Vous êtes sur la page 1sur 1

§ 192.10 49 CFR Ch.

I (10–1–04 Edition)

§ 192.10 Outer continental shelf pipe- (2) The pipeline qualifies for use
lines. under this part in accordance with
Operators of transportation pipelines § 192.14.
on the Outer Continental Shelf (as de- (b) No person may operate a segment
fined in the Outer Continental Shelf of pipeline that is replaced, relocated,
Lands Act; 43 U.S.C. 1331) must identify or otherwise changed after November
on all their respective pipelines the 12, 1970, or in the case of an offshore
specific points at which operating re- gathering line, after July 31, 1977, un-
sponsibility transfers to a producing less that replacement, relocation, or
operator. For those instances in which change has been made in accordance
the transfer points are not identifiable with this part.
by a durable marking, each operator (c) Each operator shall maintain,
will have until September 15, 1998 to modify as appropriate, and follow the
identify the transfer points. If it is not plans, procedures, and programs that it
practicable to durably mark a transfer is required to establish under this part.
point and the transfer point is located [35 FR 13257, Aug. 19, 1970, as amended by
above water, the operator must depict Amdt. 192–27, 41 FR 34605, Aug. 16, 1976;
the transfer point on a schematic lo- Amdt. 192–30, 42 FR 60148, Nov. 25, 1977]
cated near the transfer point. If a
transfer point is located subsea, then § 192.14 Conversion to service subject
the operator must identify the transfer to this part.
point on a schematic which must be (a) A steel pipeline previously used in
maintained at the nearest upstream fa- service not subject to this part quali-
cility and provided to RSPA upon re- fies for use under this part if the oper-
quest. For those cases in which adjoin- ator prepares and follows a written
ing operators have not agreed on a procedure to carry out the following
transfer point by September 15, 1998 requirements:
the Regional Director and the MMS (1) The design, construction, oper-
Regional Supervisor will make a joint ation, and maintenance history of the
determination of the transfer point. pipeline must be reviewed and, where
[Amdt. 192–81, 62 FR 61695, Nov. 19, 1997] sufficient historical records are not
available, appropriate tests must be
§ 192.11 Petroleum gas systems. performed to determine if the pipeline
(a) Each plant that supplies petro- is in a satisfactory condition for safe
leum gas by pipeline to a natural gas operation.
distribution system must meet the re- (2) The pipeline right-of-way, all
quirements of this part and ANSI/ aboveground segments of the pipeline,
NFPA 58 and 59. and appropriately selected under-
(b) Each pipeline system subject to ground segments must be visually in-
this part that transports only petro- spected for physical defects and oper-
leum gas or petroleum gas/air mixtures ating conditions which reasonably
must meet the requirements of this could be expected to impair the
part and of ANSI/NFPA 58 and 59. strength or tightness of the pipeline.
(c) In the event of a conflict between (3) All known unsafe defects and con-
this part and ANSI/NFPA 58 and 59, ditions must be corrected in accord-
ANSI/NFPA 58 and 59 prevail. ance with this part.
[Amdt. 192–78, 61 FR 28783, June 6, 1996]
(4) The pipeline must be tested in ac-
cordance with subpart J of this part to
§ 192.13 General. substantiate the maximum allowable
operating pressure permitted by sub-
(a) No person may operate a segment
part L of this part.
of pipeline that is readied for service
(b) Each operator must keep for the
after March 12, 1971, or in the case of an
life of the pipeline a record of the in-
offshore gathering line, after July 31,
vestigations, tests, repairs, replace-
1977, unless:
ments, and alterations made under the
(1) The pipeline has been designed, in-
requirements of paragraph (a) of this
stalled, constructed, initially in-
section.
spected, and initially tested in accord-
ance with this part; or [Amdt. 192–30, 42 FR 60148, Nov. 25, 1977]

36

VerDate Aug<04>2004 14:42 Nov 17, 2004 Jkt 203207 PO 00000 Frm 00036 Fmt 8010 Sfmt 8010 Y:\SGML\203207T.XXX 203207T

Vous aimerez peut-être aussi