TSXCUSB485+TSXCRJMD25
with Twido
Following are the Hardware settings for establishing the communication:
1. OS of the PC should be Windows XP.
2. Driver for TSXCUSB485 should be installed.
Open Device Manager to identify the Com port used by the Adapter.
Note : Most Schneider software only Scan Com port less than com9.
So need to set the Com port Between Com1 to Com9.
To change the com port number double click on the Device displayed in Device
Manager, a window should appear named TSX C USB 485 Properties.
Select Port setting Tab.
Click on Advance Button, a window will appear “Advance Settings for Com XX”.
Select the recommended com port as described earlier in Com port Number field and
press OK.
In TSX C USB Properties window press Restore Default Button to set the default
communication parameter as shown below. And Press ok Button.
After returning to Device Manager windows Go to Action Menu and select Scan for
Hardware changes to apply the changes made. After successfully scan TSXCUSB485
will now show the new com port defined.
You can find the version of the driver in Control Panel/Driver Manager
Open Driver Manager from Control Panel, Select Modbus Serial Driver Tab. You can
see the Driver 1 State is running and Configuration Button is highlighted.
This is all the setting for Modbus Driver to be setup. To check if the communication
is healthy or not. Follow below procedure.
Make sure the Rotary Pointer on the TSXCUSB485 is set to TER Direct (2).
Plug in the converter in PC and connect TSXCRJMD25 with TSXCUSB485 on Twido
PLC’s Terminal Port.
Open Driver Manager from Control Panel, select Modbus Test tab.
Select Modbus Serial (1) in Protocol Field from drop down menu. Slave Number field to
be set to 1(Default).
Press start Button, as soon as start button is being pressed count will get started
in Request field.( If it is not happening please follow the driver setting
recommendation again). Now your communication is healthy you can try with the
Programming software.
You need to reopen the software if it is already open after successfully
establishing the communication because Twido Soft or Twido Suite only
scan the Physical port at the time of starting.