On-load tap-changer OILTAP® V
Technical Data TD 82
Table of Contents

Table of Contents

1 General .................................................................................................................................................................................................................. 4
1.1 Summary of the technical data ....................................................................................................................................................... 4
1.2 Survey ....................................................................................................................................................................................................... 6

2 Technical Data ................................................................................................................................................................................................... 13


2.1 Rated through-current (Iu), rated step voltage (Ui) and step capacity (PStN) ................................................................ 13
2.2 On-load tap-changer V III 250 Y/D and V III 400 Y/D .............................................................................................................. 13
2.3 Restriction of the rated step voltage Ui ........................................................................................................................................ 14
2.4 Contact life ............................................................................................................................................................................................. 14
2.5 Rated withstand voltages of the internal insulation ................................................................................................................ 15

3 Appendix – dimension and installation drawings .............................................................................................................................. 17

NOTE

These technical data are intended for the calculator and designer of the transformer. These type-specific data are only
valid in connection with the information contained in the general section (TD 61) since this section contains important
information on such subjects as potential connection, leakage inductance, current division, and so on.
Dimensional drawings and connection diagrams are subject to change without prior notice.
Drawings submitted during bidding and ordering are always binding.
Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the transformer
manufacturer is responsible for selecting the correct properties of the on-load tap-changer so that the requirements
of the transformer are met.

082/02/01/0
TD 82/02 3
1 General

1 General

1.1 Summary of the technical data

On-load tap-changer V III 200 Y V III 200 D V III 350 Y V III 350 D V I 350

Number of poles and 3 3 3 3 1


application neutral point at any point on neutral point at any point on
the winding the winding
Max. rated through-current Ium 200 350
(in A)
Rated short-time withstand 4 5
current (in kA)
Rated short-circuit duration 3 3
(in s)
Rated peak withstand current
(in kA) 10 12,5
Max. rated step 10 contacts 1500 1500
voltage Uim 12 contacts 1200 to 1400 1200 to 1400
(in V) 14 contacts 1000 1000
Step capacity 10 contacts 300 525
(PStN) 12 contacts 280 420
(in kVA) 14 contacts 200 350
Rated frequency (in Hz) 50 to 60
Operating positions without change-over selector: max. of 14
with change-over selector: max. of 27
Rated insulation level
Highest voltage for 40 76 123 40 76 123/76 40 76 123 40 76 123/76 40 76
equipment Um (in kV)
Highest operating voltage 40 76 123 30 55 79 40 76 123 30 55 79 30 55
Ub (phase - phase) on
diverter switch (in kV)
Rated lightning impulse Um 40 Um 76 Um 123 Um 123/76
withstand voltage
(in kV, 1,2 I 50) 200 350 550 550
AC withstand voltage 70 140 230 230
(in kV, 50 Hz, 1 min.)
Rated withstand voltages of see table 4
internal insulation
Oil compartment Pressure-proof up to 0.3 bar, continuous difference pressure (test pressure 0.6 bar),
head and cover of the on-load tap-changer are vacuum-proof.
Oil suction pipe Installed as standard (for details, see BA 18)
Temperature range The on-load tap-changer OILTAP® V can be operated in the rated load range with
oil temperatures of -25 °C to +105 °C.

Table 1a

4 TD 82/02 082/02/01/0
1 General

On-load tap-changer V III 200 Y V III 200 D V III 350 Y V III 350 D V I 350

Weight without oil (ca. in kg) 130 140 140 150 120

Displacement without change- 125 165 140 185 85


volume over selcctor
(ca. in dm3)
with change- 155 200 170 220 115
over selcctor

Oil filling VS ∆V VS ∆V VS ∆V VS ∆V VS ∆V
quantity VS
and minimum
volume ∆V1 of without change- 100 14 145 19 110 15 165 21 68 10
the diverter over selector
switch oil
compartment
(in dm3) with 125 16 165 20 135 18 180 22 85 12
over selector

Table 1b

Notes for table 1b:


1)
Applies to oil temperature J = – 30 °C ... +100 °C

082/02/01/0
TD 82/02 5
1 General

1.2 Survey

Fig. 1 Survey of the designs (no. of poles, change-over selector, and installation lengths) 8996820E

6 TD 82/02 082/02/01/0
1 General

Survey of the basic connection diagrams (fig. 2a, 2b, 2c) with designation of the tap selector terminal contacts in accordance
with MR standards. This contact designation corresponds to the specifications in the on-load tap-changer dimension
drawings.

Fig. 2a

excerpt from 8906164E_1

082/02/01/0
TD 82/02 7
1 General

Fig. 2b

excerpt from 8906164E_2

8 TD 82/02 082/02/01/0
1 General

Fig. 2c

excerpt from 8906164E_3

082/02/01/0
TD 82/02 9
1 General

Fig. 3 Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram 10 10 0

10 TD 82/02 082/02/01/0
1 General

Fig. 4 Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram 10 19 1 W

082/02/01/0
TD 82/02 11
1 General

Fig. 5 Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram 10 19 1 G

12 TD 82/02 082/02/01/0
2 Technical Data

2 Technical Data

2.1 Rated through-current (Iu), rated step voltage (Ui) and step capacity ((PStN)

On-load tap-changer V III 200 Y/D V III 350 Y/D, V I 350

Contacts 10 12 14 10 12 14

Iu (A) 200 200 200 350 300 350 350

Ui (V) 1500 1400 1000 1500 1400 1200 1000

PStN (kVA) 300 280 200 525 420 420 350

Table 2 Rated through-currents (Iu), related rated step voltages (Ui) and step capacities (PStN), at
highest and lowest rated step voltage of the step capacity curve (see fig. 6)

8997600E

Fig. 6 Step capacities (Iu, Ui)

2.2 On-load tap-changer V III 250 Y/D and V III 400 Y/D
On-load tap-changers V III 250 Y/D and V III 400 Y/D are available as special designs with a maximum rated
through-current of Ium = 250 A or 400 A. The step capacity corresponds to the designs V III 200 Y/D or
V III 350 Y/D.
Dimensional drawings on request.

082/02/01/0
TD 82/02 13
2 Technical Data

2.3 Restriction of the rated step voltage Ui 2.4 Contact life


Due to insulation, the rated step voltage is also limited by The mean expected contact life of the arcing tap-changer
the dielectric strength of the tap-changer, i.e. by limitation contacts can be estimated based on the relative load (= Iu/
of the total operating voltage across the contact circle. Ium) as shown in fig. 7. Since actual contact life in indivi-
The total voltage must not exceed the limit values.: dual cases depends on many influencing factors while in
service, only estimations can be given (not applicable to
10 contacts: Total Ui = 13 500 V,
constant current service).
12 contacts: Total Ui = 13 200 V,
The inspection regulations must be observed.
14 contacts: Total Ui = 13 000 V.
The rated step voltages Ui of these on-load tap-changers
depend on the basic connection diagrams as shown in
figures 2a, 2b and 2c and are valid under the condition
that the rated step voltage is constant within the entire
setting range.

Basic connection diagram Rated step voltage Ui (in V)

10 10 0 1 500 ∑ Ui = 13 500 V
10 09 1 W
10 19 1 W
10 09 1 G
10 19 3 W
10 19 1 G
10 19 3 G 1 500 Fig. 7
Expected mean contact life under average load
12 12 0 1 200 ∑ Ui = 13 200 V
12 11 1 W 1 400 n – Number of operations
12 23 1 W 1 200 Iu – Rated through-current
12 23 3 W 1 320 Ium – Max. rated through-current
12 23 1 G 1 200
12 11 1 G 1 400
12 23 3 G 1 320

14 14 0 1 000 ∑ Ui = 13 000 V
14 13 1 W
14 13 1 G
14 27 1 W
14 27 3 W
14 27 1 G
14 27 3 G 1 000

Table 3
Max. rated step voltage

14 TD 82/02 082/02/01/0
2 Technical Data

2.5 Rated withstand voltages of the internal insulation


Fig. 8 shows the specific voltage stresses present on the tap winding. When selecting the on-load tap-changer, a check must
be made to determine whether the stress at the most unfavorable position on the on-load tap-changer does not exceed the
related rated withstand voltages as shown in table 4.

Insulation distances Voltage shape and V III 200 D V III 350 Y V I 350
period V III 350 D V III 200 Y

kV 1.2|50 µs 200 200 200


10 contacts
kV 50 Hz 1min 50 50 50
kV 1.2|50 µs 180 180 180
a, a1 12 contacts
kV 50 Hz 1min 50 50 50
kV 1.2|50 µs 170 170 170
14 contacts
kV 50 Hz 1min 50 50 50
b1 b2 b3
kV 1.2|50 µs 230 230 300 200
Um = 40 kV
kV 50 Hz 1min 70 70 90 70
kV 1.2|50 µs 350 490 520 200
Um = 76 kV
kV 50 Hz 1min 140 165 180 70
kV 1.2|50 µs 550 580 620
Um = 123 kV/76
kV 50 Hz 1min 150 165 180
b
kV 1.2|50 µs 200
Um = 123 kV
kV 50 Hz 1min 70
c21 c22
kV 1.2|50 µs 350 350 350
Um = 40 kV
kV 50 Hz 1min 140 140 140
kV 1.2|50 µs 490 520 350
Um = 76 kV
kV 50 Hz 1min 165 180 140
kV 1.2|50 µs 580 620
Um = 123/76 kV
kV 50 Hz 1min 165 180
c2
kV 1.2|50 µs 350
Um = 123 kV
kV 50 Hz 1min 140
f1 f2 f1 f2 f1 f2
kV 1.2|50 µs 200 300 200 300 200 300
Um = 40 kV
kV 50 Hz 1min 70 90 70 90 70 90
kV 1.2|50 µs 350 490 350 490 350 490
Um = 76 kV
f kV 50 Hz 1min 140 165 140 165 140 165
kV 1.2|50 µs 550 580
Um = 123/76 kV
kV 50 Hz 1min 230 230
kV 1.2|50 µs 550 550
Um = 123 kV
kV 50 Hz 1min 230 230

Table 4 Rated withstand voltages (in kV) of the insulation distances (rated lightning impulse withstand voltage,
AC withstand voltage) on the on-load tap-changer

082/02/01/0
TD 82/02 15
2 Technical Data

Without a1 = Between tap selector contacts of the winding of one tap position
change-over (connected or not connected)
selector a = Between beginning and end of a tapped winding and, with coarse
tap winding, between beginning and end of a coarse tap winding.
Note for coarse tapping arrangement in (-) - position of the change-
over selector:
When stressed with impulse voltage, the permissible withstand
voltage „a“ must be adhered to between the end of a coarse tap
winding connected with the K tap selector contact and the tap
selector contact at the end of the tapped winding of the same phase.
b = Between the tap selector contacts of different phases and between
With
change-over selector contacts of different phases, which are con-
reversing
nected with the beginning/end of a tapped winding or with a tap
switch
selector contact.
(+) - position
With tap-changers for delta connection, the permissible voltages
between the contacts depend on the positions of the change-over
selector and the tap selector. This is why the various withstand
voltages b1, b2 or b3 must be adhered to for any insulation distance:
b1 = Between selected contacts of different phases
b2 = From the selected contact of one phase to the unselected
contacts of other phases
With b3 = Between unselected contacts of different phases
reversing f = To ground
switch The following applies to designs without change-over selector.
(–) - position f1 = Between selected tap selector contacts and ground
f2 = Between unselected tap selector contacts and ground
The following applies to designs with change-over selector.
f1 = Between selected change-over selector contacts and ground
f2 = Between unselected change-over contacts and ground
In addition, with coarse tapping arrangement in (+) - position of the
change-over selector:
c2 = Between (-) - change-over selector contacts of different phases and
of one (-) -change-over selector and one (+) - change-over contact of
With coarse another phase
tap selector Different permissible values apply to tap-changers for delta connections.
(+) - position c21 = Between one (-) - change-over selector contact and one
(+) - change-over selector contact of another phase
c22 = Between one (-) - change-over selector contact of
different phases

With coarse
tap selector
(–) - position

8997570E

Fig. 8 Specific voltage stress of the tap winding

16 TD 82/02 082/02/01/0
3 Appendix

3 Appendix

Dimension drawings, Um = 40 kV and 123 kV


On-load tap-changer OILTAP® V III 200 Y
Without change-over selector .......................................................................................................................................................................... 893949
With change-over selector ................................................................................................................................................................................. 893950
On-load tap-changer OILTAP® V III 200 D
Without change-over selector .......................................................................................................................................................................... 893952
With change-over selector ................................................................................................................................................................................. 893951
On-load tap-changer OILTAP® V III 350 Y
Without change-over selector .......................................................................................................................................................................... 898212
With change-over selector ................................................................................................................................................................................. 898213
On-load tap-changer OILTAP® V III 350 D
Without change-over selector .......................................................................................................................................................................... 893955
With change-over selector ................................................................................................................................................................................. 893956
On-load tap-changer OILTAP® V I 350
Without change-over selector .......................................................................................................................................................................... 893957
With change-over selector ................................................................................................................................................................................. 893958

Installation drawings
On-load tap-changer OILTAP® V 200 .............................................................................................................................................................. 893945
On-load tap-changer OILTAP® V 350 .............................................................................................................................................................. 893821
On-load tap-changer OILTAP® V 200, tie-in resistors attached on the side ...................................................................................... 898289
On-load tap-changer OILTAP® V 350, tie-in resistors attached on the side ...................................................................................... 898216
On-load tap-changer OILTAP® V III 200 Y / V III 350 Y, tie-in resistors attached on the cylinder for 2, 3 or
4 tie-in resistors/phase ........................................................................................................................................................................................ 898530

Additional drawings
On-load tap-changer head ................................................................................................................................................................................ 893779
Special design for installation in bell-type tanks ....................................................................................................................................... 893864
On-load tap-changer head with mounting flange for pressure relief valve .................................................................................... 895167
Swivelling range of the gear unit, drive shaft left .................................................................................................................................... 894679
Swivelling range of the gear unit, drive shaft right .................................................................................................................................. 894680
Horizontal drive shaft (standard and special design) ................................................................................................................................ 893772
Directory of additional drawings for on-load tap-changer OILTAP® V in acc. w. note in
the dimension drawings ...................................................................................................................................................................................... 898018

082/02/01/0
TD 82/02 17
8939498E
On-load tap-changer OILTAP® V
V III 200 Y - 40 to 123 - 0, dimension drawing

18 TD 82/02 082/02/01/0
8939508E
On-load tap-changer OILTAP® V
V III 200 Y - 40 to 123 - W/G, dimension drawing

082/02/01/0
TD 82/02 19
8939528E
On-load tap-changer OILTAP® V
V III 200 D - 40 to 123/76 - 0, dimension drawing

20 TD 82/02 082/02/01/0
8939518E
On-load tap-changer OILTAP® V
V III 200 D - 40 to 123/76 - W/G, dimension drawing

082/02/01/0
TD 82/02 21
8982122E
On-load tap-changer OILTAP® V
V III 350 Y - 40 to 123 - 0, dimension drawing

22 TD 82/02 082/02/01/0
8982132E
On-load tap-changer OILTAP® V
V III 350 Y - 40 to 123 - W/G, dimension drawing

082/02/01/0
TD 82/02 23
8939559E
On-load tap-changer OILTAP® V
V III 350 D - 40 to 123/76 - 0, dimension drawing

24 TD 82/02 082/02/01/0
8939569E
On-load tap-changer OILTAP® V
V III 350 D - 40 to 123/76 - W/G, dimension drawing

082/02/01/0
TD 82/02 25
8939579E
On-load tap-changer OILTAP® V
V I 350 - 40 to 76 - 0, dimension drawing

26 TD 82/02 082/02/01/0
8939589E
On-load tap-changer OILTAP® V
V I 350 - 40 to 76 - W/G, dimension drawing

082/02/01/0
TD 82/02 27
On-load tap-changer OILTAP® V
8939456E
Installation drawing

28 TD 82/02 082/02/01/0
On-load tap-changer OILTAP® V 350
8938218E
Installation drawing

082/02/01/0
TD 82/02 29
On-load tap-changer OILTAP® V III 200 Y/D
8982891E
Tie-in resistors, attached on the side

30 TD 82/02 082/02/01/0
On-load tap-changer OILTAP® V III 350 Y/D
8982162E
Tie-in resistors, attached on the side

082/02/01/0
TD 82/02 31
On-load tap-changer OILTAP® V III 200 Y / V III 350 Y
8985302E
Tie-in resistors, attached on the cylinder for 2, 3 or
4 tie-in resistors/phase

32 TD 82/02 082/02/01/0
8937799E
On-load tap-changer OILTAP® V
On-load tap-changer head

082/02/01/0
TD 82/02 33
On-load tap-changer OILTAP® V
8938644E
Special design for bell-type tank installation

Lifting device

O-ring 44.2 - 5.7

Lifting traverse (illustrated in turned position)

Transformer
cover Washer 8

Gasket

Supporting flange

Lifting traverse

Z - Centering bolt
Further dimensions of tap changer
head see dwg. 893 779
Lifting traverse see dwg. 893 805

34 TD 82/02 082/02/01/0
On-load tap-changer OILTAP® V
8951672E
Mounting flange for pressure relief valve

082/02/01/0
TD 82/02 35
On-load tap-changer OILTAP® V
8946793E
Design with flange for pressure relief valve
Swivelling range of the gear unit, drive shaft left

36 TD 82/02 082/02/01/0
On-load tap-changer OILTAP® V
8946804E
Design with flange for pressure relief valve
Swivelling range of the gear unit, drive shaft right

082/02/01/0
TD 82/02 37
On-load tap-changer OILTAP® V
8937723E
Horizontal drive shaft (standard and special design)

38 TD 82/02 082/02/01/0
On-load tap-changer OILTAP® V
8980183E Directory of the additional drawings in acc. w. note in
dimension drawings

Installation drawing for


on-load tap-changer OILTAP® V 200........................................... 893945

Installation drawing for


on-load tap-changer OILTAP® V 350........................................... 893821

On-load tap-changer head ........................................................... 893779

On-load tap-changer head,


bell-type tank..................................................................................... 893864

Horizontal drive shaft ...................................................................... 893772

082/02/01/0
TD 82/02 39
© Maschinenfabrik Reinhausen GmbH Phone +49 941 40 90-0
www.reinhausen.com Falkensteinstrasse 8 Fax +49 941 40 90-111
93059 Regensburg, Germany E-Mail sales@reinhausen.com

Please note: The data in our publications may differ from the data of the devices delivered.
We reserve the right to make changes without notice.
TD 82/02 en • 0203/1000 • 082/02/01/0 • F0017801 • Printed in Germany