CONTRACT NO. DOC NO.

C-793162 DS-3513NO-ME-004

DATE: Jan 22,2014 SHEET : 1 OF 2

PREP'D M. KHAERON
CHK'D KOSALA NUGRAHA
APP'D JOHNSON BATUBARA / DWI SUSENO

XXXXXX
XXXXXX

Data Sheet
Air Conditioning and Ventilation
(8131.X.17....)
REV DATE PAGES DESCRIPTION PREP'D CHK'D APP'D COMPANY
A 10 31 13 ALL ISSUED FOR REVIEW MKR KN JB/DS
B 12 16 13 ALL ISSUED FOR APPROVAL MKR KN JB/DS
C 12 26 13 ALL RE-ISSUED FOR APPROVAL MKR KN JB/DS
0 01 22 14 ALL ISSUED FOR DESIGN MKR KN JB/DS
REV.

MKR
KN
JB / DS

XXXXXX
XXXXXX

ata Sheet
ning and Ventilation
131.X.17....)
COMPANY
AIR C
CONTRACT NO.
C-793162
DATE

PREP'D
CHECK'D
APP'D

Client : P.T. Chevron Pacific Indonesia Unit Tag Number

Project North Duri Development (NDD) Area 13 Service


Vendor No. Required
Purchase Order No.

Design Condition Note 2

Estimated Cooling Load : ( refer to attached list ) Location :


Building : Btu/hr
MCC/Electr Appliance : Btu/hr
Estimated Supply Air Quantity CFM
Design Room DB Temperature : 74.3 to 79.7 o
F
Design Relative Humidity : 50 - 60 %
Designn Outdoor DB : 95 o
F
Service :
General Information
Type of Equipment : Split Type
Compressor within Outdoor Unit
Refrigerant : Non CFC (Vendor to advice)
Power Supply : 120 Volt / 1 Phase / 60 Hz
Spare Unit : No

Equipment Note 2)
Cooling Capacity : Btu/hr
Supply Air Quantity : CFM

INDOOR UNIT Note 2)

Type : Wall Mounted Type :


Manufacturer : PML
Model No x Qty : Manufacturer
Air Filter Type: Washable Model No x Qty
Fan Type : Axial Centrifugal Cooling Coil

Manufacturer Fan Type :


Fan Model No x Qty
Fan Power HP
Temperature Control Compressor Type:

OTHER
Indoor Accessories Air Filter Reheater

Condensing Unit Low Oil Protection Over Current Protection


Line Service Valve Filter Dryer

Note :
1. Applicable Code/ Standard/ Specification:
ASHRAE Fundamental, Equipment, System Volume
ACCA Air Conditioning Contractors of America
SP-ME-ME-013 HVAC Air Conditioning and Ventilation
PP-PC-GG-004 Transportation & Packaging of Equipment
SID-SU-5106 Safety in Design
DRI-SU-1824-Q Induction Motor
DRI-PA-1824-1A Addendum to DRI-SU-1824-Q
ELC-DU-5135-A Electrical, General Specification

2. Building Load Stated are estimated value. Vendor shall verify the cooling load calculation
AIR CONDITIONING AND VENTILATION
CONTRACT NO. DOC. NO. REV
C-793162 DS-3513.NO-ME-004 0
Jan 22,2014 SHEET : 2 OF 2

PREP'D M. KHAERON MKR

CHECK'D KOSALA NUGRAHA KN

APP'D JOHNSON BATUBARA/DWI SUSENO JB / DS

Unit Tag Number : 8131.X....................


: Air Conditioning and Ventilation
No. Required : .......... (refer to attached list)
Purchase Order No. :
Site and Building Data

Elevation : 46 ft. Barometer : atm


Ambient temps : (min/max) 65 / 95 o
F
Relative Humidity : (min/max) 30 / 100 %
Wind speed 80 mph
Electric Area Class Class Gr Div

✘ Continuos Intermittent

Equipment Note 2)

CONDENSING UNIT Note 2)

Free standing

Air Cooled Direct Expansion


Manufacturer
Model No x Qty
Aluminium Finned
Axial Centrifugal
Fan Model No x Qty
Fan Power HP
Compressor Type: Semihermetic Hermetic
Model No x Qty
Compressor Size HP

Remote Control

Charging Valve
Refer to Attachment, Estimated cooling load calculation result summaries North Station of NDD 13
date : Jan 22,2014
rev : 0

AC Split-System Type
No Location Qty Btu/h (kW) Remark
1 IT Room 1 1 x 9000 1 x 0.75 Total 2HP AC = 14 units
2 Control Room 2 2 x 18000 2 x 1.49
3 Corridor Room 2 2 x 9000 2 x 0.75 Total 1HP AC = 5 units
4 Instrument Rack Room 4 4 x 18000 4 x 1.49
5 Sub Station _ MCC 6 6 x 18000 6 x 1.49 Total 1/2HP AC = 0 unit
6 Admin Room 1 1 x 9000 1 x 0.75
7 UPS Room 2 2 x 18000 2 x 1.49
8 Storage Room 1 1 x 9000 1 x 0.75 0

9 Toilet 1 Capacity : Exhaust Fan


91 CFM
(min)
10 Battery Room 1 Capacity : Exhaust Fan
211 CFM
(min)
1
1

1 1

1
1

1

1

1
1