Vous êtes sur la page 1sur 1

CUPIAGUA CPF

Neutral Earthing Resistor


Function Test Certificate
AC-1 No.: HC-1 No.: Certs No.
FE-12
Sheet 1 of 1

AREA / LOCATION: SYSTEM:


P & ID No.: REV SERVICE:
DATA SHEET No.: REV TAG No.
MANUFACTURER: CERTIFICATION CLASSIFICATION:
MODEL No.: TYPE No.:
SERIAL No.: S.L.D.No.:

Chk Check Description N/A INTL DATE


1. Ensure neutral earthing resistor is installed as drawings.

2. Disconnect earth cable at Earth connection.

3. Check insulation resistance of resistor. ________ M.Ohms

4. For reactive type earthing resistors check insulation resistance of resistor


secondary winding to earth with outgoing connections shorted together
_______ M.Ohms

5. Reconnect earth connection.

6. Check and record resistance from star point connection to Earth._______ Ohms

7. For reactive type earthing resistors, check and record resistance of secondary
shorting resistance using a low voltage instrument _______ Ohms

8. Measure and record current flow in earth conductor under no-load conditions.

Generator Current ________ A Neutral Current ________ A

9 Measure and record current flow in earth conductor under load conditions.

Generator Load Current ________ A Neutral Current ________ A

REMARKS:

Completed by Approved by Accepted by


(Technician) (Supervisor) (Completions)
COMPANY
SIGNATURE
PRINT NAME
DATE

Rev 01