Saad Group / Design office
Electrical Department
Cable Calculation Sheet
Project Name : New Extention Portion (H) Project No.: 54
Panel Data : Main Feeder Data :
Panel Tag No. : LVB-1 Rated Volt : 380 / 220 Feeding Panel Tag No. : T1&T2
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Transformer Room
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 3200 AT Cross Sectional Area : 8Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 4000 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 8

For This Condition; We Take No. of Cable Runs is ===> ( 8 ) Runs


Cable Voltage Drop : 0.936
% Cable Voltage Drop : 0.25

Comment : * Cable Size is =====> 8 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.
* For This Size; The %Voltage Drop is 0.25 % @ 2560 A, 380 V

Panel Data : Main Feeder Data :


Panel Tag No. : LVB-2 Rated Volt : 380 / 220 Feeding Panel Tag No. : T3&T4&T5
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Transformer Room
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 3200 AT Cross Sectional Area : 8Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 4000 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 8

For This Condition; We Take No. of Cable Runs is ===> ( 8 ) Runs


Cable Voltage Drop : 0.936
% Cable Voltage Drop : 0.25

Comment : * Cable Size is =====> 8 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.
* For This Size; The %Voltage Drop is 0.25 % @ 2560 A, 380 V

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:48


Page No.(2) of (9)
Saad Group / Design office
Electrical Department
Cable Calculation Sheet
Project Name : New Extention Portion (H) Project No.: 54
Panel Data : Main Feeder Data :
Panel Tag No. : Synch. Panel-1 Rated Volt : 380 / 220 Feeding Panel Tag No. : G1&G2&G3&G4&G5
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Generator Room
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 1600 AT Cross Sectional Area : 4Runs4x1Cx240mm²+1Cx120 mm²
Main C.B. Rating:
IP Degree : IP54 1600 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 240 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.2200 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 630.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 442.59 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 4

For This Condition; We Take No. of Cable Runs is ===> ( 4 ) Runs


Cable Voltage Drop : 1.056
% Cable Voltage Drop : 0.28

Comment : * Cable Size is =====> 4 No. X ( 1 C X 240 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 442.59 Amps.
* For This Size; The %Voltage Drop is 0.28 % @ 1280 A, 380 V

Panel Data : Main Feeder Data :


Panel Tag No. : Synch. Panel-2 Rated Volt : 380 / 220 Feeding Panel Tag No. : G6&G7&G8&G9&G10
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Generator Room
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 1600 AT Cross Sectional Area : 4Runs4x1Cx240mm²+1Cx120 mm²
Main C.B. Rating:
IP Degree : IP54 1600 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 240 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.2200 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 630.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 442.59 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 4

For This Condition; We Take No. of Cable Runs is ===> ( 4 ) Runs


Cable Voltage Drop : 1.056
% Cable Voltage Drop : 0.28

Comment : * Cable Size is =====> 4 No. X ( 1 C X 240 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 442.59 Amps.
* For This Size; The %Voltage Drop is 0.28 % @ 1280 A, 380 V

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:48


Page No.(3) of (9)
Saad Group / Design office
Electrical Department
Cable Calculation Sheet
Project Name : New Extention Portion (H) Project No.: 54
Panel Data : Main Feeder Data :
Panel Tag No. : MDB-1 Rated Volt : 380 / 220 Feeding Panel Tag No. : LVB-1
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 3200 AT Cross Sectional Area : 8Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 4000 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 8

For This Condition; We Take No. of Cable Runs is ===> ( 8 ) Runs


Cable Voltage Drop : 0.936
% Cable Voltage Drop : 0.25

Comment : * Cable Size is =====> 8 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.
* For This Size; The %Voltage Drop is 0.25 % @ 2560 A, 380 V

Panel Data : Main Feeder Data :


Panel Tag No. : MDB-2 Rated Volt : 380 / 220 Feeding Panel Tag No. : LVB-1
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 3200 AT Cross Sectional Area : 8Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 4000 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 8

For This Condition; We Take No. of Cable Runs is ===> ( 8 ) Runs


Cable Voltage Drop : 0.936
% Cable Voltage Drop : 0.25

Comment : * Cable Size is =====> 8 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.
* For This Size; The %Voltage Drop is 0.25 % @ 2560 A, 380 V

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:48


Page No.(4) of (9)
Saad Group / Design office
Electrical Department
Cable Calculation Sheet
Project Name : New Extention Portion (H) Project No.: 54
Panel Data : Main Feeder Data :
Panel Tag No. : MDB-3 Rated Volt : 380 / 220 Feeding Panel Tag No. : Synch. Panel-2
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 1600 AT Cross Sectional Area : 4Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 1600 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 240 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.2200 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 630.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 442.59 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 4

For This Condition; We Take No. of Cable Runs is ===> ( 4 ) Runs


Cable Voltage Drop : 1.056
% Cable Voltage Drop : 0.28

Comment : * Cable Size is =====> 4 No. X ( 1 C X 240 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 442.59 Amps.
* For This Size; The %Voltage Drop is 0.28 % @ 1280 A, 380 V

Panel Data : Main Feeder Data :


Panel Tag No. : MDB-3 Rated Volt : 380 / 220 Feeding Panel Tag No. : LVB-2
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 1600 AT Cross Sectional Area : 4Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 1600 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 240 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.2200 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 630.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 442.59 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 4

For This Condition; We Take No. of Cable Runs is ===> ( 4 ) Runs


Cable Voltage Drop : 1.056
% Cable Voltage Drop : 0.28

Comment : * Cable Size is =====> 4 No. X ( 1 C X 240 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 442.59 Amps.
* For This Size; The %Voltage Drop is 0.28 % @ 1280 A, 380 V

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:49


Page No.(5) of (9)
Saad Group / Design office
Electrical Department
Cable Calculation Sheet
Project Name : New Extention Portion (H) Project No.: 54
Panel Data : Main Feeder Data :
Panel Tag No. : MDB-4 Rated Volt : 380 / 220 Feeding Panel Tag No. : Synch. Panel-2
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 1600 AT Cross Sectional Area : 4Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 1600 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 240 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.2200 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 630.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 442.59 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 4

For This Condition; We Take No. of Cable Runs is ===> ( 4 ) Runs


Cable Voltage Drop : 1.056
% Cable Voltage Drop : 0.28

Comment : * Cable Size is =====> 4 No. X ( 1 C X 240 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 442.59 Amps.
* For This Size; The %Voltage Drop is 0.28 % @ 1280 A, 380 V

Panel Data : Main Feeder Data :


Panel Tag No. : MDB-4 Rated Volt : 380 / 220 Feeding Panel Tag No. : LVB-2
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 1600 AT Cross Sectional Area : 4Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 1600 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 240 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.2200 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 630.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 442.59 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 4

For This Condition; We Take No. of Cable Runs is ===> ( 4 ) Runs


Cable Voltage Drop : 1.056
% Cable Voltage Drop : 0.28

Comment : * Cable Size is =====> 4 No. X ( 1 C X 240 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 442.59 Amps.
* For This Size; The %Voltage Drop is 0.28 % @ 1280 A, 380 V

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:49


Page No.(6) of (9)
Saad Group / Design office
Electrical Department
Cable Calculation Sheet
Project Name : New Extention Portion (H) Project No.: 54
Panel Data : Main Feeder Data :
Panel Tag No. : ATS-3 Rated Volt : 380 / 220 Feeding Panel Tag No. : LVB-2
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 2000 AT Cross Sectional Area : 5Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 2500 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 5

For This Condition; We Take No. of Cable Runs is ===> ( 5 ) Runs


Cable Voltage Drop : 0.936
% Cable Voltage Drop : 0.25

Comment : * Cable Size is =====> 5 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.
* For This Size; The %Voltage Drop is 0.25 % @ 1600 A, 380 V

Panel Data : Main Feeder Data :


Panel Tag No. : ATS-3 Rated Volt : 380 / 220 Feeding Panel Tag No. : Synch. Panel-2
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 2000 AT Cross Sectional Area : 5Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 2500 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/400-230V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D = 0.55%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch. LVB
400/230V 400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55% V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m. Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 MDB -or- ATS
Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.
Calculated No. of Runs for Cable (Due to Derating Factors) : 5

For This Condition; We Take No. of Cable Runs is ===> ( 5 ) Runs


Cable Voltage Drop : 0.936
% Cable Voltage Drop : 0.25

Comment : * Cable Size is =====> 5 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.
* For This Size; The %Voltage Drop is 0.25 % @ 1600 A, 380 V

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:49


Page No.(7) of (9)
Saad Group / Design office
Electrical Department
Cable Calculation Sheet
Project Name : New Extention Portion (H) Project No.: 54
Panel Data : Main Feeder Data :
Panel Tag No. : ATS-1 Rated Volt : 220 / 127 Feeding Panel Tag No. : T6
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 3200 AT Cross Sectional Area : 8Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 4000 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/220-127V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 1.00 V.D = 0.55% V.D =1%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch.
400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001 Trans.


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 400/220-127V

Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.


Calculated No. of Runs for Cable (Due to Derating Factors) : 8 V.D = 0.65%

Max. 15.00 m.

For This Condition; We Take No. of Cable Runs is ===> ( 8 ) Runs


Cable Voltage Drop : 0.936 MDB -or- ATS
% Cable Voltage Drop : 0.43

Comment : * Cable Size is =====> 8 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.
* For This Size; The %Voltage Drop is 0.43 % @ 2560 A, 220 V

Panel Data : Main Feeder Data :


Panel Tag No. : T7 Rated Volt : 380 / 220V Feeding Panel Tag No. : Synch. Panel-2
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 15.00 m.
Mounting : Free Standing 3200 AT Cross Sectional Area : 8Runs3x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 4000 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/220-127V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.55 V.D = 0.55% V.D =1%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch.
400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001 Trans.


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 400/220-127V

Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.


Calculated No. of Runs for Cable (Due to Derating Factors) : 8 V.D = 0.65%
Max. 15.00 m.

For This Condition; We Take No. of Cable Runs is ===> ( 8 ) Runs


Cable Voltage Drop : 0.936 MDB -or- ATS
% Cable Voltage Drop : 0.25

Comment : * Cable Size is =====> 8 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:49


Page No.(8) of (9)
* For This Size; The %Voltage Drop is 0.25 % @ 2560 A, 380 V

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:50


Page No.(9) of (9)
Saad Group / Design office
Electrical Department
Cable Calculation Sheet
Project Name : New Extention Portion (H) Project No.: 54
Panel Data : Main Feeder Data :
Panel Tag No. : ATS-1 Rated Volt : 220 / 127 Feeding Panel Tag No. : T7
Panel Location : Roof Deck Rated Frequency #: ## 60 Hz Feeding Panel Location : Roof Deck
Panel Type : Indoor I.C. Current #: ## 65 kA Main Cable Length : 10.00 m.
Mounting : Free Standing 3200 AT Cross Sectional Area : 8Runs4x1Cx300mm²+1Cx150 mm²
Main C.B. Rating:
IP Degree : IP54 4000 AF Cable Type / Insulation : Cu/XLPE/PVC

Gen. Trans.
400-230V 13.8kV/220-127V

Main Cable Arrangements: Go through Cable Tray / Horizontally / Trefoil / Touching


Max. Cable's Permissible % Voltage Drop : 0.65 V.D = 0.55% V.D =1%

Max. 15.00 m. Max. 15.00 m.

Cable Derating Factors: Temperature : 0.87


Grouping : 0.85
Cable Tray : 0.95 Single conductor Cables Separated
Synch.
400/230V

Cable Sizing :
No. of Cores : 1
Cable Type : Cu/XLPE/PVC V.D = 0.55%

Cross Sectional Area : 300 mm² Max. 15.00 m.

Cable's Impedance : 0.1950 Ohms/Km <== According to Tables of BS 7671:2001 Trans.


Max. Cable's Current-Current Capacity : 730.00 A. <== According to Tables of BS 7671:2001 400/220-127V

Max. Current Capacity/Cond. (Due to Derating Factors) : 512.84 A.


Calculated No. of Runs for Cable (Due to Derating Factors) : 8 V.D = 0.65%

Max. 15.00 m.

For This Condition; We Take No. of Cable Runs is ===> ( 8 ) Runs


Cable Voltage Drop : 0.624 MDB -or- ATS
% Cable Voltage Drop : 0.28

Comment : * Cable Size is =====> 8 No. X ( 1 C X 300 ) mm²


* Cable Size is OK
* The Current Capacity / Each Conductor will be 512.84 Amps.
* For This Size; The %Voltage Drop is 0.28 % @ 2560 A, 220 V

Reference: 394354242.xls - Main Feeder Cables Data 08/12/2018 - 07:09:50