Académique Documents
Professionnel Documents
Culture Documents
Disclaimers
Alcatel products are intended for commercial uses. Without the appropriate network design
engineering, they must not be sold, licensed or otherwise distributed for use in any hazardous
environments requiring fail-safe performance, such as in the operation of nuclear facilities, aircraft
navigation or communication systems, air traffic control, direct life-support machines, or weapons
systems, in which the failure of products could lead directly to death, personal injury, or severe physical
or environmental damage. The customer hereby agrees that the use, sale, licence or other distribution
of the products for any such application without the prior written consent of Alcatel, shall be at the
customer's sole risk. The customer hereby agrees to defend and hold Alcatel harmless from any claims
for loss, cost, damage, expense or liability that may arise out of or in connection with the use, sale,
licence or other distribution of the products in such applications.
This document may contain information regarding the use and installation of non-Alcatel products.
Please note that this information is provided as a courtesy to assist you. While Alcatel tries to ensure
that this information accurately reflects information provided by the supplier, please refer to the
materials provided with any non-Alcatel product and contact the supplier for confirmation. Alcatel
assumes no responsibility or liability for incorrect or incomplete information provided about
non-Alcatel products.
However, this does not constitute a representation or warranty. The warranties provided for Alcatel
products, if any, are set forth in contractual documentation entered into by Alcatel and its customers.
This document was originally written in English. If there is any conflict or inconsistency between the
English version and any other version of a document, the English version shall prevail.
PRINTED ON
RECYCLED PAPER
Mandatory regulations
The following sections describe the mandatory regulations that govern the
installation and operation of the 7670 RSP.
List of terms
Term Expansion
ANSI American National Standards Institute
CE Conformité Européene
EN European Standards
(1 of 2)
Term Expansion
(2 of 2)
General requirements
The sections that follow outline the mandatory regulations that govern the
installation and operation of the 7670 RSP. You must adhere to these instructions so
that your system meets regulatory requirements.
SELV
Connect SELV circuits on this equipment only to other circuits that comply with
the requirements of SELV circuits as defined in CSA C22.2 No. 60950-1,
UL60950-1, EN 60950-1, AS/NZS 60950, and IEC60950-1.
Prevention of access
The 7670 RSP must be accessible only to authorized personnel. Install this apparatus
in a restricted access location or similar environment to prevent unauthorized access.
Laser interface
The 7670 RSP uses a fiber-optic communications method and is an FDA Class 1
laser product. Only trained service personnel thoroughly familiar with laser radiation
hazards should install or remove the fiber-optic cables and cards in this system.
EMC compliance
EMC compliance may require the use of ferrites, shielded cables or other special
accessories. Where required, these special accessories must be installed as per the
instructions.
Regulatory symbols
The following sections show examples of the regulatory approvals symbols that the
7670 RSP uses. They may be used on product markings such as approvals labels.
These symbols are described in IEC 417.
Power on
Figure 1 indicates that the power switch is in the on (|) position.
9715
Power off
Figure 2 indicates that the power switch is in the off (O) position.
9716
9717
9718
Canada
This section describes the mandatory regulations that govern the installation and
operation of the 7670 RSP in Canada.
United States
This section describes the mandatory regulations that govern the installation and
operation of the 7670 RSP in the United States.
CSA NRTL
This equipment is certified by the CSA as meeting the requirements of UL 60950-1,
Safety of Information Technology Equipment. The American Federal OSHA lists
the CSA as equivalent to UL and other American safety testing laboratories under
the NRTL program.
European regulations
EU compliance statement
This product has been CE marked in accordance with the requirements of European
Directive 99/05/EC, the Radio and Telecommunications Terminal Equipment
Directive.
General
This equipment must be permanently grounded.
Laser interface
The system uses laser devices that are rated in accordance with IEC60825-1 as
Class 1 devices.
The following cards use devices that are rated in accordance with IEC60825-1 as
Class 3A devices. Only trained service personnel thoroughly familiar with laser
radiation hazards should install or remove the fiber-optic cables from these cards.
• OC48 LR
• QFIC
• DFIC
• SAC
Protective earth
Protective earth is referred to as chassis ground in this document. A green and yellow
colored earth wire must be connected from the site equivalent of the ac earth to all
shelves in accordance with IEE Wiring Regulations (16th edition). This connection
is made via the chassis ground connection (refer to the installation chapter for
specific instructions on connecting the protective earth). The protective earth is also
carried by the mains plug and socket (for ac systems only).
Before you install the system, you must ensure that the site meets installation
requirements.
Note 1 — For more information about a wide range of network
services, including network design, installation, and commissioning,
contact your technical support representative.
Note 2 — To find information for references outside this chapter, see
the 7670 RSP Release 4.0 Technical Practices.
Warning — The system has been designed and tested to all relevant
standards of conducted and radiated EMI. However, the system may
be affected by very strong EMI sources, such as elevators, air
conditioners, photocopiers, and facsimile machines.
Specification Description
Pollution degree 2
Note
(1) Short-term is a period of less than 96 consecutive hours and a total of no more than 15 days yearly.
This refers to a total of 360 hours per year, with short-term periods occurring no more than 15 times
yearly.
Power information
Table 1-2 lists the voltage and ampere power rating of each fully configured shelf.
Table 1-3 lists the maximum power consumption of each of the 7670 RSP
components. Use these numbers when planning your power connections.
Voltage Maximum system current drain (total) Maximum current drain per feed
–38 V dc (1) • Single shelf, control shelf or Peripheral • Single shelf, control shelf or
shelf: 116 Adc (L2) (2) Peripheral shelf: 29 Adc (L2) (2)
• Switching shelf: 58 Adc (L2) (2) • Switching shelf: 30 Adc (L2) (2)
–48 V dc • Single shelf, control shelf or Peripheral • Single shelf, control shelf or
shelf: 92 Adc (L1) (2) Peripheral shelf: 23 Adc (L1) (2)
• Switching shelf: 46 Adc (L1) (2) • Switching shelf: 24 Adc (L1) (2)
–60 V dc • Single shelf, control shelf or Peripheral • Single shelf, control shelf or
shelf: 75 Adc (L1) (2) Peripheral shelf: 19 Adc (L1) (2)
• Switching shelf: 37 Adc (L1) (2) • Switching shelf: 19 Adc (L1) (2)
Notes
(1) –38 V dc represents the worst case input voltage condition for a fully configured shelf. –38 V dc is
used as the worst case input voltage condition because the components of the shelf have a Low
Battery Voltage shutdown feature which is activated at –38 V dc. –38 V dc input voltage is not the
normal operating condition for the shelf and is only included to enable calculation of the input wire
AWG to the shelf.
(2) List 1 (L1) current drains are used to determine the size of the dc power plant; that is, rectifiers and
batteries.
List 2 (L2) current drains are used to determine the size of the dc distribution system; that is, power
feeders and fuses or circuit breakers.
For complete definitions of L1 and L2, refer to GR-513-CORE.
Switch card 69
SSC card 37
SMX card 47
SCH card 33
SAC 28
PSC 28
CIC 22
Facilities card 7
DFIC 48
QFIC 61
PIC 20
If you require the L1 and L2 current drains for a specific shelf configuration, you can
calculate them as shown in Table 1-4.
CIC 2 22 W x 2 = 44 W e
Before you install the system in an equipment rack or cabinet, you must ensure that
you are using an Alcatel approved rack or cabinet which meets installation
requirements.
Table 1-5 describes the Alcatel 23 in, 7 ft Zone 4 seismic rack (44 RU) and the
Alcatel 7670 RSP custom cabinet which are recommended for use with 7670 RSP
shelves.
Danger 1 — Do not install a 7670 RSP shelf in a closed cabinet,
regardless of system or shelf configuration; otherwise, thermal
shutdown and/or failure may result. Alcatel’s closed cabinet design
(2200 mm × 900 mm × 750 mm ETSI footprint) with custom cooling
vents is the only exception to this rule. For seismic installations, we
recommend installation of a 7670 RSP shelf in an Alcatel 23 in, 7 ft
Zone 4 seismic rack with a custom airflow base (44 RU).
If you use an unapproved rack or cabinet, or fail to configure the
shelves according to this document, or if you fail to use the required
air intake/exhaust plenums, you may obstruct critical air intake and
exhaust openings and cause thermal shutdown and/or failure.
Please consult with your technical support representative to ensure
you are using the proper rack or cabinet and configuration.
Danger 2 — You must not obstruct the air intake openings in the
base of the Alcatel 23 in, 7 ft Zone 4 seismic rack (44 RU) or the
Alcatel 7670 RSP custom cabinet, as they are required for proper
cooling of any RSP shelf installed in the cabinet.
Table 1-5 Alcatel rack and cabinet recommended for 7670 RSP installations
Table 1-6 Installation requirements and shelf physical properties for 7670 RSP shelves installed in any rack
7670 RSP shelf Occupied RU Full load Thermal Important installation notes
configuration weight dissipation
1 × Switching shelf 22 RU 340 lb 2500 W You will usually install the two
Switching shelves (required in a
7670 RSP multishelf system) in the
same rack.
Note
(1) Peripheral shelf includes either a single shelf or a control shelf.
Table 1-7 describes the dimensional specifications of the 7670 RSP shelves.
Figures 1-1 and 1-2 show the dimensions of the Peripheral shelf and Switching shelf,
respectively.
Figure 1-1 Single shelf, control shelf, and Peripheral shelf dimensions
A1 A2 A3 A4 B1 B2 B3 B4
A Power A Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Control Card A Control Card A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c Control Control OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c
STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
21RU
I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault
933.5 mm
(36.75 in.)
A1 A2 A3 A4 B1 B2 B3 B4
A Power B Power
22 RU
Status
Active
Status
Active
Status
Active
Status
Active
Status
Active
Status
Active
Status
Active
Status
Active
977.9 mm
(38.50 in.)
Table 1-8 Physical specifications for the Alcatel 23 in, 7 ft Zone 4 seismic rack (44 RU)
Figure 1-3 shows the Alcatel 23 in, 7 ft Zone 4 seismic rack (44 RU) dimensions.
Figure 1-3 Alcatel 23 in, 7 ft Zone 4 seismic rack (44 RU) dimensions
2134 mm
(84.02 in.)
599 mm 659 mm
(23.58 in.) (25.94 in.)
16902
Warning — You cannot remove the cabinet side panels to run cables
between cabinets.
(1 of 2)
(2 of 2)
Figure 1-4 shows the Alcatel 7670 RSP custom cabinet dimensions.
2200 mm
(86.61 in.)
900 mm 750 mm
(35.43 in) (29.53 in.)
16140
Provision should be made at the site for access to the appropriate building ground
points. You ground the single shelf, control shelf, Peripheral shelf and Switching
shelf using a 2-hole lug on the top rear of the shelf. On the single shelf, control shelf,
and Peripheral shelf you must connect chassis and signal ground to the CO ground.
On the Switching shelf, chassis ground and signal ground are interconnected on the
midplane.
You must install the ground cables before powering any shelf.
Table 1-10 lists the grounds used and the various names that identify them; see the
Mandatory regulations for more information.
Signal Functional ground This ground ensures signal integrity. It usually provides a
Functional earth return path for unbalanced signaling between systems.
Telecom safety earth
Chassis Protective earth This ground ensures electrical safety. All user-accessible
Safety ground surfaces that may become energized under a fault condition
must be connected to this ground.
Frame ground
ac ground
ac earth
Signal ground
Signal ground is a communications ground that provides a current return path for
circuits that are grounded on both ends. It uses a 0 V reference when both circuits use
the ground. For the single shelf, control shelf, and Peripheral shelf, you must connect
the signal and chassis ground to the CO ground. For the Switching shelf, signal
ground and chassis ground are interconnected on the midplane. The Switching shelf
has a single ground point on the rear of the shelf.
The signal ground termination is located at the top rear of the single shelf, control
shelf, and Peripheral shelf. See Figures 1-9 and 1-10 for signal ground information
on the connection label.
Chassis ground
Chassis ground provides safety for electrical devices by drawing current away from
the device frame and chassis, preventing equipment from being energized if there is
an internal power fault in the device. Chassis ground also keeps ESD current away
from internal electronic components.
The chassis ground connection is located at the top rear of the control shelf,
Peripheral shelf and Switching shelf. The terminal supports a 2-hole lug.
If you install the shelves into a 7670 RSP cabinet, you may connect chassis ground
to the cabinet using the ground lugs provided on the cabinet.
Battery return
Also known as 0VR, battery return is the 0 V wire that returns to the battery. Because
the battery return carries a high level of current, always make sure that this wire is
separate from other ground wires. The wires that carry current should be separate
from the chassis ground, energy dumping ground, and signal ground. Never connect
the battery return to the main ground bus. See Figure 1-9 for battery return
information on the connection label.
Antistatic precautions
An antistatic kit is included with the shipment. Figure 1-5 shows the contents of the
kit.
Alligator
clip
Wrist Strap
bracelet Ring
terminal
8424
You can attach the wrist strap to ground points at the front or rear of a shelf.
Figure 1-6 and Figure 1-7 show the wrist-strap connection points on the front and
rear of a shelf.
Wrist-strap
connection point
Antistatic
wrist-strap
13946
Antistatic Wrist-strap
wrist-strap connection point
2-2 1-2
4-2 3-2
6-2 5-2
10-2 9-2
12-2 11-2
14-2 13-2
16-2 15-2
13953
The power module on the single shelf, control shelf, and Peripheral shelf provides
eight terminal blocks for external power termination. Figure 1-8 shows the terminal
blocks in the rear of a control shelf.
Connection
label
Terminal
blocks
2-2 1-2
4-2 3-2
6-2 5-2
10-2 9-2
12-2 11-2
14-2 13-2
16-2 15-2
7-1 Switch X
8-1 Switch Y
1-1
3-1 2-1
5-1 4-1
6-1
Status
9-1
11-1 10-1 Status Active
12-1 Active
14-1 13-1
16-1 15-1
14148
Figures 1-9 and 1-10 show the connection label on the inside of the cover on a single
shelf, control shelf, or Peripheral shelf.
Figure 1-9 Single shelf, control shelf, or Peripheral shelf connection label
Figure 1-10 Single shelf, control shelf, or Peripheral shelf connection label (newer shelves)
SEE INSTALLATION
INSTRUCTIONS BEFORE
CONNECTING TO THE SUPPLY.
THIS UNIT SHALL BE CONFIGURED ONLY
WITH THOSE COMPONENT ASSEMBLIES
-VBATT -VBATT SPECIFIED IN THE INSTALLATION MANUAL
-VBATT -VBATT
2B 1B
AND MOUNTED IN THE LOCATIONS
SPECIFIED.
2A 1A
0VR 0VR
CAUTION: THIS UNIT MAY HAVE UP TO FOUR
DC POWER FEEDS. DISCONNECT ALL FEEDS
BEFORE SERVICING. -VBATT INPUT RATED 0VR 0VR
-48/60 VDC
SEE INSTALLATION
INSTRUCTIONS BEFORE
CONNECTING TO THE SUPPLY.
THIS UNIT SHALL BE CONFIGURED ONLY
WITH THOSE COMPONENT ASSEMBLIES
SPECIFIED IN THE INSTALLATION MANUAL
AND MOUNTED IN THE LOCATIONS
SPECIFIED.
CAUTION: THIS UNIT MAY HAVE UP TO FOUR
DC POWER FEEDS. DISCONNECT ALL FEEDS
BEFORE SERVICING. -VBATT INPUT RATED
-48/-60 VDC
16326
Each single shelf, control shelf, or Peripheral shelf is powered by both an A input
feed and a B input feed from the terminal blocks.
The single shelf, control shelf, Peripheral shelves, and Switching shelves are fully
operational from either the A or B feeds. You must connect independent power feeds
from the dc power source to the A and B input terminal blocks to ensure equipment
reliability (redundancy) requirements. When both the A and B input feeds are
present, power is distributed between the A and B feeds. In the even of a failure of
one set of feeds, all power is supplied by the other set of feeds.
The power termination area on the Switching shelf provides four terminal blocks for
external power termination.
Each terminal block in a single shelf, control shelf, Peripheral shelf, or Switching
shelf supports two wires: one for -VBATT and one for 0VR, terminated by 2-hole
lugs. The lugs supplied with the shelf are sized for AWG#6 power feeds.
Figure 1-12 shows power termination on a terminal block.
Terminal
block
0VR
13943
The shelves have left and right terminal block safety covers installed over the
terminal block area. These covers come with the shelves. The covers must be
removed before you connect to the terminal blocks or signal ground, except on the
Switching shelf, which does not have a signal ground connection point. You must
reinstall the safety covers after you finish connecting to the terminal blocks and
signal ground. The covers have removable tabs on the sides to allow for increasing
numbers of cables. Figure 1-13 shows terminal block safety covers and the
removable tabs on a control shelf.
Note — On newer single shelves, control shelves, and Peripheral
shelves the signal and chassis grounds have been internally merged
and no longer require separate connections. A single ground point
now serves for both the signal and chassis grounds.
Removeable tabs
Right cover
1-2
10-2 9-2
12-2 11-2
14-2 13-2
16-2 15-2
7-1 Switch X
8-1 Switch Y
1-1
3-1 2-1
5-1 4-1
6-1
Status
9-1
11-1 10-1 Status Active
12-1 Active
14-1 13-1
16-1 15-1
14354
Power zones
The control shelf, Peripheral shelf and Switching shelf have four power zones with
each zone containing an A feed and a B feed for redundancy. Each feed is separately
filtered and breakered and can be powered on or powered off independently. All
power zones should be powered on at all times for normal system operation,
regardless of whether there are system cards installed in that zone. The eight circuit
breakers are located on the front of the shelves. Figure 1-14 shows the power zones
on the single shelf, control shelf, and Peripheral shelf.
Figure 1-14 Single shelf, control shelf, and Peripheral shelf power zone redundancy
7670 RSP
Routing Switch Platform
1A 2A 3A 4A 1B 2B 3B 4B
A Power A Power
OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c Control Control OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c
STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault
Cards
Status Status Status
Table 1-11 lists which Switching shelf components are in each power zone.
4 Fan units
As an example, Figure 1-15 shows the front of the breaker panel on the control and
Peripheral shelf.
Figure 1-15 Front of the breaker panel on the control and Peripheral shelves
A1 A2 A3 A4 B1 B2 B3 B4
A Power A Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Control Card A Control Card A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c Control Control OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c
STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault
1A 2A 3A 4A 1B 2B 3B 4B
A Power B Power
14058
The 7670 RSP uses a Direct Current (dc), nominal –48 V dc/ –60 V dc input voltage
source. You must use a rectifier power system to power the 7670 RSP from an ac
voltage source. You install the rectifier power system between the available ac
voltage source and the dc input terminal blocks.
Table 1-12 lists the rectifier power system requirements.
Requirement Description
You can configure up to four external synchronization sources for the 7670 RSP.
Table 1-13 lists the synchronization sources supported by the single-shelf system and
the multishelf system.
Caution — You must synchronize your nodes to the same source to
avoid traffic disruption due to timing differences between nodes.
The SSU distributes system timing to all line cards and chooses a source based on a
configurable hierarchy.
Caution — The 7670 RSP may experience cell loss if the control
complex is not accessible by the line cards and therefore cannot
distribute timing. The control complex is not accessible when both
control cards are removed from the control shelf.
1 (highest) External A
2 External B
3 Undefined
4 Undefined
5 Holdover
6 (lowest) Free-run
Signal cables
As the signal cables exit the shelves, you must route them through the cabinet using
the vertical conduit provided. The cables can be routed either through the top of the
cabinet or through the bottom.
Warning — Be careful not to bend the fiber cables past the minimum
bend radius when routing them from the termination point into the
conduit.
Power cables
Power cables should not be routed through the conduits. They should be dressed
separately and secured to the cabinet with the cable tie locations provided on the
cabinet. The cables can be routed either through the top of the cabinet or through the
bottom.
Figure 1-16 shows the cable management vertical conduits in the cabinet.
Equipment mounting
rail
Removable side
panels
Air intake
on plenum
16141
Note — The extra large cable management tray extends the depth of
the shelf to 665 mm (26.18 in.), which exceeds the standard 600 mm
(23.62 in.) limit.
Contact your technical support representative for more information
about ordering the Extra Large Cable Management System.
Cables from CICs, FICs, and Facilities cards are routed up to the power termination
area and then horizontally to the frame uprights.
Power, alarm, and ground cables leaving the system terminate at the top rear of the
shelf and are routed from the termination point horizontally to the frame uprights.
Figure 1-17 shows the cable management features of the single shelf or Peripheral
shelf.
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 8-2 6-2 5-2 4-2 3-2 2-2 1-2
Facilities CIC
Clock
B In
1 1
External Alarms
2 2
3 3
4 4
External Alarms
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 6-2 5-2 4-2 3-2 2-2 1-2
14057
Figure 1-18 shows the CSL and QFIC cable management features of the control
shelf. Optionally, you can reorient the cable supports below slots 7 and 8 on a
Peripheral or control shelf. This allows the cables from a DFIC or QFIC to run in the
same direction to either one or the other side of the shelf, or in opposite directions to
each side of the shelf. See Procedure 1-22.
Figure 1-18 CSL and QFIC cable management on the control shelf
Facilities CIC
Active Active
Facilities CIC
Clock
Out
Clock
A In
Clock
Out Clock Clock Clock
CIC
Out A In Out
Clock
B In
CIC
1 1
Clock
External Alarms
2 2
B In
3 3
4 4
External Alarms
Tx2 Tx2
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 6-2 5-2 4-2 3-2 2-2 1-2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Control shelf
ACO/LT Critical Alarm
Major Alarm
Minor Alarm
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 8-2 6-2 5-2 4-2 3-2 2-2 1-2
Facilities CIC
Clock
B In
1 1
External Alarms
2 2
4
3
External Alarms
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 6-2 5-2 4-2 3-2 2-2
2-2 1-2
1-2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
Tx2 Tx2
12861 17372
Power, alarm, and ground cables leaving the system terminate at the top rear of the
shelf and are routed from the termination point horizontally to the frame uprights.
Switching shelf
ACO/LT Critical Alarm
Major Alarm
Minor Alarm
CSL A
CSL B
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
CSL A
CSL B
Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx
Tx Tx Tx Tx Tx
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Rx Rx Rx Rx Rx
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx
12861 17371
Table 1-15 lists procedures associated with installation and connection of the
Peripheral, control, and single shelves.
Table 1-15 Single shelf, control shelf, and Peripheral shelf installation and
connection procedures
To See procedure
Move the mounting brackets from the NEBS to the ETSI position (optional) 1-3
(1 of 2)
To See procedure
Configure adjustable bracket for ICON cable management on a control shelf 1-20
Reorient adjustable cable supports for DFIC or QFIC cable management on a 1-22
control or Peripheral shelf (optional)
Connect a node management terminal to a serial port on the Facilities card or a 1-21
control card
Connect the network manager and data collector to the Ethernet ports on the 1-23
CICs
Connect alarm inputs and outputs to and from the Facilities card 1-27
(2 of 2)
Table 1-16 lists procedures associated with installation and connection of the
Switching shelves.
To See procedure
Remove filler plates from the SAC slots that will contain SACs 1-15
(1 of 2)
To See procedure
(2 of 2)
Note
(1) Repeat procedures for the second Switching shelf.
This section contains procedures associated with 7670 RSP installation and cable
connection.
Warning — Do not lift the shelf by applying pressure or force to the fiber
tray; doing so will bend the tray and damage your equipment. The fiber
tray is the horizontal metal tray below the cable management brackets;
all cables dress down to this tray and are directed to either side of the
shelf.
1 Undo the bolts that secure the front tie-downs/handles to the base of the shipping
pallet; see Figure 1-21 for an example of the tie-downs/handles on the Peripheral
shelf.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Status
Status
Active Status
Active Status Status
I/O Active Status Status
I/O Active Active
I/O Active Active Status
I/O I/O
I/O Active
Status
Status
Active Status
Active Status Status
I/O Active Status
I/O Active Active Status
I/O Active Status
I/O I/O Active
I/O Active
I/O
I/O
14337
2 Undo the bolts that secure the rear tie-downs/sliders to the base of the shipping
pallet, see Figure 1-21.
3 Remove the rear tie-downs/sliders from the shelf and keep them and their screws
for mounting the shelf.
You require the following tools and hardware to complete this procedure:
Warning — If the shelf was shipped with the fan units installed, or if you
are relocating an existing shelf, remove the fan units before proceeding
with the installation.
2 Use a slot screwdriver to turn the 1/4-turn lock on one of the fan units to the unlocked
position; see Figure 1-22.
A1 A2 A3 A4 B1 B2 B3 B4
A Power A Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Control Card A Control Card A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
14195
3 Using the handle, pull the fan unit out of the shelf.
Procedure 1-3 Move the mounting brackets from the NEBS to the
ETSI position
A Peripheral shelf and Switching shelf have the mounting brackets attached to the shelf
exterior in a NEBS position. If you require the shelf to be in an ETSI position, you must
move the mounting brackets forward prior to installing a shelf in a rack. If the shelf is
already installed in a rack, decommission and remove the shelf from the rack before
performing this procedure.
2 Remove all front-side cards and filler plates, power modules, and fan units. See
Procedure 61-2 for the cards, Procedure 1-15 for the filler plates, Procedure 61-4
for the power modules, and Procedure 61-5 for the fan units.
3 On a Switching shelf, remove the filler plates from the interior of the shelf by
removing the 5 filler-plate screws on each side. See Figure 1-23.
4 Remove the screws in the mounting brackets from the inside of the shelf.
Figure 1-23 shows a Switching shelf with a bracket removed on one side and a
bracket in the NEBS position on the other side. Figure 1-24 shows the same details
on a Peripheral shelf.
5 Place each mounting bracket in the ETSI position on the side of the shelf exterior.
ETSI position
NEBS position
1
17162
ETSI position
1 NEBS position
2
4
Mounting bracket screws
8 per side
7
8
17163
7 On a Switching shelf, replace the two filler plates using a torque of 0.9 to 1.1 N . m (8
to 10 lbf-in).
9 Re-install all front-side card and filler plates, power modules, and fan units removed
in step 2.
Procedure 1-4 Mount the single shelf, control shelf, Peripheral shelf,
or Switching shelf in a rack
You can also install the shelves into a custom 7670 RSP cabinet; see Procedure 1-6.
Warning — Do not lift the shelf by applying pressure or force to the fiber
tray; doing so will bend the tray and damage your equipment. The fiber
tray is the horizontal metal tray below the cable management brackets;
all cables dress down to this tray and are directed to either side of the
shelf.
You require the following tools and hardware to complete this procedure:
1 You and an assistant must each put on an antistatic wrist strap and connect it to the
ground point.
2 Position and fasten the rear tie-downs/sliders in the equipment rack; see
Figure 1-25.
Note — You can also use the base of the rack or the top of the lower
shelf as a guide.
14338
3 With your assistant and mechanical assistance, position the shelf on the rear
tie-downs/sliders in the equipment rack; see Figure 1-26.
A1 A2 A3 A4 B1 B2 B3 B4
A Power A Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Control Card A Control Card A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Tie-down/slider Tie-down/slider
17379
4 Use screws to fasten the mounting flanges of the shelf to the rack; see Figure 1-27.
7670 RSP
Routing Switch Platform
A1 A2 A3 A4 B1 B2 B3 B4
A Power A Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Control Card A Control Card A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Machine Machine
screws screws
13925
See Table 1-17 for the air intake positions for the installed shelves.
1 Remove the intermediate plate and duct assembly from each door of the cabinet;
see Figure 1-28. Place plates and assemblies on a surface such as a table or the
floor.
Intermediate plate
Duct assembly
Intermediate plate
Duct assembly
16272
2 Remove the duct assemblies from the intermediate plates; see Figure 1-29.
16273
3 Transpose the intermediate plates, but do not transpose the duct assemblies; see
Figure 1-30.
16274
16275
5 Attach the duct assemblies to the intermediate plates; see Figure 1-32.
16276
6 Install the intermediate plates/duct assemblies on the doors; see Figure 1-33.
Note — The duct assembly from the right door must be reinstalled on
the right door.
The duct assembly from the left door must be reinstalled on the left door.
16277
When you install shelves in the Alcatel 7670 RSP custom cabinet, you
must install them in one of the configurations listed in Table 1-17 and in
one of the mounting positions described in Table 1-18.
The adjustable air intake vent must be configured on the cabinet door
before you install the shelf. See Table 1-17 for air intake positioning for
cabinet combinations. See Procedure 1-5 for adjusting the air intake vent.
When you install the shelves into a cabinet, you must install them in one of the
configurations listed in Table 1-17. Table 1-18 describes the upper and lower mounting
positions.
Top shelf Bottom shelf Top air intake Bottom air intake
Note
(1) From top of shelf to bottom of door opening.
• #2 Phillips screwdriver
• slothead screwdriver
• socket driver
2 Check Table 1-17 to confirm that your mounting configurations are correct.
4 Using mechanical assistance, mount the first shelf into the cabinet. Use the
mounting positions listed in Table 1-18 to determine the correct position on the rack
for each shelf. Fasten the shelves to the rack using the fasteners provided with the
cabinet.
i Using the #2 Phillips screwdriver, remove the screws that attach the right
terminal block safety cover to the shelf. For an example of removing the
terminal cover screws from a control shelf, see Figure 1-34.
ii Remove the terminal block safety cover by pulling the cover toward you.
2-2 1-2
4-2 3-2
6-2 5-2
10-2 9-2
12-2 11-2
14-2 13-2
16-2 15-2
14356
iii Repeat steps i and ii for the left terminal block safety cover.
i If necessary, snap off one or more breakaway tabs from the side of both covers
to accommodate the cables. For an example of the breakaway tabs on a cover
for a control shelf, see Figure 1-35.
Break away
tabs
14357
ii Slide the terminal safety block cover into the slots. If you are installing the
terminal safety block cover on a single shelf, control shelf, or Peripheral shelf,
rest the LED cable on top of the terminal block safety cover. Figure 1-36
shows, as an example, the LED cable on a control shelf.
LED cable
2-2 1-2
4-2 3-2
6-2 5-2
10-2 9-2
12-2 11-2
14-2 13-2
16-2 15-2
14358
You require the following tools and hardware to complete this procedure:
Note — If you are connecting the chassis ground on the Switching shelf,
or newer version of the single shelf, control shelf, or Peripheral shelf, you
only need one 2-hole lug and one wire between 2 AWG and 6 AWG, for
use as a ground strap.
1 Put on the antistatic wrist strap and connect it to a grounding point.
3 Remove the plastic protective covers, nuts, and 2-hole lugs from the ground
connectors. See Figures 1-37, 1-38, and 1-39 for the connector locations. See
Procedure 1-7 for instructions on removing the protective covers.
7 Position the lug of the chassis ground strap over the chassis ground connectors,
secure with the nuts removed in step 3 and torque to 1.7-2.0 Nm (15-17 lb in.); see
Figure 1-37 and Figure 1-39.
Figure 1-37 Ground connection for single shelf, control shelf, or Peripheral shelf
Chassis ground
-Vbatt
Rear panel
cover
0VR
Signal
ground
Chassis ground
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 8-2 7-2 6-2 5-2 4-2 3-2 2-2 1-2
CIC
Status
Active
Facilities
Status
CIC
Status
Active
Signal ground
Clock Clock Clock
Out A In Out
Clock
B In
1 1
External Alarms
2 2
3 3
4 4
Mgnt. Mgnt.
RS 232 DCE
Spool Spool
Aux.1 Aux.1
Aux.2 Aux.2
13947
Figure 1-38 Ground connection for single shelf, control shelf, or Peripheral shelf (newer shelves)
Chassis ground
Chassis ground
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 8-2 7-2 6-2 5-2 4-2 3-2 2-2 1-2
CIC
Status
Active
Facilities
Status
CIC
Status
Active
Signal ground
Clock Clock Clock
Out A In Out
Clock
B In
1 1
External Alarms
2 2
3 3
4 4
Mgnt. Mgnt.
RS 232 DCE
Spool Spool
Aux.1 Aux.1
Aux.2 Aux.2
17497
Chassis ground
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
13947
17363
Connect the free end of the ground strap to the grounded equipment rack.
9 If you are installing a single shelf, control shelf, or Peripheral shelf, repeat steps 7
and 8 for the signal ground.
You require the following tools and hardware to complete this procedure:
Note — If you are connecting the power feeds on a Switching shelf, you
only need eight 2-hole lugs, eight 6-AWG wires, and 8 heat shrink tubes.
3 Remove the plastic protective covers, nuts, and 2-hole lugs from the terminal
connectors. See Figure 1-12 for the connector locations.
5 Strip approximately 0.6 cm (0.25 in.) of insulation from the end of each wire.
7 Crimp one 2-hole lug on the end of each wire; see Figure 1-40.
14708
8 Position the heat shrink tube over the 2-hole lug and warm with a heat gun until the
tube tightens around the lug and wire; see Figure 1-41.
Figure 1-41 Wire with 2-hole lug and tightened heat shrink tube
14710
9 Locate the terminal block of power zone 1 for power feed A. See Figure 1-9 for the
connection label.
10 Position the lug of the 0VR wire over the terminal connector labeled 0VR, secure it
with the nuts removed in step 3 and torque to 1.7-2.0 Nm (15-17 lb in.); see
Figure 1-12.
11 Position the lug of the -VBATT wire over the terminal connector labeled -VBATT,
secure it with the nuts removed in step 3 and torque to 1.7-2.0 Nm (15-17 lb in.).
14 At the terminal strip of all power feeds, use a voltage meter to verify the proper
polarity and voltage level.
16 Set the shelf circuit breakers to ON; see Figure 1-61. Wait for the system to
complete the power-up tests.
Warning — If any of the circuit breakers trip, verify that the power feeds
are connected correctly.
17 Check the color of the power status LED located below each circuit breaker to
ensure that the power feeds are working properly; see Table 1-19.
LED Status
Procedure 1-10 Install a fan unit in the single shelf, control shelf, or
Peripheral shelf
Warning — To prevent the shelf from overheating, install the three fan
units before powering on the shelf for operation. You must install all three
fan units to ensure adequate thermal performance of the shelf.
You require the following tools and hardware to complete this procedure:
2 Align the fan unit with the fan unit rails, and slide the fan unit into the shelf.
3 Use a slot screwdriver to turn the 1/4-turn lock on one of the fan units to the locked
position; see Figure 1-42.
A1 A2 A3 A4 B1 B2 B3 B4
A Power A Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Control Card A Control Card A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
14195
5 If the shelf is powered off, power on the shelf, check that all fan units are operating,
and power off the shelf.
The exhaust deflector tray can be installed below a Peripheral or a Switching shelf in a
rack. Two people are required to mount the tray in a rack. The tray can be mounted in a
NEBS-compliant or ETSI-compliant rack. The mounting brackets on the tray are shipped
in the ETSI position.
Note — The tray extends 5.1 cm (2 in.) beyond the front edge of the
shelf in the NEBs position. If this does not meet your requirements, you
can move the mounting brackets on the shelf to the ETSI position; see
Procedure 1-3.
You require the following tools and hardware to complete this procedure:
1 You and an assistant must each put on an antistatic wrist strap and connect it to a
ground point.
2 Have your assistant hold the tray flush with the bottom of the shelf to ensure proper
air flow. Make sure the mounting brackets on the tray match the mounting brackets
of the shelf.
3 For an ETSI-compliant tray, mount the tray to the rack with a minimum of 2 screws
per side. See Figure 1-43. The holes in the mounting brackets of the tray align with
a minimum of two holes in the rack. Use the widest spacing when more than two
holes are visible.
Fan Unit 3
Status
Exhaust
deflector
tray
Mounting
bracket
Rack
Latches
17143
i Remove the mounting brackets from the tray by removing the 2 screws on
each side.
ii Shift the brackets to the NEBS position and reattach the brackets with the
screws removed in step i, using a torque of 0.9 to 1.1 N . m (8 to 10 lbf-in); see
Figure 1-44.
Fan Unit 1
Status
Status
Exhaust
deflector
tray
Mounting
bracket
Rack
Latches For ETSI-mounting
17144
iii Mount the tray to the rack with a minimum of 2 screws per side. The holes in
the mounting brackets of the tray align with a minimum of two holes in the rack.
Use the widest spacing when more than two holes are visible.
Installing an extra large cable management tray increases the area reserved for optical
fiber routing, and enables you to route optical fibers and copper cables separately. See
section 1.7 for more information on cable management.
You require the following tools and hardware to complete this procedure:
2 Remove any fiber and copper cables from around the cable supports on the
standard cable management trays.
3 Use the Phillips screwdriver to remove the standard cable management trays from
the shelf; see Figure 1-45.
i Remove the two mounting screws from each of the upper cable management
trays.
ii Remove the four mounting screws from the lower cable management tray.
Status
Status Active
Active
17106
4 Use the Phillips screwdriver to attach the extra large cable management trays to the
shelf; see Figure 1-46.
i Install the two mounting screws in each of the upper cable management trays.
ii Install the four mounting screws in the lower cable management tray.
Status
Status Active
Active
17107
5 Route the optical fibers from the I/O cards and QFIC/DFIC cards around the cable
supports; see section 1.7 for more information.
6 Route the copper cables from the I/O cards down to the extended part of the tray
and secure the cables with a cable tie in the lance provided for each card slot; see
Figure 1-47. Ensure that the cables are routed straight down and do not interfere
with insertion or extraction of the adjacent cards. Alternatively, you can route the
ICON cables through the ICON cable management bracket as described in
Procedure 1-20.
Figure 1-47 Route copper cables to the extended cable management tray
17119
You can install or remove cards while the system is powered on.
All shelves support card installation on both the front and rear of the midplane. Table 1-20
describes card types and slot positions.
Danger — Laser emissions can damage your eyes. Never look at the
end of a live fiber-optic cable or the optical port of an installed card.
Warning 4 — When you replace a card at the rear of the shelf, use
caution to ensure that you do not damage the fiber-optic cables that are
attached to neighboring cards. Always ensure that these cables are
removed from the cable brackets before you replace a card.
Caution — Do not remove the SSC card, SCH card, or any of the SMX
cards from the active Switching shelf. If you must remove one of these
cards from the active shelf, force activity to the other shelf first.
Note 1 — You may need to remove the filler plate before you can install
a card. When you remove a card and do not install another card in its
place, you must install a filler plate to prevent cooling air from escaping
and to maintain EMC compliance.
Single shelf, control Control card (1) Front slots 7 and 8 4-1
shelf or Peripheral
shelf CC2G card (1) Front slots 7 and 8
CIC (1) Rear slots 8-2 CICB and 7-2 CICA 4-2
I/O card Rear slots 16-2 to 15-2 (top row) (3) (4) (5) 6-2
Rear slots 16-1 to 15-1 (bottom row) (3)
Rear slots 14-2 to 9-2 and 6-2 to 1-2 (top row) (4) (5)
Rear slots 14-1 to 9-1 and 6-1 to 1-1 (bottom row)
ICON I/O card Rear slots 16-1 and 15-1 (bottom row) 6-2
ICON I/O Rear slots 16-2 and 15-2 (top row) 6-2
Expansion card
DFIC and QFIC Rear slots 8-1 FabY/FIC Y and 7-1 FabX/FICX 4-2
Notes
(1) You only install control cards and CIC cards in a single shelf or control shelf.
(2) You only install Switch cards in a single-shelf system.
(3) If you plan to upgrade to a multishelf configuration, reserve line card slots 15 and 16 and I/O card slots 16 and 15 on both
the top and bottom rows.
(4) You can install the 1-port OC48/STM16 Channelized I/O card in I/O slot 1 only. The I/O card can be physically placed in I/O
slot 2, but you cannot configure the card in that slot.
(5) You can install the 4-port OC12/STM4 Channelized I/O card in I/O slot 1 only. The I/O card can be physically placed in I/O
slot 2, but you cannot configure the card in that slot.
Align the card with its slot, ensuring that the PCB is properly located in both the top
and bottom card guides. If the card has ejectors, keep them in the closed position,
flush with the faceplate.
3 Warning 1 — When you slide the card into the slot, push the card
by applying pressure at the center of the faceplate until the closed
ejectors contact the top and bottom ejector troughs. This ensures that
you do not insert the card at an angle and damage your equipment.
i Slide the card into the slot until the closed ejectors contact the shelf
metalwork.
ii Open the ejectors by pulling them away from the center of the card
faceplate while depressing the catch on the back of the ejector. The card
will pull back slightly as you perform this step. You must ensure that the
card does not get pulled back beyond the point of gasket engagement to
protect the pin field.
iii Gently slide the card the rest of the way into the shelf, until the open
latches make contact with the shelf metalwork again.
iv Push the levers of both ejectors simultaneously toward the center of the
card faceplate until the spring clips lock the card into place; see
Figure 1-48.
b For a card that does not have ejectors, slowly slide the card all the way into the
slot. You must ensure that the card is inserted evenly and gently, and do not
use force to overcome initial gasket compression load.
13920
a For a card with an ejector, use a medium slot screwdriver to secure the card
lock.
b For a card without an ejector, use a medium slot screwdriver to secure the
captive screws on the card.
Note — You must install filler plates in empty slots to prevent cooling air
from escaping and to maintain EMC compliance.
2 Pull the filler plate locking levers away from the center of the faceplate to the open
position.
3 Align the filler plate with the upper and lower card guides.
4 Slide the filler plate all the way into the slot.
5 Pull the locking levers toward the center of the faceplate until the spring clips lock
the filler plate in place.
2 Pull the locking levers away from the center of the faceplate to release the filler
plate. Gently pull on the ejectors to remove the filler plate from the chassis.
This procedure describes how to connect to, or disconnect from, optic-based cards. See
chapter 60 for information on handling, inspecting, and cleaning optical connectors and
receptacles.
Note — Use the cable clips that come with the card to join the transmit
and receive cables before connecting them to the card. The clip makes it
easier to connect and remove cables.
1 Put on the antistatic wrist strap and connect it to the ground point.
2 Take one half of a cable clip and lay the transmit and receive cables across it; see
Figure 1-49.
Cables
Cable clip
14232
3 Take the second half of a cable clip and snap it closed over the first one; see
Figure 1-50.
Cables
Cable clip
14231
4 Holding on to the cable clip, insert the transmit cable into the transmit port and the
receive cable into the receive port of the I/O card; see Figure 1-51. When properly
seated, the cable collar clicks into place.
Figure 1-51 Connecting the transmit and receive cables to an optic-based card
14233
5 To remove the cables from the card, grasp the cable clip and pull it toward you. The
cable collar releases the connection to the card.
Caution — The I/O cables for the DS3 and STM1 electrical I/O cards
must be double-shielded coaxial cable to maintain EMC compliance to
Class B.
2 Slide the transmit cable onto the transmit port until it clicks into place.
3 Slide the receive cable onto the receive port until it clicks into place.
4 To remove a cable, grasp the end of the cable and pull it toward you.
2 Slide the transmit cable into the transmit port until it clicks into place. Figure 1-52
shows a HISL cable connector.
HISL connector
HISL cable
17358
3 Slide the receive cable into the receive port until it clicks into place. Figure 1-53
shows the three possible HISL cable connector positions.
17359
4 To disconnect a cable, grasp the end of the cable and pull it toward you.
CSL cables have different connectors on each end. The DB-15 connector on one end
connects to the PIC or directly to the Switching shelf. The Lemo connector on the other
end connects to the ICON I/O or ICON I/O Expansion cards. Figure 1-54 shows the
connectors on each end of the CSL cable.
DB-15 connector
CSL cable
Lemo connector
17356
2 To connect the DB-15 connector, slide the cable connector into the card or shelf
port. When firmly seated, tighten the thumbscrews.
3 To connect the Lemo connector, slide the connector into the ICON port. Press
firmly. Figure 1-55 shows the Lemo connector attached to an ICON card.
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 8-2 6-2 5-2 4-2 3-2 2-2 1-2
Facilities CIC
Clock
B In
1 1 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
External Alarms
2 2
3 3
4 4
External Alarms
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
CSL A
CSL B Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx
16-2 15-2 14-2 13-2 12-2 11-2 10-2 9-2 6-2 5-2 4-2 3-2 2-2 1-2
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
CSL A
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
CSL B
Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx
CSL cable
12861 17357
Lemo connector DB-15 connector
4 To remove the DB-15 connector, loosen the thumbscrews and pull the cable
connector toward you.
5 To remove the Lemo connector, grasp the connector and pull it toward you.
See section 1.7 for more information on cable management. You require the following
tools and hardware to complete this procedure:
1 Put on the antistatic wrist strap and connect it to the ground point.
2 Remove the bracket faceplate by loosening the upper and lower screws; see
Figure 1-56.
Note 1 — You must retain the bracket faceplate and screws; you will
reattach them in step 4.
Note 2 — There are four hexagonal posts behind the bracket faceplate;
one post is attached to the bracket faceplate by the middle screw. You
may detach this post from the faceplate and discard it. The middle screw
is captive in the faceplate; you may leave the screw in the faceplate or
remove it from the faceplate and discard it.
Adjustable
bracket
Hexagonal post
(one of four behind
bracket faceplate)
Faceplate
3 While the bracket faceplate is off, dress the ICON cables through the posts on the
ICON cable management bracket to the left-hand frame upright; see Figure 1-57.
a Dress ICON cables from slot 16 around the first post and above the lower post.
b Dress ICON cables from slot 15 around the second post and above the lower
post.
ICON card
in slot 15
ICON card
in slot 16
4 To retain the ICON cable dressing, reattach the bracket faceplate using the upper
and lower screws previously removed.
See section 17.6 for more information on node management terminals. You require the
following tools and hardware to complete this procedure:
1 Put on the antistatic wrist strap and connect it to the ground point.
b To connect a terminal to the serial port on a control card, push the DB-9 to
RJ-45 connector into the serial port on the control card faceplate.
3 Attach the free end of the DB-9 cable to the TIA/EIA-232 port on the node
management terminal and tighten the screws.
Optionally, you can reorient the cable supports below slots 7 and 8 on a Peripheral or
control shelf. This allows the cables from a DFIC or QFIC to run in the same direction to
either one or the other side of the shelf, or in opposite directions to each side of the shelf.
• an antistatic strap
• #2 Phillips screwdriver
Note — Disengage any fiber or copper cables from the cable supports
on the lower cable management tray.
2 While holding the lower cable management tray, remove the 4 screws that attach
the tray to the shelf; see Figure 1-58.
Figure 1-58 Removing the lower cable management tray from the shelf
Cable support
Cable management
tray
Screw 4
Screw 3
Screw 2
Screw 1
17197
3 Turn the cable management tray with its back side facing you. Loosen the screw of
one or both cable supports for slots 7 and 8 for which you want to change the
orientation; see Figure 1-59.
4 Reorient each cable support in the direction you want the cables to run. Tighten the
screw.
5 Turn the cable management tray with the front side facing you. Reattach the tray to
the shelf using the 4 screws removed in step 2.
Figure 1-59 Reorienting the two cable supports for slots 7 and 8
17198
See section 17.6 for more information on Ethernet devices. You require the following
tools and hardware to complete this procedure:
2 Push the RJ-45 connectors on the Ethernet cable into the Ethernet ports on the
CICs. For each CIC, use Port 1 for the network management connection and
Port 2 for the data spooling connection.
3 Clip the ferrite beads around the Ethernet cables as close to the CIC faceplate as
possible. Secure the beads in place with cable ties.
You require the following tools and hardware to complete this procedure:
2 Attach the BNC connector for the primary timing supply to the port on the Facilities
card labeled Clock A In.
3 Attach the BNC connector for the redundant timing supply to the port on the
Facilities card labeled Clock B In.
You require the following tools and hardware to complete this procedure:
2 Attach the BNC connector for the timing output to the port on the CIC labeled
Clock Out.
You require the following tools and hardware to complete this procedure:
Caution — You must synchronize your nodes to the same BITS source
to avoid traffic disruption due to timing differences between nodes.
2 Connect the positive lead (tip) of the timing supply to the Clock A pin on the Facilities
card labeled Tip; see Figure 1-60.
Facilities
Status
Clock A In
Shield
Tip
Ring
Clock B In
Shield
Tip
Ring
External Alarms
RS 232 DCE
14328
3 Connect the negative lead (ring) of the timing supply to the Clock A pin on the
Facilities card labeled Ring.
5 If you are connecting an unshielded BITS, connect the shield grounds to the pins on
the Facilities card labeled Shield.
You require the following tools and hardware to complete this procedure:
Pin Signal
1 No connect
2 External alarm 2
3 External alarm 4
4 No connect
13 No connect
14 No connect
15 External alarm 1
16 External alarm 3
17 General purpose visual Contact
18 Common (-24 v)
2 Attach the DB-25 connector to the port on the Facilities card labeled External
Alarms.
3 Make the connections to the third-party alarm input and output devices.
Set the shelf circuit breakers to ON; see Figure 1-61 for an example of the
Peripheral shelf breaker panel. Wait for the system to complete the power-up tests.
Each card performs a self-test, a lamp test on the faceplate LEDs, and power-up
diagnostics.
2 Check the color of the Status LED on each card faceplate. A flashing red/green LED
display is normal and indicates that the slot has not yet been programmed for this
card type. A red Status LED indicates that the card has failed power-up diagnostics.
Circuit
breakers
A1 A2 A3 A4 B1 B2 B3 B4
A Power A Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Control Card A Control Card A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c Control Control OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c OC3c-OC12c
STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4 STM1-STM4
Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault I/O Fault
17355
Numbers cables
CSL
0VR, 1-14, 1-17 connecting, 1-69
2.048 MHz synchronization disconnecting, 1-69
connecting input, 1-76 electrical
connecting output, 1-76 connecting, 1-67
disconnecting, 1-67
A HISL
connecting, 1-68
alarms
disconnecting, 1-68
connecting inputs, 1-78
management, 1-23, 1-26
connecting outputs, 1-78
optic
connector pins, 1-78
connecting, 1-65
signal assignments, 1-78
disconnecting, 1-65
antistatic ground, 1-14
cards
B handling, 1-60
installing, 1-60
battery disposal, viii power consumption, 1-4
battery return, 1-14 slot positions, 1-62
BITS, 1-22 CC2G cards
connecting synchronization, 1-77 installing, 1-60
breaker panel, 1-21 chassis ground, 1-13, 1-48
CICs
C connecting 2.048 MHz output, 1-76
installing, 1-60
cabinet planning, 1-5 synchronization, 1-22
cable management clock connection points, 1-77
Switching shelf, 1-28
connecting — installation
L Q
lasers, ix QFIC
LEDs reorienting cable supports, 1-73
power status, 1-54
line cards R
installing, 1-60
rack mounting, 1-36
M rack planning, 1-5
regulations
mandatory regulations, vii Canada, x
mounting brackets CSA NRTL, xi
moving from NEBS to ETSI, 1-34 Europe, xii
FCC, xi
N FDA, xii
mandatory, vii
node management terminal USA, xi
connecting
Ethernet port, 1-75 S
serial port, 1-72
safety covers
O installing, 1-45
removing, 1-45
optic cables SELV, ix
clips, 1-65 shelf
connecting, 1-65 connecting power, 1-52
disconnecting, 1-65 dimensions, 1-7
installing, 1-33
P
mounting, 1-36
Peripheral shelf power consumption, 1-4
dimensions, 1-7 power rating, 1-3
exhaust deflector tray, 1-56 power status LEDs, 1-54
moving mounting brackets, 1-34 unpacking, 1-31
Perpheral shelf shelf dimensions, 1-5
reorienting cable supports, 1-73 signal ground, 1-13
connecting, 1-48
T
terminal blocks, 1-15
installing safety covers, 1-45
removing safety covers, 1-45
V
VBATT, 1-17
Customer documentation
http://www.alcatel.com/osds/
Product manuals and documentation updates are available through the Alcatel Support
Documentation and Software Download service at Alcatel.com. If you are a new user and
require access to this service, please contact your Alcatel sales representative.
Technical support
http://www.alcatel.com/support/
95-5879-01-00-A