0.01 .. 0.01
Inv 1: Current, Magnitude/Terminal AC in kA Inv 1: Current, Magnitude/Terminal DC- in kA
Inv 1: Current, Magnitude/Terminal AC in kA
Inv 1: Current, Magnitude/Terminal AC in kA
16.00 30.00
12.00 25.00
8.000 20.00
4.000 15.00
0.00 10.00
-4.000 5.000
-0.008 -0.004 0.00 0.00 0.01 .. 0.01 -0.008 -0.004 0.00 0.00 0.01 .. 0.01
Inv 1: Extinction Angle Inv 1: overlap Angle in deg
8
Commutation Failure
Commutation Failure
DIgSILENT
3.000
2.000
1.00
0.00
-1.000
-2.000
-3.000
-0.100 0.00 0.10 0.20 0.30 .. 0.40
Inv 1: Phase Current A/Terminal AC in kA
Inv 1: Phase Current B/Terminal AC in kA
Inv 1: Phase Current C/Terminal AC in kA
375.0
250.0
125.0
0.00
-125.0
-250.0
-0.100 0.00 0.10 0.20 0.30 .. 0.40
Inverter Bus Bar: Phase Voltage in kV
9
Commutation Failure
DIgSILENT
3.000
2.000
1.00
0.00
-1.000
-2.000
-3.000
-0.100 0.00 0.10 0.20 0.30 .. 0.40
Inv 1: Current, Magnitude/Terminal AC in kA
Inv 1: Current, Magnitude/Terminal AC in kA
Inv 1: Current, Magnitude/Terminal AC in kA
375.0
250.0
125.0
0.00
-125.0
-250.0
-0.100 0.00 0.10 0.20 0.30 .. 0.40
Inverter Bus Bar: Line-Neutral Voltage, Magnitude in kV
Discontinuous Operation
DIgSILENT
0.04
0.02
0.00
-0.020
-0.040
0.00 0.00 0.01 0.01 0.02 .. 0.02
Inv 1: Phase Current A/Terminal AC in kA
Inv 1: Phase Current B/Terminal AC in kA
Inv 1: Phase Current C/Terminal AC in kA
0.03
0.02
0.02
0.01
0.01
-0.001
0.00 0.00 0.01 0.01 0.02 .. 0.02
Inv 1: DC-Current in kA
10
HVDC Supervision
• Max current limit (short term limit at 1.2...1.3 above continuous current
rating)
• Min. current limit for avoiding discontinuous operation
• Voltage dependent current order: At low voltages, current order has to be
reduced for avoiding commutation failures and voltage stability problems in
the DC-system
• Faults /sustained commutation failures: Fault clearing by blocking and
bypassing the converters (no DC-circuit breakers)
11
Weak AC Systems
Weak AC Systems
• Classifying ESCR:
– High: >5
– Moderate: 3...5
– Low: <3
12
Weak AC Systems
Weak AC Systems
13