RTD Pt-100, 2 / 3 / 4 Wire(Temperature resistance 2 Working Principle : measurment 3 Tag No. : As per Annexure-1 4 Qty : As per Annexure-1 Output Signal
5 Output Signal : 4-20 mA DC signal with standard protocol HART
6 Under ranging : 3.6 mA
7 Over ranging : 23 mA INPUT 8 Input Type : Single Input to suit 3 or 4 wire Pt 100 RTD 9 Lead resistance(max) : 100 ohms (3-wire) 10 Measuring current : 0.2 mA 11 Burnout/Short-circuit limit : Downscale, <3.6 mA 12 Operating Voltage : 12-42 V dc GENERAL 13 Response time : < 5 sec 14 Accuracy : 0.1% of span 15 Enclosure Class : IP-20 16 Ambient Temperature Limit : -40 °C to 85 °C 17 Humidity : 0 - 99% relative humidity 18 Stability : ±0.2% of span for 5 years