A CASE STUDY 

     Cooling Tower Treatment of District Cooling Plant, Al Hamra Real Estate Development – Al Hamra     
                                                                                             RAK 
 
 
  P
THE CHALLENGE  THE PROCESS a
g
A leading real estate developer of the Ras Al Khaimah  1. Pre‐Cleaning and Passivation chemicals were  e
region faced elevated levels of iron present in the district  carefully chosen to match the system specification 
cooling plant that serves the chillers systems of the  that facilitated the eliminate all debris in the  1
whole community.  system and provide a further enhanced anti‐
The plant was designed to be used in based on the  corrosive protection, there by bringing down the 
make‐up water provided by the TSE polishing unit.  corrosion levels to less that 1.00 ppm within less 
  than one week of operation. 
The municipal water of the area had high levels of  2. Further addition of multi‐metal scale & corrosion 
Chloride & TDS present with low levels of Calcium &  inhibitors facilitated an effective control of 
Magnesium hardness & alkalinity with low pH leading to  Calcium Carbonate, Calcium Sulphate and Calcium 
highly corroding the entire system.  Phosphate scaling and minimise fouling. 
   
   
SYSTEM DETAILS  THE RESULT 
Condenser: ‐  INDION® treatment program resulted in  
 2 x Duty Pumps (Winter 1 W + 1S, Summer 2W)   Reducing corrosion levels to less that 1.00 ppm on 
Make‐Up: ‐  the both the condenser as well as the chiller side. 
 100 % TSE Water.   Further the treatment led to higher levels of cycles 
Chiller: ‐  of concentration leading to immense water savings 
 3,890 m3 (including TES Tank)  for the client. 
   This led to an efficient heat transfer system which 
  led to cost savings from the client’s side. 
THE SOLUTION   
After a detailed study of the entire system, Ion Exchange 
proposed an entirely new treatment program that  After 
Before 
consisted of the following steps: ‐   Condenser Water  INDION 
Treatment 
  Treatment 
 Pre‐Cleaning 
 Passivation  pH 8.67  8.01
 INDION® Treatment  Conductivity  µS/cm  1,750  2,469 
 
The INDION® treatment consisted of multi‐metal  Iron  Ppm  2.1  0.25 
corrosion inhibitors, dispersants & biocides purposed to 
LSI       
tackle an aggressive system as well as the environment. 
Ion Exchange conducted vigorous site visits and water  RSI       
analysis during the time of the treatment with monthly 
technical review meetings with the developer.  
Cycles    1.8  3.1 
 
 

ION EXCHANGE LIMITED 
www.ionindia.com 
Empowering a sustainable future 
UAE | OMAN | SAUDI ARABIA | USA | CANADA | INDIA | MALAYASIA | SINGAPORE | SOUTH AFRICA | THAILAND |BANGLADESH |KENYA | 
NIGERIA | BAHRAIN 
 
 