PROPIEDADES DE LA MAMPOSTERÍA
TIPO de
Tabique ESFUERZOS RESISTENTES
barro rojo COMPRESIÓN CORTANTE
recocido
fm* (kg/cm )
2
v* (kg/cm2)
unido con
mortero tipo 19.00 3.5
I
PESO DE CADA NIVEL DE LA EDIFICACIÓN
ANÁLISIS GRAVITACIONAL (CM+CVmáxima)
PESO DE LOSA PESO TOTAL DE MUROS POR NIVEL
PESO PESO PESO PESO DE LOSA MÁS
PESO Peso ALTURA UNITARIO/L Longitud MURO W=Wl +Wm
UNITARI AREA TOTAL
O
Unitario TOTAL ONGITUD de muros
DE MURO DE
NIVEL CM+CVmáx A Wl w w L MUROS Kg
Kg/m2 m2 Kg ACUMUL
Kg/m2 h (m) h (m) m W (Kg) W (Kg) Kg PROPIO
ADO
AZOTEA 470.00 64.00 30080.00 340.00 0.00 1.15 49.00 0.00 19159.00 19159.00 49239.00 49239.00
h2/2=1.15
PLANTA BAJA 460.00 64.00 29440.00 340.00 1.15 2.30 37.60 19159.00 29403.20 48562.20 78002.20 127241.20
h /2=1.15
m2 W2=70.32 ton m2 W2=70.32 ton 2 m2 m2
W2=49.24 ton W2=49.24 ton
h1=2.30
m1 W1=63.96 ton m1 W1=134.28 ton m1 W1=78.0 ton m1 W1=127.24 ton
11 11 11 11
PESOS POR NIVEL PESOS ACUMULADOS POR PESOS POR NIVEL PESOS ACUMULADOS
ANÁLISIS NIVEL ANÁLISIS SÍSMICO POR NIVEL
GRAVITACIONAL ANÁLISIS GRAVITACIONAL ANÁLISIS SÍSMICO
INSTITUTO TECNOLÓGICO SUPERIOR DE LA COSTA CHICA
ACADEMIA DE INGENIERÍA CIVIL
ANÁLISIS Y COMPORTAMIENTO DE ESTRUCTURAS DE MAMPOSTERÍA
CARGA ACTUANTE EN MUROS DE PLANTA BAJA DEBIDO A PESO DE LOSA, PESO PROPIO DE MUROS Y DESCARGA DE
2 MUROS DE PLANTA ALTA
3 CARGA ACTUANTE EN MUROS DE PLANTA BAJA DEBIDO A PESO DE LOSA Y PESO PROPIO DE MUROS
TRANSMISIÓN O BAJADA DE CARGA GRAVITACIONAL POR ÁREAS TRIBUTARIAS A LOS MUROS RESISTENTES DE P. B.
CARGAS TRANSMITIDAS A CADA UNO DE LOS MUROS DEL NIVEL CARGA
ANALIZADO TRANSMITIDA
PESO TOTAL TRANSMITIDO A LOS MUROS
POR MUROS DE
PESO PROPIO DE MURO DE CARGA DEL NIVEL ANALIZADO
PESO DE LOSA A MURO ( Wl ) SUMA PISOS
(Wm) DE
MUR SUPERIORES
PESO CARGAS
O Nº PESO ÁREA MUROS SUMA CARGA NOMINAL
LONGIT PESO UNITARIO PESO DE CARGA ÚLTIMA
UNITARI TRIBUTA EN QU DE
UD PROPIO LOSA LOSA ( P ) ( Pu )
O MURO RIA (CM+CV ) MURO APORTA CARGAS
máx
N
m kg/m kg m2 kg/m2 kg kg Kg kg ton FC ton
1 1.30 782.00 1016.60 2.6327 540.00 1421.66 2438.26 16 2423.86 4862.11 4.86 1.40 6.81
2 1.30 782.00 1016.60 2.6327 540.00 1421.66 2438.26 16 2423.86 4862.11 4.86 1.40 6.81
3 1.80 782.00 1407.60 6.5302 540.00 3526.31 4933.91 17 Y 19 4686.62 9620.53 9.62 1.40 13.47
4 1.80 782.00 1407.60 4.6250 540.00 2497.50 3905.10 20 Y 31 4938.45 8843.55 8.84 1.40 12.38
5 2.00 782.00 1564.00 4.0250 540.00 2173.50 3737.50 21 3241.15 6978.65 6.98 1.40 9.77
6 2.00 782.00 1564.00 3.8749 540.00 2092.45 3656.45 22 3214.70 6871.15 6.87 1.40 9.62
7 1.80 782.00 1407.60 4.7495 540.00 2564.73 3972.33 23 3947.35 7919.68 7.92 1.40 11.09
8 0.80 782.00 625.60 2.7028 540.00 1459.51 2085.11 24 2133.51 4218.62 4.22 1.40 5.91
9 0.80 782.00 625.60 2.6885 540.00 1451.79 2077.39 24 2133.51 4210.90 4.21 1.40 5.90
10 8.00 782.00 6256.00 9.3227 540.00 5034.26 11290.26 18 Y 25 12363.43 23653.69 23.65 1.40 33.12
11 2.00 782.00 1564.00 2.0417 540.00 1102.52 2666.52 16 Y 27 3968.36 6634.88 6.63 1.40 9.29
12 2.00 782.00 1564.00 4.0250 540.00 2173.50 3737.50 18-26-28 5031.62 8769.12 8.77 1.40 12.28
13 2.00 782.00 1564.00 2.1750 540.00 1174.50 2738.50 29 2614.00 5352.50 5.35 1.40 7.49
INSTITUTO TECNOLÓGICO SUPERIOR DE LA COSTA CHICA
ACADEMIA DE INGENIERÍA CIVIL
14 2.00 782.00 1564.00ANÁLISIS
2.6539 Y COMPORTAMIENTO
540.00 1433.11 DE ESTRUCTURAS
2997.11 DE MAMPOSTERÍA
24 Y 30 4776.79 7773.90 7.77 1.40 10.88
15 8.00 782.00 6256.00 9.3205 540.00 5033.07 11289.07 19 Y 32 12384.53 23673.60 23.67 1.40 33.14
37.60 64.0001 ### ### 134244.99 134.24 187.70
RESISTENCIA A COMPRESIÓN FRiDE CADA UNO DE LOS MUROS DE CARGA DE LA PLANTA ALTA
FACTOR
REDUCCIÓN DE LONGITUD DE RESISTENCIA A
ÁREA RESISTENTE REDUCIDA ESFUERZO REDUCCI
DE MURO POR COMPRESIÓN DE LOS
DE LOS MUROS DE CARGA RESISTENTE A ÓN DE
Muro EXCENTRICIDAD
LONGIT
Y ESBELTEZ
LONGIT COMPRESIÓN DE RESISTE
MUROS DE CARGA
Nº UD FACTOR ESPESO A= F *A =(F L )t=t*L LA MAMPOSTERÍA NCIA A
DE
UD
COMPRE
PRi = FR FE (f*m+4)At
ORIGIN REDUCCIÓ REDUCI R E t E i RE
SIÓN
AL L iN F
DA t (cm) (cm2) f*m (kg/cm )
2
FR Kg Ton
(m)
E
LRE=FELi
1 1.30 0.60 0.78 14.00 1092.00 19.00 0.60 15069.60 15.07
2 1.30 0.60 0.78 14.00 1092.00 19.00 0.60 15069.60 15.07
3 1.80 0.70 1.26 14.00 1764.00 19.00 0.60 24343.20 24.34
4 1.80 0.70 1.26 14.00 1764.00 19.00 0.60 24343.20 24.34
5 2.00 0.70 1.40 14.00 1960.00 19.00 0.60 27048.00 27.05
6 2.00 0.70 1.40 14.00 1960.00 19.00 0.60 27048.00 27.05
7 1.80 0.70 1.26 14.00 1764.00 19.00 0.60 24343.20 24.34
8 0.80 0.60 0.48 14.00 672.00 19.00 0.60 9273.60 9.27
9 0.80 0.60 0.48 14.00 672.00 19.00 0.60 9273.60 9.27
10 8.00 0.60 4.80 14.00 6720.00 19.00 0.60 92736.00 92.74
11 2.00 0.70 1.40 14.00 1960.00 19.00 0.60 27048.00 27.05
12 2.00 0.70 1.40 14.00 1960.00 19.00 0.60 27048.00 27.05
13 2.00 0.70 1.40 14.00 1960.00 19.00 0.60 27048.00 27.05
INSTITUTO TECNOLÓGICO SUPERIOR DE LA COSTA CHICA
ACADEMIA DE INGENIERÍA CIVIL
14 2.00 0.70 1.40 ANÁLISIS
14.00 Y COMPORTAMIENTO
1960.00 DE ESTRUCTURAS
19.00 0.60 DE MAMPOSTERÍA
27048.00 27.05
15 8.00 0.60 4.80 14.00 6720.00 19.00 0.60 92736.00 92.74
37.60
RESISTENCIA A COMPRESIÓN FRiDE CADA UNO DE LOS MUROS DE CARGA DE LA PLANTA BAJA
FACTOR
REDUCCIÓN DE LONGITUD DE RESISTENCIA A
ÁREA RESISTENTE REDUCIDA ESFUERZO REDUCCI
DE MURO POR COMPRESIÓN DE LOS
EXCENTRICIDAD Y ESBELTEZ DE LOS MUROS DE CARGA RESISTENTE A ÓN DE
MUROS DE CARGA
Muro LONGIT LONGIT COMPRESIÓN DE RESISTE
Nº UD FACTOR ESPESO A= F *A =(F L )t=t*L LA MAMPOSTERÍA NCIA A
DE
UD
COMPRE
PRi = FR FE (f*m+4)At
ORIGIN REDUCCIÓ REDUCI R E t E i RE
SIÓN
AL L iN F
DA t (cm) (cm2) f*m (kg/cm )
2
FR Kg Ton
(m)
E
LRE(m)
16 4.60 0.6 2.76 14.00 3864.00 19.00 0.60 53323.20 53.32
17 1.80 0.7 1.26 14.00 1764.00 19.00 0.60 24343.20 24.34
18 2.00 0.7 1.4 14.00 1960.00 19.00 0.60 27048.00 27.05
19 2.00 0.7 1.4 14.00 1960.00 19.00 0.60 27048.00 27.05
20 1.80 0.7 1.26 14.00 1764.00 19.00 0.60 24343.20 24.34
21 2.00 0.7 1.4 14.00 1960.00 19.00 0.60 27048.00 27.05
22 2.00 0.7 1.4 14.00 1960.00 19.00 0.60 27048.00 27.05
23 1.80 0.7 1.26 14.00 1764.00 19.00 0.60 24343.20 24.34
24 4.80 0.6 2.88 14.00 4032.00 19.00 0.60 55641.60 55.64
25 8.00 0.6 4.8 14.00 6720.00 19.00 0.60 92736.00 92.74
26 1.08 0.7 0.7525 14.00 1053.50 19.00 0.60 14538.30 14.54
27 2.00 0.7 1.4 14.00 1960.00 19.00 0.60 27048.00 27.05
28 2.00 0.7 1.4 14.00 1960.00 19.00 0.60 27048.00 27.05
INSTITUTO TECNOLÓGICO SUPERIOR DE LA COSTA CHICA
ACADEMIA DE INGENIERÍA CIVIL
29 2.00 0.7 1.4 ANÁLISIS
14.00 Y COMPORTAMIENTO
1960.00 DE ESTRUCTURAS
19.00 0.60 DE MAMPOSTERÍA
27048.00 27.05
30 2.00 0.7 1.4 14.00 1960.00 19.00 0.60 27048.00 27.05
31 1.08 0.70 0.7525 14.00 1053.50 19.00 0.60 14538.30 14.54
32 8.00 0.60 4.8 14.00 6720.00 19.00 0.60 92736.00 92.74
48.95
REVISIÓN DE LA RESISTENCIA DE LOS MUROS POR CARGA GRAVITACIONAL:
CM+CVmáx
PLANTA BAJA
REVISIÓN DE LA RESISTENCIA A
Muro
COMPRESIÓN DE MUROS CALIFICACIÓN DE LA
RESISTENCIA DE LOS
Carga concentrada Resistencia a MUROS DE CARGA
Longitud actuante Compresión
Nº original Li
Pu PRi = FR FE (f*m+4)A
BUENA MALA
m Kg Kg
1 1.30 6806.9606 15069.60 X
2 1.30 6806.9606 15069.60 X
3 1.80 13468.7402 24343.20 X
4 1.80 12380.9700 24343.20 X
5 2.00 9770.1100 27048.00 X
6 2.00 9619.6044 27048.00 X
7 1.80 11087.5520 24343.20 X
8 0.80 5906.0726 9273.60 X
9 0.80 5895.2618 9273.60 X
10 8.00 33115.1595 92736.00 X
11 2.00 9288.8312 27048.00 X
12 2.00 12276.7717 27048.00 X
13 2.00 7493.5000 27048.00 X
14 2.00 10883.4578 27048.00 X
15 8.00 33143.0390 92736.00 X
37.60 187942.9914 469476.00
REVISIÓN DE LA RESISTENCIA DE LOS MUROS POR CARGA GRAVITACIONAL:
CM+CVmáx
PLANTA ALTA
REVISIÓN DE LA RESISTENCIA A
Muro
COMPRESIÓN DE MUROS CALIFICACIÓN DE LA
RESISTENCIA DE LOS
Carga concentrada Resistencia a MUROS DE CARGA
Longitud actuante Compresión
Nº original Li
Pu PRi = FR FE (f*m+4)A
BUENA MALA
m Kg Kg
16 4.60 8854.0200 53323.20 X
17 1.80 5527.2000 24343.20 X
18 2.00 4223.0300 27048.00 X
19 2.00 4246.6900 27048.00 X
20 1.80 4547.6900 24343.20 X
21 2.00 4537.6100 27048.00 X
22 2.00 4500.5800 27048.00 X
23 1.80 5526.2900 24343.20 X
24 4.80 9172.8700 55641.60 X
25 8.00 14105.6300 92736.00 X
26 1.08 2364.8100 14538.30 X
27 2.00 3486.5600 27048.00 X
28 2.00 3659.6000 27048.00 X
29 2.00 3659.6000 27048.00 X
30 2.00 3486.5600 27048.00 X
31 1.08 2366.1400 14538.30 X
32 8.00 14125.7200 92736.00 X
48.96 98390.6000 612927.00
ANÁLISIS SÍSMICO ESTÁTICO DE EDIFICIOS
DIRECCIÓN "Y"
CENTRO CORTANT
FUERZA HORIZONTAL SISMICA POR PISO FUERZA CORTANTE CENTRO DE CORTANTE
DE MASA E BASAL
Wi hi Wi hi Fiy xy i Viy Fixy i å Fixy i xvi Voy=csyWo
NIVEL ENTREPISO
(ton) (m) (ton - m) (ton) (m) (m) (ton - m) (ton - m) (m) (ton)
2 49.24 4.60 226.50 30.53 1.00 30.5313 30.5313
2 30.53 1.00
1 78.00 2.30 179.40 24.18 1.00 24.1819 54.7132 54.71
1 54.71 1.00
c Wo Wo
Fi n
Wi hi cs n
Wi h
Q
åWi hi
i 1
åW h
i 1
i i
Fi n
o
Wi hi cs n
o
Wi h
Q
åW h
i 1
i i åW h
i 1
i i
m2 m2
m1 m1
11 11
FUERZA CORTANTE FUERZA CORTANTE
POR ENTREPISO POR ENTREPISO
dirección "x" dirección "y"
c
REVISIÓN DE LA RESISTENCIA POR SISMO DE LOS MUROS DE PLANTA BAJA DIRECCIÓN "X"
ÁREA EFECTIVA DE MUROS FUERZA CORTANTE RESISTENTE DE LOS
DATOS DEL MURO
CARGA RESISTENTES AL CORTANTE MUROS DE CARGA DIRECCIÓN "x"
ESFUE RESISTEN RESISTENCI
ÁREA RZO AXIAL FACTOR DE ÁREA INDIREC
LONGITUD
ALTURA
ESPESOR RESIST PROPIA CIA A ÚLTIMA
BRUTA EN REDUCCIÓN EFECTIVA TA
ÚLTIMA MÁXIMA
ENTE
MUROS
≤ 1.33
Nº L H t Ao v*m P H/L FAE = 1.00
Ae=FAE*Ao FR 0.5v*mAe 0.3P VRx VRx
> 1.33
m m cm cm2 kg/cm2 kg s/d FAE= (1.33L/H)2 cm2 Kg Kg ton ton
1 1.30 2.30 14.00 1820.00 3.50 4588.79 1.77 0.5651 1028.50 0.70 1799.88 1376.64 2.22 3.78
2 1.30 2.30 14.00 1820.00 3.50 4588.79 1.77 0.5651 1028.50 0.70 1799.88 1376.64 2.22 3.78
3 1.80 2.30 14.00 2520.00 3.50 8924.22 1.28 1.0000 2520.00 0.70 4410.00 2677.27 4.96 9.26
4 1.80 2.30 14.00 2520.00 3.50 8312.14 1.28 1.0000 2520.00 0.70 4410.00 2493.64 4.83 9.26
5 2.00 2.30 14.00 2800.00 3.50 6556.02 1.15 1.0000 2800.00 0.70 4900.00 1966.81 4.81 10.29
6 2.00 2.30 14.00 2800.00 3.50 6462.11 1.15 1.0000 2800.00 0.70 4900.00 1938.63 4.79 10.29
7 1.80 2.30 14.00 2520.00 3.50 7387.34 1.28 1.0000 2520.00 0.70 4410.00 2216.20 4.64 9.26
8 0.80 2.30 14.00 1120.00 3.50 3947.72 2.88 0.2140 239.69 0.70 419.45 1184.32 1.12 0.88
9 0.80 2.30 14.00 1120.00 3.50 3941.15 2.88 0.2140 239.69 0.70 419.45 1182.34 1.12 0.88
13.60 19040.00 54708.27 15696.38
REVISIÓN DE LA RESISTENCIA POR SISMO DE LOS MUROS DE PLANTA BAJA DIRECCIÓN "Y"
ÁREA EFECTIVA DE MUROS FUERZA CORTANTE RESISTENTE DE LOS
DATOS DEL MURO
CARGA RESISTENTES AL CORTANTE MUROS DE CARGA DIRECCIÓN "y"
ESFUE RESISTEN RESISTENCI
ÁREA RZO AXIAL FACTOR DE ÁREA INDIREC
LONGITUD
ALTURA
ESPESOR RESIST PROPIA CIA A ÚLTIMA
BRUTA EN REDUCCIÓN EFECTIVA TA
ÚLTIMA MÁXIMA
ENTE
MUROS ≤ 1.33
FR
Nº L H t Ao v*m P H/L FAE = 1.00
Ae=FAE*Ao 0.5v*mAe 0.3P VRy VRy
> 1.33
m m cm cm2 kg/cm2 kg s/d FAE= (1.33L/H)2 cm2 Kg Kg ton ton
10 8.00 2.30 14.00 11200.00 3.50 22612.60 0.29 1.0000 11200.00 0.70 19600.00 6783.78 18.47 41.16
11 2.00 2.30 14.00 2800.00 3.50 6377.72 1.15 1.0000 2800.00 0.70 4900.00 1913.32 4.77 10.29
12 2.00 2.30 14.00 2800.00 3.50 8312.17 1.15 1.0000 2800.00 0.70 4900.00 2493.65 5.18 10.29
13 2.00 2.30 14.00 2800.00 3.50 5115.50 1.15 1.0000 2800.00 0.70 4900.00 1534.65 4.50 10.29
14 2.00 2.30 14.00 2800.00 3.50 7447.41 1.15 1.0000 2800.00 0.70 4900.00 2234.22 4.99 10.29
15 8.00 2.30 14.00 11200.00 3.50 22631.24 0.29 1.0000 11200.00 0.70 19600.00 6789.37 18.47 41.16
24.00 33600.00 72496.64 33600.00
REVISIÓN DE LA RESISTENCIA POR SISMO DE LOS MUROS DE PLANTA ALTA DIRECCIÓN "X"
16 4.60 2.30 14.00 6440.00 3.50 6160.67 0.50 1.0000 6440.00 0.70 11270.00 1848.20 9.18 23.67
17 1.80 2.30 14.00 2520.00 3.50 3795.58 1.28 1.0000 2520.00 0.70 4410.00 1138.67 3.88 9.26
18 2.00 2.30 14.00 2800.00 3.50 2929.30 1.15 1.0000 2800.00 0.70 4900.00 878.79 4.05 10.29
19 2.00 2.30 14.00 2800.00 3.50 2945.19 1.15 1.0000 2800.00 0.70 4900.00 883.56 4.05 10.29
20 1.80 2.30 14.00 2520.00 3.50 3137.91 1.28 1.0000 2520.00 0.70 4410.00 941.37 3.75 9.26
21 2.00 2.30 14.00 2800.00 3.50 3140.52 1.15 1.0000 2800.00 0.70 4900.00 942.16 4.09 10.29
22 2.00 2.30 14.00 2800.00 3.50 3115.66 1.15 1.0000 2800.00 0.70 4900.00 934.70 4.08 10.29
23 1.80 2.30 14.00 2520.00 3.50 3794.97 1.28 1.0000 2520.00 0.70 4410.00 1138.49 3.88 9.26
24 4.80 2.30 14.00 6720.00 3.50 6384.14 0.48 1.0000 6720.00 0.70 11760.00 1915.24 9.57 24.70
22.80 31920.00 35403.93 31920.00
REVISIÓN DE LA RESISTENCIA POR SISMO DE LOS MUROS DE PLANTA ALTA DIRECCIÓN "Y"
ÁREA EFECTIVA DE MUROS FUERZA CORTANTE RESISTENTE DE LOS
DATOS DEL MURO
CARGA RESISTENTES AL CORTANTE MUROS DE CARGA DIRECCIÓN "y"
ESFUE RESISTEN RESISTENCI
ÁREA RZO AXIAL FACTOR DE ÁREA INDIREC
LONGITUD
ALTURA
ESPESOR RESIST PROPIA CIA A ÚLTIMA
BRUTA EN REDUCCIÓN EFECTIVA TA
ÚLTIMA MÁXIMA
ENTE
MUROS
≤ 1.33
FR
Nº L H t Ao v*m P H/L FAE = 1.00
Ae=FAE*Ao 0.5v*mAe 0.3P VRy VRy
> 1.33
m m cm cm2 kg/cm2 kg s/d FAE= (1.33L/H)2 cm2 Kg Kg ton ton
25 8.00 2.30 14.00 11200.00 3.50 9846.28 0.29 1.0000 11200.00 0.70 19600.00 2953.88 15.79 41.16
26 1.08 2.30 14.00 1505.00 3.50 1638.24 2.14 0.3864 581.57 0.70 1017.75 491.47 1.06 2.14
27 2.00 2.30 14.00 2800.00 3.50 2434.82 1.15 1.0000 2800.00 0.70 4900.00 730.44 3.94 10.29
28 2.00 2.30 14.00 2800.00 3.50 2551.00 1.15 1.0000 2800.00 0.70 4900.00 765.30 3.97 10.29
29 2.00 2.30 14.00 2800.00 3.50 2551.00 1.15 1.0000 2800.00 0.70 4900.00 765.30 3.97 10.29
30 2.00 2.30 14.00 2800.00 3.50 2434.82 1.15 1.0000 2800.00 0.70 4900.00 730.44 3.94 10.29
31 1.08 2.30 14.00 1505.00 3.50 1639.13 2.14 0.3864 581.57 0.70 1017.75 491.74 1.06 2.14
32 8.00 2.30 14.00 11200.00 3.50 9859.77 0.29 1.0000 11200.00 0.70 19600.00 2957.93 15.79 41.16
26.15 36610.00 32955.06 34763.14
m
m m2 m2
2
2
Vux2=32.40 VRx2= 43.91 ton Vuy2=32.40 ton VRy2= 47.82
ton ton
m m1 m1 m
1 1
Vux1=53.23 VRx1= 26.28 ton Vuy1=53.23 ton VRy1= 56.25
ton ton
Vux1=53.23 VRx1= 26.28 ton Vuy1=53.23 ton VRy1= 56.25
ton ton
1 11 11 1
1
FUERZA FUERZA CORTANTE FUERZA CORTANTE 1
FUERZA
CORTANTE RESISTENTE ACTUANTE CORTANTE
ACTUANTE POR ENTREPISO POR ENTREPISO RESISTENTE POR
POR ENTREPISO dirección "y" ENTREPISO
dirección "x"
FUERZAS CORTANTES DE DISEÑO POR ENTREPISO (Vui)
Vux Vuy
ENTREPISO
ton ton
2 33.58 33.58
1 60.18 60.18
ACTUANTE DE DISEÑO TE
RESISTENCIA DE
U
ÚLTIMO
M
ACTUANTE DE DISEÑO TE
RESISTENCIA DE
U
ÚLTIMO
M
ACTUANTE DE DISEÑO TE
RESISTENCIA DE
U
ÚLTIMO
M
ACTUANTE DE DISEÑO TE
RESISTENCIA DE
U
ÚLTIMO
M
m2 m2 m2
m1 m1 m1
Vux1=60.18 ton VRx1= 30.23 ton Vuy1=60.18 ton
11 11 11
FUERZA CORTANTE FUERZA CORTANTE FUERZA CORTANTE
ACTUANTE RESISTENTE ACTUANTE
POR ENTREPISO POR ENTREPISO POR ENTREPISO
dirección "x" dirección "y"
m2 m2 m2
m1 m1 m1
11 11 11
FUERZA CORTANTE FUERZA CORTANTE FUERZA CORTANTE
ACTUANTE RESISTENTE ACTUANTE
POR ENTREPISO POR ENTREPISO POR ENTREPISO
dirección "x" dirección "y"
m2
m1
VRy1= 56.38 ton
11
ZA CORTANTE FUERZA CORTANTE
CTUANTE RESISTENTE POR
ENTREPISO ENTREPISO
ección "y"
m2
m1
11
ZA CORTANTE FUERZA CORTANTE
CTUANTE RESISTENTE POR
ENTREPISO ENTREPISO
ección "y"
MUROS DE PLANTA BAJA DIRECCIÓN "X"
DISTANCI
ÁREA ÁREA EFECTIVA DE MUROS A DE MOMEN
DATOS DEL MURO TRANSVE CENTROI TO CENTRO
RESISTENTES AL CORTANTE
RSAL FACTOR DE ÁREA DE DE ESTÁTIC DE MASA
LONGITUDALTURA
ESPESORBRUTA MURO A O
REDUCCIÓN EFECTIVA
≤ 1.33 EJE "y"
L H t Ao H/L Ae=FAE*Ao xi Qx=Ao xi `x
Nº FAE = 1.00
> 1.33
m m cm cm2 s/d FAE= (1.33L/H)2 cm2 m cm2 m
Nº
≤ 1.33
L H t Ao H/L Ae=FAE*Ao yi Qy=Ao yi `y
Nº FAE = 1.00
> 1.33
m m cm cm2 s/d FAE= (1.33L/H)2 cm2 m cm2 m