Académique Documents
Professionnel Documents
Culture Documents
Control Unit
Data Sheet
ZY8932IMA01E– 31/03/2016
Total or partial reproduction of this publication by any means or
procedure is prohibited without previous express written
authorisation by Ingeteam Power Technology.
One of the primary goals of Ingeteam Power Technology is the Parque Tecnológico de Bizkaia
continuous improvement of its equipment; consequently, the Edificio 110
48170 Zamudio (Bizkaia)
information contained in this catalogue may be modified without
Tel +34-944 039 600
previous notice. Fax +34-944 039 679
For further information, please refer to the manual or contact us. http://www.ingeteam.com
Contents Table
1 Introduction .................................................................................................4
3 Housing ......................................................................................................15
5 Time Synchronization..............................................................................23
INGEPAC DA - C U 0 A H C X F A X X X X -
MODEL
Control Unit RTU
8 DIGITAL INPUT Generic CU0
5 DIGITAL OUTPUT
EXTENDED FEATURES
Basic A
HOUSING
1/3 19" H
POWER SUPPLY
24/48 Vdc DI 24/48 Vdc A
12 Vdc DI 12 Vdc D
TERMINALS
Pin Type A
BOARD SELECTION
None XX
15 DI / 8 DO, 24/48 Vdc XC
24 DI / 16 DO (13 NO / 3NC), 24/48 Vdc XM BOARD1
8 DC (mA) 15 DI, 24/48 Vdc XN BOARD2
15 DI / 8 DO, 12 Vdc CC
24 DI / 16 DO (13 NO / 3NC), 12 Vdc CM
8 DC (mA) 15 DI, 12 Vdc CN
RESERVED
RESERVED -
INGEPAC ™ DA-CU
2/3 19” Housing
INGEPAC DA - C U 0 A I C X F A -
MODEL
Control Unit RTU
8 DIGITAL INPUT Generic CU0
5 DIGITAL OUTPUT
EXTENDED FEATURES
Basic A
HOUSING
2/3 19" I
POWER SUPPLY
24/48 Vdc DI 24/48 Vdc A
12 Vdc DI 12 Vdc D
TERMINALS
Pin Type A
BOARD SELECTION
None XX
15 DI / 8 DO 24 / 48 Vdc XC BOARD1
24 DI / 16 DO (13 NO / 3NC), 24/48 Vdc XM BOARD2
8 DC (mA) 15 DI, 24/48 Vdc XN BOARD3
15 DI / 8 DO, 12 Vdc CC BOARD4
24 DI / 16 DO (13 NO / 3NC), 12 Vdc CM
8 DC (mA) 15 DI, 12 Vdc CN
RESERVED
RESERVED -
INGEPAC ™ DA-CU
Compact Housing
INGEPAC DA - C U 0 A G C X F A X X X X X X -
MODEL
Control Unit RTU
8 DIGITAL INPUT
5 DIGITAL OUTPUT Generic CU0
EXTENDED FEATURES
Basic A
HOUSING
Compact G
POWER SUPPLY
24/48 Vdc DI 24/48 Vdc A
12 Vdc DI 12 Vdc D
TERMINALS
Pin Type A
BOARD SELECTION
None XX
15 DI / 16 DO, 24/48 Vdc XT
8 DC (mA) 15 DI, 24/48 Vdc XN BOARD1
15 DI / 16 DO, 12 Vdc CT
8 DC (mA) 15 DI, 12 Vdc CN
RESERVED
RESERVED -
2 Technical Features
ENVIRONMENTAL CONDITIONS
Operating temperature -40 to +65 ºC
Storage temperature -40 to +85 ºC
Relative humidity Up to 95% without condensation
CPU FEATURES
Number of CPU modules 1
Microprocessor ARM-Cortex A-8
RAM memory 256 MB
Storage memory 128 MB
NVRAM memory 512 KB
Number of USB 2.0 port 1
Logic programming IEC 61131-3 with10 ms cycle time
Time synchronization SNTP
Element
1 ETH 1
2 ETH 2
3 SP 1
4 Status LED
5 Power LED
3.2 DA2505 - 2/3 19” Housing
Element
1 ETH 1
2 ETH 2
3 SP 1
4 Status LED
5 Power LED
3.1 DA2609 - Compact Housing
Element
1 ETH 1
2 ETH 2
3 Status and configurable LEDs
4 SP 0
5 SP 1
6 USB
7 Power LED
8 Status LED
9 I / O LEDs
Fig. 3.8 Status and confgiurable LEDs
INGEPAC™ DA-CU can work with the following communication standards and protocols:
INGEPAC™ DA-CU have been proven with the following maximum recommended
configurations.
5 Time Synchronization
6 Logic Programming
Logic editing in the INGEPAC™ DA-CU equipment complies with the directives defined by the
IEC61131-3 standard. It is possible to program in the following languages:
INGEPAC™ DA-CU is fully configurated with the engineering software INGESYS™ eFS.
INGESYS™ eFS is a powerful, native IEC61850 framework, specifically developed by
INGETEAM to support the IEC61850 standards and derived standards simply and intuitively.
INGESYS™ eFS facilitates engineering tasks in automation systems, covering all the concepts
associated with the following:
Protection functions.
Control functions.
Telecontrol functions.
Measurements.
Architectural design and electrical diagrams.
Definition of operational concepts.
Transfer of information and configurations.
Integration of other communication protocols.
Regulatory configuration files.
Etc.
INGEPAC™ DA-CU stores information about system events and commands. This information
can be audited with INGESYS™ eFS.
8 Standards and Tests
Electromagnetic
Emissions
Conducted radio-electric emissions IEC 60255-25 (2000) Class B
measurement in DC power supply
EN 55022 (2006)
terminals.
IEC 60255-25 (2000) Class A
Radiated radio-electric emissions
EN 55022 (2006)
measurements.
EN 55011 (2007)
Insulation
Dielectric strength measurement IEC 60255-5 (2000) 2 kVac
Insulation resistance measurement IEC 60255-5 (2000) 500 Vdc, >100 Mohm
Isolation measurement with voltage +5 kV
IEC 60255-5 (2000)
pulses.
Immunity
Electrostatic discharges IEC 61000-4-2 (2001) Level 4, +8 kV/+15 kV
Radiofrequency electromagnetic field IEC 61000-4-3 (2006) Level 3. 10 V/m
Fast transient bursts IEC 61000-4-4 (2004) Level 4, +4 kV, 5KHz
CM: +4 kV
PS: +2 kV
Surges or shockwaves IEC 61000-4-5 (2006)
I/O
DM: +2 kV
Climatic
Cold test IEC 60068-2-1 (1994) -40°C, 16 h
Dry heat test IEC 60068-2-2 (1994) 85°C, 16 h
Temperature variation test IEC 60068-2-14 (1994) -25ºC / 70ºC
Continuous humidity heat test IEC 60068-2-78 (1994) 40ºC+2ºC, 93% 4 days
Mechanical
Vibration test (sinusoidal) IEC 60255-21-1 (1998) Class I
5-200 Hz
Vibration random EN 60068-2-64 (2008)
ASD 1 m2/s3
Shock and bump IEC 60255-21-2 (1998) Class I
Seismic
Seismic tests IEC 60255-21-3 (1993) Class 1
Drop ETSI EN 300 019-2-2 (1999)
IP30
IP protection grade: UNE EN 20 324 (1993)
Frontal IP32
www.ingeteam.com