Académique Documents
Professionnel Documents
Culture Documents
ON
66 KV SUB STATION
TRANING OF PSPCL
1
INDUSTRIAL TRAINING REPORT
ON
66 KV SUB STATION
AT
66 KV SUBSTATION M.E.S.(BATHINDA)
NAME:- MANPREET SINGH
BRANCH:- ELECTRICAL ENGG.
UNI. R.NO:- 99150340014
BATCH:- 2015-2019
TRAINING AT:- P & M OFFICE(BTI)
TRAINING ON:- 66 KV SUBSTATION(MES,BTI)
DATE:- FROM 05/06/2017 TO 02/07/2017
2
CONTENTS
TOPIC`S PAGE NO.
1.ACKNOWLEDGEMENT
2.SUBSTATION 1-5
3.TRANSFORMER 5-12
4.PARTS OF TRANSFORMER 12-23
5.CURRENT TRANSFORMER 23-31
6.POTENTIAL TRANSFORMER 31-32
7.ELECTRICAL ISOLATOR 32-36
8.BUS BARS 36-46
9.BUS COUPLER 46-47
10.CIRCUIT BRAEKER 47-50
11.CONTROL PANEL 50-51
12.OVER CURRENT AND EARTH FAULT RELAY 51-53
13.CAPACITOR BANK 53-57
14.EARTHING 58-60
15.INSULATOR 60-66
16.BATTERY ROOM 66
3
ACKNOWLEDGEMENT
NOTHING CAN BE ACHIEVED WITHOUT AN OPYIMUM
COMBINATION OF INSTECTION AND PERSPIRATION.I OWE A LOT
TO MANY OF INSTIRATION PATH.BUT THINKING PEOPLE WHO
HAVE CONTRIBUTED TO THE TRAINING IS LITTLE LIKE SAYING
THANKS AT THE ACADEMY AWARDS.
THANK YOU
4
SUBSTATION
A substation is a part of an electrical generation, transmission,
and distribution system. Substations transform voltage from high to
low, or the reverse, or perform any of several other important
functions. Between the generating station and consumer, electric
power may flow through several substations at different voltage
levels. A substation may include transformers to change voltage
levels between high transmission voltages and lower distribution
voltages, or at the interconnection of two different transmission
voltages.
Substations may be owned and operated by an electrical utility, or
may be owned by a large industrial or commercial customer.
Generally substations are unattended, relying on scada for remote
supervision and control.
The word substation comes from the days before the distribution
system became a grid. As central generation stations became larger,
smaller generating plants were converted to distribution stations,
receiving their energy supply from a larger plant instead of using
their own generators. The first substations were connected to only
one power station, where the generators were housed, and were
subsidiaries of that power station.
TYPES:-
Substations may be described by their voltage class, their
applications within the power system, the method used to insulate
most connections, and by the style and materials of the structures
used. These categories are not disjointed; for example, to solve a
particular problem, a transmission substation may include significant
distribution functions.
Transmission substation :-
5
A transmission substation connects two or more transmission
lines The simplest case is where all transmission lines have the
same voltage. In such cases, substation contains high-voltage
switches that allow lines to be connected or isolated for fault
clearance or maintenance. A transmission station may
have transformers to convert between two transmission
voltages, voltage control/power factor correction devices such as
capacitors, reactors or static VAR compensators and equipment
such as phase shifting transformers to control power flow between
two adjacent power systems.
Distribution substation:-
A distribution substation transfers power from the transmission
system to the distribution system of an area. It is uneconomical to
directly connect electricity consumers to the main transmission
network, unless they use large amounts of power, so the distribution
station reduces voltage to a level suitable for local distribution.
The input for a distribution substation is typically at least two
transmission or sub-transmission lines. Input voltage may be, for
example, 115 kV, or whatever is common in the area. The output is a
number of feeders. Distribution voltages are typically medium
voltage, between 2.4 kV and 33 kV, depending on the size of the area
served and the practices of the local utility. The feeders run along
streets overhead (or underground, in some cases) and power the
distribution transformers at or near the customer premises.
6
In addition to transforming voltage, distribution substations also
isolate faults in either the transmission or distribution systems.
Distribution substations are typically the points of voltage regulation,
although on long distribution circuits (of several miles/kilometers),
voltage regulation equipment may also be installed along the line.
The downtown areas of large cities feature complicated distribution
substations, with high-voltage switching, and switching and backup
systems on the low-voltage side. More typical distribution
substations have a switch, one transformer, and minimal facilities on
the low-voltage side.
Collector substation
In distributed generation projects such as a wind farm, a collector
substation may be required. It resembles a distribution substation
although power flow is in the opposite direction, from many wind
turbines up into the transmission grid. Usually for economy of
construction the collector system operates around 35 kV, and the
collector substation steps up voltage to a transmission voltage for
the grid. The collector substation can also provide power factor
correction if it is needed, metering, and control of the wind farm. In
some special cases a collector substation can also contain an HVDC
converter station.
Collector substations also exist where multiple thermal or
hydroelectric power plants of comparable output power are in
proximity. Examples for such substations are Brauweiler in Germany
and Hradec in the Czech Republic, where power is collected from
nearby lignite-fired power plants. If no transformers are required for
increasing the voltage to transmission level, the substation is a
switching station.
Converter substations
Converter substations may be associated with HVDC converter
plants, traction current, or interconnected non-synchronous
networks. These stations contain power electronic devices to change
7
the frequency of current, or else convert from alternating to direct
current or the reverse. Formerly rotary converters changed
frequency to interconnect two systems; nowadays such substations
are rare.
Switching station
A switching station is a substation without transformers and
operating only at a single voltage level. Switching stations are
sometimes used as collector and distribution stations. Sometimes
they are used for switching the current to back-up lines or for
parallelizing circuits in case of failure. An example is the switching
stations for the HVDC Inga–Shaba transmission line.
A switching station may also be known as a switchyard, and these
are commonly located directly adjacent to or nearby a power station.
In this case the generators from the power station supply their
power into the yard onto the Generator Bus on one side of the yard,
and the transmission lines take their power from a Feeder Bus on the
other side of the yard.
An important function performed by a substation is switching, which
is the connecting and disconnecting of transmission lines or other
components to and from the system. Switching events may be
planned or unplanned. A transmission line or other component may
need to be de-energized for maintenance or for new construction,
for example, adding or removing a transmission line or a
transformer. To maintain reliability of supply, companies aim at
keeping the system up and running while performing maintenance.
All work to be performed, from routine testing to adding entirely
new substations, should be done while keeping the whole system
running.
Unplanned switching events are caused by a fault in a transmission
line or any other component, for example:
8
The function of the switching station is to isolate the faulty portion of
the system in the shortest possible time. De-energizing faulty
equipment protects it from further damage, and isolating a fault
helps keep the rest of the electrical grid operating with stability.
TRANSFORMER
9
Power can be transferred between the two coils through the
magnetic field, without a metallic connection between the two
circuits. Faraday's law of induction discovered in 1831 described this
effect. Transformers are used to increase or decrease the alternating
voltages in electric power applications.
Since the invention of the first constant-potential transformer in
1885, transformers have become essential for
the transmission, distribution, and utilization of alternating current
electrical energy. A wide range of transformer designs is
encountered in electronic and electric power applications.
Transformers range in size from RF transformers less than a cubic
centimeter in volume to units interconnecting the power grid
weighing hundreds of tons.
10
Faraday's Laws of Electromagnetic Induction:-
According to these Faraday's laws, "Rate of change of flux linkage
with respect to time is directly proportional to the induced EMF in
a conductor or coil".
11
The winding which gives the desired output voltage due to
mutual induction in the transformer, is commonly known as
secondary winding of transformer. Here in our example it is second
winding.
12
The above mentioned form of transformer is theoretically
possible but not practically, because in open air very tiny portion of
the flux of the first winding will link with second; so the current that
flows through the closed circuit of later, will be so small in amount
that it will be difficult to measure.
The rate of change of flux linkage depends upon the amount of
linked flux with the second winding. So, it is desired to be linked to
almost all flux of primary winding to the secondary winding. This is
effectively and efficiently done by placing one low reluctance path
common to both of the winding. This low reluctance path is core of
transformer, through which maximum number of flux produced by
the primary is passed through and linked with the secondary
winding. This is the most basic theory of transformer.
13
Construction of Transformer:-
Cores
Closed-core transformers are constructed in 'core form' or 'shell
form'. When windings surround the core, the transformer is core
form; when windings are surrounded by the core, the transformer is
shell form.
Shell form design may be more prevalent than core form design for
distribution transformer applications due to the relative ease in
stacking the core around winding coils. Core form design tends to, as
a general rule, be more economical, and therefore more prevalent,
than shell form design for high voltage power transformer
applications at the lower end of their voltage and power rating
ranges (less than or equal to, nominally, 230 kV or 75 MVA). At
higher voltage and power ratings, shell form transformers tend to be
more prevalent. Shell form design tends to be preferred for extra-
high voltage and higher MVA applications because, though more
labor-intensive to manufacture, shell form transformers are
characterized as having inherently better kVA-to-weight ratio, better
short-circuit strength characteristics and higher immunity to transit
damage.
14
Laminated steel cores:-
Transformers for use at power or audio frequencies typically have
cores made of high permeability silicon steel. The steel has a
permeability many times that of free space and the core thus serves
to greatly reduce the magnetizing current and confine the flux to a
path which closely couples the windings.
15
currents to highly elliptical paths that enclose little flux, and so
reduce their magnitude. Thinner laminations reduce losses, but are
more laborious and expensive to construct. Thin laminations are
generally used on high-frequency transformers, with some of very
thin steel laminations able to operate upto10 kHz.
One common design of laminated core is made from interleaved
stacks of E-shaped steel sheets capped with I-shaped pieces, leading
to its name of 'E-I transformer'. Such a design tends to exhibit more
losses, but is very economical to manufacture. The cut-core or C-core
type is made by winding a steel strip around a rectangular form and
then bonding the layers together. It is then cut in two, forming two C
shapes, and the core assembled by binding the two C halves together
with a steel strap.[55] They have the advantage that the flux is
always oriented parallel to the metal grains, reducing reluctance.
A steel core's remanence means that it retains a static magnetic
field when power is removed. When power is then reapplied, the
residual field will cause a high inrush current until the effect of the
remaining magnetism is reduced, usually after a few cycles of the
applied AC waveform. Over current protection devices such
as fuses must be selected to allow this harmless inrush to pass. On
transformers connected to long, overhead power transmission lines,
induced currents due to geomagnetic disturbances during solar
storms can cause saturation of the core and operation of
transformer protection devices.
Distribution transformers can achieve low no-load losses by using
cores made with low-loss high-permeability silicon steel
or amorphous (non-crystalline) metal alloy. The higher initial cost of
the core material is offset over the life of the transformer by its
lower losses at light load.
PARTS OF TRANSFORMER
16
Conservator Tank :-
This is a cylindrical tank mounted on supporting structure on the roof
the transformer main tank. The main function of conservator tank of
transformers to provide adequate space for expansion of oil inside
the transformer.
Generally silica gel breather fixing pipe enters into the conservator
from top. If it enters from bottom, it should be projected well above
the level of oil inside the conservator. This arrangement ensure that
oil does not enter the silica gel breather even at highest operating
level.
17
Working of Conservator Tank:-
When volume of transformer insulating oil increases due to load and
ambient temperature, the vacant space above the oil level inside the
conservator is partially occupied by the expanded oil. Consequently,
corresponding quantity of air of that space is pushed away through
breather. On other hand, when load of transformer decreases, the
transformer is switched off and when the ambient temperature
decreases, the oil inside the transformer contracts. This causes
outside air to enter in the conservator tank of transformer through
silica gel breather.
18
prevents direct contact of oil with air, thereby reduces ageing affect
of oil.
The diphram is held between the the two halves and bolted.
As oil expands it pushes up the diaphragm. The position of the
diaphragm is indicated by the oil level indicator i.e. magnetic oil
19
gauge (Here MOG is not shown in the figure above) as the rod of this
MOG is connected to the diaphragm. When the oil level falls down in
the conservator, the diaphragm deflects and the atmospheric air fills
the vacant place. This air is sucked through silica gel breather which
is connected to the top middle of conservator tank of transformer.
(Here silica gel breather is not shown in the figure above)
This type of conservator has one advantage over air cell conservator.
If gas is pressurized to a high level, it gets dissolved in oil. Over a
period of time the amount of gas in oil reaches the saturation point.
If at this stage, the load of transformer is suddenly dropped or the
ambient temperature falls severely, the pressure falls, oil becomes
supersaturated and the gas bubbles will be evolved. If there is a pimp
connected in the cooling circuit, it will help generating bubbles.
These bubbles may cause insulation failure in the region of strong
fields. (Here silica gel breather, MOG, Drain Valves, Air Pockets,
Conservator to main tank connections is not shown in the figure
above.)
Breather :-
Whenever electrical power transformer is loaded, the
temperature of the transformer insulating oil increases,
consequently the volume of the oil is increased. As the volume of the
oil is increased, the air above the oil level in conservator will come
out. Again at low oil temperature; the volume of the oil is decreased,
which causes the volume of the oil to be decreased which again
causes air to enter into conservator tank.
The natural air always consists of more or less moisture in it and this
moisture can be mixed up with oil if it is allowed to enter into the
transformer. The air moisture should be resisted during entering of
the air into the transformer, because moisture is very harmful for
20
transformer insulation. A silica gel breather is the most commonly
used way of filtering air from moisture.
21
breather; the moisture of the air is absorbed by them. Therefore, the
air reaches to the conservator is quite dry, the dust particles in the
air get trapped by the oil in the oil seal cup. The oil in the oil sealing
cup acts as barrier between silica gel crystal and air when there is no
flow of air through silica gel breather. The color of silica gel crystal is
dark blue but, when it absorbs moisture; it becomes pink.
When there is sufficient difference between the air inside the
conservator and the outside air, the oil level in two components of
the oil seal changes until the lower oil level just reaches the rim of
the inverted cup, the air then moves from high pressure
compartment to the low pressure compartment of the oil seal. Both
of these happen when the oil acts as core filter and removes the dust
from the outside air.
Buchholz Relay:-
Buchholz relay in transformer is an oil container housed
the connecting pipe from main tank to conservator tank. It has
mainly two elements. The upper element consists of a float. The
float is attached to a hinge in such a way that it can move up and
down depending upon the oil level in the Buchholz
relay Container. One mercury switch is fixed on the float. The
alignment of mercury switch hence depends upon the position of the
float.
The lower element consists of a baffle plate and mercury
switch. This plate is fitted on a hinge just in front of the inlet (main
tank side) of Buchholz relay in transformer in such a way that when
oil enters in the relay from that inlet in high pressure the alignment
of the baffle plate along with the mercury switch attached to it, will
change.
22
In addition to these main elements a Buchholz relay has gas release
pockets on top. The electrical leads from both mercury switches are
taken out through a molded terminal block.
Fall of oil level means lowering the position of float and thereby
tilting the mercury switch. The contacts of this mercury switch are
closed and an alarm circuit energized. Sometime due to oil leakage
on the main tank air bubbles may be accumulated in the upper part
the Buchholz container which may also cause fall of oil level in it and
alarm circuit will be energized. By collecting the accumulated gases
23
from the gas release pockets on the top of the relay and by analyzing
them one can predict the type of fault in the transformer.
More severe types of faults, such as short circuit between phases or
to earth and faults in the tap changing equipment, are accompanied
by a surge of oil which strikes the baffle plate and causes the
mercury switch of the lower element to close. This switch energized
the trip circuit of the circuit breakers associated with the transformer
and immediately isolate the faulty transformer from the rest of
the electrical power system by inter tripping the circuit breakers
associated with both LV and HV sides of the transformer. This is
how Buchholz relay functions.
Buchholz Relay Operation Certain Precaution:-
The Buchholz relay operation may be actuated without any fault in
the transformer. For instance, when oil is added to a transformer, air
may get in together with oil, accumulated under the relay cover and
thus cause a false Buchholz relay operation.
That is why mechanical lock is provided in that relay so that one can
lock the movement of mercury switches when oil is topping up in the
transformer. This mechanical locking also helps to prevent
unnecessary movement of breakable glass bulb of mercury switches
during transportation of the Buchholz relays.
The lower float may also falsely operate if the oil velocity in the
connection pipe through, not due to internal fault, is sufficient to trip
over the float. This can occurs in the event of external short circuit
24
when over currents flowing through the winding cause overheated
the copper and the oil and cause the oil to expand.
Bushing:-
They are made for highly insulating material to insulate end to
bring out the terminals of the transformer from the container.
25
utilized in situations in which a transformer's turn ratio does not
require frequent changing and it is permissible to de-energize the
transformer system. This type of transformer is frequently employed
in low power, low voltage transformers in which the tap point often
may take the form of a transformer connection terminal, requiring
the input line to be disconnected by hand and connected to the new
terminal. Alternatively, in some systems, the process of tap changing
may be assisted by means of a rotary or slider switch.
No load tap changers are also employed in high voltage transformers
in which the system includes a no load tap changer on the primary
winding to accommodate system variations within a narrow band
around the nominal rating. In such systems, the tap changer will
often be set just once, at the time of installation, although it may be
changed later during a scheduled outage to accommodate a long-
term change in the system voltage profile.
On Load Tap Changers:-
It is also called On Circuit Tap Changer.For many power transformer
applications, a supply interruption during a tap change is
unacceptable, and the transformer is often fitted with a more
expensive and complex on load tap changing (OLTC, sometimes Load
Tap Changer, LTC) mechanism. On load tap changers may be
generally classified as either mechanical, electronically assisted, or
fully electronic.
26
Tap changers typically use numerous tap selector switches which
may not be switched under load, broken into even and odd banks,
and switch between the banks with a heavy-duty diverter
switch which can switch between them under load. The result
operates like a dual-clutch transmission, with the tap selector
switches taking the place of the gearbox and the diverter switch
taking the place of the clutch.
CURRENT TRANSFORMER
The Current Transformer ( C.T. ), is a type of “instrument
transformer” that is designed to produce an alternating current in its
secondary winding which is proportional to the current being
measured in its primary.
Current transformers reduce high voltage currents to a much
lower value and provide a convenient way of safely monitoring the
27
actual electrical current flowing in an AC transmission line using a
standard ammeter. The principal of operation of a basic current
transformer is slightly different from that of an ordinary voltage
transformer.
28
voltage induced in the secondary is big enough to saturate the core
or cause failure from excessive voltage breakdown.
Unlike a voltage transformer, the primary current of a current
transformer is not dependent of the secondary load current but
instead is controlled by an external load. The secondary current is
usually rated at a standard 1 Ampere or 5 Amperes for larger primary
current ratings.
There are three basic types of current
transformers: wound, toroidal and bar.
Wound Current Transformer – The transformers primary
winding is physically connected in series with the conductor that
carries the measured current flowing in the circuit. The
magnitude of the secondary current is dependent on the turns
ratio of the transformer.
Toroidal Current Transformer – These do not contain a primary
winding. Instead, the line that carries the current flowing in the
network is threaded through a window or hole in the toroidal
transformer. Some current transformers have a “split core”
which allows it to be opened, installed, and closed, without
disconnecting the circuit to which they are attached.
Bar-type Current Transformer – This type of current transformer
uses the actual cable or bus-bar of the main circuit as the
primary winding, which is equivalent to a single turn. They are
fully insulated from the high operating voltage of the system
and are usually bolted to the current carrying device.
29
hour meters, protective relays, or as trip coils in magnetic circuit
breakers, or MCB’s.
30
current in the primary and secondary windings are related by an
inverse proportion.
A current transformer, like any other transformer, must satisfy the
amp-turn equation and we know from our tutorial on double wound
voltage transformers that this turns ratio is equal to:
The current ratio will sets the turns ratio and as the primary usually
consists of one or two turns whilst the secondary can have several
hundred turns, the ratio between the primary and secondary can be
quite large. For example, assume that the current rating of the
primary winding is 100A. The secondary winding has the standard
rating of 5A. Then the ratio between the primary and the secondary
currents is 100A-to-5A, or 20:1. In other words, the primary current
is 20 times greater than the secondary current.
It should be noted however, that a current transformer rated as
100/5 is not the same as one rated as 20/1 or subdivisions of 100/5.
This is because the ratio of 100/5 expresses the “input/output
current rating” and not the actual ratio of the primary to the
secondary currents. Also note that the number of turns and the
current in the primary and secondary windings are related by an
inverse proportion.
But relatively large changes in a current transformers turns ratio can
be achieved by modifying the primary turns through the CT’s window
where one primary turn is equal to one pass and more than one pass
through the window results in the electrical ratio being modified.
31
So for example, a current transformer with a relationship of say,
300/5A can be converted to another of 150/5A or even 100/5A by
passing the main primary conductor through its interior window two
or three times as shown. This allows a higher value current
transformer to provide the maximum output current for the
ammeter when used on smaller primary current lines.
32
secondary winding becomes open-circuited and the transformer acts
as a step-up transformer due to the very large increase in
magnetising flux in the secondary core as there is no opposing
current in the secondary winding to prevent this.
The results is a very high voltage induced in the secondary winding
equal to the ratio of: Vp(Ns/Np) being developed across the
secondary winding. So for example, assume our current transformer
from above is used on a 480 volt three-phase power line. Therefore:
33
There are many specialized types of current transformers now
available. A popular and portable type which can be used to measure
circuit loading are called “clamp meters” as shown.
Clamp meters open and close around a current carrying conductor
and measure its current by determining the magnetic field around it,
providing a quick measurement reading usually on a digital display
without disconnecting or opening the circuit.
As well as the handheld clamp type CT, split core current
transformers are available which has one end removable so that the
load conductor or bus bar does not have to be disconnected to install
it. These are available for measuring currents from 100 up to 5000
amps, with square window sizes from 1″ to over 12″ (25-to-300mm).
Then to summarise, the Current Transformer, (CT) is a type of
instrument transformer used to convert a primary current into a
secondary current through a magnetic medium. Its secondary
winding then provides a much reduced current which can be used for
detecting overcurrent, undercurrent, peak current, or average
current conditions.
A current transformers primary coil is always connected in series
with the main conductor giving rise to it also being referred to as a
series transformer. The nominal secondary current is rated at 1A or
5A for ease of measurement. Construction can be one single primary
turn as in Toroidal, Doughnut, or Bar types, or a few wound primary
turns, usually for low current ratios.
34
Current transformers are intended to be used as proportional
current devices. Therefore a current transformers secondary winding
should never be operated into an open circuit, just as a voltage
transformer should never be operated into a short circuit.
Very high voltages will result from open circuiting the secondary
circuit of an energized CT so their terminals must be short-circuited if
the ammeter is to be removed or when a CT is not in use before
powering up the system.
In the next tutorial about Transformers we will look at what happens
when we connect together three individual transformers in a star or
delta configuration to produce a larger power transformer called
a three phase transforme used to supply 3-phase
POTENTIAL TRANSFORMER
35
The secondary voltage of the PT is generally 110 V. In an
ideal potential transformer or voltage transformer, when rated
burden gets connected across the secondary; the ratio of primary
and secondary voltages of transformer is equal to the turns ratio and
furthermore, the two terminal voltages are in precise phase opposite
to each other. But in actual transformer, there must be an error in
the voltage ratio as well as in the phase angle between primary and
secondary voltages.
The errors in potential transformer or voltage transformer can be
best explained by phasor diagram, and this is the main part
of potential transformer theory.
ELECTRIC ISOLATOR
36
required. Electrical isolators separate a part of the system from rest
for safe maintenance works.
So definition of isolator can be rewritten as Isolator is a manually
operated mechanical switch which separates a part of the electrical
power. Isolators are used to open a circuit under no load. Its main
purpose is to isolate one portion of the circuit from the other and is
not intended to be opened while current is flowing in the line.
Isolators are generally used on both ends of the breaker in order that
repair or replacement of circuit breaker can be done without and
danger.
1. Bus side isolator – the isolator is directly connected with main bus
2. Line side isolator – the isolator is situated at line side of any feeder
3. Transfer bus side isolator – the isolator is directly connected with
transfer bus.
37
contact which can be rotated horizontally with rotation of central
post insulator. This rod type contact is also called moving contact.
The female type contacts are fixed on the top of the other post
insulators which fitted at both sides of the central post insulator. The
female contacts are generally in the form of spring loaded figure
contacts.
38
Constructional features of Single Break Isolators:-
The contact arm is divided into two parts one carries male contact
and other female contact. The contact arm moves due to rotation of
the post insulator upon which the contact arms are fitted. Rotation
of both post insulators stacks in opposite to each other causes to
close the isolator by closing the contact arm. Counter rotation of
both post insulators stacks open the contact arm and isolator
becomes in off condition. This motorized form of this type of
isolators is generally used but emergency hand driven mechanism is
also provided.
Earthing Switches:-
Earthing switches are mounted on the base of mainly line side
isolator. Earthing switches are normally vertically break switches.
Earthing arms (contact arm of earthing switch) are normally aligned
horizontally at off condition during switching on operation, these
earthing arms rotate and move to vertical position and make contact
with earth female contacts fitted at the top of the post insulator
stack of isolator at its outgoing side. The erarthing arms are so
interlocked with main isolator moving contacts that it can be closed
39
only when the main contacts of isolator are in open position.
Similarly the main isolator contacts can be closed only when the
earthing arms are in open position.
BUS BAR
40
The Main Criteria’s To be Considered During Selection of on
Particular Bus – Bar Arrangement Scheme Among Others
1. Simplicity of system.
2. Easy maintenance of different equipments.
3. Minimizing the outage during maintenance.
4. Future provision of extension with growth of demand.
5. Optimizing the selection of bus bar arrangement scheme so that it
gives maximum return from the system.
Some very commonly used bus bar arrangement are discussed
below-
41
1. One but major difficulty of these type of arrangement is that,
maintenance of equipment of any bay cannot be possible without
interrupting the feeder or transformer connected to that bay.
2. The indoor 11 KV switch boards have quite often single bus bar
arrangement.
Single Bus System with Bus Sectionalizer:-
Some advantages are realized if a single bus bar is sectionalized with
circuit breaker. If there are more than one incoming and the
incoming sources and outgoing feeders are evenly distributed on the
sections as shown in the figure, interruption of system can be
reduced to a good extent.
42
1. As in the case of single bus system, maintenance of equipment of
any bay cannot be possible without interrupting the feeder or
transformer connected to that bay.
2. The use of isolator for bus sectionalizing does not fulfill the
purpose. The isolators have to be operated ‘off circuit’ and which
is not possible without total interruption of bus – bar. So
investment for bus-coupler breaker is required.
By closing any of the isolators one can put the feeder to associated
bus. Both of the buses are energized and total feeders are divided
into two groups, one group is fed from one bus and other from other
bus. But any feeder at any time can be transferred from one bus to
43
other. There is one bus coupler breaker which should be kept close
during bus transfer operation. For transfer operation, one should
first close the bus coupler circuit breaker then close the isolator
associated with the bus to where the feeder would be transferred
and then open the isolator associated with the bus from where
feeder is transferred. Lastly after this transfer operation he or she
should open the bus coupler breaker.
44
One and A Half Breaker Bus System:-
This is an improvement on the double breaker scheme to effect
saving in the number of circuit breakers. For every two circuits only
one spare breaker is provided. The protection is however
complicated since it must associate the central breaker with the
feeder whose own breaker is taken out for maintenance. For the
reasons given under double breaker scheme and because of the
prohibitory costs of equipment even this scheme is not much
popular. As shown in the figure that it is a simple design, two feeders
are fed from two different buses through their associated breakers
and these two feeders are coupled by a third breaker which is called
tie breaker. Normally all the three breakers are closed and power is
fed to both the circuits from two buses which are operated in
parallel. The tie breaker acts as coupler for the two feeder circuits.
45
During failure of any feeder breaker, the power is fed through the
breaker of the second feeder and tie breaker, therefore each feeder
breaker has to be rated to feed both the feeders, coupled by tie
breaker.
46
This is an alternative of double bus system. The main conception of
Main and Transfer Bus System is, here every feeder line is directly
connected through an isolator to a second bus called transfer bus.
The said isolator in between transfer bus and feeder line is generally
called bypass isolator. The main bus is as usual connected to each
feeder through a bay consists of circuit breaker and associated
isolators at both side of the breaker. There is one bus coupler bay
which couples transfer bus and main bus through a circuit breaker
and associated isolators at both sides of the breaker. If necessary the
transfer bus can be energized by main bus power by closing the
transfer bus coupler isolators and then breaker. Then the power in
transfer bus can directly be fed to the feeder line by closing the
bypass isolator. If the main circuit breaker associated with feeder is
switched off or isolated from system, the feeder can still be fed in
this way by transferring it to transfer bus.
47
2. Then close the bypass isolator of the feeder which is to be
transferred to transfer bus.
3. Now energized the transfer bus by closing the bus coupler circuit
breaker from remote.
4. After bus coupler breaker is closed, now the power from main bus
flows to the feeder line through its main
5. breaker as well as bus coupler breaker via transfer bus.
6. Now if main breaker of the feeder is switched off, total power flow
will instantaneously shift to the bus coupler breaker and hence this
breaker will serve the purpose of protection for the feeder.
7. At last the operating personnel open the isolators at both sides of
the
8. main circuit breaker to make it isolated from rest of the live
system.
48
This is combination of the double bus system and main and transfer
bus system. In Double Bus System with Bypass Isolators either bus
can act as main bus and second bus as transfer bus. It permits
breaker maintenance without interruption of power which is not
possible in double bus system but it provides all the advantages of
double bus system. It however requires one additional isolator
(bypass isolator) for each feeder circuit and introduces slight
complication in system layout. Still this scheme is best for optimum
economy of system and it is best optimum choice for 220 KV system.
49
ring loop is switch of reliability of system becomes very poor as
because closed loop becomes opened. Since, at that moment for any
tripping of any breaker in the open loop causes interruption in all the
feeders between tripped breaker and open end of the loop.
BUS COUPLER
Bus coupler is a device which is used to couple onebus to the other
without any interruption in power supply and without creating
hazardous arcs. Bus coupler is a breaker used to couple two busbars
in order to perform maintenance on other circuit breakers associated
with that busbar.
50
.
CIRCUIT BREAKER
Electrical circuit breaker is a switching device which can be operated
manually and automatically for controlling and protection
of electrical power system respectively. As the modern power system
deals with huge currents, the special attention should be given
during designing of circuit breaker for safe interruption of arc
produced during the operation of circuit breaker. This was the
basic definition of circuit breaker.
51
For saving these equipment and the power networks the fault
current should be cleared from the system as quickly as possible.
Again after the fault is cleared, the system must come to its normal
working condition as soon as possible for supplying reliable quality
power to the receiving ends. In addition to that for proper controlling
of power system, different switching operations are required to be
performed.
So for timely disconnecting and reconnecting different parts of
power system network for protection and control, there must be
some special type of switching devices which can be operated safely
under huge current carrying condition. During interruption of huge
current, there would be large arcing in between switching contacts,
so care should be taken to quench these arcs in circuit breaker in
safe manner. The circuit breaker is the special device which does all
the required switching operations during current carrying condition.
This was the basic introduction to circuit breaker.
Working Principle of Circuit Breaker:-
The circuit breaker mainly consists of fixed contacts and moving
contacts. In normal "ON" condition of circuit breaker, these two
contacts are physically connected to each other due to applied
mechanical pressure on the moving contacts. There is an
arrangement stored potential energy in the operating mechanism of
circuit breaker which is released if switching signal is given to the
breaker. The potential energy can be stored in the circuit breaker by
different ways like by deforming metal spring, by compressed air, or
by hydraulic pressure. But whatever the source of potential energy, it
must be released during operation. Release of potential energy
makes sliding of the moving contact at extremely fast manner. All
circuit breaker have operating coils (tripping coils and close coil),
whenever these coils are energized by switching pulse, and the
plunger inside them displaced. This operating coil plunger is typically
attached to the operating mechanism of circuit breaker, as a result
52
the mechanically stored potential energy in the breaker mechanism
is released in forms of kinetic energy, which makes the moving
contact to move as these moving contacts mechanically attached
through a gear lever arrangement with the operating mechanism.
After a cycle of operation of circuit breaker the total stored energy is
released and hence the potential energy again stored in the
operating mechanism of circuit breaker by means of spring charging
motor or air compressor or by any other means. Till now we have
discussed about mechanical working principle of circuit breaker. But
there are electrical characteristics of a circuit breaker which also
should be considered in this discussion of operation of circuit
breaker.
53
According to their arc quenching media the circuit breaker can be
divided as-
CONTROL PANEL
The substation control panel is designed to form automated control
systems (SCADA) of the traction substations, using digital protection
and programmable logic controllers.
Substation control panel provides:
54
Collection and transmission of the telemetry and diagnosing data via
digital channels of the data transmission network (DTN)
55
Over Current and Earth Fault protection relays may be also provided
in load side of the transformer too, but it should not inter trip the
primary side circuit breaker like the case of backup protection at in-
feed side. The operation is governed primarily by current and time
settings and the characteristic curve of the relay.
To permit use of over load
capacity of the transformer and co-ordination with other similar
relays at about 125 to 150% of full load current of the transformer
but below the minimum short circuit current.
Backup protection of transformer has four elements; three
over current relays connected each in each phase and one earth fault
relay connected to the common point of three over current relays as
shown in the figure. The normal range of current settings available
on IDMT over current relays are 50% to 200% and on earth fault
relay 20 to 80%.
56
Another range of setting on earth fault relay is also available and
may be selected where the earth fault current is restricted due to
insertion of impedance in the neutral grounding. In the case of
transformer winding with neutral earthed, unrestricted earth fault
protection is obtained by connecting an ordinary earth fault relay
across a neutral current transformer.
The unrestricted over current and earth fault relays should have
proper time lag to co-ordinate with the protective relays of other
circuit to avoid indiscriminate tripping.
CAPACITOR BANK
The demand of active power is expressing Kilo Watt (kw) or mega
watt (mw). This power should be supplied from electrical generating
station. All the arrangements in electrical pomes system are done to
meet up this basic requirement. Although in alternating power
system, reactive power always comes in to picture. This reactive
power is expressed in Kilo VAR or Mega VAR. The demand of this
reactive power is mainly originated from inductive load connected to
the system. These inductive loads are generally electromagnetic
circuit of electric motors, electrical transformers, inductance of
57
transmission and distribution networks, induction
furnaces, fluorescent lightings etc. This reactive power should be
properly compensated otherwise, the ratio of actual power
consumed by the load, to the total power i.e. vector sum of active
and reactive power, of the system becomes quite less.
58
These categories are mainly based on the methods of
connecting capacitor bank with the system. Among these two
categories, shunt capacitors are more commonly used in the power
system of all voltage levels. There are some specific advantages of
using shunt capacitors such as,
59
On the other hand has no control over flow of current. As these are
connected in series with load, the load current always passes
through the series capacitor bank. Actually, the capacitive reactance
of series capacitor neutralizes the inductive reactance of the line
hence, reduces, effective reactance of the line. Thereby, voltage
regulation of the system is improved. But series capacitor bank has a
major disadvantage. During faulty condition, the voltage across the
capacitor maybe raised up to 15 times more than its rated value.
Thus series capacitor must have sophisticated and elaborate
protective equipments. Because of this, use of-series capacitor is
confined in the extra high voltage system only.
Shunt Capacitor
Construction of Shunt Capacitor:-
The active parts of capacitor unit are composed by two aluminum
foils separated by impregnated papers. The thickness of the papers
may vary from 8 microns to 24 microns depending upon the voltage
level of the system. The thickness of the aluminum foil is in the order
of 7 microns. For low voltage applications, there may be one layer of
impregnated paper of suitable thickness between the foils but for
higher voltage applications more than one layer of impregnated
papers are placed between the aluminum foil to avoid unwanted
circulation of short circuit current between the foil due to presence
of conducting matters in the papers.
The capacitor sections are wound into rolls thereafter
they are flattened out, compressed into packs, enclosed in multiple
layers of heavy paper insulations and inserted into the containers.
When the lid had been welded to the container, the capacitor unit is
dried and integrated in large autoclaves by a combination of heat
and vacuum. After the paper is completely dried and all gases
removed from the insulation the capacitor tank is filled with
impregnant degassed at the same vacuum.
In the early stages of development, it was generally mineral
60
insulating oil which was used as impregnant. This has now been
replaced by most of the manufacturers with synthetic liquids of
chlorinated diphenyl group bearing different trade names. Mineral
insulating oil has very low electric conductivity and very high
dielectric strength. But it has however some drawbacks such as,
61
EARTHING
62
Earth Mat in substation
63
Earth Resistance Value:-
The value of earth resistance of the ground system determines the
voltage rise of the various earthed points during the earth fault.
If earth fault current is I, earth resistance is R, the voltage rise under
short circuit condition would be V= IR. The permissible potential rise
and the maximum possible earth fault current set a limit on the
maximum value of earth resistance. To achieve earth resistance
within specified limits, enough number of earth spikes and sufficient
surface area of the earth grid and closer ground mesh rods are
necessary.The touch potential and earth potential in the switchyard
under any earth fault condition should be within safe limits.
INSULATOR
Electrical Insulator must be used in electrical system to prevent
unwanted flow of currentto the earth from its supporting points.
The insulator plays a vital role in electrical system. Electrical
Insulator is a very high resistive path through which practically no
current can flow. In transmission and distribution system,
the overhead conductors are generally supported by supporting
towers or poles.
Insulating Material:-
The main cause of failure of overhead line insulator, is flash over,
occurs in between line and earth during abnormal over voltage in the
system. During this flash over, the huge heat produced by arcing,
causes puncher in insulator body. Viewing this phenomenon the
64
materials used for electrical insulator, has to posses some specific
properties.
65
. The surface of the insulator should be glazed enough so that water
should not be traced on it. Porcelain also should be free from
porosity since porosity is the main cause of deterioration of its
dielectric property. It must also be free from any impurity and air
bubble inside the material which may affect the insulator properties.
Glass Insulator:-
Now days glass insulator has become popular in transmission and
distribution system. Annealed tough glass is used for insulating
purpose. Glass insulator has numbers of advantages over
conventional porcelain insulator
66
8. After all, glass is cheaper than porcelain.
Disadvantages of Glass Insulator:-
1. Moisture can easily condensed on glass surface and hence air dust
will be deposited on the wed glass surface which will provide path
to the leakage current of the system.
2. For higher voltage glass can not be cast in irregular shapes since
due to irregular cooling internal cooling internal strains are caused.
Polymer Insulator:-
In a polymer insulator has two parts, one is glass fiber reinforced
epoxy resin rod shaped core and other is silicone rubber or EPDM
(Ethylene Propylene Diene Monomer) made weather sheds. Rod
shaped core is covered by weather sheds. Weather sheds protect the
insulator core from outside environment.
67
Advantages of Polymer Insulator:-
1. It is very light weight compared to porcelain and glass insulator.
2. As the composite insulator is flexible the chance of breakage
becomes minimum.
3. Because of lighter in weight and smaller in size, this insulator has
lower installation cost.
4. It has higher tensile strength compared to porcelain insulator.
5. Its performance is better particularly in polluted areas.
6. Due to lighter weight polymer insulator imposes less load to the
supporting structure.
68
7. Less cleaning is required due to hydrophobic nature of the
insulator.
Disadvantages of Polymer Insulator
1. Moisture may enter in the core if there is any unwanted gap
between core and weather sheds. This may cause electrical failure
of the insulator.
2. Over crimping in end fittings may result to cracks in the core which
leads to mechanical failure of polymer insulator.
In addition to these, some other disadvantages might be
experienced. Let us give a practical example where many difficulties
are faced in maintaining a distribution network in Victoria Australia
due to polymeric insulator. There are many Cockatoos, Galahs and
Parrots in that area of Australia, which love to chew on polymeric
strain insulators. Here, the 22 KV network has many of polymeric
strain insulators installed and now after a few years of installing
polymeric strain insulators, the authority is now replacing many of
them back with Glass disc insulators. Another disadvantage is that
they have had post type polymeric insulators melt and bend in bush
fire areas. They have a concrete pole and a steel cross arm that
survives a bush fire, however the polymers in some cases fail. This
would not be the case with glass or porcelain insulators. They have
also had polymeric insulators fail in areas close to the ocean
coastline where there are high salt levels in the air.
Types of Insulator:-
There are mainly three types of insulator likewise
69
1. Pin Insulator
2. Suspension Insulator
3. Stray Insulator
In addition to that there are other two types of electrical insulator
available mainly for low voltage application, e.i. stay insulator and
shackle insulator.
BATTERY ROOM
A battery room is a room in a facility used to house batteries for
backup or uninterruptible power systems. Battery rooms are found
in telecommunication central offices, and to provide standby power
to computing equipment in datacenters. Batteries provide direct
current(DC) electricity, which may be used directly by some types of
equipment, or which may be converted to alternating current (AC)
by uninterruptible power supply (UPS) equipment. The batteries may
provide power for minutes, hours or days depending on the electrical
system design, although most commonly the batteries power the
UPS during brief electric utility outages lasting only seconds.
70