Flushing of the oil lines
Purging the oil lines
Step 1: All valves are closed

Calisto

Pump
OFF

OUTLET valve INLET valve


CLOSED CLOSED

Oil sampling Quick


Connect port
CLOSED

RETURN valve SUPPLY valve


CLOSED CLOSED
Purging the oil lines
Step 2: Slowly open the transformer valves

Calisto

Pump
OFF

OUTLET valve INLET valve


CLOSED CLOSED

Oil sampling Quick


Connect port
CLOSED

RETURN valve SUPPLY valve


OPEN OPEN
Purging the oil lines
Step 3: Open the OUTLET valve

Calisto

Pump
OFF

OUTLET valve INLET valve


OPEN CLOSED

Oil sampling Quick


Connect port
CLOSED

RETURN valve SUPPLY valve


OPEN OPEN
Purging the oil lines
Step 4: Connect the Sampling port and flush 0.5 L of oil

Calisto

Pump
OFF

OUTLET valve INLET valve


OPEN CLOSED

Oil sampling Quick


Connect port
OPEN

RETURN valve SUPPLY valve


OPEN 0.5 L OPEN
Purging the oil lines
Step 5: Close the OUTLET valve

Calisto

Pump
OFF

OUTLET valve INLET valve


CLOSE CLOSED

Oil sampling Quick


Connect port
OPEN

RETURN valve SUPPLY valve


OPEN 0.5 L OPEN
Purging the oil lines
Step 6: Open the INLET valve

Calisto

Pump
OFF

OUTLET valve INLET valve


CLOSE OPEN

Oil sampling Quick


Connect port
OPEN

RETURN valve SUPPLY valve


OPEN 0.5 L OPEN
Purging the oil lines
Step 7: Power ON the monitor and flush 0.5 L of oil

Calisto

Pump
ON

OUTLET valve INLET valve


CLOSE OPEN

Oil sampling Quick


Connect port
OPEN

RETURN valve SUPPLY valve


1L
OPEN OPEN
Purging the oil lines
Step 8: Disconnect the sampling tube

Calisto

Pump
ON

OUTLET valve INLET valve


CLOSE OPEN

Oil sampling Quick


Connect port
CLOSE

RETURN valve SUPPLY valve


OPEN OPEN
Purging the oil lines
Step 9: Open the OUTLET valve

Calisto

OIL FLOW
Pump
ON

OUTLET valve INLET valve


OPEN OPEN

Oil sampling Quick


Connect port
OIL FLOW OIL FLOW
CLOSE

RETURN valve SUPPLY valve


OPEN OPEN
Calisto Manager
Installing Calisto Manager
1. Insert the CD or download the software from our website
2. Follow the on-screen instructions
3. At the Choosing Components step, make sure to check the USB Drivers
box

Notes:
• A notification window may appear, choose the Continue Anyway option
• Prior to starting Calisto Manager, your computer should be properly connected
to the monitor using the supplied USB cable and proper drivers should be
installed when asked by the operating system.
Connecting to a new Calisto 9
1. Launch Calisto Manager
2. Under Tracking, click on Add Monitor to List
3. At the Choosing Components step, check the USB Drivers box
Connecting to a new Calisto 9
4. Select Serial under Connection Type for local USB
5. Select the virtual COM create under Port
6. Click on Find (The monitor will appear in the Found Monitor window)
7. Click the Checkbox next to the monitor and click Add
8. The connected monitor will now appear in the list of monitors displayed
in the main window
Calisto 9 Settings
1. Under the Tools menu, click on Advanced Mode…
2. Enter the password “accuracy” to unlock the Advanced Mode.
3. Highlight the Calisto in the list.
4. Under the Calisto menu, click on Settings…
5. The settings will be downloaded from the unit and the Settings window
will appear
Settings – Identification

Adjust the date and time

Enter the unit


information
Settings – Communication

The RS485 ID is used


as the monitor ID for
all protocols.
Settings – Oil Type

• Mineral Oil (ASTM3612)


• Voltesso 35
• Technol US4000
• Nytro
• Midel 7131
• Silicone
• Envirotemp FR3
• Luminol TRI
• Luminol TR
• Luminol BI
• Custom
Settings – I/Os

Dedicated 4-20 mA
input for the Carrier
Gas pressure
Settings – Alarm Limits
Settings – Relays
Settings - Relays
Two different ‘Fail-safe’ relay configurations:
• ‘energized-when-always’
• ‘energized-when not-condition’

Morgan Schaffer recommends the following to establish


the best levels of alarm limits and trend values:
• Work with the transformer manufacturer;
• Consult an industry expert;
• Carry out a statistical analysis of gas levels on a population of
similar transformers being used in similar loading,
environment, etc.

Alarm level and relay logic should always be set


with great care to maximize protection.
4. Maintenance
Maintenance
The Calisto monitor is virtually maintenance free. To maximize
product reliability, the following points should be verified every 6 to
12 months:
1. Install the latest firmware (if available)
2. Inspect the mounting
3. Inspect wiring, no unplugged entry holes
4. External fan is ON (for ambient > 15degC)
5. Internal fan is ON (always)
6. Verify the relay logic using Calisto Access
7. Ensure alarm limits are configured properly
8. Verify that the date and time are set properly
9. Verify that all valves are fully open
10. No material, cable, manual, etc. inside Calisto
11. Enclosure latches are tightened down
12. Inspect the oil line connections for possible leaks
13. Inspect underneath Calisto for possible leaks
14. Verify the response of the display
Maintenance
Calisto 5 / Calisto 9 consumables to be replaced every 2 years:

1. Calibration gas cylinder


2. Carrier gas cylinder (helium)

For more details, refer to the Calisto5/Calisto 9 Installation Manual and to the Calisto
Manager User Guide.
Gas cylinder replacement
Calisto 5 / Calisto 9
Starting the gas flow
1. Turn ON the monitor
2. Follow instructions on the Display (30 min.)
3. Go to Maintenance, then Combined bottle change

Only open the gas cylinder shut-off valves as directed by


the bottle change procedure to avoid contamination.
Installing the carrier gas cylinder
Install the carrier gas adaptor onto the helium cylinder

Note: You will require a large capacity 1 ½ adjustable wrench.


Installing the carrier gas cylinder
Installing the high pressure carrier gas line
1. Connect the preswaged 1/8 tubing to the cylinder, tighten ¼ turn
Installing the calibration gas cylinder
1. Install the calibration gas cylinder inside the door
2. Insert one end of the cylinder in the bracket hole until captive screws
become aligned with their respective nuts
3. Insert the preswaged 1/16 tubing and tighten 1/8 turn
Maintenance
Most common error codes and respective solution:
1 External fan replace fan
2 Internal fan replace fan

2000 External analog input Wiring or Calisto Access


8000 No/low oil flow Verify all valves

For more details, refer to the Calisto/Calisto 2 Installation and Operation Manual.