17.9 Combination, Multi-Criteria, and Multi- Sensor Detectors 17.10 Gas Detection 17.11 Other Fire Detectors 17.12 Sprinkler Waterflow Alarm-Initiating Devices 17.13* Detection of the Operation of Other Automatic Extinguishing Systems Initiating Devices 17.8 Radiant Energy-Sensing Fire Detectors 17.8.1.1 GENERAL – 17.8 describe the standards to install these dev
17.8.2 FIRE CHARACTERISTICS and DETECTOR
SELECTION 17.8.2.1 Type and quantity of devices --> analysis 17.8.2.2 Selection based upon match and minimize
17.8.3 SPACING CONSIDERATIONS
Initiating Devices 17.8 Radiant Energy-Sensing Fire Detectors 17.8.3.1 GENERAL RULES 17.8.3.1.1 Follow listing and inverse square law 17.8.3.1.2 Quantity based upon non-obstruction Initiating Devices 17.8 Radiant Energy-Sensing Fire Detectors 17.8.3.2 SPACING CONSIDERATIONS for FLAME DETECTORS 17.8.3.2.1 Location and spacing based on: (1) Size of fire to be detected (2) Fuel involved (3) Detector sensitivity (4) Detector field-of-view (5) Distance between fire and detector (6) Radiant energy absorption of the atmosphere (7) Presence of extraneous sources of emissions (8) Purpose of the detection system (9) Response time required Initiating Devices 17.8 Radiant Energy-Sensing Fire Detectors 17.8.3.2 SPACING CONSIDERATIONS for FLAME DETECTORS 17.8.3.2.2 System design shall specify size of fire 17.8.3.2.3 Reduce distance if not on axis 17.8.3.2.4 Reduce distance if application & test differ 17.8.3.2.5 Do not obstruct the detector field of view 17.8.3.2.6 Keep detector window clean and clear Initiating Devices 17.8 Radiant Energy-Sensing Fire Detectors 17.8.3.3 SPACING CONSIDERATIONS for SPARK/EMBER DETECTORS 17.8.3.3.1 Location and spacing based upon: (1) Size of the spark or ember to be detected (2) Fuel involved (3) Detector sensitivity (4) Detector field-of-view (5) Distance between fire and detector (6) Radiant energy absorption of the atmosphere (7) Presence of extraneous sources of emissions (8) Purpose of the detection system (9) Response time required Initiating Devices 17.8 Radiant Energy-Sensing Fire Detectors 17.8.3.3 SPACING CONSIDERATIONS for SPARK/EMBER DETECTORS
17.8.3.3.2 Design shall specify size of spark
17.8.3.3.3 All detection points shall be in field of view 17.8.3.3.4 Location/spacing based on inv. square law 17.8.3.3.5 Reduce distance if not in optical axis 17.8.3.3.6 Keep detector window clean and clear Initiating Devices 17.8 Radiant Energy-Sensing Fire Detectors
17.8.4 OTHER CONSIDERATIONS