Data Sheet
Air Conditioning and Ventilation
(8131.X.17....)
REV DATE PAGES DESCRIPTION PREP'D CHK'D APP'D COMPANY
A 10 31 13 ALL ISSUED FOR REVIEW MKR KN JB/DS
B 12 16 13 ALL ISSUED FOR APPROVAL MKR KN JB/DS
C 12 26 13 ALL RE-ISSUED FOR APPROVAL MKR KN JB/DS
0 01 22 14 ALL ISSUED FOR DESIGN MKR KN JB/DS
REV.
MKR
KN
JB / DS
XXXXXX
XXXXXX
ata Sheet
ning and Ventilation
131.X.17....)
COMPANY
AIR C
CONTRACT NO.
C-793162
DATE
PREP'D
CHECK'D
APP'D
Equipment Note 2)
Cooling Capacity : Btu/hr
Supply Air Quantity : CFM
OTHER
Indoor Accessories Air Filter Reheater
Note :
1. Applicable Code/ Standard/ Specification:
ASHRAE Fundamental, Equipment, System Volume
ACCA Air Conditioning Contractors of America
SP-ME-ME-013 HVAC Air Conditioning and Ventilation
PP-PC-GG-004 Transportation & Packaging of Equipment
SID-SU-5106 Safety in Design
DRI-SU-1824-Q Induction Motor
DRI-PA-1824-1A Addendum to DRI-SU-1824-Q
ELC-DU-5135-A Electrical, General Specification
2. Building Load Stated are estimated value. Vendor shall verify the cooling load calculation
AIR CONDITIONING AND VENTILATION
CONTRACT NO. DOC. NO. REV
C-793162 DS-3513.NO-ME-004 0
Jan 22,2014 SHEET : 2 OF 2
✘ Continuos Intermittent
Equipment Note 2)
Free standing
Remote Control
Charging Valve
Refer to Attachment, Estimated cooling load calculation result summaries North Station of NDD 13
date : Jan 22,2014
rev : 0
AC Split-System Type
No Location Qty Btu/h (kW) Remark
1 IT Room 1 1 x 9000 1 x 0.75 Total 2HP AC = 14 units
2 Control Room 2 2 x 18000 2 x 1.49
3 Corridor Room 2 2 x 9000 2 x 0.75 Total 1HP AC = 5 units
4 Instrument Rack Room 4 4 x 18000 4 x 1.49
5 Sub Station _ MCC 6 6 x 18000 6 x 1.49 Total 1/2HP AC = 0 unit
6 Admin Room 1 1 x 9000 1 x 0.75
7 UPS Room 2 2 x 18000 2 x 1.49
8 Storage Room 1 1 x 9000 1 x 0.75 0
1 1
1
1
1
✘
1
1
1