Vous êtes sur la page 1sur 6

Dead Time Dominance Does Not Have to Be Deadly Page 1 of 6

MENU

The Control Talk Blog provides guidance from a user's viewpoint on the design of automation
systems, equipment, and piping for process control improvement. Details are offered on the
selection and installation of PID controllers, control valves, variable speed drives, and
measurements to maximize loop performance. The blogs are often more intensive and extensive
and less vendor specific than a white paper. The goal is an advancement of the profession by
sharing conceptual principle based knowledge.

Greg McMillan is a retired Senior Fellow from Solutia/Monsanto and an ISA Fellow. At present,
McMillan is a part time modeling and control consultant in Technology for Process Simulation for
Emerson Automation Solutions specializing in the use of the Virtual Plant for exploring new
opportunities. He spends most of his time writing, teaching and leading the ISA Mentor Program
he founded in 2011. He received the ISA Kermit Fischer Environmental Award for pH control in
1991, received the Control magazine Engineer of the Year Award for the Process Industry in
1994, was inducted into the Control magazine Process Automation Hall of Fame in 2001, was
honored by InTech magazine in 2003 as one of the most influential innovators in automation, and
received the ISA Life Achievement Award in 2010.

Also, you can read McMillan's monthly Control Talk Column printed in Control magazine.

Category: Analyzers Wireless Control Deadtime Compensator Feedforward Deadtime Dominant


Submitted by Greg McMillan on Thu, 07/19/2012 - 11:12
Severely dead-time-dominant loops are particularly challenging because a control loop cannot see
and start to correct for an unmeasured disturbance until after one dead time. Complete correction
takes at least two dead times. Also, such loops are more susceptible to noise, since there is not a
major process time constant acting as a filter. Many tuning methods break down and model-based
methods are prone to failure. Here is the lowdown and some workable solutions.

Since you may not be into conceptual revelations and technical jibber-jabber, here is a summary of
what does and doesn't work so well for severely deadtime dominant loops.

1. Feedforward of measured disturbances is robust and exceptionally beneficial


2. Feedforward of setpoint changes helps reduce the time to reach setpoint
3. A head start logic can provide the greatest improvement in setpoint response
Email address
4. Derivative mode should not be used (rate time should be zero)
5. Traditional PI best gain is about ¼ the inverse of the open gain Country
6. Near integrator tuning gives PI best gain if deadtime block used in identification
7. Traditional PI best reset time is about half of the total loop deadtime

https://www.controlglobal.com/blogs/controltalkblog/dead-time-dominance-does-not-... 22.07.2018
Dead Time Dominance Does Not Have to Be Deadly Page 2 of 6

8. Enhanced PID developed for wireless gives extraordinary performance and simplifies tuning when
wireless or an analyzer is the largest source of deadtime
9. Contrary to popular opinion, deadtime compensation has marginal value
10. Contrary to popular opinion, model predictive control has marginal value

Since the peak error is essentially the open loop error for deadtime dominant systems per Equation
C-2 in Appendix C of the January/February 2012 InTech article “PID Tuning Rules Appendices”,
feedback control can do nothing to attenuate the maximum excursion for step disturbances. If the
disturbance can be measured, feedforward control can provide a dramatic improvement provided the
feedforward correction is not too late. Dynamic compensation is quite easy since just a delay is
needed if the feedforward arrives too soon. A lead-lag is not needed for dynamic compensation since
time constants are by definition negligible. Also, the feedforward timing window is quite large since the
deadtime is large.

Setpoint feedforward can provide an improvement in the rise time (time to reach a new setpoint). The
more the controller is detuned, the greater the improvement. In general a 2:1 or more reduction in rise
time is possible for severely deadtime dominant loops.

The biggest improvement in setpoint response comes from a head start as discussed in the output
tracking strategies in the ISA Automation Week 2012 paper "Effective Use of PID Features." The
strategy simplifies for severely deadtime dominant systems to simply putting the PID output at the
final resting value for one deadtime.

The rate time should be zero since the lack of a significant process time constant means the process
variable response is nearly a step and oscillations appear as square waves. While the derivative
mode has a built in filter, whenever the PV does respond, there will be a bump from the derivative
action. Also, severely deadtime dominant systems tend to be noisy since attenuation in the process is
nearly nonexistent because the process time constant is negligible.

The reset time can be decreased. The reset time low limit is about ½ the total loop deadtime allowing
for some error in the deadtime. The Equation C-13 in Appendix C of the January/February 2012
InTech article "PID Tuning Rules Appendices" provides a way of estimating the change in the reset
time factor as a function of the relative amount of total loop deadtime to open loop time constant.

Severely deadtime dominant systems have a total loop deadtime much greater than the open loop
time constant. If we look at the equations from last week for controller tuning, we see that controller
gain nearly goes to zero. However if we use the near-integrator method of tuning discussed last week
and the deadtime block to compute the rate of change of the process variable as mentioned in Future
PV Values are the Future, we end up with a controller gain that is the "a" coefficient times the
inverse of the open loop gain. The derivation of this surprising finding is shown in Universal-Method-
of-Computing-PID-Gain.pdf . Here the detuning factor Kx is the "a" coefficient from last week. The
near-integrator was thought to be only applicable to self-regulating responses with large process time
constants. If you use the deadtime block in the identification, the method can be used for all known
types of dynamics including runaway and integrating besides self-regulating. The method can even
handle inverse response, if the response in the wrong direction is recognized.

If most of the deadtime comes from a wireless measurement or analyzer, an enhanced PID
developed for wireless can simplify the whole control application. The controller does not need to beEmail address
detuned for the additional deadtime. In fact, the PID gain can be set equal to the inverse of open loop
gain providing a full and immediate correction for a setpoint change or a recognized disturbance (a =Country
1.0). The July/August 2010 InTech article "Wireless – Overcoming challenges of PID control &
analyzer applications." This PID even handles the extremely variable and large update time from an
offline analyzer.

https://www.controlglobal.com/blogs/controltalkblog/dead-time-dominance-does-not-... 22.07.2018
Dead Time Dominance Does Not Have to Be Deadly Page 3 of 6

Deadtime compensation can quite easily be done by simple insertion of a deadtime block in the back
calculate path for the positive feedback implementation of the integral mode. While it is natural to
believe that a system dominated by deadtime would benefit from deadtime compensation, the reality
is quite different. When the deadtime becomes much greater than the time constant, two things
happen that make improvement tenuous. First, the compensator becomes much more sensitive to an
underestimate or overestimate of the deadtime. A slight overestimate can cause high frequency
oscillations. Second, the tuning cannot be made much faster. For sheet thickness control by
manipulation of die bolt actuators, the deadtime is known well enough from sheet speed to use a
deadtime compensator. However, most other industrial processes have sources of deadtime with
unknown variability making deadtime estimates difficult at best.

Strangely enough, loops with a process time constant much greater than the deadtime benefit the
most from deadtime compensation. Slides 107-110 in ISA-Edmonton-2012-Effective-Use-of-
Measurements-Valves-PID-Controllers-Rev1.pdf debunk many of the myths on deadtime
compensators and gives the real scoop on what benefits exists. Model Predictive Control (MPC)
suffers a similar fate as noted in the ISA book Models Unleashed.

• 4461 reads
• Permalink

Show Comments

Email address

Country

https://www.controlglobal.com/blogs/controltalkblog/dead-time-dominance-does-not-... 22.07.2018
Dead Time Dominance Does Not Have to Be Deadly Page 4 of 6

E-Newsletters Digital Editions

Biweekly updates delivering feature articles, headlines with direct links to the top news stories that are
critical to staying up to date on the industry — company news, product announcements, technical
issues and more. Subscribe Today.

Past 7 Days Past 30 Days Past 6 Months All Time

Email address

Country

https://www.controlglobal.com/blogs/controltalkblog/dead-time-dominance-does-not-... 22.07.2018
Dead Time Dominance Does Not Have to Be Deadly Page 5 of 6

Contact Us
Advertise
Media Kit
Rates & Spec
Privacy Policy
Legal / T&C

Voices
Blogs Email address

Out of Control Cartoons


Country

Webinar series

https://www.controlglobal.com/blogs/controltalkblog/dead-time-dominance-does-not-... 22.07.2018
Dead Time Dominance Does Not Have to Be Deadly Page 6 of 6

White Papers
Multimedia

Events
Products
Technology Roundups
E-lits

Subscribe
Digital Edition
Issue Archive
Reprints

Knowledge Center
Microsites
Company Profiles
Site Map

My Account
Newsletters
Social Media
RSS

Contact Us | Advertise | Privacy Policy | Legal Disclaimers, Terms & Conditions


Copyright © 2004 - 2018 Control Global. All rights reserved.
P: 630-467-1300 | 1501 E. Woodfield Road, Suite 400N, Schaumburg, IL 60173

Chemical Processing | Control | Control Design | Food Processing | Pharmaceutical Manufacturing | Plant Services
| Smart Industry

Email address

Country

https://www.controlglobal.com/blogs/controltalkblog/dead-time-dominance-does-not-... 22.07.2018

Vous aimerez peut-être aussi