Académique Documents
Professionnel Documents
Culture Documents
» Pulse-width modulator
The pulse-width modulation (PWM) charge
controller is the most common type. These charge
controllers operate using basic ON/OFF
switching to regulate the charging voltage.
31
MODULE 2: COMPONENTS AND ELECTRICAL CONNECTIONS
» AC switch disconnect
AC switch disconnect which must be double-pole and
lockable in the “OFF” position. This device usually separates
the load from the inverter output.
» Fuses
Fuses are the most common form of OPCD. In photovoltaic
systems, DC fuses protect wires connected to the battery. In
large PV arrays with more than three solar module strings,
they are sometimes used to protect the modules and wiring
from fault currents which can occur under certain
conditions. The rating should be based on the maximum
current which the string generates.
Figure 2.27: Double pole MCB
Figure 2.28: 100 A DC fuse for Figure 2.29: Array protected with string fuses and main
battery connection disconnect
you select and use a DC SPD with the Figure 2.31: PV surge arrestor max 500 V/DC in combiner box
matching voltage to the equipment. (left) and wiring of SPD (right)
The AC output of an inverter is also sensitive to voltage surges that can occur, for example,
due to inductive load switching (motors) or lightning-induced surges. Many PV inverters
have built-in SPDs, while battery inverters are usually not equipped with SPDs. Some
additional equipment/features that are used to protect electrical systems:
Insulation: All active parts or bodies such as conductors and connectors must be
covered with an insulating material which can withstand several times the nominal
operating voltage and which can only be removed by destroying it.
Enclosures: Enclosures for parts such as switches or sockets must be properly
secured. Removal should only be possible with the use of tools. Their protection class
must match their application (system voltage, installation environment).
Spacing: Distribution lines must be installed in a way that people cannot touch them
under normal conditions.
The table below explains the ingress protection (IP) rating system published by the
International Electrotechnical Commission (IEC).
33
MODULE 2: COMPONENTS AND ELECTRICAL CONNECTIONS
The necessity of lightning protection for the PV system depends on the risk of lightning
strikes and the value of the system. A solar home system in an area with a low risk for
lightning strikes and a value of no more than NGN 200,000 will not need a NGN 100,000
LPS. Sometimes certain types of buildings require LPS due to their function and due to legal
regulations (e.g. public buildings, certain types of industry). If lightning protection is
required for a building, the solar PV system must be integrated into the LPS. However, a
solar PV system does not increase the risk of lightning striking a building as long as its
installation does not change the building’s shape significantly.
Damage due to nearby lightning strikes is far more common than damage due to direct lightning strikes.
Nevertheless, the damage caused by direct lightning strikes is often significantly more devastating.
34
MODULE 2: COMPONENTS AND ELECTRICAL CONNECTIONS
Down conductor
Ground termination system (earth or ground rod)
The LPS for external lightning protection has to lead a lightning strike safely to the ground
without causing damage due to heat or sparking.
Note: Complete equipotential bonding requires the inclusion of all active conductors such as power supply and
data lines via surge protection devices.
GROUNDING
There are two ways to ground solar systems:
Equipment grounding means
connecting all metal bodies of the
equipment to the ground electrode.
These include solar panel frames,
inverter and charge controller
housings, metal junction boxes as
well as potential earth conductors on
the AC side of the installation. When
grounded properly, in the event of
lightning strike the induced high
voltages on all metal parts of the Figure 2.33: External and internal LPS with equipotential
system are on the same voltage and bonding of all metal equipment housings, shielded and
grounded cable from array to charge controller and AC
zero potential to earth. No current
and DC surge protective devices (surge arrestors)
flow is possible, which can injure
people and damage equipment.
System grounding of a solar system means connecting either the positive or the
negative wire of the battery to ground. System grounding is necessary when
manufacturers demand it for the proper function of their equipment. Certain types of
PV modules must be negatively grounded, otherwise they lose power output due to
the accumulation of electrostatic charge. Also, some protective devices such as DC
RCDs will not function without system grounding.
35
MODULE 2: COMPONENTS AND ELECTRICAL CONNECTIONS
Note: Grounding one of the DC poles increases risk of electric shock during installation and maintenance work
on the solar system, as the installer will get an electric shock when touching the opposite pole.
Figure 2.34: Equipotential bonding of module Figure 2.35: Laying a ground electrode
frames through a solid copper band
Figure 2.36: DC surge arrestors Figure 2.37: Ground connection on cable shield
36