Vous êtes sur la page 1sur 1

DATA SHEET FOR TEMPERATURE TRANSMITTER

1 Type : Rail Mount Temperature Transmitter


RTD Pt-100, 2 / 3 / 4 Wire(Temperature resistance
2 Working Principle :
measurment
3 Tag No. : As per Annexure-1
4 Qty : As per Annexure-1
Output Signal

5 Output Signal : 4-20 mA DC signal with standard protocol HART

6 Under ranging : 3.6 mA


7 Over ranging : 23 mA
INPUT
8 Input Type : Single Input to suit 3 or 4 wire Pt 100 RTD
9 Lead resistance(max) : 100 ohms (3-wire)
10 Measuring current : 0.2 mA
11 Burnout/Short-circuit limit : Downscale, <3.6 mA
12 Operating Voltage : 12-42 V dc
GENERAL
13 Response time : < 5 sec
14 Accuracy : 0.1% of span
15 Enclosure Class : IP-20
16 Ambient Temperature Limit : -40 °C to 85 °C
17 Humidity : 0 - 99% relative humidity
18 Stability : ±0.2% of span for 5 years