NEUTRAL GROUNDING RESISTOR

Power Resistor PT. POWER SYSTEM INDONESIA

Introduction

NEUTRAL GROUNDING RESISTOR


Feature
Neutral Grounding Resistors are used for resistance
• Stainless-steel or NiCr resistor elements
grounding of industrial power system. They are generally
• Current transformer included (EN 60044-1)
connected between ground and neutral of transformers,
• Bolted resistor element connections instead of
generators and grounding transformers. Neutral
welded connections in order to be able to
Grounding Resistors are used in order to limit maximum
assemble spare parts on site immediately
fault current to a value which will not damage the
• Typically, RAL 7032(and others) painted
equipment in the power system, yet allow sufficient flow
• Typically, 2 mm hot dip galvanized steel enclosure
of fault current to operate protective relays to clear the
• Typically, 1.5 mm Stainless steel enclosure
fault. Although it is possible to limit fault currents with
• High thermal capacity to absorb high currents
high resistance Neutral Grounding Resistors, phase to
• High altitude ratings
ground short circuit currents can be extremely reduced.
• Custom made lifting eyes provide secure lifting
As a result of this fact, protection devices may not sense
• Rugged shock-resistant construction
the fault. Therefore, it is the most common application to
limit single phase fault currents with low resistance
Resistors are designed to absorb a large amount of
Neutral Grounding Resistors.
energy without exceeding temperature limitations
defined in IEEE 32. Neutral Grounding Resistors
manufacture can be used for indoor and outdoor and
the neutral point is connected with a porcelain
bushing or with a (minimum cross-section = 70 mm2
copper or 95 mm2 aluminum) high voltage (XLPE)
cable from the bottom, top or side. The most common
protection degree preferred for Neutral Grounding
Resistors is IP 23 as it allows the resistor elements to
cool easier and they can be used both at sea shores
and deserts because the resistor elements are
completely stainless steel and does not get affected by
extreme conditions. Neutral Grounding Resistors are
Functional shipped with maintains and installation guidelines. In
• Reducing single phase fault currents which occur in M.V. maintains and installation guidelines, recommended
electrical networks to prevent damages on transformers relay settings for each Neutral Grounding Resistor are
and generators stated as well. provides complete technical assistance
• Reducing temporary over voltages occurred by braking in order to meet your specifications or site conditions.
instantaneous fault current, . Providing long-life for
switchgear
• Reducing step voltages to a harmless level for staff
NEUTRAL GROUNDING RESISTOR
Power Resistor PT. POWER SYSTEM INDONESIA

SPECIFICATION

NEUTRAL GROUNDING RESISTOR


Scope Resistors

This specification covers the design, manufacture and The resistive elements shall be low temperature
testing of high-voltage, low-resistance type Neutral coefficient, resistor grade stainless steel of sufficient mass
Grounding Resistors (NGR) for installation outdoors onto a to withstand the rated current and prescribed duty.
concrete pad or power transformer.
The resistors shall be mounted in corrosion resistant
support frames, using stainless-steel hardware.
Applicable Standards
The entire resistor assembly shall be mounted on
The NGR shall be designed, manufactured and tested as per
insulators rated for the system voltage.
the latest revisions of IEEE-32.
All resistor terminals and interconnections between
Enclosures resistor units shall be stainless-steel using stainless- steel
hardware including lock washers. High
The frame of the enclosure shall be made from structural current connections shall be spot or TIG welded as
steel angles welded together, or bolted together with appropriate.
stainless-steel hardware. The top of the enclosure shall be
solid, slightly overhung and sloped. Connections between resistors and bushings or current
It shall be embossed with stiffening ribs. The enclosure transformers shall be solid copper or stainless steel bus or
shall have forged eyebolts in each corner for lifting copper cables.
purposes.

The bottom of the enclosure shall be screened with


expanded or perforated metal with openings of 1/2" or
less. This screening shall be welded or bolted in and is not
removable. It shall be elevated 4 to 6 inches above the base
of the unit.

Bolt-on side covers on all four sides shall be used. Screened


covers may be furnished for certain applications. Stainless-
steel hardware shall be used. Louvered or screened
openings shall not exceed 1/2".

A durable nameplate, permanently attached to one side


cover shall show the manufacturer and the complete
rating. Painted enclosures shall be suitably cleaned, primed
and painted. Stainless-steel and aluminum enclosures (in
particular) shall be protected from scratching during
manufacture, assembly and shipment.
NEUTRAL GROUNDING RESISTOR
Power Resistor PT. POWER SYSTEM INDONESIA

NEUTRAL GROUNDING RESISTOR


Description Unit Specification
Operation Voltage * kV 20 (±10%) / √3
Max operation voltage* kV 24
Ohmic value at 25 C* Ohm 40 (±10%)
Rate short time current* A 300
Rate continuous current* A 30
Operating duration Sec 10
Duty Cycle - 300 A 10 Sec per Hour
Miminum cooling down time 1 hour
Maximum resistance ratio AO °C / % <50 %
Resistor Material - NiCr / Stainless Steel
Insulation (EN 60273) - Porcelain and air
Resistor temperature rise max C <700
Max ambient temperature C <55
Protection degree (EN 60529) IP IP 23 outdoor / indoor
Input/output (EN 60137) Cable
Dimension mm 1000MM X 1000MM X 2440MM
Disconnecting Switch* A N/A
Current transformer (EN6004)(EN6004) A 300/5, 5P10, 15 VA
Weight/shipping position KG ±350 kg
Stainless /Powder Coating/Hot Dip
Enclosure
Galvanize
*: Customized as per User Request

Office Addres/ Workshop : Jl. Kampung Kaum No 12


Cielungsi Bogor 16820
Website : www.powersys-indo.com
Email : marketing@powersys-indo.com
Phone : 021 - 82460229
NEUTRAL GROUNDING RESISTOR
Power Resistor PT. POWER SYSTEM INDONESIA

PROJECT REFERENCE

NEUTRAL GROUNDING RESISTOR


No Customers Project
1 PT. Navitas PT. Rekind
2 PT. Cahaya Sejati Metal PT. Indonesia Power
3 PT Schneider Indonesia TPS Surabaya Peti Kemas
4 PT. MEIDEN ENGINEERING INDONESIA PT KRAKATAU STEEL
5 PT. NINDYA JOIN ARIA GI PLN Bandara Soetta Terminal 3
6 CV. Kartika GI PLN Raja Ampat Papua
7 PT. Arena Maju Bersama PLTGB TAYAN Kalimantan Barat 9 x 1000 KVA
8 PT. Rimau Elektrik PLTU Tamiyang 2 x 3 MW
9 PT. BBG PLTMG Bontang
10 PT. Califpena PLTMH Lambursari
11 PT. Venturindo PT. Venturindo
12 PT. Intan Mufakat GI PLN Cielungsi – Jonggol II
13 PT. BME (Berkat Manunggal Energi) TPS Surabaya Peti Kemas
14 PT. Teknik Integrasi Mandiri PLTD Tersebar PT. PLN Area Ambon
15 PT. Fautran Gawai Nusantara PT. Gunung Madu Plantations Lampung
Modification Synchronising Panel SOCI
PT. Mandiri Dinamika Sejahtera (MDS)
16 Medan
17 PT. Megarindo Jaya PT. Megarindo Jaya
18 PT. Anugerah Fuji Utama PT. Anugerah Fuji Utama Makasar
19 PT. Adi Teknik Pelindo Surabaya
20 PT. Califpena PLTU Baturaja
21 PT. Indokomas PLTU Berau 2 x 7 MW
22 PT. Industira PLTMH Ciromoang 4 x 3 MW
23 PT. Industira PLTU Ampana Sulawesi