D60

Transmission Line Protection


Line Distance
Protection System
High-speed transmission line
protection with three/single pole tripping
Key Benefits
• High-speed cost effective five zone quad or mho, phase and • Reduced relay to relay wiring and associated installation
ground distance protection costs through high-speed inter-relay communications
• Complete IEC 61850 Process Bus solution providing resource • Simplified teleprotection interfaces with Direct I/O
optimization and minimizing total P&C life cycle costs communications hardware for Transfer Trip and Pilot-Aided
• Reliable and secure protection on series compensated lines distance schemes
• Superior phase selection algorithm ensures secure high speed • Robust network security enabling Critical Infrastructure
single pole tripping Protection through user command logging, and dual
permission access control
• Supports multiple standard pilot schemes for fast fault
clearance within the protected zone • Phasor Measurement Unit - Synchronised phasor information
according to IEEE C37.118 standard
• Flexible programmable logic for building customized schemes
• Ambient temperature monitoring with alarming when outside
• Embedded IEC61850 Protocol temperature exceeds upper thresholds

Applications
• Overhead lines including series compensated lines and • Circuits with in-zone power transformers and tapped
underground cables of different voltage levels transformer feeders
• Single and dual-breaker circuits requiring single pole/three- • Secure application with Capacitively-Coupled Voltage
pole autoreclosing and independent synchrocheck Transformers (CCVTs)
• Backup protection for generators, transformers and reactors
Features
Protection and Control IEC 61850 Process Bus Interface
• Phase Distance (five zones) with independent compensation • Robust communications with up to 8 HardFiber Bricks
settings for in-zone power transformers • Seamless integration with existing D60 functions
• Ground distance (five zones) with independent self and mutual • Redundant architecture for dependability and security
zero sequence compensation
• Out-of-step tripping and power swing blocking Monitoring and Metering
• Line pickup • Synchronised measurement of voltage & current and
sequence component phasors - 1 to 60 phasors/sec
• Directional overcurrent: Phase, neutral and negative sequence
• Metering - current, voltage, power, energy, frequency
• Synchronism check for dual breaker applications
• Oscillography – analog and digital parameters at
• Four-shot dual breaker auto-recloser 64 samples/cycle
• VT fuse failure detector, compensated over-voltage • Event Recorder - 1024 time tagged events with 0.5ms scan of
Communications digital inputs
• Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485, • Setting Security Audit Trail for tracking changes to D60
RS232, RS422, G.703, C37.94 configuration
• Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU,
Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD) EnerVista™ Software
• Graphical Logic Designer and Logic Monitor to simplify
• Direct I/O – secure, high-speed exchange of data between URs
designing and testing procedures
for Direct Transfer Trip and pilot-Aided schemes
• Document and software archiving toolset to ensure reference
• Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber
material and device utilities are up-to-date
optic ports and 2 copper ports

g
• EnerVista™ Integrator providing easy integration of data in
the D60 into new or existing monitoring and control systems
Digital Energy
Multilin
235
D60 Line Distance Protection System

Protection & Control D60 - Protection, Metering, Monitoring and Control


The D60 is a high-end, cost effective distance
protection relay intended for protecting
transmission lines and cables providing
Transmission Line Protection

reliable and secure operation even under


the worst case power system conditions.
Part of the Universal Relay family, the D60
comes with a variety of versatile features
truly integrating protection, monitoring,
metering, communication and control in
one easy-to-use device. The Universal Relay
family offers a high degree of modularity
in its design and functionality providing
superior performance in protection and
control meeting the toughest requirements
of the marketplace.

Distance Protection
The D60 is the single point for protection, control, metering, and monitoring in one integrated device that
The core of the D60 relay is the distance can be easily connected directly to HMI or SCADA monitoring and control systems.
function providing high degree of sensitivity
and selectivity for all types of faults. The suit for different power system conditions. monitoring function provides extra security
distance function comes with five zones to the distance element, which can be
The advanced comparator based distance
of phase distance and ground distance used to block the distance elements under
elements provide utmost security, sensitivity
providing the user maximum flexibility voltage source fuse failure conditions.
and selectivity for different types of faults.
to cater for different applications which
Superior digital filtering techniques provide In-Zone Transformer Compensation
include primary line protection and back-
secure and optimum reach accuracy even
up protection for busbars generators, Phase distance protection in the D60 can
under worst-case CVT transients. Secure
transformers and reactors. The relay can be used to detect faults through different
directional discrimination is achieved by
be applied to power systems with different types of three-phase wye/delta transformer,
using positive sequence memory voltage
earthing conditions, lines with in-zone allowing application of the D60 for backup
polarization providing reliable directionality
transformers or tapped transformer protection on generators. VTs and CTs can
for worst-case close-in faults. The D60
feeders, and overhead lines with series be installed independent of each other
employs a well-proven algorithm for phase
compensation. Each zone element for on either side of the power transformer.
selection which provides faster, secure
the phase and ground distance can The relay automatically compensates for
and reliable faulted phase identification
be independently set as Quad or Mho transformer connections, to guarantee
for single pole tipping and proper fault
characteristics with the flexibility of accurate reach for any type of fault.
distance calculation for a variety of power
designing different characteristic shapes to
system conditions. An additional voltage

ANSI Device Numbers & Functions


Functional Block Diagram
Device
Number Function
21G Ground Distance
21P Phase Distance
25 Synchronism Check
27P Phase Undervoltage
52 52 27X Auxiliary Undervoltage
50BF Breaker Failure
50DD Current Disturbance Detector
50G Ground Instantaneous Overcurrent
CLOSE TRIP 50N Neutral Instantaneous Overcurrent
Monitoring 50P Phase Instantaneous Overcurrent
59X 27X 25 (2)
50_2 Negative Sequence Instantaneous Overcurrent
79 51G Ground Time Overcurrent
51N Neutral Time Overcurrent
50DD 50P (2) 50_2 (2) 51_2 (2) 50BF (2) 21P (4) 67P (2) 67_2 (2) 68 78 50N (2) 51N (2) 67N/G (2) 21G (4)
51P Phase Time Overcurrent
51P (2)
51_2 Negative Sequence Time Overcurrent
59P
52 AC Circuit Breaker
Data From/To Remote End Pilot FlexElement
TM

Metering Transducer
Inputs
59C Compensated Overvoltage
(via Communications) Schemes
59N Neutral Overvoltage
27P (2)
50G (2) 51G (2) 59P Phase Overvoltage
59X Auxiliary Overvoltage
59N
59_2 Negative Sequence Overvoltage
67N Neutral Directional Overcurrent
D60 Line Distance Protection System
67P Phase Directional Overcurrent
837709AE.CDR
67_2 Negative Sequence Directional Overcurrent
68 Power Swing Blocking
ANSI DEVICE NUMBERS AND FUNCTIONS 78 Out-of-Step Tripping
DEVICE
FUNCTION DEVICE
FUNCTION
79 Automatic Recloser
NUMBER NUMBER

21G Ground Distance 51P Phase Time Overcurrent


21P Phase Distance 51_2 Negative Sequence Time Overcurrent
25 Synchrocheck 52 AC Circuit Breaker
27P Phase Undervoltage 59N Neutral Overvoltage
236 27X Auxiliary Undervoltage www.GEDigitalEnergy.com
59P Phase Overvoltage
50BF Breaker Failure 59X Auxiliary Overvoltage
50DD Current Disturbance Detector 59_2 Negative Sequence Overvoltage
D60 Line Distance Protection System

(line end open). Three instantaneous • Hybrid Permissive Overreach Transfer


overcurrent elements are used to identify Trip (HYB POTT) permissive echo and
a previously de-energized line that has transient blocking logic incorporated
been closed on to a fault.
• Directional comparison blocking

Transmission Line Protection


scheme
Power Swing Detection
• Directional comparison unblocking
Z3 Z1 Dynamic transients in the power system
scheme (DCUB)
Z1 looking through a transformer due to short-circuits, circuit switching,
or load unbalance changes can travel
Undervoltage & Overvoltage
across the power network as power swings
Protections
characterized by fluctuating currents and
voltages. This can result in unwanted Long lines under lightly loaded conditions
tripping since distance elements can or no-load may experience voltages
respond to these power swings as faults. exceeding the rated insulation voltage level;
The D60 power swing detection element use the D60’s phase overvoltage element
provides both power swing blocking and to detect them and trip the line. A second
Z3 Z1 out-of-step tripping functions. The element compensated overvoltage element detects
Z1 & Z3 looking through a transformer overvoltage caused by breakers opening
measures the positive sequence apparent
impedance and traces its locus with respect at the remote end. The D60 also provides
Load Encroachment additional voltage functions including
to either a two or three step user selectable
The load encroachment feature offers neutral overvoltage, negative sequence
mho or quad operating characteristics.
discrimination between line loading overvoltage and phase undervoltage.
conditions and fault conditions especially Series Compensated Lines
for long lines under heavy loads by Overcurrent Functions
D60 provides enhanced stability and
supervising the distance elements or The D60 provides overcurrent functions for
security by employing an adaptive
any overcurrent element. This prevents phase, neutral and ground which can run
distance reach control to cope with the
unwanted tripping under heavy line parallel with distance protection or can be
overreaching and sub-synchronous
load conditions and enables optimum programmed to provide primary protection
oscillations when applied to, or in the
operation of the line while meeting under conditions when distance elements
vicinity of series compensated lines. For
regulatory requirements for line loading. are blocked during fuse-failure conditions.
directional integrity the relay uses memory
voltage polarization and a multi-input
Autorecloser
comparator to deal with current inversion
issues in series compensated lines. The D60 provides multi shot autoreclosing
for single pole or three pole autoreclose
Single-Pole Tripping on all types of faults with independently
The D60 relay uses an advanced phase settable dead time for each shot.
selection algorithm that provides fast Autoreclosing also can be dynamically
and accurate fault type identification blocked by user programmable logic. Four
even under weak-infeed conditions. different autoreclose modes are available
A convenient trip function is built-in to enabling the users to select the reclosing
coordinate actions of the key elements of mode to suit specific applications.

Distance relay quadrilateral characteristics the single-pole tripping package


Synchronism Check
supervised by Load Encroachment function
Communication Aided (Pilot) The D60 monitors voltage difference,
Schemes phase angle difference and slip frequency
Fault Locator
D60 supports different teleprotection to ensure proper breaker closure as per
The integrated fault locator provides user defined settings. The D60 provides
functions for fast fault clearance for
distance to fault in km or miles. Parallel additional enhancements in synchronizing
any faults within the protected line. The
line zero-sequence current compensation by checking dead source conditions
following types of pilot-aided schemes are
and load current compensation enables for synchronism bypass under these
available in the D60:
the D60 to provide improved accuracy for conditions.
fault distance measurement.
• Direct Under reach Transfer Trip (DUTT)
Multiple Breaker Configurations
Line Pickup (Switch-on-to Fault) • Permissive Under reach Transfer Trip
The D60 supports dual-breaker busbar
The Line Pickup feature uses a combination (PUTT)
configurations such as breaker-and-a-half
of undercurrent and undervoltage to • Permissive Overreach Transfer Trip or ring bus arrangements, providing dual
identify a line that has been de-energized (POTT) breaker auto reclose, dual synch-check

www.GEDigitalEnergy.com 237
D60 Line Distance Protection System

elements, and dual independent Breaker Custom Programmable Logic Designer


Failure elements. The design provides
secure operation during external faults
with possible CT saturation.
Transmission Line Protection

Breaker Failure
The D60 is able to provide fully independent
breaker failure protection for the breakers
associated to the line when connected to
a substation with a breaker-and-a-half or
ring bus arrangement. The D60 provides
the elements to perform two independent
breaker failure functions.

IEC 61850 Process Bus


The IEC 61850 Process Bus module is
designed to interface with the GE Multilin
HardFiber System, allowing bi-directional
IEC 61850 fiber optic communications.
The HardFiber System is designed to FlexLogicTM allows customizing the D60 for custom protection, control and automation allowing users
integrate seamlessly with the existing to build line protection schemes and applications for their equipment.
Universal Relay applications, including
protection functions, FlexLogic, metering
and communications. FlexLogic™ Scalable Hardware
FlexLogic™ is the powerful UR-platform The D60 is available with a multitude of I/O
The GE Multilin HardFiber System offers the programming logic engine that provides the configurations to suit the most demanding
following benefits: ability of creating customized protection application needs. The expandable modular
• Communicates using open standard and control schemes thereby minimizing design allows for easy configuration and
IEC 61850 messaging the need, and the associated costs, of future upgrades.

• Drastically reduces P&C design, auxiliary components and wiring.


installation and testing labor by Using FlexLogic™, the D60 can be • Flexible, modular I/O covering a broad
eliminating individual copper programmed to provide required tripping range of input signals and tripping
terminations logic along with custom scheme logic for schemes
breaker control (including interlocking with
• Integrates with existing D60’s by • Types of digital outputs include trip-
external synchronizers), transfer tripping
replacing traditional CT/VT inputs with rated Form-A and Solid State Relay
schemes for remote breakers and dynamic
IEC 61850 Process Bus module (SSR) mechanically latching, and
setting group changes.
Form-C outputs
• Does not introduce new Cyber Security
concerns • RTDs and DCmA inputs are available to
D60 Breaker-and-Half Configuration monitor equipment parameters such as
Visit the HardFiber System product page on temperature & pressure
the GE Multilin web site for more details.

Monitoring and Metering


Advanced Automation The D60 includes high accuracy metering
The D60 incorporates advanced automation and recording for all AC signals. Voltage,
features including powerful FlexLogic™ current, and power metering are built into
programmable logic, communication, and the relay as a standard feature. Current
SCADA capabilities that far surpass what is and voltage parameters are available
found in the average line protection relay. as total RMS magnitude, and as
The D60 integrates seamlessly with other fundamental frequency magnitude and
UR relays for complete system protection, angle.
including the unit and auxiliary transformers,
and Balance of Plant protection.
Fault and Disturbance Recording
D60 supports Breaker-and-Half configuration. Two CTs The advanced disturbance and event
can be brought in individually and summed off at each
terminal. recording features within the D60 can

238 www.GEDigitalEnergy.com
D60 Line Distance Protection System

significantly reduce the time needed for Settings Security & Device Status Reports
postmortem analysis of power system
events and creation of regulatory reports.
Recording functions include:

Transmission Line Protection


• Sequence of Event (SOE)
- 1024 time stamped events
• Oscillography,
- 64 digital & up to 40 Analog channels
• Data Logger, disturbance recording –
16 channels up to 1 sample / cycle /
channel
• Fault Reports
- Powerful summary report of pre-fault
and fault values

The very high sampling rate and large


amount of storage space available for
data recording in the D60 can eliminate
the need for installing costly standalone
recording equipment.
Track changes of settings to your D60 & view health and operating status by generating a report at the
Advanced Device Health click of a button
Diagnostics
The D60 performs comprehensive device communication architectures in an easy, • Integrate GE Multilin IEDs and generic
health diagnostic tests during startup and cost-effective manner. IEC61850-compliant devices seamlessly
continuously at runtime to test its own major The D60 supports the most popular industry in EnerVista™ Viewpoint Monitoring
functions and critical hardware. These standard protocols enabling easy, direct
diagnostic tests monitor for conditions that integration into monitoring and SCADA Direct I/O Messaging
could impact security and availability of systems. Direct I/O allows for sharing of high-speed
protection, and present device status via digital information between multiple UR
SCADA communications and front panel • IEC61850 relays via direct back-to-back connections
display. Providing continuous monitoring or multiplexed through a standard DS0
• DNP3.0
and early detection of possible issues helps multiplexer channel bank. Regardless of
improve system uptime. • Ethernet Global Data (EGD)
the connection method, Direct I/O provides
• IEC60870-5-104 continuous real-time channel monitoring
• Comprehensive device health • Modbus RTU, Modbus TCP/IP that supplies diagnostics information on
diagnostic performed during startup channel health.
• Monitors the CT/VT input circuitry to Interoperability with Embedded Direct I/O provides superior relay-to-relay
validate the integrity of all signals IEC61850 communications that can be used in
The D60 with integrated IEC61850 can advanced interlocking and other special
be used to lower costs associated with protection schemes.
Communications protection, control and automation. GE
The D60 provides for secure remote Multilin’s leadership in IEC61850 comes • Communication with up to 16 UR relays
data and engineering access, making it from thousands of installed devices and in single or redundant rings rather
easy and flexible to use and integrate follows on Multilin’s extensive development than strictly limited to simplistic point-
into new and existing infrastructures. experience with UCA 2.0. to-point configurations between two
Fiber optic Ethernet provides high- devices
bandwidth communications allowing for • Replace expensive copper wiring • Connect to standard DS0 channel
low-latency controls and high-speed file between devices with direct transfer of banks through standard RS422, G.703
transfers of relay fault and event record data using GOOSE messaging or IEEE C37.94 interfaces or via direct
information. The available redundant • Configure systems based on IEC61850 fiber optic connections
Ethernet option and the embedded and also monitor and troubleshoot • No external or handheld tester
managed Ethernet switch provide them in real-time with EnerVista™ required to provide channel diagnostic
the means of creating fault tolerant Viewpoint Engineer information

www.GEDigitalEnergy.com 239
D60 Line Distance Protection System

Multi-Language all of the setup and support tools needed systems. Viewpoint Monitoring provides a
The D60 supports English, French, Russian, for configuring and maintaining GE Multilin complete HMI package with the following
and Chinese languages on the front panel, products. The setup software within functionality:
EnerVista™ setup software, and product Launchpad allows configuring devices in
Transmission Line Protection

manual. Easily switch between English real-time by communicating using serial, • Plug-&-Play Device Monitoring
and an additional language on the local Ethernet, or modem connections, or offline
• System Single-Line Monitoring & Control
displays without uploading new firmware. by creating setting files to be sent to
• Annunciator Alarm Screens
devices at a later time.
• Trending Reports
EnerVistaTM Software Included in Launchpad is a document • Automatic Event Retrieval
The EnerVista™ Suite is an industry-leading archiving and management system
• Automatic Waveform Retrieval
set of software programs that simplifies that ensures critical documentation is
up-to-date and available when needed.
every aspect of using the D60 relay. The Viewpoint Engineer
EnerVista™ suite provides all the tools Documents made available include:
Viewpoint Engineer is a set of powerful
to monitor the status of the protected tools that will allow the configuration and
asset, maintain the relay, and integrate • Manuals
testing of UR relays at a system level
information measured by the D60 into • Application Notes in an easy-to-use graphical drag-and-
DCS or SCADA monitoring systems. • Guideform Specifications drop environment. Viewpoint Engineer
Convenient COMTRADE and Sequence provides the following configuration and
• Brochures
of Events viewers are an integral part commissioning utilities:
of the UR Setup software included with • Wiring Diagrams
every UR relay, to carry out postmortem • FAQ’s
• Graphical Logic Designer
event analysis to ensure proper protection • Service Bulletins
system operation. • Graphical System Designer
Viewpoint Monitoring • Graphical Logic Monitor
EnerVista™ Launchpad
Viewpoint Monitoring is a simple-to-use • Graphical System Monitor
EnerVista™ Launchpad is a powerful
and full-featured monitoring and data
software package that provides users with
recording software package for small

Power System Troubleshooting


The D60 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Graphically view zone settings for ground


Analyse transmission line faults using system phase distance elements for the selected
voltage, current and appropriate pickup flags that zones and the power swing detection
are measured & recorded up to 64 samples/cycle. element.

Record the operation of the internal D60 elements and external


connected devices with 1ms time-stamped accuracy to identify
the Sequence of Operation of station devices during faults and
disturbances.

240 www.GEDigitalEnergy.com
D60 Line Distance Protection System

Viewpoint Maintenance Typical Wiring


Viewpoint Maintenance provides tools that
A
will create reports on the operating status
B
of the relay, simplify the steps to download 52 52

Transmission Line Protection


C

fault and event data, and reduce the work


required for cyber-security compliance A B C

audits. Tools available in Viewpoint CURRENT


POLARIZATION

Maintenance include: SOURCE

• Settings Security Audit Report

F 1a

F 1b

F 2a

F 2b

F 3a

F 3b

F 4a

F 4b

F 5a

F 6a

F 7a

F 8a
F 1c

F 2c

F 3c

F 4c

F 5c

F 6c

F 7c

F 8c
• Device Health Report

VX
VB

VC
VA

VX
IG5

IG1

VB

VC
IG

VA
IA5

IA1

IB

IC
IA

IC5

IC1
IB5

IB1
• Single Click Fault Data Retrieval
H7a 6H I H1a TC 1

EnerVista™ Integrator H7c


H8a
H1
V
H1b
H1c
H8c I H2a
EnerVista™ Integrator is a toolkit that allows H7b H2
V
H2b
H2c
H8b SURGE

seamless integration of GE Multilin devices


I H3a
H3 H3b
V TC 2
H3c
into new or existing automation systems. Digital Energy H4
I H4a
H4b
V
Multilin
Included in EnerVista™ Integrator is: I
H4c
H5a

D60
H5 H5b
V
H5c
I H6a
D60-H07-HLH-F8L-H6H-M6K-P6C-U6D-W6A H6
• OPC/DDE Server V
H6b
H6c
W5a 6A I W1a
• GE Multilin Drivers W5c
W6a
W1
V
W1b
W1c
W6c I W2a

• Automatic Event Retrieval W5b W2


V
W2b
W2c
W7a
W3a
W7c
• Automatic Waveform Retrieval W8a
W8c
W3 W3b
W3c
W4a
W7b
W4 W4b
W8b SURGE W4c
P1a

User Interface

6C
P1 P1b
P1c
P2a
P2 P2b

The D60 front panel provides extensive U1a P2c


6D

U1c P3a
P3 P3b
local HMI capabilities. The local display
U2a
U2c P3c
U1b P4a
is used for monitoring, status messaging, U3a
P4 P4b
P4c
U3c
fault diagnosis, and device configuration.
P5a
U4a
P5 P5b
U4c
U3b P5c
User configurable messages that combine U5a P6
P6a
P6b
U5c
text with live data, can be displayed when U6a
P6c
P7a
U6c P7 P7b
user-defined conditions are met. U5b
U7a
P7c
P8a
U7c P8 P8b
U8a P8c PERSONAL
COMPUTER
U8c
U7b
U8b SURGE
M1a
6K

RS-232 1 M1b
B1b M1c
CRITICAL DB-9
1

B1a M2a CONNECTOR CONNECTOR


FAILURE
B2b (front) 2 M2b 1 1 8
B3a M2c TXD 2 2 3 RXD
DC OUTPUT
B3b M3a RXD 3 3 2 TXD
B5b HI 3 M3b 4 4 20
CONTROL
B6b LO M3c 5 5 7 SGND
POWER SGND
B6a M4a 6 6 6
B8a SURGE 4 M4b 7 7 4
B8b FILTER M4c 8 8 5
M5a 9 9 22
* Optic
Fibre Tx1 10BaseFL
NORMAL
5 M5b
M5c
UR COMPUTER
Rx1

Tx2 10BaseFL COM M6a


ALTERNATE 6 M6b
Rx2 1
M6c
Shielded 10BaseT M7a
Remote 7 M7b
Device D1a
RS485 M7c
D2a
D3a com M8a
8 M8b
D4b
D4a IRIG-B M8c
Input
Co-axial BNC

IRIG-B
Co-axial BNC Output

837774A6.CDR
Minimum
X W V U T S R P N M L K J H G F D B
6 6 6 6 6 8 9 1
Inputs/ Inputs/ Inputs/ Inputs/
outputs outputs outputs outputs Inputs/ CT/VT CPU Power
* * * * outputs Supply
PROVIDED

This diagram is based on the following order code:


D60-H07-HLH-F8L-H6H-M6K-P6C-U6D-W6A .This
diagram provides an example of how the device is
wired, not specifically how to wire the device. Please
refer to the Instruction Manual for additional details
on wiring based on various configurations.

www.GEDigitalEnergy.com 241
D60 Line Distance Protection System

Ordering
D60 - * ** - H * * - F ** - H ** - M ** - P ** - U ** - W ** For Full Sized Horizontal Mount
Base Unit D60 Base Unit
CPU E RS485 & RS485 (IEC61850 option not available)
Transmission Line Protection

G RS485 + Multi-mode ST 10BaseF


H RS485 + Mutli-mode ST Redundant 10BaseF
J RS485 + Multi-mode ST 100BaseFX
K RS485 + Multi-mode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
S RS485 + 6 port, 100 Mbps, Managed Ethernet Switch
Software Options 00 No Software Options
02 Breaker & Half
03 IEC61850
05 Breaker and Half + IEC61850
06 Phasor Measurement Unit (PMU)
07 IEC61850 + Phasor Measurement Unit (PMU)
08 Breaker and Half + Phasor Measurement Unit (PMU)
09 Breaker and Half + IEC61850 + Phasor Measurement Unit (PMU)
Mount H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
F Vertical Front Panel with English display
Power Supply H RH 125/250 V AC/DC w/ redundant 125/250 V AC/DC power supply
H 125/250 V AC/DC
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
IEC 61850 Process Bus 81 8 Port IEC 61850 Process Bus Module
Digital I/O XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
73 1550 nm, single-mode, LASER, 2 Channels
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
2B C37.94SM, 1300nm Singlemode, ELED, 2 Channel Single mode
2S 6 port, 100 Mbps, Managed Ethernet Switch, HI (125/250V AC/DC)
2T 6 port, 100 Mbps, Managed Ethernet Switch, LO (24-48 Vdc)

Ordering Notes:
1 - For vertical mounting order codes, please visit our online store
2 - To view the latest options available for the D60, or to order the UR Classic Front Panel, please visit our online store for more details.

Accessories for the D60 Visit www.GEMultilin.com/D60 to:


  •  UR Applications I Learning CD TRCD-URA1-C-S-1   •  View Guideform specifications
  •  Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-G1   •  Download the instruction manual
  •  Viewpoint Engineer VPE-1   •  Review applications Notes and support documents
  •  Viewpoint Maintenance VPM-1   •  Buy a D60 online
  •  Viewpoint Monitoring IEC61850 VP-1-61850   •  View the UR Family brochure