Vous êtes sur la page 1sur 2

*1. Single-dotted lines indicate wiring not supplied with the unit.

*2. Dot-dash lines indicate the control box boundaries.


*3. Refer to the Data book for connecting input/output

MEE14K039
4. ELECTRICAL WIRING DIAGRAMS

signal connectors.
*4. Daisy-chain terminals (TB3) on the outdoor units in the
same refrigerant system together.
*5. Faston terminals have a locking function. 63H1

Make sure the terminals are securely locked in place P

after insertion. Press the tab on the terminals to


removed them. 1 CNSNR 12 456 6
2 FAN Board 5
3 CN81 4
*6. Control box houses high-voltage parts. 4 F121 green CN80 3
5 DC700V 2
Before inspecting the inside of the control box, turn off 4A T 1
4 C151,C152
OFF ON 1 CNDC 6
the power, keep the unit off for at least 10 minutes, and 1 1 3 red 12 654 21 321 4321 5
1 CN82 2
IPM blue 3 CN801 CN61 CN2 CN4 4 M
confirm that the voltage between FT-P and FT-N on CNVDC RSH01/02 4 CPU power red green black CNLVA 3
6 2
7 CN83 1 supply circuit 1 LEV1
SW001 black 2
INV Board has dropped to DC20V or less. U
Fan motor V 4 5 6
MS LED1:Normal operation(Lit)
*7. Difference of appliance (Heat exchanger) 3~ 72C 2 ZNR400
CNINV / Error(Blink) 6 1 CNRYB M
W
1 Control Board CNLVB 43
Model name Appliance LED4:CPU in operation U Power failure
red 2
detection circuit 1 LEV2
P200/P250/P300 *7 do not exist C100
R1,R5 *5 6
P350/P400/P450 *7 exist DCL 5 LED1
black LED3
red 1 2 SV1a 3 CN505 3
3 72C 4 LED2:Normal operation(Lit)
21S4a X06 1
red black 1 OFF ON OFF ON OFF ON CNTYP2
CN43 2 SWU2 SWU1 1 1 1 / Error(Blink) black
6 CN5 21 yellow 1 *7 X05 10's 1's
5 CN4 red 1 3 SC-P1 6
1 3 blue SC-P2 CN6 digit digit
CN2 7 5
R5 D1 R4
6 SWP1
3 *6 LED1:Normal operation(Lit) 5 CN506 Z25
+ SV5b 3 red Unit address
CN1 P FT-P / Error(Blink) CN2 CNTYP5 3
1 R6 10 10 10 SET UP(SW6-10) green
21S4b X08 setting 1
4 1 SW4 SW5 SW6
Surge C11 Z5 N FT-N C1 1
1 LED1
absorber X07
+ U - C30,C32, C31,C33, ZNR1 RSH1 6
Noise C34,C36 CNTYP 3 Display Function
DB1 C35,C37 U black CN213 2
Filter + + 1 CN507 setting/ setting t° TH6
IPM SV9 green 1
3 black Function
R30,R32, R31,R33, t° 4 t° TH7
4. ELECTRICAL WIRING DIAGRAMS

F4 R34 R35 THHS X10 setting CN212 3


1
AC250V DC12V CN51 red 2 TH3
Noise filter t°
6.3A T SC-V 1
SC-L1 1
SC-U SC-W *3 CN990 2
red red 3 t° TH5
green 1
4 Compressor ON/OFF output
Noise filter white white 5 1
Error detection output
black black
CN202 32 2 63LS
SC-L2 red 1 3
PUHY-P200, 250, 300, 350, 400, 450YKA(-BS)

1 black
SC-L3 3 1
CT3 CN110 TB7 Power CN201 2 2 63HS1
L1 L2 L3 N 3 2 1
selecting 3
CN1A CN3 CT12 CT22 1
<Symbol explanation> 3 1 4
green INV Board connector 4 t° TH4
1 CN1B red white black CN211 3
TB21 TB22 TB23 TB24 CN40 green 2
Symbol Explanation F01 t° TH2
AC250V 1234 ON 1
21S4a 4-way valve Cooling/Heating switching L 3.15A T yellow yellow blue red green red
CNPOW CN3K CN3N CN3S CN3D CN62 CN41 CNPS
21S4b Heat exchanger capacity control 3 1 2 1 black 12 321 321 321 321 12 3456 1234 12345
CNAC CNAC2 OFF
63H1 Pressure High pressure protection for the
switch outdoor unit *3
63HS1 Pressure Discharge pressure
TB1
63LS sensor Low pressure L1 L2 L3 N
72C Magnetic relay(inverter main circuit)
red white black CN04 CNIT
C30~C37 Capacitor (inverter main circuit) V 1 3 red 21 1 2 3 4 CN102 red 54321
CT12,22,3 Current sensor(AC) U W CNS2
MS LED1:Power supply to
yellow Indoor/Outdoor
DCL DC reactor 3~ M-NET power transmission line
L Choke coil (for high frequency noise reduction) supply circuit
L1 L2 L3 N Motor TB3 TB7
LEV1 Linear HIC bypass,Controls refrigerant Power Source (Compressor) M1 M2 M1 M2 S
expansion flow in HIC circuit 3N~ TP1 TP2
LEV2 valve Pressure control,Refrigerant flow 50/60Hz
380/400/415V M-NET Board
rate control
R1,5 Resistor For inrush current prevention
RSH01/02,RSH1 For current detection
SV1a Solenoid For opening/closing the bypass
valve circuit under the O/S *4
SV5b Outdoor unit heat exchanger Indoor/Outdoor Central control
capacity control
transmission transmission
cable cable
SV9 For opening/closing the bypass
circuit
TB1 Terminal Power supply
TB3 block Indoor/Outdoor transmission cable
TB7 Central control transmission cable
TH2 Thermistor Subcool bypass outlet
temperature
TH3 Pipe temperature
TH4 Discharge pipe temperature
TH5 ACC inlet pipe temperature
TH6 Subcooled liquid refrigerant
temperature
TH7 OA temperature
THHS IPM temperature
Z25 Function setting connector
OUTDOOR

57
Y
Y

*1. Single-dotted lines indicate wiring not supplied with the unit.
*2. Dot-dash lines indicate the control box boundaries.
*3. Refer to the Data book for connecting input/output signal

MEE14K039
connectors.
*4. Daisy-chain terminals (TB3) on the outdoor units in the same
refrigerant system together.
*5. Faston terminals have a locking function.
Make sure the terminals are securely locked in place after
insertion. Press the tab on the terminals to removed them.
*6. Control box houses high-voltage parts. Before inspecting the
inside of the control box, turn off the power, keep the unit
off for at least 10 minutes, and confirm that the voltage
between FT-P and FT-N on INV Board has dropped to DC20V or less.
1 CNSNR 6
2 5
3 FAN Board CN80 4
PUHY-P500YKA(-BS)

4 F121 3
5 DC700V 2
OFF ON 1
4 4A T C151,C152 1 63H1
1
1 IPM CN81 2 P
6 green
CNVDC RSH01/02 SW001
7
U 6
MS V 4 LED1:Normal operation(Lit)
3~ / Error(Blink)
1 CNINV
W LED4:CPU in operation
Fan motor
(Heat exchanger) 1 CNSNR 12 456 6
2 FAN Board 5
3 CN81 CNDC
4 F121 green CN80 43 1 3 red 21 12 654 21 321 321 4321 4321 6
CN104 4 1 CONNECT Board 1 3 5 DC700V 2 5
1 CN332 CN801 CN61 CN2 CN2A CN4 CN4A 4
FT2-P FT2-N CN202 4 4A T C151,C152 blue red green black black CNLVA 3 M
green OFF ON 1 CPU power
1 2
F101 C102 CN82 2 supply circuit 1 LEV1
DC700V
C101 + + 1 IPM ZNR400
blue 3 5
4A T CNVDC RSH01/02 4 6
R101~R103 R104~R106 CN201 3 6 72C 2 U
black 4 1 blue 7 CN83 1 6 1 CNRYB Power failure
1 SW001 black 2 detection circuit M
CN103 U
CNLVB 43
red 2
MS V 4 Control Board
LED1:Normal operation(Lit) 1 LEV2
Fan motor 3~ CNINV / Error(Blink)
4. ELECTRICAL WIRING DIAGRAMS

W 1 LED1
(Heat exchanger) LED4:CPU in operation
C100 LED3
3
R1,R5 *5 6
DCL black 5 LED2:Normal operation(Lit) 1
SWU2 SWU1 OFF ON OFF ON OFF ON CNTYP2
red 1 2 SV1a 1 1 1 / Error(Blink) black
3 CN505 10's 1's
3 72C 4 digit digit
21S4a X06
red black CN43 2 1
6 CN5 21 SWP1
SC-P2 yellow 1 X05 Z25
5 CN4 red 1 3 SC-P1 Unit address CNTYP5 3
1 3 blue CN6 7 6 10 10 10 SET UP(SW6-10)
CN2 R5 D1 R4 black red 5 setting green 1
3 6 SW4 SW5 SW6
*6 LED1:Normal operation(Lit) 5 CN506
+ / Error(Blink) SV5b LED1
R6 CN1 P FT-P CN2 3 red
1
4 21S4b X08 Display Function
Z5 N FT-N C1 1 1
<Symbol explanation> Surge C11 1 setting/ setting CN213 2
X07 t° TH6
absorber + U - C30,C32, ZNR1 green 1
Symbol Explanation Noise C31,C33, RSH1 CNTYP 3 6 Function
DB1 C34,C36 C35,C37 4
U black setting t° TH7
21S4a 4-way valve Cooling/Heating switching Filter + + 1 SV9 CN507
CN212 3
IPM red 2 TH3
21S4b Heat exchanger capacity control 3 black t°
R30,R32, R31,R33, t° DC12V CN51 1
F4 R34 R35 THHS X10 1
63H1 Pressure High pressure protection for the 1 CN990 2 t° TH5
Noise filter AC250V SC-V *3 green 1
switch outdoor unit 6.3A T 3
4 Compressor ON/OFF output
63HS1 Pressure Discharge pressure SC-L1 SC-U SC-W 5 Error detection output 1
63LS sensor Low pressure red red CN202 32 2 63LS
red 1 3
72C Magnetic relay (inverter main circuit) Noise filter white white black 3 1
black black CN110 CN201 2 2 63HS1
C30~C37 Capacitor (inverter main circuit) SC-L2 2 1 3
1 1 TB7 Power
CT12,22,3 Current sensor(AC) CT3 SC-L3
selecting 4 t° TH4
DCL DC reactor L1 L2 L3 N 3 CT12 CT22 CN211 3
CN1A CN3
connector green 2
L Choke coil (for high frequency noise reduction) INV Board red white black F01 t° TH2
3 1 4 1 CN1B green AC250V CN40 1
LEV1 Linear HIC bypass,Controls refrigerant TB21 TB22 TB23 TB24 3.15A T 12 3 4
yellow yellow blue red green
ON
expansion flow in HIC circuit black red
L CNAC2 CNPOW CN3K CN3N CN3S CN3D CN62 CN41 CNPS
LEV2 valve Pressure control,Refrigerant flow CNAC 3 1 21 12 321 321 321 321 12 3456 1234 OFF 12345
rate control
R1,5 Resistor For inrush current prevention *3
RSH01/02,RSH1 For current detection
SV1a Solenoid For opening/closing the bypass TB1
L1 L2 L3 N
valve circuit under the O/S
SV5b red white black CN04 CNIT
Outdoor unit heat exchanger V 1 3 red 21 1 2 3 4 CN102 5 4 3 2 1 red
capacity control U W
MS CNS2 LED1:Power supply to
SV9 For opening/closing the bypass circuit 3~ yellow Indoor/Outdoor
TB1 Power supply M-NET power transmission line
Terminal L1 L2 L3 N Motor supply circuit
TB3 block Indoor/Outdoor transmission cable Power Source TB3 TB7
(Compressor)
3N~ M1 M2 M1 M2 S
TB7 Central control transmission cable TP1 TP2
50/60Hz
TH2 Thermistor Subcool bypass outlet temperature 380/400/415V
TH3 Pipe temperature M-NET Board
TH4 Discharge pipe temperature
TH5 ACC inlet pipe temperature
TH6 Subcooled liquid refrigerant
temperature *4
TH7 OA temperature Indoor/Outdoor Central control
THHS IPM temperature transmission transmission
Z25 Function setting connector cable cable
OUTDOOR

58