Académique Documents
Professionnel Documents
Culture Documents
Infiltration air
Total Volume
Surrounding
Temp. to be
Occupancy
maintained
maintained
Condition
Condition
Monsoon
RH to be
Ambient
AHU No.
(CFM)
No of
in m³
AHU-DH-GF-49 1 NON FLP DB°F 112.82 WB°F 91.5 DB°F 73.4 WB°F62.4 474.00 NMT 75 °F NMT 40 14 196
AHU-SH-GF-02 A 1 NON FLP DB°F 112.82 WB°F 91.5 DB°F 73.4 WB°F62.4 131.60 NMT 73.4 °F NMT 20 4 0
AHU-SH-GF-02 B 1 NON FLP DB°F 112.82 WB°F 91.5 DB°F 73.4 WB°F62.4 60.37 NMT 73.4 °F NMT 20 4 0
AHU-SH-GF-09 1 NON FLP DB°F 112.82 WB°F 91.5 DB°F 73.4 WB°F62.4 160.81 NMT 73.4 °F NMT 20 4 588
Infiltration air
Room SA qty.
No of service
load(ERSH)
Condition
condition
Fresh air
sensible
opening
BTU/HR
Internal
(CFM)
(CFM)
DB°F 73.4 WB°F 63.91 5,675 4 NIL 131,341 1,304 DB°F 52 WB°F 52
DB°F 73.4 WB°F 63.91 11,626 1 NIL 11,233 392 DB°F 52 WB°F 53
DB°F 73.4 WB°F 63.91 5,327 1 NIL 11,233 392 DB°F 52 WB°F 53
DB°F 73.4 WB°F 63.91 1,740 4 NIL 11,233 392 DB°F 52 WB°F 53